Merlin Gerin Multi 9 SystemProtectionMiniature Circuit BreakersGet more with the world’s Power & Control specialist

ProtectionMerlin Gerin Multi 9 SystemMiniature circuit breakersTripping curvesMarkings & limitation capabilityTrip Unit VariationsCircuit Breaker MarkingCircuit ProtectionA choice of several curvesWhatever circuit has to be protected, a C60 or C120 circuitbreaker provides the perfectsolution with a suitable curve.Curve Btripping:3 to 5 times the ratedcurrent (In);protection of generators,persons, very longcables.1Curve Ctripping:5 to 10 In;protection of circuits,general applications.multi 9C60HC63415V 23458352461000032.Curve Dtripping:10 to 14 In;protection of high surgecircuits, welders, transformers, motors.Curve MA(magnetic only)tripping: 12 In;protection of motorstarters ( thermal protection when combinedwith contactor).161.2.3.4.5.6.7.8.7Circuit Breaker Model NumberTripping CurveCircuit Breaker Current RatingOperating VoltageRated Breaking CapacityCircuit Breaker Part NumberElectrical Diagram - No. of PolesI2t classificationCircuit Breaker Limitation CapabilityThe limitation capability of a circuit breaker is that characteristic wherebyonly a current less than the prospective fault current is allowed to flow undershort-circuit conditions.This is illustrated by limitation curves which give:Installation of current limiting circuit breakersoffers several advantages:" The limited peak current in relation to theRMS value of the prospective short-circuitcurrent (the short-circuit current being thatcurrent which would flow continuously in theabsence of protection equipment).# Better network protectionCurrent limiting circuit breakers considerablyreduce the undesirable effects of short-circuitcurrents in an installation." The limited current stress in relation to theRMS value of the prospective short-circuitcurrent.# Reduced thermal effectsCable heating is reduced, hence longer cablelife." Current limiting capability. The advanceddesign of the Multi-9 range provides currentlimitation with far better protection than conventional circuit breakers. For example, on a6A rating with a prospective short circuit of5000A, the current will be limited at 350A or7%.# Reduced mechanical effectsElectrodynamic forces reduced, thus electrical contacts are less likely to be deformed orbroken.# Reduced electromagnetic effectsMeasuring equipment situated near an electrical circuit less affected.

Miniature Circuit Breakers – up to 63A18mm pole widthPageC60a – 4.5kA2C60N – 6kA3C60H – 10kA4C32H-DC – 10kA(circuit breakers for DC applications)18electrical auxiliaires– C6010accessories– C6016Miniature Circuit Breakers – up to 125A27mm pole widthC120N – 10kA6C120H – 15kA8electrical auxiliaries– C12010accessories– C12016Tm Motor MechanismTM C60/C12021Dimensions23For supplementary technical information, consult AUS010306Page 1

protectioncircuit-breakers up to 63 AC60a circuit-breakers4.5 kA, C curveAS/NZS 4898functionsdescriptionApproval No: N13634The circuit-breakers combine the followingfunctions:- protection of circuits against short-circuitcurrents,- protection of circuits against overloadcurrents,- control,- isolation,- protection of persons against indirectcontact.technical dataC60a circuit-breakersC curvec power circuitv voltage rating: 240 V ACv number of cycles (O-C): 10 000v foolproof terminal design- moving barrier prevents incorrect cableinsertion- cable strand centering guides ensurecorrect cable positions and strand groupingv isolation with positive contact indicationv bistable din clip, simplifies disassemblyc environmentv tropicalisation: treatment 2(relative humidity: 95 % at 55 C)v connection: tunnel terminals for thefollowing cables:- up to 25A : 25mm2 stranded- 32 to 63A : 35mm2 strandedcatalogue numberstyperating(A)- C60a circuit-breakers are used in thedomestic sectors where single phase faultlevels are less than or equal to 4.5kA.utilisationcables feeding conventional loads.technical datac power circuitv tripping curves: the magnetic trip unitoperates between 5 and 10 Inv breaking capacity- according to AS/NZS 4898 Icu ultimatebreaking capacity (0-C0 eakingcapacityIcu (A)4500widthquantityin mod. per boxof 9 mmC curve 57Page 2Schneider Electric Help Centre: 1300 369 233

protectioncircuit-breakers up to 63 AC60N circuit-breakers6kA, C curveAS/NZS 4898Approval No: N13634functionsThe circuit-breakers combine the followingfunctions:- protection of circuits against short-circuitcurrents,- protection of circuits against overloadcurrents,- control,- isolation,- protection of persons against indirectcontact.descriptiontechnical data common toC60N circuit breakersC curvec power circuitv voltage rating: 240/415 V AC- for 2P single phase 240/480Vv I2t classification: 3v number of cycles (O-C): 20 000v foolproof terminal design- moving barrier prevents incorrect cableinsertion- cable strand centering guides ensurecorrect cable positions and strand groupingv isolation with positive contact indicationv bistable din clip, simplifies disassemblyc environmentv tropicalisation: treatment 2(relative humidity: 95 % at 55 C)v connection: tunnel terminals for thefollowing cables:- up to 25A : 16mm2 flexible with cable end: 25mm2 stranded- 32 to 63A : 25mm2 flexible with cable end: 35mm2 strandedcatalogue numberstypeutilisationcables feeding conventional loads.technical datac power circuitv tripping curves: the magnetic trip unitsoperate between 5 and 10 Inv breaking capacity according toAS/NZS 4898, Icu ultimate breaking capacity(O-CO cycle):ratingtype(A)1 631P2P3Pvoltage(V)breakingcapacityIcu (A)240/415415.4804156 0006 0006 34258352583625837C curve C60N1P1Width in modof 9mm - 22258042P13Width in modof 9mm - 42413258183P5Width in modof 9mm - 624625832Page 3

protectioncircuit-breakers up to 63 AC60H circuit-breakers10kA, B, C and D curvesAS/NZS 4898Approval No: N13634functionsThe circuit-breakers combine the followingfunctions:- protection of circuits against short-circuitcurrents,- protection of circuits against overloadcurrents,- control,- isolation,- protection of persons against indirectcontact.descriptiontechnical data common toC60H circuit-breakersB curvec power circuitv voltage rating: 240/415 V ACv breaking capacity- according to AS/NZS 4898,Icv ultimate breaking capacity (O-CO cycle):rating(A)typevoltage(V)break. cap.Icu (A)1 631P, 2P3P, 4P240/415415 48010 00010 000v I2t classification: 3v foolproof terminal design- moving barrier prevents incorrect cableinsertion- cable strand centering guides ensurecorrect cable positions and strand groupingv isolation with positive contact indicationv bistable din clip, simplifies disassemblyv isolation with positive contact indication:opening is indicated by a green strip on thedevice operating handle. This indicatorshows opening of all the polesv number of cycles (O-C): 20 000c environmentv tropicalisation: treatment 2(relative humidity: 95 % at 55 C)v connection: tunnel terminals for thefollowing cables:- up to 25A :16mm2 flexible with cable end;25mm2 stranded- 32 to 63A :25mm2 flexible with cable end;35mm2 strandedPage 4utilisationwhen there are small inrush currents(generators, long cables).technical datac power circuitv tripping curve:the magnetic trip units operate between3 and 5 In.C curveutilisationcables feeding conventional loads.technical datac power circuitv tripping curve:the magnetic trip units operate between 5and 10 In.D curveutilisationloads with a high inrush current(motors, transformers).technical datac power circuitv tripping curve:the magnetic trip units operate between10 and 14 In.Schneider Electric Help Centre: 1300 369 233

protectioncircuit-breakers up to 63 AC60H circuit-breakers10kA, B, C and D curveAS/NZS 4898catalogue numbersApproval No: 1625217252182521925220252212522225223C60H1P12Width in modof 9mm - 2258452P1324Width in modof 9mm - 4258573P135246Width in modof 9mm - 6258714P13572468Width in modof 9mm - 825883Page 5

protectioncircuit breakers up to 125AC120N circuit-breakers10kA, B, C curves - AS/NZS 489810kA, D curve AS 3947-2functionThe circuit-breakers combine the followingfunctions:- protection of circuits against short circuitcurrents,- protection of circuits against overloadcurrents,- control,- isolation,- protection of persons against indirectcontact.descriptionTechnical data common to C120N circuitbreakersB curvec power circuitv current rating: 63 to 125 Av voltage rating 415 V ACv insulation voltage Ui: 500 Vv impulse withstand voltage Uimp: 6 kVv breaking capacity:- according to AS/NZS 4898 Icv ultimatebreaking capacity (O-CO cycle)type1, 2, 3, 4Pvoltage(V)240/415breaking cap.Icu (A)10000technical datac power circuitv tripping curve:the magnetic trip units operate between3 and 5 In.C curveApproval No:Q00542v according to AS3947-2 Icu ultimatebreaking capacity (O-CO cycle)utilisationcables feeding conventional loads.typetechnical data1P2, 3, 4Pvoltage(V)240415400 415breaking cap.Icu (kA)10310v mechanical durability:- 20000 cycles (O-C)v electrical durability:- 63 A: 10000 cycles (O-C)- 80 125 A: 5000 cycles (O-C)v I2t classification: 3v isolation with positive contact indication:opening is indicated by a green strip on thedevice operating handle. This indicatorshows opening of all the polesv foolproof terminal design- moving barrier prevents incorrect cableinsertion- cable strand centering guides ensurecorrect cable positions and strand groupingv bistable din clip: simplifies disassemblyv 63 to 125A: - up to 35mm2 flexible withcable end- up to 50mm2 strandedPage 6Approval No:Q00542utilisationwhen there are small inrush currents(generators, long cables).c power circuitv tripping curve:the magnetic trip units operate between 5and 10 In.D curve - For industrial use onlyutilisationloads with a high inrush current(motors, transformers).technical datac power circuitv tripping curve:the magnetic trip units operate between10 and 14 In.Schneider Electric Help Centre: 1300 369 233

protectioncircuit-breakers up to 125 AC120N circuit-breakers10kA, B, C curves - AS/NZS 489810kA, D curve AS 3947-2catalogue 90183911839218393B curve C120N1P1218340Width in modof 9mm - 32P1 32 418344Width in modof 9mm - 63P1 3 52 4 618349Width in modof 9mm - 94P1 3 5 712 4 6 818355Width in modof 9mm - 12Page 7

protectioncircuit breakers up to 125AC120H circuit-breakers15kA, B, C curves - AS/NZS 489815kA, D curve AS 3947-2functionThe circuit-breakers combine the followingfunctions:- protection of circuits against short circuitcurrents,- protection of circuits against overloadcurrents,- control,- isolation,- protection of persons against indirectcontact.descriptionTechnical data common to C120N circuitbreakersB curvec power circuitv current rating: 10 to 125 Av voltage rating 415 V ACv insulation voltage Ui: 500 Vv impulse withstand voltage Uimp: 6 kVv breaking capacity:- according to AS/NZS 4898 Icu ultimatebreaking capacity (O-CO cycle)type1, 2, 3, 4Pvoltage(V)240/415breaking cap.Icu (A)15000Approval No:Q00542utilisationwhen there are small inrush currents(generators, long cables).technical datac power circuitv tripping curve:the magnetic trip units operate between3 and 5 In.C curveApproval No:Q00542v according to AS3947-2 Icu ultimatebreaking capacity (O-CO cycle)utilisationcables feeding conventional loads.typetechnical data1P2, 3, 4Pvoltage(V)240415400 415breaking cap.Icu (kA)154.515v mechanical durability:- 20000 cycles (O-C)v electrical durability:- 63 A: 10000 cycles (O-C)- 80 125 A: 5000 cycles (O-C)v I2t classification: 3v isolation with positive contact indication:opening is indicated by a green strip on thedevice operating handle. This indicatorshows opening of all the polesv foolproof terminal design- moving barrier prevents incorrect cableinsertion- cable strand centering guides ensurecorrect cable positions and strand groupingv bistable din clip: simplifies disassemblyv 63 to 125A: - up to 35mm2 flexible withcable end- up to 50mm2 strandedPage 8c power circuitv tripping curve:the magnetic trip units operate between 5and 10 In.D curve - For industrial use onlyutilisationloads with a high inrush current(motors, transformers).technical datac power circuitv tripping curve:the magnetic trip units operate between10 and 14 In.Schneider Electric Help Centre: 1300 369 233

protectioncircuit-breakers up to 125 AC120H circuit-breakers15kA, B, C curves - AS/NZS 489815kA, D curve AS 3947-2catalogue P1218394Width in modof 9mm - 32P1 32 418412Width in modof 9mm - 63P1 3 52 4 618424Width in modof 9mm - 94P1 3 5 72 4 6 818437Width in modof 9mm - 12Page 9

protectionelectrical auxiliariesfor C60 and C120 circuit-breakersfunctionThey allow remote tripping or indication ofcircuit-breakers, with or without a Vigimodule.descriptionc they are mounted on the left-hand side ofthe circuit-breaker within a width limit of54 mmc fixed using clips (without tools) on theleft-hand side of the circuit-breakerc compatible with Vigi modules(adaptable on the right-hand side)c a maximum of 3 indication auxiliaries onthe same circuit-breakerc a maximum of 2 OF SD/OF auxiliaryswitches on the same circuit-breakerc a maximum of 2 MX OF or MN trippingauxiliaries on the same circuit-breakerc a maximum of 1 MNs or MNx or MSUtripping auxiliary on the samecircuit-breaker.auxiliary combination54 mm max.27 mm max. OF SD/OFauxiliarycontactPage 1036 mm max. OFauxiliarycontact SD faultindicatingswitch MNs , MNx orMSU auxiliary MX OFor MNauxiliarycircuit-breakerSchneider Electric Help Centre: 1300 369 233

protectionelectrical auxiliariesfor C60 and C120 circuit-breakerstrippingremote indicationVisualisation of tripping by means of the redindicator on front face.MX OF shunt tripRemote tripping of a circuit-breaker:c equipped with an OF changeover switch:- to indicate the circuit-breaker’s position- to carry out self-breaking allowing thecontrol circuit to remain energized.Undervoltage releases(MN, MN s )Controls the tripping of a circuit-breakerwhen its supply voltage drops(threshold between 70 and 35 % of Un)It allows for manual closing of thecircuit-breaker if its voltage exceeds 85 % ofthe rated voltagedelayed MN s release0.2 second time-delay: prevents tripping dueto brownouts or momentary voltagedecreases.MNx release for opening pushbuttonCompletely unaffected by power supplycircuit cuts, it is recommended for fail-safeemergency stopping. Replaces the MX“voluntary“ release equipped with its NO/NCindicator lights.MSU overvoltageMSU voltage threshold releaseSpecially designed to monitor voltagebetween the neutral and phase(s)conductors, it cuts power supply by openingthe circuit-breaker in event of an overvoltage.For overvoltages lasting for more than a fewseconds.technical dataComplance with standard: AS 3947-2v release consumptiontypevoltage(V AC or DC)MX OF 415 VAC220.240 V AC110.130 V ACDC48 VACDC24 VACDC12 VACDCMN220.240 V AC48 VACDCMNs220.240 V ngholdingholdinginrushinrushinrushinrushpower(W or F auxiliary switchv changeover switch that indicates the“open” or “closed” position of thecircuit-breaker.v test button on the front face that allows forthe indication circuit to be verified withoutoperating the circuit-breakerSD fault indicating switchv changeover switch that indicates the ”faulttrip” position of the circuit-breakerv visualisation of the fault (SD) by means ofa mechanical indicator on front face.OF SD/OF selector switchv double changeover switch that indicates:v the “open” or “closed” position of thecircuit-breaker (OF)v the “fault trip” position of the circuit-breaker(SD).v 2 circuits:- upper: OF- lower: SD or OF.v function is selected using rotary selectorswitch on the right-hand sidev the selected function is indicated on thefront facev visualisation of the fault (SD) by means ofa red mechanical indicator on front face.technical dataComplies with standard: AS 3947-2v rated current of auxiliary contactsvoltage(V AC or DC)415 VAC 240 VAC130 VDC 48 VDC 24 VDCrated current(A)36126connectionc using screw clamp terminals for 1 or 2cables (max. 2.5 mm2)c visible markers near terminals.Page 11

protectionelectrical auxiliariesfor C60 and C120 circuit-breakersreferencestypecontrol voltage(V AC)(V DC)cataloguenumberwidthin mod.of 9 240269634220.240269694380.415269714MX OF shunt releaseU 1412110.130482412C2 C126946MSU overvoltage release1P NU NL3P N26979U NL1L2L3MN undervoltage releaseinstantaneous48U D1 D2delayed s26963MNx release for opening pushbuttonPh NU E1E2NLPh to PhU 26969E1Page 12E2L1L2Schneider Electric Help Centre: 1300 369 233

protectionelectrical auxiliariesfor C60 and C120 circuit-breakerstypecontrol voltage(V AC)(V DC)cataloguenumberwidthin mod.of 9 mm269271269241269291SD fault indicating switch94929126927OF auxiliary contact14121126924OF SD/OF selector switch14249212229411219126929Page 13

protectionOF contact and SD switch, MX OF, MN and MNs releasesfor C60 and C120 circuit-breakersshunt release MX OFapplicationconnectionc remote opening by circuit-breaker tripping,of electrical lighting circuits, etcc terminals 12 and 14 are used for indicationof the circuit-breaker OF position, at avoltage identical to coil voltagec indication on the front face of the trippedfunction, by a red mechanical indicator.U 14 12 C2 C1L or closedopenundervoltage releaseMN or MNsapplicationN or-N or-L or N or connectionc opening of electrical circuits bycircuit-breaker tripping:v either by

Circuit Breaker Limitation Capability . Miniature Circuit Breakers – up to 63A C60a – 4.5kA 2 C60N – 6kA 3 C60H – 10kA 4 C32H-DC – 10kA 18 . Page 2 Schneider Electric Help Centre: 1300 369 233 protection circuit-breakers up to 63 A C60a circuit-breakers 4.5 kA, C curve

Related Documents:

Les prophéties de Merlin Décode le message de Merlin et conjugue le verbe au futur. CENDRILLON DEVENIR UNE SERVANTE Les prophéties de Merlin Décode le message de Merlin et conjugue le verbe au futur. ALICE APERCEVOIR UN LAPIN Les prophéties de Merlin Décode le message de Merlin et conjugue le verbe au futur. ARIEL VOULOIR

Merlin III Iron Merlin X Aluminum Merlin 409 SMALL BLOCK FORD: Man O’War Iron Man O’War Aluminum CHRYSLER BIG BLOCK: 426H/Wedge INDEX CYLINDER HEADS SMALL BLOCK CHEVROLET: S/R Iron S/R Torquer Iron Sportsman II Iron Motown Iron Motown Aluminum LS CHEVROLET: Warhawk LS1 Aluminum Warhawk LS7 Aluminum BIG BLOCK CHEVROLET: Merlin Iron

Merlin III BBC 6 Merlin Gen VI BBC 7 Motown II SBC 8 Motown II RC SBC 9 Motown LS SBC 10 Motown LS Accessories 11 Cast Iron Cylinder Heads Pg. S/R SBC 12 S/R Torquer SBC 13 Sportsman II SBC 14 Motown 200 SBC 15 Motown 220 SBC 16 Merlin BBC 17 Merlin BBC 18 Windsor Jr. 19 Windsor Sr. 20 Intake Manifolds 21

merlin entertainments limited annual report and accounts 2019 at a glance a global leader in location based, family entertainment 2 merlin is europe’s number one and the world’s second-largest visitor attraction operator and now operates 130 attractions, 20 hotels and six hol

The Merlin@home transmitter model EX1150 and the Merlin@home transmitter model EX1150W can be used with the cellular adapter provided with your transmitter. For more information, see the Set Up Guide, Quick Start Guide, and the Icons and Connections Guide provided with your transmitter. Can

Harley Merlin and the First Ritual (Book 4) Harley Merlin and the Broken Spell (Book 5) Harley Merlin and the Cult of Eris (Book 6) . A Shade of Vampire (Book 1) A Shade of Blood (Book 2) A Castle of Sand (Book

1 Rolls-Royce Merlin The Rolls-Royce Merlin engines were a series of 12 cylinder, 60 "V", 27 litre, liquid cooled piston aircraft engines built during World War II by Rolls-Royce, and under licence in the United States by Packard. They are widely considered to File Size: 266KBPage Count: 7

AssemblyLine flow and Hooks .26 Controlling the flow of an AssemblyLine . . . 30 Expressions .30 Expressions in component parameters .33 Expressions in LinkCriteria .33 Expressions in Branches, Loops and Switch/Case 34 Scripting with Expressions .34 The Entry object.35 Chapter 2. Scripting in TDI .37 Internal data model: Entries, Attributes and Values 38 Working with .