PowerMonitor 1000 Unit User Manual, Publication 1408 .

2y ago
28 Views
3 Downloads
3.77 MB
206 Pages
Last View : 23d ago
Last Download : 3m ago
Upload by : Madison Stoltz
Transcription

User ManualOriginal InstructionsPowerMonitor 1000 UnitCatalog Numbers 1408-BC3A-485, 1408-BC3A-ENT, 1408-TS3A-485, 1408-TS3A-ENT, 1408-EM3A-485, 1408-EM3A-ENT

Important User InformationRead this document and the documents listed in the additional resources section about installation, configuration, andoperation of this equipment before you install, configure, operate, or maintain this product. Users are required tofamiliarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,and standards.Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance arerequired to be carried out by suitably trained personnel in accordance with applicable code of practice.If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment maybe impaired.In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting fromthe use or application of this equipment.The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables andrequirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility orliability for actual use based on the examples and diagrams.No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, orsoftware described in this manual.Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,Inc., is prohibited.Throughout this manual, when necessary, we use notes to make you aware of safety considerations.WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardousenvironment, which may lead to personal injury or death, property damage, or economic loss.ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, propertydamage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.IMPORTANTIdentifies information that is critical for successful application and understanding of the product.Labels may also be on or inside the equipment to provide specific precautions.SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerousvoltage may be present.BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces mayreach dangerous temperatures.ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people topotential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALLRegulatory requirements for safe work practices and for Personal Protective Equipment (PPE).

Table of ContentsTable of ContentsPreface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Summary of Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Catalog Number Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55555Chapter 1PowerMonitor 1000 OverviewSafety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7About the PowerMonitor 1000 Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7PowerMonitor 1000 Unit Features and Functions . . . . . . . . . . . . . . . . 8Communication Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Chapter 2Installation and SetupPre-installation Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Mount the PowerMonitor 1000 Unit . . . . . . . . . . . . . . . . . . . . . . . . . . .Wire the PowerMonitor 1000 Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . .Set Up the PowerMonitor 1000 Unit . . . . . . . . . . . . . . . . . . . . . . . . . . .13172034Chapter 3PowerMonitor 1000 UnitFeaturesSecurity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Analog Input Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Wiring Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Troubleshooting Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .RS-485 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Optional Ethernet Network Communication . . . . . . . . . . . . . . . . . . .Energy Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Demand Metering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Power Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Voltage, Current, and Frequency Metering . . . . . . . . . . . . . . . . . . . . . .Date and Time Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Energy Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Min/Max Log. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Load Factor Log. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Time of Use Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Unit Status Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Alarm Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .I/O Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Status Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Restore Defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Configuration Lock Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Miscellaneous Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Rockwell Automation Publication 1408-UM002D-EN-P - November 3

Table of ContentsChapter 4PowerMonitor 1000 Memory Organization . . . . . . . . . . . . . . . . . . . . . 83Communication Command Summary . . . . . . . . . . . . . . . . . . . . . . . . . . 84Explicit Messaging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86Explicit Message Setup – Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86Unit Setup by Using Explicit Messaging. . . . . . . . . . . . . . . . . . . . . . . . . 96Reading Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103Implicit Messaging (Class 1 Connection). . . . . . . . . . . . . . . . . . . . . . . 107SCADA Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113CommunicationAppendix APowerMonitor 1000 Data TablesSummary of Data Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121Data Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123Appendix BSpecificationsTechnical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181Appendix CCertificationsEtherNet/IP Network Conformance Testing. . . . . . . . . . . . . . . . . . . 183UL/CU-L . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183CE Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183Appendix DAdditional EtherNet/IPInformationCommon Industrial Protocol (CIP) Objects. . . . . . . . . . . . . . . . . . . . 185Identity Object - CLASS CODE 0x0001. . . . . . . . . . . . . . . . . . . . . . . 185Message Router - CLASS CODE 0x0002 . . . . . . . . . . . . . . . . . . . . . . 187Assembly Object - CLASS CODE 0x0004 . . . . . . . . . . . . . . . . . . . . . 187Base Energy Object - CLASS CODE 0x004E . . . . . . . . . . . . . . . . . . . 188Electrical Energy Object - CLASS CODE 0x004F . . . . . . . . . . . . . . 190TCP/IP Interface Object - CLASS CODE 0x00F5 . . . . . . . . . . . . . 193Ethernet Link Object - CLASS CODE 0x00F6 . . . . . . . . . . . . . . . . . 195Parameter Object - CLASS CODE 0x000F . . . . . . . . . . . . . . . . . . . . 197File Object - CLASS CODE 0x0037. . . . . . . . . . . . . . . . . . . . . . . . . . . 198Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2014Rockwell Automation Publication 1408-UM002D-EN-P - November 2019

PrefaceYou must have a basic understanding of electrical circuitry and familiarity withrelay logic, industrial communication, and programmable controllers. If you donot, obtain the proper training before using this product.Use this document as a guide to configure communication with the Bulletin1408 PowerMonitor 1000 unit by using other applications and controllers.This document is intended for advanced users. You must already be familiarwith data communication and programmable controller messaging.This manual contains new and updated information as indicated in thefollowing table.Summary of ChangesTopicPageAdded a note that Word Range Write and Read is not supported in firmwarerevision 4.010 and later.85Catalog Number Explanation1408 - BC3 A - 485Bulletin Number1408 - PowerMonitor 1000UnitAdditional ResourcesFunctionalityBC3 - Basic consumption meterTS3 - Basic consumption andtroubleshooting meterEM3 - Energy, demand, and powermonitorCommunication485 - SerialENT - Serial and EthernetControl PowerA - 120/240V ACor125 250V DCThese documents contain additional information concerning related productsfrom Rockwell Automation.ResourceDescriptionIndustrial Automation Wiring and Grounding Guidelines,publication 1770-4.1Provides general guidelines for installing a RockwellAutomation industrial system.Product Certifications website, rok.auto/certificationsProvides declarations of conformity, certificates, andother certification details.You can view or download publications at rok.auto/literature.Rockwell Automation Publication 1408-UM002D-EN-P - November 20195

PrefaceNotes:6Rockwell Automation Publication 1408-UM002D-EN-P - November 2019

Chapter1PowerMonitor 1000 OverviewSafetyFollow these advisories when using this product.ATTENTION: Only qualified personnel, following accepted safetyprocedures, can install, wire, and service the power monitor and itsassociated components. Before beginning any work, disconnect all sources ofpower and verify that they are de-energized and locked out. Failure to followthese instructions can result in personal injury or death, property damage, oreconomic loss.ATTENTION: Never open a current transformer (CT) secondary circuit withprimary current applied. Include a shorting terminal block in the CTsecondary circuit when wiring between the CT’s and the power monitor. Ashorting block, line fuses, and control power fuses are included in the powermonitor accessory kit, catalog number 1400-PM-ACC. Shorting thesecondary with primary current present allows other connections to beremoved if needed. An open CT secondary with primary current appliedproduces a hazardous voltage, which can lead to personal injury, death,property damage, or economic loss.IMPORTANTAbout the PowerMonitor1000 UnitThe power monitor is not designed for, or intended for, use as a circuitprotective device. Do not use this equipment in place of a motor overloadrelay or circuit protective relay.The power monitor is a compact, cost-effective, electric power, and energymetering device intended for use in industrial control applications, such asdistribution centers, industrial control panels, and motor control centers. Itmeasures voltage and current in an electrical circuit, meeting revenue accuracystandards. It communicates power and energy parameters to applications suchas FactoryTalk EnergyMetrix , SCADA systems, and programmablecontrollers, over Ethernet or serial networks. The power monitor works withthese applications to address key customer applications. Load profiling – log power parameters such as real power, apparentpower, and demand, for analysis of power usage by loads over time Cost allocation – reporting actual energy cost by department or processto integrate energy information into management decisionsRockwell Automation Publication 1408-UM002D-EN-P - November 20197

Chapter 1PowerMonitor 1000 Overview Billing and sub-billing – charging users of energy the actual usage costrather than allocating by square footage or other arbitrary methods Power system monitoring and control – display and control power flowand energy utilization Capacitor bank control - provides real and reactive power values for usein a PLC-based control systemThe power monitor connects to your three-phase or split-phase AC powersystem directly or through instrument transformers (PTs and CTs). The powermonitor converts instantaneous voltage and current values to digital values,and uses the resulting digital values in calculations of voltage, current, power,and energy.PowerMonitor 1000 UnitFeatures and FunctionsThe power monitor family includes three models: BC3 - Basic consumption meter TS3 - Basic consumption and troubleshooting meter EM3 – Energy, demand, and power monitorPowerMonitor 1000 unit models TR1, TR2, EM1, and EM2 have beendiscontinued.Hardware Features11423456xx : xx : xx : xx : 00 : 00EtherNet/IPRS-485RS-485RXTXSTATUSModPowerMonitor 1000Net - SHLDACT78LNK8910Rockwell Automation Publication 1408-UM002D-EN-P - November 2019111213

PowerMonitor 1000 OverviewChapter 1Table 1 - Hardware FeaturesFeatureDescriptionBC3TS31. Ethernet network port - standard RJ45jack with status indicatorsEthernet network port hardware is included on all models. The port functions only on units that areordered with or upgraded to the Ethernet network. The following protocols and functions are supported. EtherNet/IP Modbus TCP HTML webpage for configuration and data accessLNK indicator– Solid GREEN: IP link established– Off: no link establishedACT indicator– Flashing YELLOW: data present on Ethernet port– Off: no data activity presentXXX2. Serial port - three-pin RS-485 connector All models include RS-485 serial communication that supports the following protocols and functions. DF1 half-duplex slave DF1 full-duplex Modbus RTU slave Configuration by using terminal emulation software DH-485XXX3. Serial port status indicators TX indicator flashes YELLOW when data is being transmitted RX indicator flashes YELLOW when data is being receivedXXX4. LCD Unit configuration Data display– Not present on BC3 modelXX5. Module and network status indicators Module indicator– GREEN: Normal operation– Alternating RED/GREEN: Performing self-test– RED (solid or blinking): Initial power-up or failed self-test Network indicator– GREEN: Ethernet connection established– Blinking GREEN: Ethernet port looking for a connection– RED: Duplicate IP address detectedXX6. LCD interface buttons Unit configuration Data display navigation– Not present on BC3 modelXX7. Voltagesensing wiring terminals Direct connect up to 600V AC three-phase line-to-line Maximum nominal line-to-ground voltage 347V Use potential transformers (PTs) for higher voltagesXXX8. Currentsensing wiring terminals Nominal input current 5 A Use current transformers (CTs) to connect to power systemXXX9. DIN rail clips Top and bottom clips for mounting unit on DIN railXXX10. Status-input wiring terminalsRestore factory defaults wiringterminals (BC3) Two internally powered inputs (TS3, EM3) S2 can be used for demand period synchronization (TS3, EM3) FD1 and FD2 can be used to restore factory default configuration (BC3).XXX11. Configurationlock wiring terminals Wire together to help prevent configuration changesXXX12. KYZ-output wiring terminals DPDT solid-state relay for signaling use– Not present on BC3 modelXX13. Control power and ground wiringterminals 120 240V AC, 50 60 HzXXX14. MAC ID label aa:bb:cc:dd:ee:ff, used when assigning an IP address by using DHCP; X; X; XXXXRockwell Automation Publication 1408-UM002D-EN-P - November 2019XEM39

Chapter 1PowerMonitor 1000 OverviewFunctionality by ModelThe power monitor models differ by the data sets available to clientapplications. This table indicates the measurements and functions available ineach model.Table 2 - Model FunctionsMeasured VAXXXTrue Power equencyXXVoltage UnbalanceXXCurrent UnbalanceXXkW DemandXkVAR DemandXkVA DemandXProjected kW DemandXProjected kVAR DemandXProjected kVA DemandXDemand Power FactorXTime Of Use LogXXXEnergy LogXXXMinimum/Maximum LogXXXLoad Factor LogStatus LogXXDisplayXXXXAlarmsXStatus InputXXKYZ OutputXXTroubleshooting mode lets you enter a password-protected command thattemporarily promotes your PowerMonitor 1000 unit to an EM3 model. Thismode makes all measured parameters available for troubleshooting purposes.10Rockwell Automation Publication 1408-UM002D-EN-P - November 2019

PowerMonitor 1000 OverviewCommunication OverviewChapter 1All PowerMonitor 1000 units come standard with an RS-485 serialcommunication port. Models with catalog numbers ending in -ENT areequipped with an Ethernet 10Base-T communication port. This section coversserial and Ethernet communication, the available protocols, and whatprotocols to use for your application.What Can I Do Using Communication Networks?When you use communication networks with the power monitor, you can dothe following things. Configure analog input parameters such as PT/CT ratios Configure communication parameters such as IP address Read real-time power and energy data Read energy logsSerial CommunicationThe RS-485 serial communication port allows serial communication to yourpower monitor. This port can be configured to communicate by using theprotocols listed in this table.Table 3 - Serial Communication ProtocolsProtocolApplicationsDF1 Half-duplex SlaveThe DF1 Half-duplex Slave protocol can be used for point-to-point or multi-drop communication when using a DF1Polling Master driver in RSLinx Classic software, or using explicit messages from Rockwell Automation controllerscommunicating via DF1 Half-duplex Master.DF1 Full-duplexThe DF1 Full-duplex protocol can be used only for point-to-point communication by using an RS-232 DF1 driver forRSLinx software, or when using explicit messages from Rockwell Automation controllers communicating via DF1Full-duplex.Modbus RTU SlaveThe Modbus RTU Slave protocol can be used for point-to-point or multi-drop communication with a client by usingthe Modbus RTU Master protocol for PLC controller communication.Auto-senseWith auto-sense selected, the RS-485 port switches among the available serial protocols based on the format of thepackets the port receives.DH-485The DH-485 protocol can be used for point-to-point or multi-drop communication by using a 1747-PIC/AIC driverfor RSLinx software, or when using explicit messages from Allen-Bradley controllers or HMI (PanelView )terminals communicating via DH-485.ASCIIThe ASCII protocol is used with terminal emulation software to configure and read data using point-to-pointcommunication.TIPAll devices communicating on a serial network must be configured with thesame data rate and data format.DH-485 ProtocolDH-485 is a token-passing protocol that allows messaging by up to 32 nodeson a serial network. The master is the node that owns the token; only themaster can transmit messages. When a node has completed transmittingmessages, it passes the token to the next node.Rockwell Automation Publication 1408-UM002D-EN-P - November 201911

Chapter 1PowerMonitor 1000 OverviewThe power monitor does not initiate DH-485 data messages. When requested,it transmits reply messages to the initiator when it gets the token, and thenpasses the token to its successor.TIPPowerMonitor 1000 units only support DH-485 Local Link messages and donot support Send and Receive Data (SRD) messages for DH-485 non-tokenpassing slave devices.The DH-485 protocol uses the same data table addressing as DF1 protocols.See the CSP file number column of the PowerMonitor 1000 Data Tables.The following configuration factors have a significant effect on networkperformance and must be considered when you plan a DH-485 network. Number of Nodes - unnecessary nodes slows the data transfer rate. Themaximum number of nodes on the network is 32. Fewer nodes arebetter. Node Addresses - best to start node addresses at 0 and assign insequential order. Controllers cannot be node 0. Assigned the lowestnumbered addresses to initiators such as personal computers. Communication Rate - higher is better. All devices must be at the samecommunication rate. Maximum Node Address - set as low as possible to reduce the time ittakes to initialize the network.Ethernet Network CommunicationThe Ethernet network communication port allows communication with yourpower monitor by using a local area network (LAN). The Ethernet port canalso be used to view the internal webpage of the power monitor. This Ethernetport uses a static IP address by default (DHCP address assignment optional),and can simultaneously communicate by using the protocols that are listed.The Ethernet communication port supports 10 Mbps data rate, half-duplex.EtherNet/IP ProtocolThe power monitor supports the EtherNet/IP protocol for communicating viaEthernet or EtherNet/IP drivers in RSLinx Classic software, or when usingexplicit messages from Rockwell Automation controllers communicating viaEthernet or EtherNet/IP network.Modbus TCP ProtocolModbus TCP protocol is also supported for communicating via Modbus TCPfor communication.TIP12When configuring Ethernet communication, verify that IP addresses do notconflict with the existing infrastructure, and that subnet masks andgateways are properly set.Rockwell Automation Publication 1408-UM002D-EN-P - November 2019

Chapter2Installation and SetupPre-installation SetupWe recommend that you perform at least a minimal setup of the EthernetPowerMonitor 1000 unit before installation. This setup establishes a securitypolicy holder and configures the network port addressing so that the unit setupcan be completed over the Ethernet network after the unit is installed, wired,and power is applied.IMPORTANTPre-installation setup of the BC3 model is especially important since the BC3model has no display or keypad, and therefore all configuration must bedone by using communication.This section describes the equipment and steps that are needed to perform preinstallation setup.IMPORTANTIf the catalog number of your power monitor ends in -485, refer to the UseTerminal Emulation Software for Setup section.Equipment RequiredThe following equipment is needed for initial setup of the unit: A personal computer that can run Internet Explorer web browser A standard or cross-over patch Ethernet communication cable A power cordConfigure your computer LAN port with a fixed address. The recommendedsettings are the following: IP address: 192.168.254.250 Subnet mask: 255.255.0.0 Gateway: none requiredRockwell Automation Publication 1408-UM002D-EN-P - November 201913

Chapter 2Installation and SetupTemporarily Connect PowerConnect an unplugged power cord to the PowerMonitor 1000 unit as shownin Figure 1. L1 to L2 voltage must be 120 240V AC, 50 60 Hz. The groundterminal must be connected to earth ground. After the power cord isconnected, plug it in to a suitable electrical outlet. After the power on self test(POST) is complete, the left status indicator remains lit.Figure 1 - Temporary Power ConnectionConnect the Ethernet NetworkConnect the unit Ethernet port to your computer LAN port. The followingmethods can be used: Connect by using a cross-over UTP patch cable Connect by using two straight through UTP patch cables and a hub orswitch Connect by using a straight through UTP patch cable, if your computerNIC supports Auto MDIX14Rockwell Automation Publication 1408-UM002D-EN-P - November 2019

Installation and SetupChapter 2First Run WebpageFollow these steps after you have connected your computer to thePowerMonitor 1000 unit via the Ethernet network.1. Open Internet Explorer web browser and browse to the default IPaddress 192.168.254.x, where x is the Unit ID found on the label on theleft end of the unit.2. When the first run webpage appears, enter a policy holder user name, apassword, and password confirmation.You can also optionally enter your contact information.3. Click Confirm.IMPORTANTA security policy holder username and password must be entered toconfigure and use the PowerMonitor 1000 unit.IMPORTANTWrite down the policy holder username and password and keep them in asecure location. If these credentials are lost or forgotten, the factory defaultconfiguration has to be restored to recover the ability to configure security inthe unit.Figure 2 - Set Security Policy4. Confirm the prompt to reload the webpages.You can choose to continue with the security policy setup at this time orwait until later. See Security on page 51 for further information. If you choose to configure security now, you are already logged in as thepolicy holder. You can add admin and/or application users and enablewebpage access and CIP explicit message security. If you choose to wait, do not enter anything into the page, click Log Outand confirm when prompted. To configure security later, log in with thepolicy holder username and password and select the Security web link.Rockwell Automation Publication 1408-UM002D-EN-P - November 201915

Chapter 2Installation and SetupWith security disabled, the unit configuration is protected from inadvertent orunauthorized changes by a Table Password, with a default value of 0. You canassign another table password by using the Advanced Configuration web link.TIPIf you have updated firmware in a Series A PowerMonitor 1000 unit, thetable password remains the same as it had been before the update.With security enabled, an admin user must be logged in to the webpage tomodify the unit configuration. The table password fields are disabled and areignored by the unit.Figure 3 - Security Enabled16Rockwell Automation Publication 1408-UM002D-EN-P - November 2019

Installation and SetupChapter 2Initial Network ConfigurationThe next step is to assign the Ethernet network address. Follow these steps toassign a fixed address.1. Expand the Configuration Options folder and select EthernetConfiguration.2. Enter the table password, the 4 bytes of the IP address, subnet mask, andgateway address.3. When the values are entered, click Apply to store and apply the newnetwork address.Your power monitor unit is now ready to be installed. The unit cancommunicate on the Ethernet network and is ready to accept your finalconfiguration.Mount the PowerMonitor1000 UnitMount the PowerMonitor 1000 unit in a suitable protective enclosure. Selectan enclosure that helps protect the unit from atmospheric contaminants, suchas oil, water, moisture, dust, corrosive vapors, and other harmful airbornesubstances.The enclosure must help protect against personal contact with energizedcircuits. The ambient temperature within the enclosure must remain withinthe limits that are listed in Appendix B, Specifications. Select an enclosure thatprovides adequate clearance for ventilation and wiring for the power monitorand other equipment to be installed within the enclosure.See PowerMonitor 1000 Unit Dimensions on page 19 for dimensions andspacing guidelines for the power monitor.When installed in a substation or switchgear lineup, we recommend that thepower monitor is mounted within a low-voltage cubicle, isolated from mediumand high-voltage circuits. Be sure that the mounting panel is properlyconnected to a low-impedance earth ground.Rockwell Automation Publication 1408-UM002D-EN-P - November 201917

Chapter 2Installation and SetupMount the enclosure in a position that allows full access to the unit. The powermonitor can be mounted on a panel or a DIN rail.Panel MountFollow these steps to mount the unit on a panel or any flat surface.1. Extend the top and bottom DIN rail clips to the panel mount position.2. Insert a small screwdriver under the spring pin to move the clip, lift it,and pull the clip forward until it extends approximately 6 mm (0.25 in.)from the enclosure.3. Release the pin and lock the clip in the panel mount position.4. Mount the unit by using three M4 or #8 machine screws.DIN Rail MountYou can mount the unit on standard 35 x 7.5 mm (EN 50 022 – 35 x 7.7) DINrail. To mount on a DIN rail, leave the mounting clips retracted so themounting holes are hidden behind the unit.InstallFollow these steps to mount the unit on a DIN rail.1. Tilt the bottom of the unit slightly away from the rail until the notchesgrab onto the top flange of the DIN rail.2.

Rockwell Automation Publication 1408-UM002D-EN-P - November 2019 7 Chapter 1 PowerMonitor 1000 Overview Safety Follow these advisories when using this product. About the PowerMonitor 1000 Unit The power monitor

Related Documents:

rather than allocating by square footage or other arbitrary methods Power system monitoring and control - display and control power flow and energy utilization. 8 Rockwell Automation Publication 1420-UM001G-EN-P - April 2018 Chapter 1 PowerMonitor 500 Unit Overview

Cable Pack Sony Cable Pack P/Oly Cable Fuji. CAPTUR Compatibility Part No. 1000 710.0 1000 710.1 1000 710.4 1000 710.3 1000 710.2 1000 708.1 1000 708.3 1000 710.5 1000 710.6 1000 710.7 1000 711.0 1000 710.8 Range Up to 100m Up to 100m Up to 100m Up to 100m Up to 100m Up to 100m Up to 100m Up to 100m

4 PowerMonitor 5000 USB Driver Installation and Configuration 4. In the Found New Hardware Wizard dialog box, click Browse. 5. Select the folder containing the driver .inf file from the explorer dialog box. 6. Click Next in the previous dialog box. Wait while the driver installs. 7. Click Finish when the driver installation is complete.

panoramic X-ray machine and the PC-1000/Laser 1000 dental panoramic/cephalometric dental X-ray machine. The PC-1000 will enable the user to take panoramic X-ray images. The PC-1000/Laser 1000 will enable the user to take panoramic X-ray images, as well as cephalometric X-ray images. A laser alignment device is incorporated into the PC-1000 .

panoramic X-ray machine and the PC-1000/Laser 1000 dental panoramic/cephalometric dental X-ray machine. The PC-1000 will enable the user to take panoramic X-ray images. The PC-1000/Laser 1000 will enable the user to take panoramic X-ray images, as well as cephalometric X-ray images. A laser alignment device is incorporated into the PC-1000 .

Morphy Richards Fastbake Breadmaker 48280 User Manual Honda GCV160 User Manual Canon Powershot A95 User Manual HP Pocket PC IPAQ 3650 User Manual Navman FISH 4200 User Manual - Instruction Guide Jensen VM9021TS Multimedia Receiver User Manual Sanyo SCP-3100 User Manual Honda GC160 User Manual Canon AE-1 Camera User Manual Spektrum DX7 User Manual

EnKa English-Kannada 10,955 1000 1000 EnBa English-Bangla 13,623 1000 1000 EnHe English-Hebrew 10,501 1000 1000 HeEn Hebrew-English 9,447 1000 1000 Table 1: Official data sets in NEWS 2018 which we use in our experiments. transliteration datasets (Haizhou et al.,2004), and the VNU-HCMUS dataset (Cao et al.,2010;Ngo et al.,2015), respectively .

Ademco Passpoint Plus User Manual Morphy Richards Fastbake Breadmaker 48280 User Manual Honda GCV160 User Manual Canon Powershot A95 User Manual HP Pocket PC IPAQ 3650 User Manual Navman FISH 4200 User Manual - Instruction Guide Jensen VM9021TS Multimedia Receiver User Manual Sanyo SCP-3100 User Manual Honda GC160 User Manual Canon AE-1 Camera .

Trigonometry Unit 4 Unit 4 WB Unit 4 Unit 4 5 Free Particle Interactions: Weight and Friction Unit 5 Unit 5 ZA-Chapter 3 pp. 39-57 pp. 103-106 WB Unit 5 Unit 5 6 Constant Force Particle: Acceleration Unit 6 Unit 6 and ZA-Chapter 3 pp. 57-72 WB Unit 6 Parts C&B 6 Constant Force Particle: Acceleration Unit 6 Unit 6 and WB Unit 6 Unit 6

E-816 DLL Manual, PZ120E E-621.CR User Manual, PZ160E E-816 LabVIEW Software Manual, PZ121E E-621.SR, .LR User Manual, PZ115E Analog GCS LabVIEW Software Manual, PZ181E E-625.CR User Manual, PZ166E PIMikromove User Manual, SM148E E-625.SR, .LR User Manual, PZ167E E-665 User Manual, PZ127E E-801 User Manual

lEC 1000-4-3. Radiated Electromagnetic Field Requirements lEC 1000-4-4. Electrical Fast Transient (Burst) Requirements lEC 1000-4-5. Surge Voltage Immunity Requirements lEC 1000-4-6. Immunity to Conducted Disturbances Induced by Radio Frequency Fields Above 9kHz Sections lEC 1000-4-2 through lEC 1000-4-

Very Special Functions — unbeknownst to Mathematica and kinship numerical explorations of random matrix distributions 6 (a) (c)-1000 -500 0 500 1000-1000-500 0 500 1000 0 1000 2000 3000 0 500 1000 1500 2000 (b) (d) (mm) (mm) Fig. 3 Growing DSM2 cluster with a circular (a,b) and at (c,d) in

For more information contact Mike Cook 817.829.5174, mikesgdnctrld@swbell.net or contact Mark Cortez 817.360.7084, markcortez@aol.com Awards Sponsor 1000 Driving Range Sponsor 1000 Golf Cart Sponsor 1000 Hole In One Sponsor 1000 Putting Green Sponsor 1000 Beverage Sponsor 1000 Scorecard

Foiled Embossed (2 Designs in Catalog Only) Qty 500 Qty 1000 Add’l 1000’s Ink Colors Black 1 Color 2 Color Qty 250 Qty 500 Qty 1000 Add’l 1000’s Number of Sets 1 Set 2 Sets 3 Sets 4 Sets Qty 250 Qty 500 Qty 1000 Add’l 1000’s Business Cards 1 - 5 Working Days Finished Quantity i

Engraving Basswood 6-8 280 1000 Hardwood 6-8 280 1000 Bamboo 6-8 280 1000 Acrylic 6-8 280 1000 Kraftpaper 6-8 180 1000 Mirrors 6-8 280 1000 Stainlesssteel /aluminum alloy . machine cannotbe connectedto thesoftware (hererefersto the LaserGRBL software) DriverMissing, Canno

automatic tuners and related products for every amateur need. Congratulations on selecting the AT-1000 Pro 1000-watt automatic tuner. The AT-1000 Pro provides semi-automatic and fully automatic antenna tuning across the entire HF spectrum plus 6 meters, at power levels up to 1000 watts (S

A dc range 999.9 A 600 A 600A Best resolution 0.1 A 0.1 A 0.1 A V ac range 1000 V 1000 V 1000 V V dc range 1000 V 1000 V 1000 V mV dc range 500 mV 500 mV Ohms range 60.00 kΩ 60.00 kΩ 6,000 Ω Frequency 5-500.0 Hz 5-500.0 Hz Capacitance 1 μF-1,000 μF 1 μF-1,000 μF 1

eur/jpy 1.4 6.00% 1000 -0.0038% 0.0056% 24/5 eurjpy no aud/usd 0.8 4.50% 3.00% 1000 -0.0048% 0.0049% 24/5 audusd no eur/chf 1.5 6.00% 1000 -0.0051% 0.0048% 24/5 eurchf no eur/gbp 1 6.00% 1000 -0.0032% 0.0064% 24/5 eurgbp no usd/cad 1.5 3.00% 2.00% 1000 -0.0050% 0.0048% 24/5 usdcad no usd/chf 1 4.50% 3.00% 1000 -0.0068% 0.0031% 24/5 usdchf no

ice cream Unit 9: ice cream ka bio Unit 3: say it again kaa Unit 10: car kakra Unit 3: a little Kofi Unit 5: a name (boy born on Fri.) Koforidua Unit 4: Koforidua kↄ Unit 9: go Kↄ so Unit 7: Go ahead. kↄↄp Unit 9: cup kube Unit 10: coconut Kumase Unit 4: Kumasi Labadi Beach Unit 10: Labadi Beach

Keyboards Together 2 Music Medals Bronze Ensemble Pieces (ABRSM) B (T) In the Meadow Stood a Little Birch Tree Trad. Russian, arr. Mike Cornick: p. 3 B (T) Jazz Carousel Jane Sebba: p. 4 B (T) Heading for Home John Caudwell: p. 5 B (T) Don’t Mess with Me! Peter Gritton: p. 6