TEST REPORTReport No.: E1051.04-501-47Rendered to:CLIMATE GUARD MANUFACTURINGChicago, IllinoisPRODUCT TYPE: PVC Out Swing Casement WindowSERIES/MODEL: CG THERMAFORCESPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11, NAFS 2011 - North AmericanFenestration Standard/Specification for Windows, Doors, and SkylightsAAMA/WDMA/CSA 101/I.S.2/A440-08, NAFS - North American FenestrationStandard/Specification for Windows, Doors, and SkylightsAAMA/WDMA/CSA 101/I.S.2/A440-05, Standard/Specificationfor Windows, Doors, and Unit Skylights.CSA A440S1-09, Canadian Supplement to AAMA/WDMA/CSA 101/I.S.2/A440, NAFS - NorthAmerican Fenestration Standard/Specification for Windows, Doors, and Skylights.Test Date(s): 10/28/14Through: 11/13/14Report Date: 07/12/161140 Lincoln AvenueSpringdale, PA 15144www.archtest.comwww.intertek.com/buildingp. 724.275.7100f. 717.764.4129

SUMMARY OF RESULTSTitleAAMA/WDMA/CSA 101/I.S.2/A44008 and -11AAMA/WDMA/CSA 101/I.S.2/A44005Design PressureAir InfiltrationCanadian Air Infiltration/ExfiltrationLevelWater Penetration Resistance TestPressureSummary of ResultsTest Specimen #1Test Specimen #2with 1/8" glass,with 3/32" glass,two snubbers,one snubber, and nonand reinforced stilesreinforced stilesClass R-PG50 914 x 1905Class R-PG60 610 x 1524(36 x 75)-C(24 x 60)-CC-R50 914 x 1905 (36 x 75)C-R60 610 x 1524 (24 x 60) 2400 Pa ( 50.13 psf)0.1 L/s/m2 (0.02 cfm/ft2) 2880 Pa ( 60.15 psf)0.1 L/s/m2 (0.02 cfm/ft2)A3A3540 Pa (11.28 psf)540 Pa (11.28 psf)TitleAAMA/WDMA/CSA 101/I.S.2/A440-08 and -11AAMA/WDMA/CSA 101/I.S.2/A440-05Design PressureSummary of ResultsTest Specimen #3with 3/32" glass,one snubber,and reinforced stilesClass R-PG65 610 x 1524 (24 x 60)-CC-R65 610 x 1524 (24 x 60) 3120 Pa ( 65.16 psf)Test Completion Date:11/13/14Reference must be made to Report No. E1051.04-501-47, dated 07/12/16 for complete testspecimen description and detailed test results.

Test Report No.: E1051.04-501-47Report Date: 07/12/16Page 1 of 111.0 Report Issued To:Climate Guard Manufacturing2662 N. Pulaski RoadChicago, Illinois 606392.0 Test Laboratory:Architectural Testing, Inc.1140 Lincoln AvenueSpringdale, Pennsylvania 15144724-275-71003.0 Project Summary:3.1 Product Type: PVC Out Swing Casement Window3.2 Series/Model: CG THERMAFORCE3.3 Compliance Statement: Results obtained are tested values and were secured byusing the designated test method(s). The specimens tested successfully met theperformance requirements for the following ratings:Test Specimen(s)112233Title101/I.S.2/A440-08 and -11101/I.S.2/A440-05101/I.S.2/A440-08 and -11101/I.S.2/A440-05101/I.S.2/A440-08 and -11101/I.S.2/A440-05Summary of ResultsClass R-PG50 914 x 1905 (36 x 75)-CC-R50 914 x 1905 (36 x 75)Class R-PG60 610 x 1524 (24 x 60)-CC-R60 610 x 1524 (24 x 60)Class R-PG65 610 x 1524 (24 x 60)-CC-R65 610 x 1524 (24 x 60)This product was originally tested as the LINEAL SUPPLIER Series/Model 440.720CA-001, PVC Out Swing Casement Window and is a reissue of the original ReportNo. E1051.01-501-47. This report is reissued in the name of Climate GuardManufacturing through written authorization by Deceuninck North America, LLC.3.4 Test Dates: 10/28/14 - 11/13/143.5 Test Record Retention End Date: All test records for this report will be retaineduntil November 13, 2018.3.6 Test Location: Deceuninck North America, LLC test facility in Monroe, Ohio.Calibration of test equipment was performed by Architectural Testing inaccordance with AAMA205-01 "In-Plant Testing Guidelines for Manufacturers andIndependent Laboratories".3.7 Test Specimen Source: The test specimen(s) were provided by the client.Representative samples of the test specimen(s) will be retained by ArchitecturalTesting for a minimum of four years from the test completion date.

Test Report No.: E1051.04-501-47Report Date: 07/12/16Page 2 of 113.0 Project Summary: (Continued)3.8 Drawing Reference: The test specimen drawings have been reviewed byArchitectural Testing and are representative of the test specimen(s) reportedherein. Test specimen construction was verified by Architectural Testing per thedrawings located in Appendix C. Any deviations are documented herein or on thedrawings.3.9 List of Official Observers:NameCompanyDean ErbaughJames GrippoDeceuninck North America, LLCArchitectural Testing, Inc.4.0 Test Specification(s):AAMA/WDMA/CSA 101/I.S.2/A440-11, NAFS 2011 - North American FenestrationStandard/Specification for Windows, Doors, and SkylightsAAMA/WDMA/CSA 101/I.S.2/A440-08, NAFS - NorthStandard/Specification for Windows, Doors, and SkylightsAmericanFenestrationAAMA/WDMA/CSA 101/I.S.2/A440-05, Standard/Specification for Windows, Doors,and Unit Skylights.CSA A440S1-09, Canadian Supplement to AAMA/WDMA/CSA 101/I.S.2/A440, NAFS North American Fenestration Standard/Specification for Windows, Doors, and Skylights.5.0 Test Specimen Description:5.1 Product Sizes:Test Specimen #1:WidthOverall Area:1.7 m² (18.75 ft2) millimetersinchesOverall size91436Heightmillimetersinches190575Vent size88334-3/4187373-3/4Screen size81632-1/8180771-1/8

Test Report No.: E1051.04-501-47Report Date: 07/12/16Page 3 of 115.0 Test Specimen Description: (Continued)5.1 Product Sizes: (Continued)Test Specimens #2 and #3:WidthOverall Area:21.0 m² (10.1 ft )millimetersinchesOverall size61624-1/4Heightmillimetersinches153060-1/4Vent size58423149959Screen size51820-3/8143256-3/8The following descriptions apply to all specimens.5.2 Frame Construction:Frame MemberHead, sill andjambsAll cornersMaterialPVCJoinery TypeMiteredDescriptionExtrudedDetailThermally welded5.3 Vent Construction:Vent MemberAll rails andstilesAll cornersMaterialPVCJoinery TypeMiteredDescriptionExtrudedDetailThermally welded

Test Report No.: E1051.04-501-47Report Date: 07/12/16Page 4 of 115.0 Test Specimen Description: (Continued)5.4 Weatherstripping:Description1/4" wide by 5/16" high foamfilled vinyl bulb(Amesbury QEZD 260)3/16" diameter foam-filledvinyl bulb (Amesbury AP425)1/4" diameter hollow vinyl bulb(Amesbury AP427)QuantityLocation1Vent perimeter (exterior)1Frame)1Frame5.5 Glazing: No conclusions of any kind regarding the adequacy or inadequacy of theglass in any glazed test specimen(s) can be made.TestSpecimen(s)#1# 2 and #3GlassType7/8"IG7/8"IGTestSpecimen(s)#1# 2 and #3SpacerTypeSiliconefoam, singlesealedSiliconefoam, 8"annealed3/32"annealed3/32"annealedGlazing MethodSet from the exterioragainst a double-sidedadhesive tape and securedwith rigid glazing beads.1Daylight Openingmillimetersinches800 x 179131-1/2 x 70-1/2GlassBite1/2"1502 x 14161/2"Quantity19-3/4 x 55-3/45.6 Drainage:Drainage MethodWeepslotWeepslotWeep notchWeep notchSize1/4" wide by1/8" deep1/4" wide by1/8" deep1” wide bywstp height1” wide bywstp heightQuantity242LocationBottom rail, glazing pocket, one ateach endBottom rail, bottom surface, two ateach endBottom rail wstp, one at each endSill wstp, one at each end

Test Report No.: E1051.04-501-47Report Date: 07/12/16Page 5 of 115.0 Test Specimen Description: (Continued)5.7 Hardware:DescriptionLever lockmulti-pointsystemwithlockDie cast metalsnubberDie cast metalsnubberDual arm rotaryoperatorwithmetal guide trackConcealed singlearm hinge withstainlesssteeltrackQuantity12 sets1 setLocationLock jamb/stile:Test specimen #1, five metal keepers on the lockstile located at 2-3/4", 28-3/4", 43-7/8", 62-7/8"and 69-1/4" up from the bottom;Test specimens #2 and #3, three metal keeperson the lock stile located at 2-3/4", 29-7/8" and50-1/2" up from the bottom.Hinge jamb/stile, one each at approximate 1/3pointsHinge jamb/stile, one at the midspan on TestSpecimen #2 and #3,1Sill/bottom rail2One each at the head/top rail, and sill/bottom railBottom vent rail, secured with three #8 x 1-1/2"long screws.5.8 Reinforcement: No reinforcement was utilized on Test specimen #2Metal stud bracketDrawing Number100006721LocationTest specimens #1 and #3All stilesMaterialFiberglass5.9 Screen Construction:Frame MaterialExtrudedaluminumCorner ConstructionMitered with plasticcorner keysMesh TypeMesh Attachment MethodFiberglassFlexible vinyl spline

Test Report No.: E1051.04-501-47Report Date: 07/12/16Page 6 of 116.0 Installation:Each specimen was installed into a Spruce-Pine-Fir wood buck. The rough openingallowed for a 3/16" shim space. The nail fin perimeter of the specimen was sealed withsilicone sealant.LocationAnchor DescriptionIntegral nail fin #8 x 5/8" long pan head screwAnchor LocationNominally spaced at 12" oncenter and starting 2" from eachcorner.

Test Report No.: E1051.04-501-47Report Date: 07/12/16Page 7 of 117.0 Test Results: The temperature during testing was 21.6 C (71 F). The results aretabulated as follows:Test Specimen #1:Title of TestOperating Force,per ASTM E 2068Air Leakage,Infiltration per ASTM E 283at 75 Pa (1.57 psf)Air Leakage,Exfiltration per ASTM E 283at 75 Pa (1.57 psf)Canadian AirInfiltration/Exfiltration LevelWater Penetration,per ASTM E 547Uniform Load Deflection,per ASTM E 330Uniform Load Structural,per ASTM E 330Forced Entry Resistance,per ASTM F 588,Type: B - Grade: 10Thermoplastic Corner WeldInsect Screen Serviceabilityper NAFS Canadian Supplement(CSA A440S1-09)60 N (13.5 lbf)Sash Vertical Deflection200 N (45 lbf)Distributed Load240 Pa (5.0 psf)ResultsInitiate motion:45 N (10 lbf)Maintain motion:18 N (4 lbf)Locks:13 N (3 lbf)AllowedNote60 N (13 lbf) max.30 N (7 lbf) max.100 N (22.5 lbf) max.0.1 L/s/m2(0.02 cfm/ft2)1.5 L/s/m2(0.3 cfm/ft2) max.10.2 L/s/m2(0.03 cfm/ft2)1.5 L/s/m2(0.3 cfm/ft2) max.1A30.5 L/s/m2(0.1 cfm/ft2) max.N/AN/A3N/AN/A3N/AN/A3PassPassNo entryMeets as statedPassMeets as stated1.5 mm (0.06")17.8 mm (0.70") max.PassNo damage8

Test Report No.: E1051.04-501-47Report Date: 07/12/16Page 8 of 117.0 Test Results: (Continued)Test Specimen #1: (Continued)Title of TestResultsAllowedOptional PerformanceWater Penetration,per ASTM E 547at 540 Pa (11.28 psf)PassNo leakageUniform Load Deflection,per ASTM E 330Deflections taken at the top rail 2400 Pa ( 50.13 psf)3.3 mm (0.13")Report Only-2400 Pa (-50.13 psf)15.5 mm (0.61")Uniform Load Structural,per ASTM E 330Permanent sets taken atthe top rail 3600 Pa ( 75.19 psf)0.3 mm (0.01")3.5 mm (0.14") max.-3600 Pa (-75.19 psf)1.0 mm (0.04")3.5 mm (0.14") max.Test Specimen #2:Title of TestOperating Force,per ASTM E 2068Air Leakage,Infiltration per ASTM E 283at 75 Pa (1.57 psf)Air Leakage,Exfiltration per ASTM E 283at 75 Pa (1.57 psf)Canadian AirInfiltration/Exfiltration LevelWater Penetration,per ASTM E 547Uniform Load Deflection,per ASTM E 330Uniform Load Structural,per ASTM E 330ResultsInitiate motion:45 N (10 lbf)Maintain motion:22 N (5 lbf)Locks:18 N (4 lbf)AllowedNote4, 6, 75, 6Note60 N (13 lbf) max.30 N (7 lbf) max.100 N (22.5 lbf) max.0.1 L/s/m2(0.02 cfm/ft2)1.5 L/s/m2(0.3 cfm/ft2) max.0.2 L/s/m2(0.04 cfm/ft2)A31.5 L/s/m2(0.3 cfm/ft2) max.0.5 L/s/m2(0.1 cfm/ft2) max.N/AN/A3N/AN/A3N/AN/A311

Test Report No.: E1051.04-501-47Report Date: 07/12/16Page 9 of 117.0 Test Results: (Continued)Test Specimen #2: (Continued)Title of TestResultsAllowedForced Entry Resistance,per ASTM F 588,PassNo entryType: B - Grade: 10Thermoplastic Corner WeldPassMeets as statedInsect Screen Serviceabilityper NAFS Canadian SupplementPassMeets as stated(CSA A440S1-09)60 N (13.5 lbf)Sash Vertical Deflection0.8 mm (0.03")11.7 mm (0.46") max.200 N (45 lbf)Distributed LoadPassNo damage240 Pa (5.0 psf)Optional PerformanceWater Penetration,per ASTM E 547PassNo leakageat 540 Pa (11.28 psf)Uniform Load Deflection,per ASTM E 330Deflections taken at the top rail 2880 Pa ( 60.15 psf)0.5 mm (0.02")Report Only2.5 mm (0.10")-2880 Pa (-60.15 psf)Uniform Load Structural,per ASTM E 330Permanent sets taken atthe top rail 4320 Pa ( 90.23 psf) 0.3 mm ( 0.01")2.3 mm (0.09") max.-4320 Pa (-90.23 psf)0.5 mm (0.02")2.3 mm (0.09") max.Note84, 6, 75, 6

Test Report No.: E1051.04-501-47Report Date: 07/12/16Page 10 of 117.0 Test Results: (Continued)Test Specimen #3:Title of TestResultsOptional PerformanceAllowedNoteUniform Load Deflection,per ASTM E 330Deflections taken at the top rail 3120 Pa ( 65.16 psf)1.5 mm (0.06")Report Only4, 6, 7-3120 Pa (-65.16 psf)2.5 mm (0.10")Uniform Load Structural,per ASTM E 330Permanent sets taken atthe top rail 4680 Pa ( 97.74 psf)0.3 mm (0.01")2.3 mm (0.09") max.-4680 Pa (-97.74 psf)0.5 mm (0.02")2.3 mm (0.09") max.5, 6Note 1: The tested specimen meets (or exceeds) the performance levels specified inAAMA/WDMA/CSA 101/I.S.2/A440 for air leakage resistance.Note 2: With and without insect screen.Note 3: The client opted to start at a pressure higher than the minimum required. Testresults are reported under Optional Performance.Note 4: The deflections reported are not limited by AAMA/WDMA/CSA 101/I.S.2/A440for this product designation. The deflection data is recorded in this report for specialcode compliance and information only.Note 5: Loads were held for 10 seconds.Note 6: Tape and film were used to seal against air leakage during structural testing. Inour opinion, the tape and film did not influence the results of the test.Note 7: Loads were held for 52 seconds.Note 8: Please note the stud bracket screw detail under the hardware description.

Test Report No.: E1051.04-501-47Report Date: 07/12/16Page 11 of 11This report is reissued in the name of Climate Guard Manufacturing through writtenauthorization of Deceuninck North America, LLC to whom the original report wasrendered. The original Deceuninck North America, LLC Report No. is E1051.01-501-47.Architectural Testing will service this report for the entire test record retention period.Test records such as detailed drawings, datasheets, representative samples of testspecimens, or other pertinent project documentation, will be retained by ArchitecturalTesting, Inc. for the entire test record retention period.This report does not constitute certification of this product nor an opinion or endorsementby this laboratory. It is the exclusive property of the client so named herein and relatesonly to the specimen(s) tested. This report may not be reproduced, except in full, withoutthe written approval of Architectural Testing, Inc.For ARCHITECTURAL TESTING, Inc.James P. GrippoTechnicianLynn GeorgeDirector- Regional OperationsJPG:sldAttachments (pages): This report is complete only when all attachments listed are included.Appendix-A: Alteration Addendum (1)Appendix-B: Location of Air Seal (1)Appendix-C: Drawing(s) (12)This report produced from controlled document template ATI 00438, revised 06/27/14.

Test Report No.: E1051 .04 -501 -47 Report Date: 07/12/16 Page 7 of 11 7.0 Test Results : The temperature during testing was 21.6 C ( 71 F). The results are tabulated as follows: Test Specimen #1 : Title of Test Results Allowed Note Operating Force, per ASTM E 2068 Initiate motion: 45 N ( 10 lbf) 60 N (13 lbf) max. Maintain motion:

Related Documents:

Field density and field moisture determinations shall be made according to ASTM D 6938. 501.07.04.02 Method A The Contractor is responsible for establishing QC procedures. Page 5 Rev. Date: 11/2014 OPSS.MUNI 501 501.07.04.03 Method B 501.07.04.03.01 General When Method B is specified in the Contract Documents, QC compaction testing shall be based on material placed and compacted in the Work on .

501 Concrete 501.1 Description (1) This section describes proportioning, mixing, placing, and protecting concrete mixtures. 501.2 Materials 501.2.1 Portland Cement (1) Use cement conforming to ASTM specifications as follows: - Type I portland cement; ASTM C150. - Type II portland cement; ASTM C150. - Type III portland cement; ASTM C150, for high early strength. - Type IP portland-pozzolan .

Research & Writing Skills Success in 20 Minutes a Day, or Getting Down to Busi-ness. A basic knowledge of language will also help you become a better writer. Use these books to get the extra practice you need: 501 Vocabulary Questions, 501 Synonyms and Antonyms, 501 Word Analogies, Goof-Proof Spelling, or Goof-Proof Grammar. x 501 Writing Prompts

SY0-501 Exam Dumps SY0-501 Exam Questions SY0-501 PDF Dumps SY0-501 VCE Dumps . A network technician is trying to determine the source of an ongoing network based attack. Which . options will pro-vide the best performance and availability for both the VoIP traffic, as well as the

501/453/Universal 501/453/RAC/L 501/453/RAC 501/423 501/421 ICG 623 ICG 653/Universal International 4 Connection Solutions www.ehawke.com Cable Gland Type Colour Code/ Page Material Sealing/Ingress Protection Application/Cable Type Certification Protection Concept t Ca b le Gland Selection Ch

THE STATE OF ILLINOIS Order entered June 9, 2020. (Deleted material is struck through, and new material is underscored.) Effective July 1, 2020, Illinois Supreme Court Rules 501, 526, 556, and 585 are amended, as follows. Amended Rule 501 Rule 501. Definitions (a) Bond Certificates. Bail sec

501:571 Financial Health Administration (3) 501:565 Information Systems for Health Care (3) 501:595 Professional Practicum (6) Six Credits of Approved Electives(6) Current "automatically approved" electives include: 501:510 Human Resources Policy and Practice in Health Care 501:512 Health Care Economics

Completed ASTM D2992 testing to achieve ASTM D2996 and D2310 HDB Category U rating of 12,500 PSI Used to regulate air flow or shut off and isolate a system, Belco AMCA-licensed fiberglass dampers are corrosion resistant and designed to match operating conditions of the duct system. Premium vinyl-ester resins are used throughout the damper. Fire retardant resins are also available for a .