Compact Room Automation Stations, BACnet MS/TP, AC 24 V

2y ago
21 Views
2 Downloads
623.02 KB
16 Pages
Last View : 22d ago
Last Download : 3m ago
Upload by : Kaleb Stephen
Transcription

Desigo Room AutomationCompact room automation stations, BACnet MS/TP, AC 24 VDXR2.M11., DXR2.M12P., DXR2.M12PX., DXR2.M18.For building with increased demands placed on functionality and flexibility in RoomAutomation and VAV applications. CM1N9207en2020-10-08Compact, programmable room automation stations for HVAC, lighting, andshadingCommunication BACnet MS/TP (BTL certified)KNX PL-Link bus to connect sensors, actuators, and operator units (including buspower)USB interfaceOperating voltage AC 24 VMounted on standard DIN rails or on the wallPlug-in terminal blocksSmart Infrastructure

FeaturesProgrammableThe DXR2. room automation stations provide the infrastructure for system and applicationspecific functions and can be programmed.Compact seriesThe compact build permits mounting in narrow spaces and on standardized rails, and isparticularly well suited for compact panels or plants with integrated panel.Plug-in terminal blocksPlug-in terminal blocks to easily exchange room automation stations.Use Room automation applications combining multiple disciplines (HVAC, lighting, shading)into one comprehensive solution. Desigo TM room automation offers the highest degreeof flexibility for energy-optimized solutions without sacrificing on comfort.Room automation applications can be extended with lighting and blinds applications viathe KNX PL-Link.Preinstalled applications Variable (VAV) and constant (CAV) air volume or variable air volume with a serial orparallel fan powered box– with 2-stage electric heating– with hot water– with hot water and flow temperature control Fan coil: Cooling or heating with heat pump, outside air control– Single stage, multi-stage, or variable speed fan– Single stage, multi-stage, or variable speed compressor– Internal or external reversing valve– Geothermal or water circuit source– Optional hot gas reheater– Optional electric (staged or modulating) or hot water reheater or hot gas reheater Fan coil: Cooling or heating, cooling and heating (2-pipe) or cooling/heating (4-pipe),supply air minimum limitations, outside air control Dual duct variable air volume (VAV)– Cold air duct, hot air duct with configurable ventilation delivery– Dual duct, dedicated configurable ventilation duct with hot water or electric heatingcoils– Dual duct with constant volume option Chilled beam active or passive cooling (2-pipe) or cooling/heating (2-pipe) orcooling/heating (4-pipe) Radiant ceiling: Cooling, cooling and heating (2-pipe) or cooling/heating (4-pipe) Radiator: Hot water, steam (2-pipe or 4-pipe) or electric stage controlled Lighting: Up to 4 different zones Blinds: 1 or 2 motorsApplication options Separate temperature and volume setpoints for all 4 operating modes Singe-stage or variable ventilation control (fan powered box) Chilled water and hot water valve (2-pipe or 4-pipe) Extract air flow acquisition and control2SiemensSmart InfrastructureCM1N9207en2020-10-08

FunctionsThe selected application and its parameters as well as input and output configurationdetermine the room automation station's functionality.A detailed description of functionality is available in the ABT (Automation Building Tool)online help.Communication BACnet MS/TP USB connection for service and commissioning, firmware download, and LAN access. The following functions are available with the KNX PL-Link bus:– Communication with room operator units, switches, sensors, actuators, andluminaires.– Plug-and-play connection of Siemens field devices with KNX PL-Link.LED indicationLEDColorActivityFunctionRUNGreenSteady ONDevice is ready for operationSteady OFFDevice is not poweredRegular flashingStart-up or the program is stoppedSteady OFFOKSteady ONProgram errorCommunications error (KNX PL-Link)Hardware faultRapid flashingWrong or corrupt softwareNo application loadedBlinking per wink commandPhysical device identificationRed5 Hz2s1s5 Hz2s1sService button (SVC)Physical identification on the network.Technical designPower supplyThe power supply provides controlled voltages for inputs and outputs. The room automationstations also supply AC 24 V field supply (DXR2.18, DC 24 V too). The supply is located inthe device to simplify wiring and diagnostics.The processor controls the power supply. This ensures clean conditions for field devicesconnected to the I/Os during startup, shutdown, and undervoltage.Bus power supplyThe room automation station includes the bus power for KNX PL-Link. The bus power isswitched on by default, but can be switched off via web interface or configuration in theAutomation Building Tool (ABT).The internal KNX PL-Link supply cannot be operated parallel to external power supplies. Theinternal KNX PL-Link power must be switched off during the engineering phase for externalpower. This is typically the case if the 50 mA from the internal supply is not enough to supplyall devices connected on the KNX PL-Link bus.SiemensSmart Infrastructure3CM1N9207en2020-10-08

Type summaryThe devices are supplied without terminal covers. The terminal covers must be orderedseparately. See Accessories.Order numbers: World (excluding the U.S. and Canada)TypeStock -C112Fan coil, radiant ceiling, radiator,4 luminaires & 2 blinds1 DI, 2 UI6 Triacs, 2 AODXR2.M12P-102A(Version with 30data points)S55376-C114Variable air volume, dual duct VAV, fanpowered box, radiant ceiling, radiator,4 luminaires & 2 blinds1 DI, 2 UI,ΔP sensor6 Triacs, 2 AODXR2.M12PX-102A(Version with 60data points)S55376-C144Variable air volume, dual duct VAV, fanpowered box, radiant ceiling, radiator,4 luminaires & 2 blinds1 DI, 2 UI,ΔP sensor6 Triacs, 2 AODXR2.M18-101AS55376-C113Fan coil, dual duct VAV, radiant ceiling,radiator, 4 luminaires & 2 blinds2 DI, 4 UI8 Triacs, 4 AODXR2.M18-102AS55376-C129Variable air volume, fan-powered box,radiant ceiling, radiator, 4 luminaires &2 blindsOrder numbers: U.S. and CanadaTypeStock -C122Fan coil, heat pump, radiant ceiling,radiator, 4 luminaires & 2 blinds1 DI, 2 UI6 Triacs, 2 AODXR2.M12P-102B(Version with 30data points)S55376-C123Variable air volume, dual duct VAV, fanpowered box, radiant ceiling, radiator,4 luminaires & 2 blinds1 DI, 2 UI,ΔP sensor6 Triacs, 2 AODXR2.M12PX-102B(Version with 60data points)S55374-C251Variable air volume, dual duct VAV, fanpowered box, radiant ceiling, radiator,4 luminaires & 2 blinds1 DI, 2 UI,ΔP sensor6 Triacs, 2 AODXR2.M18-101BS55376-C124Fan coil, dual duct VAV, heat pump,radiant ceiling, radiator, 4 luminaires &2 blinds2 DI, 4 UI8 Triacs, 4 AOTypeStock numberDesignationDXA.H180S55376-C120Terminal cover for DXR. 180 mm, 2 piecesAccessoriesProduct documentationTopicTitleDocument ID:Engineering, mounting and installationDesigo TM Room AutomationCM111043Engineering and commissioning,workflowABT online helpn/aCommissioningDesigo Raumautomation - Setup and ServiceAssistantCM111050Product environmental declarationProduct environmental declaration 230 VCM1E9204Product environmental declarationProduct environmental declaration 24 VCM1E9205Related documents such as the environmental declarations, CE declarations, etc., can bedownloaded from the following Internet rt InfrastructureCM1N9207en2020-10-08

NotesSafetyCAUTIONNational safety regulationsFailure to comply with national safety regulations may result in personal injury and propertydamage. Observe national provisions and comply with the appropriate safety regulations.EngineeringIdentificationEach device has a unique serial number to ensure efficient commissioning. It is provided onthe adhesive barcode label. The serial number can be read directly into the engineering toolusing a barcode reader.WiringWiring must be sufficiently insulated to the available rated voltage. Sizing and fusing of thewiring depends on the connected load.Triac outputs AC 24 VIndividual Triac outputs may have a max. load of 6 VA (heating up the device). The followingpossibilities are permitted: Multiple motorized actuators with a total of max. 6 VA. 1 thermal actuator with 6 VA start load in a cold state, controlled using the algorithmPWM 0.100%. 2 thermal actuators with 6 VA start load each in a cold state, controlled using thealgorithm PWM 5.50%.For transformer design (voltage drop off), each thermal actuator must be counted at the fullstart load, since the Triac outputs can be freely controlled.The heating sequence and cooling sequence are not normally active at the same time(Exception: Downdraft compensation).The sum total of the base load, bus power, field supply, and Triacs may not exceed 72 VA(DXR2.E.) or 70 VA (DXR2.M.). Power consumption is 96 VA with pulse width modulation.See Section Power data.For the DXR2. 24 V variant, the high side switch Triacs (closed the contact at AC 24 V) areused. As a result, the VAV compact controllers GDB181.1E/3 or GLB181.1E/3 can only beset to operating mode "con" via 0.10 V.DC 0 10 V outputsThe DC 0 10 V outputs supply max. 1 mA.AC 24 V supply for field devices (V )Actuators (valves, dampers) and active sensors are supplied directly by the device. SeparateAC 24 V power supply is only required if field devices consume more than 12 VA (onDXR2.x11. and DXR2.x12.) or 18 VA (on DXR2.x18).DC 24 V power supply for field devices (V ), DXR2.x18 onlyActuators (valves, dampers) and active sensors are supplied directly by the device. Aseparate DC 24 V field supply is only required if field devices use more than 2.4 Watts.Digital inputsDigital inputs are not suitable for operating lighting or blinds. Use the KNK PL-Linkpushbutton.SiemensSmart Infrastructure5CM1N9207en2020-10-08

MountingThe room automation stations can be snapped onto standard rails or screwed onto a flatsurface.CAUTIONRisk of overheating for failure to comply with ambient temperatureBurning and damage to the device Ensure sufficient ventilation to comply with the permissible ambient temperature withinthe panel or installation box. The temperature must be 10 C (18 F) lower outside theinstallation box.Mounting positionAmbient temperature -5.45 C (23.113 F)Ambient temperature -5.50 C (23.122 F)1.2. 3.OverheadWall, vertically–From top to bottom–From bottom to topWall, horizontal–From left to right–From right to leftOn a horizontal surfaceDifferential pressure sensor Avoid bends and pressure when attaching the tube. Connect the " " connection on the side with the higher pressure and the "-" connectionon the side with the lower pressure. A tube length of 2 m (6 ft) is recommended.InstallationWARNINGRisk of fire and injury due to short circuits! Adapt as per local regulations the wiring cross section to the rated value of the installedfuse.Strain reliefStrain relief protects flexible electrical wiring against mechanical stress.The wiring must be fixed using cable binders to the tabs on the housing base.9205J01Terminal coverBreak off the cable inlets to insert the cables to the room automation station.To take off the terminal cover:6SiemensSmart InfrastructureCM1N9207en2020-10-08

OperationThe outputs have no electricity when power fails.USB communications that does not work points to improper grounding of AC 24 V operatingvoltage (connection must be grounded).DisposalThe device is considered an electronic device for disposal in accordancewith the European Guidelines and may not be disposed of as domesticgarbage. Dispose of the device through channels provided for this purpose. Comply with all local and currently applicable laws and regulations.WarrantyTechnical data on specific applications is only valid on Siemens products. Siemens rejectsany and all warranties in the event that third-party products are used.SiemensSmart Infrastructure7CM1N9207en2020-10-08

Technical dataHousingColorRAL 7035 (light-gray)DimensionsSee al coverPackagingca. 330 gca. 340 gca. 360 gca. 80 gca. 40 gProcessorTexas Instruments AM3352, 300 MHzRAM128 MByte SDRAM (DDR3)512 MByte NAND FlashFunction dataCommunicationA/D Resolution (analog in)D/A Resolution (analog out)14 Bit12 BitPower dataPower supplyOperating voltageAC 24 V -15%/ 20%Frequency50/60 HzPower consumption including connected field devicesDXR2.M11.DXR2.M12P.DXR2.M18.Max. 58 VAMax. 58 VAMax. 82 VAInternal fuse4 A irreversibleTransformer with secondary current limitation of max. 10A or external secondary current fuseMax. 10 A, slowNon-renewable fuseMax. 13 A, characteristic B, C, D as per EN 60898Circuit breakersApparent power (VA) for transformer designBase loadincluding I/Owithout loadby fielddevicesMax. outputload Triac at250 mA eachMax. load forAC 24 V fieldsupply at500/750 mAMax. loadKNX PL-Linkat 50 mAMax. load forDC 24 V fieldsupply at 100mAPowerconsumptionincludingconnectedfield devicesDXR2.M11.66 x 6 36(72 withPWM *)124-58(94 withPWM *)DXR2.M12P.66 x 6 36(72 withPWM *)124-58(94 withPWM *)DXR2.M18.68 x 6 48(88 withPWM *)184682(96 withPWM *)*) For thermal valve actuators (starting current) with pulse width modulation 5.50% andpulse length of ca. 1 s.Power for the Triac outputs must be reduced if the max. load of 18 VA is required for AC 24V field supply on the DXR2.x18.8SiemensSmart InfrastructureCM1N9207en2020-10-08

InputsThe inputs are protected against incorrect wiring AC 24 V.Inputs: OverviewTypeInputsDXR2.M11.1 DI, 2 UIDXR2.M12P.1 DI, 2 UI, ΔP sensorDXR2.M18.2 DI, 4 UIResistance sensor, analog (inputs X.)TypeRange (over range)ResolutionAI 1000 Ohm *)1 kΩ (0.1.05 kΩ)1ΩAI 2500 Ohm *)2.5 kΩ (0.2.625 kΩ)2.5 ΩAI 10 kOhm *)10 kΩ (0.10.5 kΩ)10 ΩAI 100 kOhm *)100 kΩ (0.105 kΩ)100 ΩTemperature measurement, analog (inputs X.)TypeRange (over range)ResolutionAI PT1K 375 (NA) *)-40.70 C (-45.75 C)-40.158 F (-49.167 F)25 mK0.045 FAI PT1K 385 (EU) *)-40.70 C (-45.75 C)-40.158 F (-49.167 F)25 mK0.045 FAI (LG-)Ni1000 *)-40.70 C (-45.75 C)-40.158 F (-49.167 F)25 mK0.045 FAI Ni1000 DIN *)-40.70 C (-45.75 C)-40.158 F (-49.167 F)25 mK0.045 FAI T1 (PTC) *)-40.70 C (-45.75 C)-40.158 F (-49.167 F)100 mK0.18 FAI NTC10K-40.70 C (-45.75 C)-40.158 F (-49.167 F)25 mK (25 C)0.045 F (77 F)AI NTC100K-10.70 C (-15.75 C)14.158 F (5.167 F)25 mK (25 C)0.045 F (77 F)*) A fixed value of 1 Ω is calibrated to correct line resistance.Voltage measurement, analog (inputs X.)TypeRange (over range)ResolutionAI 0.10 V0.10 V (-1.11 V)2 mVAI 0.10 V standard0.100% (-10.110%)2 mVOpen connection: Negative voltage -1.5 V, 8 μA (line failure detection)Digital input (inputs X. or D.)SiemensSmart InfrastructureContact query voltageUniversal input: 18 VDigital input: 21 VContact query currentUniversal input: 1.2 mA, 7.4 mA initial currentDigital input: 1.6 mA; 9.4 mA initial currentContact resistance for closed contactsMax. 100 ΩContact resistance for open contactsMin. 50 kΩ9CM1N9207en2020-10-08

Differential pressure sensor (inputs P1 , P1-)Connections (nipple diameter)5.2 mmMeasuring range0.500 PaOverload range0.100 kPaMeasuring range accuracyZero point accuracyResolution4.5%0.2 Pa12 BitOutputsThe outputs are protected against short circuiting and incorrect wiring AC 24 V.Outputs: OverviewTypeOutputsDXR2.M11.6 Triacs, 2 AODXR2.M12P.6 Triacs, 2 AODXR2.M18.8 Triacs, 4 AOAnalog (outputs Y10.Y40)TypeRange (over range)ResolutionOutput currentAO 0-10 V0.10 V (0 10.5 V)2 mVMax. 1 mAAO 0-10 V standard0.100%0% 0 V, 100% 10 V(0.10.5 V)2 mVMax. 1 mASwitching outputs Triac (outputs Y1.Y8)TypeHigh sideThe Triac closes the contact to AC 24 VSwitching voltageAC 24 VPermissible load250 mA / 6 VA per output (cos phi 0.35)(500 mA / 12 VA per output with PWM *)ProtectionShort-circuit proof*) For thermal valve actuators (starting current) with pulse width modulation 5.50% andpulse length of ca. 1 s.Supply for field devices (outputs V )Output voltageAC 24 VPermissible loadDXR2.x11. und DXR2.x12P.DXR2.x18.500 mA / 12 VA overall750 mA / 18 VA overallProtection against overloadShort-circuit proofPower supply for field devices on DXR2.x18 (output V )10SiemensSmart InfrastructureOutput voltageDC 24 VPermissible load100 mA/2.4 WProtection against overloadShort-circuit proofCM1N9207en2020-10-08

ConnectionsInterfacesMS/TPInterface type: RS485Galvanic isolation: YesBaud rates: 9600, 19200, 38400, 57600, 115200Protocol: BACnet over MS/TPShort-circuit proof protection against faulty wiring at max. AC 24 VUSB (2.0)Plug: Type BData rate: 12 MbpsKNXType: KNX TP1 PL-Link, galvanic isolationBaud rate: 9.6 kbpsBus power: 50 mAShort-circuit proof, and protected against faulty wiring at max. AC 24 VWiring connectionsPluggable screw terminalsCopper wire or copper stranded wire with connector sleeves1 x 0.6 mm ø to 2.5 mm2 (22 to 14 AWG) or2 x 0.6 mm ø to 1 mm2 (22 to 18 AWG)Copper stranded wire without connector sleeves1 x 0.6 mm ø to 2.5 mm2 (22 to 14 AWG) or2 x 0.6 mm ø to 1.5 mm2 (22 to 16 AWG)Stripping length6.7.5 mm (0.24.0.29 in)Slotted screwsSize 1, tightening torque 0.6 Nm (0.44 lb-ft)Wiring lengths for signalsKNX PL-Link 80 m (260 ft) with internal bus power or 300 m(990 ft) with external power supplyMS/TP 1,000 m (3,290 ft)Signal lines 80 m (260 ft)For inputs AI 100 kOhm, AI NTC10K, AI NTC100K: 30 m (100 ft)or 80 m (260 ft), if shielded.ConformityAmbient conditions and protection classificationClassification per IEC/EN 60730Function of automatic control devicesPollution degreeOvervoltage categoryDesign typeDegree of protection of housing to IEC EN 60529Room automation stationWith terminal coverDevice suited for use with equipment of safety classes Iand IIIP20IP30Climatic ambient conditions Transport (packaged for transport) as per IECEN 60721-3-2 Operation as per IEC/EN 60721-3-3Mechanical ambient conditionsTransport as per IEC/EN 60721-3-2Operation as per IEC/EN 60721-3-3SiemensSmart InfrastructureType 12IIIClass 2K3Temperature -25.70 C (-13. 158 F)Air humidity 5.95% (non-condensing)Class 3K5Temperature -5.45 C (23. 113 F)/-5.50 C (23. 122 F)See MountingAir humidity 5.95% (non-condensing)Class 2M2Class 3M211CM1N9207en2020-10-08

Standards, directives and approvalsProduct standardIEC/EN 60730-1Automatic electronic controls for household and similaruseProduct family standardEN 50491-2, EN 50491-3, EN 50491-5General requirements for Home and Building ElectronicSystems (HBES) and Building Automation and ControlSystems (BACS)Electromagnetic compatibilityFor residential, commercial, and industrial environmentsEU conformity (CE)EU declaration of conformance DXR2. AC 230 V, seeCM1T9204xx 1EU declaration of conformance DXR2. AC 24 V, seeCM1T9204xx 2RCM conformityRCM declaration of conformance DXR2. seeCM1T9204xx C1EAC complianceEurasien compliance for all DXR2.xxx-xxxA variantsUL ApprobationUL as per UL916, http://ul.com/databasecUL as per CSA – C22.2 No. 205FCC CFR 47 Part 15 Class BFederal Communications CommissionBACnetBTL listed, BACnet Advanced Application Controller(B-AAC)BACnet Protocol Revision 13Environmental compatibilityThe product environmental declaration () contains dataon environmentally compatible product design andassessments (RoHS compliance, materialscomposition, packaging, environmental benefit,disposal).See Section Product documentation.QualityISO 9001 (Quality)Connection 3 MS/TPMS/TP connection11, 12 KNXKNX connection , -31.36 inputsDigital inputUSB12SiemensSmart InfrastructureTerminalModuleChannelD111Universal inputX1, X215, 6System neutral Field supply AC 24 V for active sensorsV , , -USB interfaceCM1N9207en2020-10-08

PinDescriptionTerminal51.52 power 24 V Power supply AC 24 VV System neutral (must always be grounded at thetransformer) Switching output AC 24 VY1.Y6System neutral Positioning output DC 0.10 VY10, Y20System neutral Field supply AC 24 VV ServiceService buttonSVCDisplayOperation LEDRUN61.69 Triacs81.84 analogoutputsModuleChannel111.6211, 29205Z01DXR2.M12PDXR2.M12PPinDescription21.23 MS/TPMS/TP connection11, 12 KNXKNX connection , -31.36 inputsDigital inputUniversal inputSystem neutral Field supply AC 24 V for active sensorsV ModuleChannelD111X1, X215, 6111.6211, 2, , -USBUSB interface51.52 power 24 V Power supply SELV / PELV AC 24 VV System neutral (must always be grounded at thetransformer) Switching output AC 24 VY1.Y6System neutral Positioning output DC 0.10 VY10, Y20System neutral Field supply AC 24 VV ΔP differentialpressure detectorConnected to the higher pressureP1 311Connected to the lower pressureP1-311ServiceService buttonSVCDisplayOperation LEDRUN61.69 Triacs81.84 analogoutputsSiemensSmart InfrastructureTerminal13CM1N9207en2020-10-08

9205Z03DXR2.M18DXR2.M18PinDescription21.23 MS/TPMS/TP connection11, 12 KNXKNX connection , -31.41 inputsDigital inputUniversal inputSystem neutral Field supply AC 24 V for active sensorsV Field supply DC 24 V for active sensorsV ModuleChannelD1, D211, 2X1.X415.8111.8211.4, , -USBUSB interface51.52 power 24 V Power supply SELV / PELV AC 24 VV System neutral (must always be grounded at thetransformer) Switching output AC 24 VY1.Y8System neutral Positioning output DC 0.10 VY10.Y40System neutral Field supply AC 24 VV ServiceService buttonSVCDisplayOperation LEDRUN61.72 Triacs81.88 analogoutputs14SiemensSmart InfrastructureTerminalCM1N9207en2020-10-08

DimensionsWithout terminal cover4,5 mm(0.18 in)4,2 mm (0.16 in)165 mm (6.5 in)9205M0159,5 mm(2.34 in)104,5 mm (4.11 in)35,5 mm(1.4 in)97,6 mm (3.84 in)6180 mm (7.09 in)59,5 mm(2.34 in)SiemensSmart Infrastructure137,3 mm(5.4 in)35,5 mm(1.4 in)With terminal cover9205M0215CM1N9207en2020-10-08

Issued bySiemens Switzerland LtdSmart InfrastructureGlobal HeadquartersTheilerstrasse 1aCH-6300 ZugTel. 41 58 724 mart InfrastructureDocument IDCM1N9207enEdition2020-10-08 Siemens Switzerland Ltd, 2013Technical specifications and availability subject to change without notice.CM1N9207en2020-10-08

4 luminaires & 2 blinds 1 DI, 2 UI, ΔP sensor 6 Triacs, 2 AO DXR2.M18-101A S55376-C113 Fan coil, dual duct VAV, radiant ceiling, radiator, 4 luminaires & 2 blinds 2 DI, 4 UI 8 Triacs, 4 AO DXR2.M18-102A S55376-C129 Variable air volume, fan-powered box, radiant ceiling, radiator, 4 luminaires & 2 blinds

Related Documents:

The MCS-BACNET-ROUTER2 is a BTL-certified BACnet router between MS/TP and B/IP (BACnet over IP) as well as a BBMD (BACnet Broadcast Management Device) for transportation of BACnet broadcasts over an IP network with several subnets. Additionally, it can serve as a BACnet time master and a BACnet MS/TP slave proxy.

2.4.2 Setting the Device Instance (Node-ID) for BACnet MS/TP and BACnet/IP on ProtoNode RER (FPC-N34 BACnet) The A Bank of DIP switches are also used to set the BACnet Device Instance. The BACnet Device Instance can range from 1 to 4,194,303. BACnet/IP/BACnet MS/TP Addressing: The BACnet device will be set by taking the instance

Control or BACnet/IP specific decoding), BACnet (BACnet NPDU or network layer decoding), and BACapp (BACnet APDU or application layer decoding). A common display filter to view all BACnet messages containing an NPDU would be "bacnet." A display filter to view only BACnet WriteProperty service packets would be "bacapp.confirmed_service

Product Name: BACnet OPC-Client Product Model Number: 1.0 Applications Software Version: 1.0 Firmware Revision: 1.0 BACnet Protocol Revision: 1.4 (BACnet ANSI/ASHRAE 135-2004) Product Description: The BACnet OPC-Client is a software-product which converts data from an OPC-Server to a BACnet-Server. BACnet Standardized Device Profile (Annex L):

The purpose of this document is to describe implemented BACnet functionality and available BACnet objects on tSENSE. The reader of this document is assumed to have basic knowledge about the BACnet protocol. Information about BACnet can be found at www.bacnet.org. 3. BACnet protocol services and object types supported

The i-Vu or Field Assistant BACnet Discovery feature locates all accessible BACnet networks, BACnet devices, and BACnet objects (including devices in your i-Vu Plus or Pro or Field Assistant system) on a BACnet network. NOTE BACnet Discovery is not available in the i-Vu Standard application. To use BACnet Discovery:

2.1 CIM 3XX BACnet module Fig. 1 CIM 3XX BACnet module 1. Symbols used in this document 4 2. Applications 4 2.1 CIM 3XX BACnet module 4 3. Installation 5 3.1 Connecting the BACnet module 5 3.2 Termination resistor 5 3.3 Setting the BACnet MAC address 6 3.4 Setting the Device Object instance number 6 3.5 Setting the BACnet transmission speed 6 4 .

1.1 About BACnet OPC Server The BACnet OPC Server is a software gateway which translates the BACnet protocol on one side (typically BACnet/IP) to an OPC data format so that data can be exchanged between a Building Automation network and a SCADA system. The BACnet OPC Server software must be loaded on the same physical computer as the OPC Client .