Programming Guide

3y ago
26 Views
3 Downloads
2.35 MB
72 Pages
Last View : 2m ago
Last Download : 2m ago
Upload by : Kairi Hasson
Transcription

VISTA-128FBPVISTA-250FBPCommercial Fire and BurglaryPartitioned Security System with SchedulingProgramming GuideK0376PRV5 2/11 Rev. A

Table of ContentsRelay Voice Descriptors and Custom WordSubstitutes Vocabulary. 41System Layout Worksheets. 43Output Devices Worksheets . 59Scheduling Menu Prompts . 65Scheduling Worksheets. 66Programming Field Settings for UL864 Compliance 2Recommended Programming Procedure. 6Program Field Index . 7VISTA-128FBP/VISTA-250FBP Programming Form8Partition-Specific Fields. 14Programming With #93 Menu Mode . 165800 Series Transmitters Loop Designations . 21Alpha Descriptor Vocabulary. 31Programming Field Settings for UL864 ComplianceNOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVEDPARTIESThis product incorporates field-programmable software. In order for the product to comply with the requirementsin the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming featuresor options must be limited to specific values or not used at all as indicated below.Program feature or option Permitted in Possible settingsSettings permitted in UL 864UL864? Y/N 08 TEMPORAL SIREN PULSEN0 disable1 enableNot used at this time. Must be set to“0” (disable). 13 ALARM SOUNDER (BELL)TIMEOUT 14 TRIGGER OR RS232YEnter 01-15 multiplied by 2 minutes.00 no timeout.0 trigger1 RS232 input0 disable1 enableEnter 01 - 09 for the first digit;enter11 for “*” or 12 for “#” for thesecond digit.0 disable1 enableMust be set to “3” (Minimum of 6minutes).Must be set to “0”.0 disable1 enable0 disable1 enableEnter 0001-9999 for the test reportinterval in hours.Enter 0000 for test reporting.0 disable1 enable0 disable1 enable0 EOLR supervision1 N.C. loopsEnter the wait time for dial tonedetection:0 5 seconds; 1 11 seconds; 2 30seconds.Enter 00 to disable ring detection.Enter 01-14 for ring counts of 1-14.Enter 15 to select Answering MachineDefeat ModeMust be set to “1” (enabled).N 17 AC LOSS KEYPADSOUNDING 20 VIP MODULE PHONECODEN 22 KEYPAD PANICENABLES (PARTITIONSPECIFIC) 23 MULTIPLE ALARMS(PARTITION SPECIFIC) 26 INTELLIGENT TESTREPORTING 27 TEST REPORT INTERVALN 28 POWERUP IN PREVIOUSSTATE 37 DOWNLOAD COMMANDENABLES 41 NORMALLY CLOSED OREOLR (ZONES 3-8) 42 DIAL TONE PAUSEY 44 RING DETECTIONCOUNTNNNYNNYN–2–Must be set to “1” (enabled).Not used. Must be set to “00”.Must be set to “000” for partition 1in fire systems.Must be set to “0” (disable).Must be set to “0024” (Maximum 24hours)Must be set to “1” (enable).Must be set to “0” for all entries(disable).Must be set to “0” (EOLRSupervision).Must be set to “0” (5 seconds).Must be set to “00” (disable).

Program feature or option 54 UNATTENDED MODE 56 DYNAMIC SIGNALINGDELAY 77 AUTO TROUBLERESTORE 80 ZONE TYPE RESTORESFOR TYPES 9, 10 & 141 12 PROGRAMNOTIFICATION SIGNAL1 13 SYSTEM SENSORREVERSING RELAYPermitted inUL864? Y/NNYYNYN1 18 AFFECTS LOBBYN1 19 ARMS LOBBYN1 22thru 1 25 CROSS-ZONINGPAIRS (1 – 4)1 28 RF TRANSMITTER LOWBATTERY SOUND1 29 RF TRANSMITTER LOWBATTERY REPORTING1 30 RF RECEIVERSUPERVISION CHECK-ININTERVALN1 31 RF TRANSMITTERCHECK-IN INTERVALN1 35 ACCESS CONTROLDIALER ENABLES1 44 WIRELESS KEYPADTAMPER DETECTION1 45 EXIT DELAY SOUNDING(PARTITION SPECIFIC)1 48 WIRELESS KEYPADASSIGNMENT1 49 SUPPRESS TXSUPERVISION SOUND1 53 DISABLE DOWNLOADCALLBACK1 57 5800 RF BUTTONGLOBAL ARM1 58 5800 RF BUTTON FORCEARM1 60 ZONE 5 AUDIO ALARMVERIFICATION1 69 PRINTER TYPENNNNNNNNNNNNN1 72 EVENT LOG PRINTERONLINE1 73 PRINTER BAUD RATEN1 76 CONTROL RELAY(PART-SPECIFIC)1 78 EXTENDED HOMECONT EVENTSN1 79 HOME CONTROLEVENTS2 07 AUTO-DISARM DELAY(PART SPECIFIC)NNNNPossible settingsSettings permitted in UL 8640 disable1 enableEnter 00-15 times 15 seconds.Must be set to “0” (disable).0 disable1 enable0 disable1 enable0 no1 yesMust be set to “1” (enable).0 use neither Zone 1 or Zone 2 inputs1 use Zone 1 input;2 use Zone 2 input;3 use Zone 1 and Zone 2 inputs.0 disable1 enable0 disable1 enableEnter 001-250Enter 000,000 to disable0 disarmed state only1 both armed and disarmed states0 disable1 enableEnter 02–15 times 2 hours (4–30hours)Enter 00 to disable receiversupervisionEnter 02–15 times 2 hours (4–30hours)Enter 00 to disable transmittersupervision0 disable1 enable0 disable1 enable0 disable1 enable0 none1-8 partition number0 disable1 enable0 callback required1 no callback required0 disable1 enable0 disable1 enable0 disable1 enable0 parallel printer1 serial printer0 disable1 enable0 12001 30001-96 relay number00 relay not used.1 extended0 limited0 disable1 enable00 no delay.01-14 times 4 minutes (04-56) delay.15 no auto disarming.–3–Must be set to “6” (90 seconds).Must be set to “1” (enable) for zonetype 9.Must be set to “1” (yes).Not Used. Must be set to “0”.Must be set to “0” (disabled) forpartition 1.Must be set to “0” (disabled) forpartition 1.Must be set to “000,000” (disabled)for fire zones.Must be set to “1” (both armed anddisarmed states).Must be set to “1” (enable).Maximum is 02 (4 hours) for fireinstallations.Maximum is 02 (4 hours) for fireinstallations.Not used. Must be set to “0”.Not used. Must be set to “0”.Must be set to “0” (disable) forpartition 1.Not used. Must be set to “0”.Must be set to “0” (disable).Must be set to “0” (callbackrequired).Must be set to “0” (disable).Must be set to “0” (disable).Must be set to “0” (disable).Not used.Not used. Must be set to “0”.Not used.Must be set to “00” (relay not used)for partition 1.Not used. Must be set to “0”.Not used. Must be set to “0” in eachentry.Must be set to “15” (no autodisarming) for partition 1.

Program feature or optionPermitted inUL864? Y/N2 18 ENABLE GOTO FORTHIS PARTITION (partitionspecific)2 21 SUPERVISION PULSESFOR COMMUNICATIONSDEVICE2 22 DISPLAY FIRE ALARMSOF OTHER PARTITIONS2 23 DISPLAY BURG, PANICAND CO ALARMS FOR OTHERPARTITIONS2 24 DISPLAY TROUBLES OFOTHER PARTITIONS2 30 - 2 88 (PAGER OPTIONS)3 01 EVENTS DISPLAY LOCKN0 disable1 enableMust be set to “0” (disable) forpartition 1.N0 disable1 enableNot used. Must be set to “00000”(disable).N0 disable1 enable0 disable1 enableMust be set to “0” (disable) forpartition 1.Must be set to “0” (disable) forpartition 1.Must be set to “0” (disable) forpartition 1.Not used.Must be set to “1” (enable).3 12 ZN TYPE 18 DELAY USEN3 13 FIRE SUPERVISORYRESPONSE TO OPEN/SHORT(APPLIES TO ZONE TYPE 18)3 14 WATERFLOW ALARMSILENCE OPTION3 16 DELAY FOR ZONETYPES 17 & 18(Waterflow/Supervisory)3 18 EXTENDED DELAY FORZONE TYPES 17 & 18 Multipliesdelay in 3*16 x 4)3 19 AUXILIARY INPUTALTERNATE FUNCTIONENABLE3 20 TRIGGER OUTPUTSFUNCTION SELECTION3 21 MAXIMUM NUMBER OFDIALER ATEMPTS3 50 ZONE TYPE RESTOREENABLES FOR TYPES 16-183 55 RESET ON SECOND OFFFOR BELL 13 56 RESET ON SECOND OFFFOR BELL 23 57 BELL 2 AND AX RELAYCONFIRM ARMING DING3 59 ENABLE BELL 2 &AUXILIARY RELAY CHIMEANNUNCIATION3 60 BELL 2 & AUX RELAYTIMEOUT3 82 BURGLARY FEATURESON PARTITION 1 ENABLERESTRICTION FOR FIRERELAYSN0 disable1 enableNA0 disable1 enable0 disable1 enable0 Trouble on open/Supv on short1 Supv on open/Supv on short0 Silenced by User Code OFF1 Silenced when zone restoresEnter 01-15 times 2 secondsEnter 00 for no delayMust be set to “0” (Silenced by UserCode OFF).Must be set to 00 (no delay).N0 no extended delay1 multiply delay by 4Must be set to 0 (no extended delay).N0 disable1 enableMust be set to 0 (disable).N0 remote keypad sounder1 keyswitch LEDs1-8Must be set to 0 (remote keypadsounder).Must be set at 3, 4 or 5.0 disable1 enable0 disable1 enable0 disable1 enable0 disable1 enable0 disable1 enableMust be set to “1” (enable).Enter 01-15 multiplied by 2 minutes.00 no timeout.0 disable1 enableYesNoMust be set to “3” (Minimum of 6minutes).Must be set to “0” (disable).NNNNNNYNNNNNYNYPossible settings–4–Settings permitted in UL 864Must be set to “0” (disable).Must be set to “0”.Must be set to “0” (disable).Must be set to “0” (disable).Must be set to “0, 0” (disable).Must be set to “0” (disable) if Bell 2or Aux Relay is used for Fire.Restriction for # 70 must be set toYes when programming fire relays.

NOTE: All references in this manual for number of zones, number of user codes, number of access cards, and theevent log capacity, use the VISTA-250FBP’s features. The following table lists the differences between the VISTA128FBP and the VISTA-250FBP control panels. All other features are identical.FeatureNumber of ZonesNumber of User CodesEvent Log CapacityVistakey ModulesNumber of Access 0015500The purpose of this document is to provide a quick and easy way to program your entire system. A recommendedprogramming procedure is included, followed by a list of program fields with the corresponding program group they belong to(system-wide, partition-specific, scheduling, etc.). Two program forms are included. One contains all the programming fields,and the other contains the partition-specific fields. If you are setting up a single-partition system, the partition-specific fieldsbecome system-wide fields.Following the program forms are system layout worksheets. We recommend that you use these sheets to plan your systembefore programming is performed. If you need further information about specific programming options, see the VISTA128FBP/VISTA-250FBP Installation and Setup Guide.Make sure that one two-line alpha keypad is connected to the control and is set to device address "00."Single-Partition SystemThe system default is for a single-partition system. Use the VISTA-128FBP/VISTA-250FBP SINGLE PARTITIONPROGRAMMING FORM when programming for single-partition usage. Follow the steps outlined in RECOMMENDEDPROGRAMMING PROCEDURE of this document for proper programming procedure.Multiple-Partition SystemYou must enter the number of partitions you are using in data field 2*00 to set the system for multiple partitions. Use theVISTA-128FBP/VISTA-250FBP SINGLE PARTITION and the PARTITION-SPECIFIC PROGRAM FORMS whenprogramming the system for multiple partitions. Follow the steps outlined in RECOMMENDED PROGRAMMINGPROCEDURE of this document for proper programming procedure. SUMMARY OF PROGRAMMING COMMANDSTo enter program mode, enter installer code [8] [0] [0] [0]To set standard defaults, press 97To change to next page of program fields, press 94To return to previous set of fields, press 99To erase account and phone number field entries, press [ ] field number [ ]To assign zone descriptors, press #93 follow menu promptsTo add custom words, press #93 follow menu promptsTo enter Installer's Message, press #93 follow menu promptsTo exit program mode, enter 99 OR 98: 99 allows re-access to programming mode by installer code. 98 prevents re-access to programming mode by installer code. The only way to re-access programmingmode is by depressing both the [ ] and [#] keys at the same time within 30 seconds of power-up.Standard default ( 97) values are shown in brackets [ ], otherwise default 0.–5–

Recommended Programming ProcedureThe following is a step-by-step procedure recommended for programming your VISTA-128FBP/VISTA-250FBPsystem.1. Set the keypads (and other peripheral devices) to the appropriate addresses.2. Set factory defaults by pressing 97.This will automatically enable keypad addresses 00-01, so be sure at least one keypad is set to one of theseaddresses.3. Program system-wide (global) data fields.Using the programming form as a guide, enter program mode and program all system-wide programmingfields. These options affect the entire system, regardless of partitions. They include control options,downloader and dialer options, RF options, event logging options, etc. Refer to the Program Field Index for alisting of the program fields and their function.Note that field 2 00 (number of partitions) must be programmed before continuing.4. Program partition-specific fields.When the system-wide fields have been programmed, program all partition-specific programming fields byfirst pressing 91 to select a partition (while still in data field program mode). Then enter the first partitionspecific field number 09. When you are finished, the next partition-specific field is automatically displayed.Partition-specific fields can have different values for each partition. To program the fields for the next partition,press 91, enter the desired partition number, then enter field 09. Refer to the MECHANICS OFPROGRAMMING section in the VISTA-128FBP/VISTA-250FBP Installation and Setup Guide for detailedinstructions.5. Use #93 Menu Mode for device programming.Refer to Device Programming in this guide to assign keypad ID numbers and default partitions for eachkeypad, and to selectively suppress certain keypad sounding options. Also use this mode to assign RFreceivers, relay modules, the VIP module, and Communicators (7845i-ent, 7845GSM, 7845i-GSM).6. Use #93 Menu Mode for zone programming.Refer to Zone Programming in this guide to program zone response types, assign right loop zones andwireless zones, assign zones to partitions, and to program alarm report codes.7. Use #93 Menu Mode for programming outputs.Refer to Output Programming in this guide to program desired output operation.8. Program Communication options.Refer to System Communication section in the VISTA-128FBP/VISTA-250FBP Installation and Setup Guidefor detailed instructions. Then use #93 menu mode to program report codes.9. Use #93 Menu Mode for programming alpha descriptors.Refer to Alpha Programming in this guide to enter zone and partition descriptors and a custom installer'smessage.10. Use #80 Mode for programming schedules.Refer to the Scheduling Menu Prompts in the VISTA-128FBP/VISTA-250FBP Installation and Setup Guide toprogram open/close schedules, temporary and holiday schedules, limitation of access schedules, and timedriven events.11. Define user access codes.Refer to User Access Codes in the VISTA-128FBP/VISTA-250FBP Installation and Setup Guide to programauthority level, O/C reporting option, partition assignments, and wireless key assignments for each user.12. Exit Programming Mode.Exit programming mode by pressing either 98 or 99. Additional entries of 99 are required if the exit isbeing done from fields 1 00 and above.To prevent re-access to programming mode using the Installer's code, use 98. The only way to re-accessprogramming mode is by depressing both the [ ] and [#] keys at the same time within 30 seconds of powerup.Exiting by using 99 always allows reentry into programming mode using the Installer code. Either way ofexiting allows access via downloading. Note that if local programming lockout is set via downloading,programming mode cannot be entered at the keypad.–6–

Program Field IndexOn the following pages, the programming fields have been arranged in numerical order. Use this index to cross-reference thefields on the programming form.FieldGroupField GroupField System-Wide

VISTA-128FBP/VISTA-250FBP Programming FormSome fields are programmed for each partition (shown as shaded fields). If you are programming a multiple-partition system,see the Partition-Specific Fields section for programming these fields. Standard default (*97) values are shown in brackets [ ];otherwise, default 0.*00 INSTALLER CODE *17 AC LOSS KEYPAD SOUNDINGEnter 4 digits, 0-9 [5140][1]1 enable; 0 disableMust be "1" for Commercial Fire installations.*04 ENABLE RANDOM TIMERS*19 RANDOMIZE AC LOSS REPORT12345678Enter 1 to make available the randomizing of pre-programmedtime driven events for each partition. [0 disable].Must be "0" for Commercial Burg installations.*05 SYSTEM EVENTS NOTIFY0 within 2 minutes; 1 10-40 min; 2 1-3 hours; 3 6-12 hourswithout Type 13, 1-3 hours with Type 13.*20 VIP MODULE PHONE CODE - Not used. [0]*06 QUICK EXIT[1]1 enable; 0 disable*22 KEYPAD PANIC ENABLES*08 TEMPORAL SIREN PULSE – Not Used at this time.00,

NOTE: All references in this manual for number of zones, number of user codes, number of access cards, and the event log capacity, use the VISTA-250FBP’s features. The following table lists the differences between the VISTA-128FBP and the VISTA-250FBP control panels. All other features are identical. Feature VISTA-128FBP VISTA-250FBP

Related Documents:

Object Oriented Programming 7 Purpose of the CoursePurpose of the Course To introduce several programming paradigms including Object-Oriented Programming, Generic Programming, Design Patterns To show how to use these programming schemes with the C programming language to build “good” programs.

Functional programming paradigm History Features and concepts Examples: Lisp ML 3 UMBC Functional Programming The Functional Programming Paradigm is one of the major programming paradigms. FP is a type of declarative programming paradigm Also known as applicative programming and value-oriented

1 1 Programming Paradigms ØImperative Programming – Fortran, C, Pascal ØFunctional Programming – Lisp ØObject Oriented Programming – Simula, C , Smalltalk ØLogic Programming - Prolog 2 Parallel Programming A misconception occurs that parallel

About this Programming Manual The PT Programming Manual is designed to serve as a reference to programming the Panasonic Hybrid IP-PBX using a Panasonic proprietary telephone (PT) with display. The PT Programming Manual is divided into the following sections: Section 1, Overview Provides an overview of programming the PBX. Section 2, PT Programming

Programming paradigms Structured programming: all programs are seen as composed of control structures Object-oriented programming (OOP): Java, C , C#, Python Functional programming: Clojure, Haskell Logic programming based on formal logic: Prolog, Answer set programming (ASP), Datalog

Programming is the key word here because you make the computer do what you want by programming it. Programming is like putting the soul inside a body. This book intends to teach you the basics of programming using GNU Smalltalk programming language. GNU Smalltalk is an implementation of the Smalltalk-80 programming language and

A Guide to Programming in Java is written for a one-term or two-term course. No previous programming experience is required or assumed. . ment programming solutions with proper algorithm design and code conventions. Programming Style Throughout the text, proper programming style . Each lesson includes assignments, teaching notes, worksheets,

2.3 Installer's Programming Commands Installer's programming commands are used only in Installer's Programming Mode. To execute an installer's command, enter the command and press [#]. Table 4 on page 5 shows the installer's programming commands. Table 4: Installer's Programming Commands Command Description 959 Test programming key