Low VoltageGeneral Purpose Motors

Making you more competitiveABB’s General purpose motor is designed for use in general industry, meeting thedemands of standard applications for OEM's. Motors are readily available fromcentral stock locations and distributors around the world. The motors have highbuild quality, are available with all the features needed by the OEM market andcan be modified to meet most specifications.1ABB (www.abb.com) is a leader inpower and automation technologiesthat enable utility and industrycustomers to improve performancewhile lowering environmental impacts.The ABB Group of companiesoperates in around 100 countries andemploys around 103,000 people.2ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors GB 12-2004

Low Voltage General Purpose MotorsSizes 56 to 400, from 0.055 to 630 kWContentsPage411Aluminum motors1123Steel motors8134Cast iron motors11345Open drip proof motors14756Global motors16767Brake motors19378Single phase motors21989Integral motors23791General information2ABB reserves the right to change thedesign, technical specification anddimensions without prior notice.ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors GB 12-20043

General informationStandardsABB motors are of the totally enclosed and open dripproof, single or three phase squirrel cage type, builtto comply with international IEC and EN standards.Motors conforming to other national and internationalspecifications are also available on request.1All production units are certified to ISO 9001 international quality standard as well ISO 14000 environmental standard and confirm to all applicable EUDirectives.4IEC / ENElectricalMechanicalIEC/EN 60034-1IEC/EN 60034-2IEC 60034-8IEC 60034-12IEC 60072IEC/EN 60034-5IEC/EN 60034-6IEC/EN 60034-7IEC/EN 60034-9IEC 60034-14ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors GB 12-2004

Motors for EU motor efficiency levelsA Europe-wide agreement willensure that the efficiency levelsof electric motors manufacturedin Europe are clearly displayed. Incontrast to the American legislationon motor efficiency the Europeanagreement does not establishmandatory efficiency levels.It basically establishes three classesgiving motor manufacturers anincentive to qualify for a higherclass.ABB is one of only a handful ofleading motor manufacturers inEurope to have a motor rangeto meet or exceed the minimumefficiencies stated in the highestlevel of the EU agreement of LVmotors.These efficiency levels apply to2- and 4-pole, three phase squirrelcage induction motors rated for400V, 50Hz with S1 duty class withthe output 1.1 to 90 kW, whichEU efficiency classes for 2-pole .693.9account for the largest volume onthe market.The efficiency of motors fromdifferent manufacturers are collatedin a database, EURODEEM,published by the EuropeanCommission. It is accessible overthe Internet at http://iamest.jrc.it/projects/eem/eurodeem.htm.ABB Three phase induction motors, 400 V50 Hz - EU motor efficiency 92.993.393.794.094.695.0EU efficiency classes for 4-pole 93.293.693.994.294.795.0ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors GB 12-200451

General technical specificationMechanical and electrical designMounting arrangementsCodeI/CodeIIProduct code pos. 12Foot-mounted motor.IM B3IM V5IM V6IM B6IM B7IM B8IM 1001 IM 1011 IM 1031 IM 1051 IM 1061 IM 1071A foot-mounted,term.box topR foot-mounted,term.box RHSL foot-mounted,term.box LHSFlange-mounted motor,large flangeIM B5IM V1IM V3*)*)*)IM 3001 IM 3011 IM 3031 IM 3051 IM 3061 IM 3071B flange mounted,large flangeFlange-mounted motor,small flangeIM B14 IM V18 IM V19 *)*)*)IM 3601 IM 3611 IM 3631 IM 3651 IM 3661 IM 3671C flange mounted,small flange1Foot- and flange-mounted IM B35 IM V15 IM V36 *)*)*)motor with feet,IM 2001 IM 2011 IM 2031 IM 2051 IM 2061 IM 2071large flangeFoot- and flange-mounted IM B34 IM V17motor with feet,IM 2101 IM 2111 IM 2131 IM 2151 IM 2161 IM 2171small flangeH foot/flange-mounted,term.box topS foot/flange-mounted,term.box RHST foot/flange-mounted,term.box LHSJ foot/flange-mounted,small flangeFoot-mounted motor,shaft with free extensions IM 1002 IM 1012 IM 1032 IM 1052 IM 1062 IM 1072*) Not stated in IEC 60034-7.6ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors GB 12-2004

CoolingDesignation system concerningmethods of cooling refers to standard IEC 60034-6.ExampleIC4(A)1(A) 6International CoolingCircuit arrangement0: Free circulation (open circuit)4: Frame surface cooledPrimary coolantA for air (omitted for simplified designation)Method of movement of primary coolant0: Free convection1: Self-circulation6: Machine-mounted independent component1Secondary coolantA for air (omitted for simplified designation)W for waterMethod of movement of secondary coolant0: Free convection1: Self-circulation6: Machine-mounted independent component8: Relative displacementDegrees of protection: IP code/IK codeClassification of degrees of protection provided by enclosures of rotating machines are refers to:- Standard IEC 60034-5 or EN 60529 for IP code- Standard EN 50102 for IK codeIP protection:Protection of persons against gettingin contact with (or approaching) liveparts and against contact with moving parts inside the enclosure. Alsoprotection of the machine against ingress of solid foreign objects. Protection of machines against the harmfuleffects due to the ingress of waterIK code :Classification of degrees of protection provided by enclosure formotors against external mechanicalimpacts.IP55Characteristic letterDegree of protection to persons and to parts of the motors inside the enclosure2: Motors protected against solid objects greater than 12 mm4: Motors protected against solid objects greater than 1 mm5: Dust-protected motors6: Dust-tight motorsDegree of protection provided by the enclosure with respectto harmful effects due to ingress of water3: Motors protected against spraying water4: Motors protected against splashing water5: Motors protected against water jets6: Motors protected against heavy seasIK08International mechanical protectionCharacteristic groupRelation between IK code and impact energy:IK codIK 0IK 01 IK 02 IK 03IK 04Impact*0.150.20.350.5energyJoule* not protected according to EN 50102IK 050.7IK 061ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors GB 12-2004IK 072IK 085IK 0910IK 1020ABBStandard7

InsulationABB uses class F insulation systems, which, withtemperature rise B, is the most common requirementamong industry today.1The use of Class F insulation with Class B temperaturerise gives ABB products a 25 C safety margin. This canbe used to increase the loading for limited periods, to operate at higher ambient temperatures or altitudes, or withgreater voltage and frequency tolerances. It can also beused to extend insulation life. For instance, a 10 K temperature reduction will extend the insulation life.Class F insulation system– Max ambient temperature 40 C– Max permissible temperature rise 105 K– Hotspot temperature margin 10 KClass B rise– Max ambient temperature 40 C– Max permissible temperature rise 80 K– Hotspot temperature margin 10 KInsulation system temperature class– Class F 155 C– Class B 130 C– Class H 180 CSafety margins per insulation class8ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors GB 12-2004

Frequency converter drivesSquirrel cage induction motors offer excellentavailability, reliability and efficiency. With a frequencyconverter – a variable speed drive (VSD) – the motorwill deliver even better value. A variable speed drivemotor can be started softly with low starting current,and the speed can be controlled and adjusted to suitthe application demand without steps over a widerange. Also the use of a frequency converter togetherwith a squirrel cage motor usually leads to remarkableenergy and environmental savings.However, all motors are not suitable for variable speeddrive. There are several points that have to be taken intoaccount in the design and selection of the motor, if it isintended for variable speed operation.Within the General purpose motor range ABB offersmotors designed for both Direct On Line (DOL) andvariable speed applications.For more demanding applications the use of ABBProcess performance motors is recommended.The following points must be taken into account, whenselecting a motor to a variable speed drive:1. DimensioningThe voltage (or current) fed by the frequency converteris not purely sinusoidal. This may increase the losses,vibration, and noise of the motor. Furthermore, achange in the distribution of the losses may affect to thetemperature rise of the motor. In each case, the motormust be correctly sized according to the instructionssupplied with the selected frequency converter.When using ABB converters, please use ABB'sDriveSize dimensioning programme or the loadabilitycurves of the corresponding converter type for sizingthe motors. The loadability curve for applicable Generalpurpose motors used with ABB's ACS 600- and ACS800- frequency converters can be found in figure 3.2. Speed rangeIn a frequency converter drive, the actual operatingspeed of the motor may deviate considerably from itsnominal speed (i.e. the speed stamped on the ratingplate).For higher speeds, ensure that the highest permissiblerotational speed of the motor or the critical speed of theentire equipment is not exceeded. When high speedoperation exceeds the nominal speed of the motor, thefollowing points should be checked:– Maximum torque of the motor– Bearing construction– Lubrication– Balancing– Critical speeds– Shaft seals– Ventilation– Fan noiseGuideline values of maximum speeds for M3AA motorswithin the General purpose motor range are describedin figure 1 below. Exact values are available on request.Figure 1. Guideline values of maximum speeds for Generalpurpose motor in aluminium frame:Motor sizeSpeed r/min2-pole4-poleM3AA 90-100M3AA 112-200M3AA 225-280600045003600600045003600At low speed operation the motor’s ventilation fanlooses its cooling capacity, which causes a highertemperature rise in the motor and in the bearings. Aseparate constant speed fan can be used to increasecooling capacity and loadability at low speed. It is alsoimportant to check the performance of the grease at lowspeeds.3. LubricationVariable speed operation affects on the bearingtemperature, which must be taken into account whenselecting the lubrication method and grease type.For example the life time of sealed bearings can beremarkably shorter than in direct on line operation. Moreinformation can be found from product specific sectionsof this catalogue and from ABB’s Low Voltage MotorsManual.4. Insulation protectionFrequency converter supply causes higher voltagestresses at the windings of the motor than thesinusoidal supply. Thus, the insulation system andpossible filters must be selected according to the usedvoltage, cable length and converter type.When using ABB’s low voltage frequency converters,selection criterias mentioned in figure 2 must befollowed.5. Bearing currentsBearing voltages and currents must be avoided in allmotors. Assuming the use of ABB ACS 800 or ACS 550drive, with uncontrolled DC-voltage, insulated bearingsand/or properly dimensioned filters at the converteroutput must be used according to the instructions infigure 2. (For other alternatives and converter types,please contact ABB.) When ordering, clearly statewhich alternative will be used.For more information about bearing currents andvoltages, please contact ABB.ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors GB 12-200491

6. Cabling, grounding and EMCThe use of a frequency converter puts higher demandson the cabling and grounding of the drive system. Themotor must be cabled by using shielded symmetricalcables and cable glands providing 360 bonding(also called EMC-glands). For motors up to 30 kWunsymmetrical cables can be used, but shielded cablesare always recommended.“Grounding and cabling of the drive system” (Code:3AFY 61201998 R0125 REV A) and the ABB’s LowVoltage Motors Manual.For fulfilling the EMC requirements, special EMCcable(s) must be used in addition to the correct cablegland mounting, with special, extra earthing pieces.Please refer to the manuals of the frequency converter.More information about grounding and cabling of avariable speed drive can be found from the manual1ValidityMeasures mentioned in Figure 2 apply to the applicable motors within the General motors range (not high-outputversions) with ACS 800 and ACS 550 drives with uncontrolled DC-voltage. For other alternatives and convertertypes, please contact ABB.Figure 2. Selection rules for insulation and filtering in variable speed drivesMotor nominal power PN or frame sizePN 100 kWPN 100 kW or IEC 315PN 350 kW IEC 450UN 500 VStandard motorStandard motor Insulated N-bearingStandard motor Insulated N-bearing Common mode filterUN 600 VStandard motor dU/dt-filterORReinforced insulationStandard motor dU/dt-filter (reactor) Insulated N-bearingORReinforced insulation Insulated N-bearingStandard motor Insulated N-bearing dU/dt-filter Common mode filterORReinforced insulation Insulated N-bearing Common mode filterUN 690 VReinforced insulation dU/dt-filterReinforced insulation dU/dt-filter (reactor) Insulated N-bearingReinforced insulation Insulated N-bearing dU/dt-filter Common mode filterdU/dt filter (reactor)Series reactor. DU/dt -filter decreases the changing rate of the phaseand main voltages and thus reduces voltage stresses in the windings.DU/dt -filters also decrease so-called common mode currents and therisk of bearing currents.Common mode filtersCommon mode filters reduce so-called common mode currents inVSD applications and thus decrease the risk of bearing currents.Common mode filters do not significantly affect the phase or mainvoltages on the motor terminals.Insulated BearingsBearings with insulated inner or outer races are used as the standardsolution. So-called hybrid bearings, i.e. bearings with non-conductiveceramic balls, can also be used in special applications. Moreinformation for spare part selection is available on request.Figure 3. Motor loadability with ACS 600 and ACS 800, Field weakening point 50 Hz.10ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors GB 12-2004

General Purpose Aluminum MotorsTotally enclosed squirrel cage three phase lowvoltage motors,Sizes 56 - 280, 0.06 to 95 kW2www.abb.com/motor&drives Motors Low voltage motors General purpose motorsMechanical design. 12Rating plates . 22Ordering information . 23Technical data . 24Variant codes . 46Dimension drawings . 53Accessories . 74Aluminum motors in brief . 77ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors / Aluminum GB 12-200411

Mechanical designStatorStator framework, bearing shields and feet are madeof an extra corrosion resistant aluminum alloy with lowcopper content with the following exceptions:M2AA 180-250 and M3AA 250 SMA-2 basic version,have cast iron feet.M3AA 280 has feet and D-end shield of cast iron.M3AA 250 SMB 2-pole, high output version, as wellas M3AA 280 2-pole have cast iron feet and bearingshields.The flange bearing shields of sizes 180 to 280 aremade of cast iron.Drain holes2Motors that will be operated in very humid or wetenvironments and especially under intermittent dutyshould be provided with drain holes. The appropriate IMdesignation, such as IM 3031, is specified on the basisof the method of mounting the motor.Motors are provided with closable plastic plugs in thedrain holes (see diagram below). The plugs will be openon delivery. When mounting the motors it should be ensured that the drain holes face downwards. In the caseof vertical mounting, the upper plug must be hammered home completely. In very dusty environments both12plugs should be hammered home.Sizes 56 to 63 are supplied as standard with drainholes on D-end while sizes 71 to 280 are supplied withdrain holes both on D-end and N-end.When mounting arrangement differs from foot mountedIM B3, please mention variant code 066 when ordering.See variant codes 065, 066 and 076 under the heading“Drain holes”.ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors / Aluminum GB 12-2004

Terminal boxSizes 56 to 180 and M2AA 200The terminal box is made of aluminum alloy and islocated on top of the stator. The lower part of the box isintegrated with the stator. It is provided with 2 knockoutopenings on each side. Sizes 160-180 also have a thirdsmaller opening. Cable glands are not included.other side is provided with a cover flange.The motors can also be provided with an extra largeterminal box, standard for voltage code S and framesize 280. See variant code 019 under the heading“Terminal box”. This will increase the dimension HD by32 mm. The box is supplied with two FL 21 openings.The right opening is provided with a flange with twoholes for M63 cable glands. The holes are sealed bymeans of plastic plugs. Cable glands are not supplied.The opening on the other side is provided with a coverflange. The box can also be provided with an FL 13opening towards the N-end.Sizes 200 to 280, except M2AA 200The terminal box and cover are made of deep drawnsteel and mounted on top of the stator. The box is bolted to the stator and is not rotatable. The size of the boxis the same for all motors.In the basic design the terminal box is provided withtwo FL 13 flange openings, one on each side. The opening on the right side, seen from the D-end, is suppliedwith a flange with two holes for M40 cable glands. Ondelivery the holes are sealed by means of plastic plugs.Cable glands are not supplied. The opening on theTerminal box size 56-80.Terminal box size 112-132.Terminal box size 90-100.Terminal box size 200-280,except M2AA 200.Terminal box size 160-180and M2AA 200.ConnectionsThe terminal block is provided with6 terminals for connecting Cu-cable. The terminals are marked inaccordance with IEC 60034-8.When new motors are manufactured the terminal boxcan be mounted on the left or the right side. See variantcodes 021 and 180 under the heading “Terminal box”.Connection openingsMotorsizeOpening56-63Knock-out opening71-80Knock-out opening90-100112-132160-180200 1)200-250 2)280Knock-out openingKnock-out openingKnock-out openingKnock-out opening2 x FL 132 x FL 211)M2AA2)Metriccable entryMethod ofconnectionTerminalbolt sizeMaximumconnectableCu-cablearea, mm21 x M16 x 1.51 x Pg 112 x M20 x 1.52 x Pg 162 x (M25 M20)2 x (M25 M20)2 x (2 x M40 M16)2 x (2 x M40 M16)1 x (2 x M40 M16)1 x (2 x M63 M16)Screw terminalM42.5Screw terminalM44Screw terminalCable lugCable lugCable lugCable lugCable lugM4M5M6M6M10M1061035357070M2AA 200 excludedABB LV Motors / Cat. BU / Low Voltage General Purpose Motors / Aluminum GB 12-2004132

BearingsThe motors are provided with bearings according to thetables below.in such cases the axial force must only operate in onedirection.Greater axial forces can be tolerated if the motors areprovided with angular contact ball bearings. Note thatMotor versions with roller bearings tolerate greaterradial forces.Basic version with deep groove ball bearingsAlternative designs:Version with roller bearings2Basic design motorsMotorsizeFoot- and flange-mounted motorD-endN-end5663718090100112 2)112 2)132 2)132 2)160180200 1)200225 1)225250 1)2502802806201-2Z/C

In a frequency converter drive, the actual operating speed of the motor may deviate considerably from its nominal speed (i.e. the speed stamped on the rating plate). For higher speeds, ensure that the highest permissible rotational speed of the motor or the critical speed of the entire equipment is not exceeded. When high speed operation exceeds the nominal speed of the motor, the following .

Related Documents:

Low voltage induction motors – IEC and NEMA High voltage induction motors Inverters Eddy current variable speed drives Drip proof motors – LV and HV DC motors Synchronous motors Vertical hollow shaft motors Hazardous area motors High efficiency motors Brake motor

Motors with corrosion resistant parts Wheel motors with recessed mounting flange OMP, OMR- motors with needle bearing OMR motor in low leakage version OMR motors in a super low leakage version Short motors without bearings Ultra short motors Motors with integrated positive holding brake Motors with integrated negative holding brake .

2 Low voltage General performance IE2 high efficiency motors EN 06-2011 ABB Motors and Generators We provide motors and generators, services and expertise to save energy . Motor range for cast iron motors 71 to 355, 0.25 to 250 kW and aluminum motors is 56 to 250, 0.06 to 55 kW.

2 ABB LV Motors / Cat. BU / General purpose motors GB 09-2003 1 Making you more competitive ABB's General purpose motors are readily available from central stock locations and distributors throughout the world. While designed for standard and straightforward uses, the motors can be modified to meet most specifications.

There is a separate manual for e.g. Ex motors ‘Low voltage motors for hazardous areas: Installation, operation and maintenance Manual’ (Low Voltage Motors/Manual for Ex-motors). Additional information is required for some machine types due to special a

the supplier's works. Squirrel-cage and slip-ring motors in mechanical/electrical modifications: Three-phase motors for use aboard ships, squirrel-cage type 0.09 - 490 kW Three-phase motors to IEC/DIN, squirrel-cage type 0.06 - 500 kW Three-phase motors, squirrel-cage type 2.2 - 315 kW Three-phase brake motors 0.12 .

2 ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors EN 12-2006. 1. ABB is a global leader in power and automation technologies that enable utility and industry customers to improve their performance while lowering environmental impact. The ABB Group of companies operates in around 100 countries and employs about 107,000 people.

pump Conventional water pump Switchable water pump Variable water pump Module Engine cooling fan motors Geared motors for engine mount Idle speed control stepping motors Base bracket for oil cooler Heat-Resistant Products Powertrain ABS/EPS motors Suspension oil valve control ABS ECU stepping motors Chassis Electric power steering motors & ECU