Creating An Accessible WorldELVORON STELLA HOME ELEVATORDesign And Planning GuideLuxury Residential Elevator (shown with glass enclosure)www.garaventalift.com

Please note:Dimensions provided in this Guide are for REFERENCE ONLYand should not be used for site preparation or construction.

Table of ContentsWhat is an Elvoron Stella? . 4Design Assistance . 4Finishes . 4How It Works . 5Hoistway . 6Construction of Pit . 7Overhead Clearance (Refuge Space) . 7Pit Lighting . 7Loading Diagram . 8Car Sizes & Configurations . 9Layouts & Clearances . 10Operating Controls . 16Car Operating Panel (COP) . 16Hall Stations . 16Car Direction Lantern . 16Doors - Entrance and Car Doors . 17Door Details – Masonry Walls . 18Door Details – Wood and Drywall Walls . 19Technical Information . 20Machine Room Requirements . 21Machine Room Layouts. 22Mains Power Requirements . 23

Design Hot Line: 1-800-663-6556 or 1-604-594-0422What is an Elvoron Stella?FinishesThe Elvoron Stella is a luxury residential elevator withsliding elevator doors. It utilizes the same drive andcontrol systems as a LU/LA (limited use, limited application) commercial elevator. A LU/LA elevator is apower passenger elevator. The use of these productsis limited by local regulations, which can vary fromplace to place.Your Elvoron Stella elevator will quickly become partof everyday movement within your home. Designyour elevator car using a variety of attractive anddurable wall and ceiling finishes. All Elvoron Stellacars are supplied with basic plywood floors ready forinstallation of your preferred flooring material, assupplied by others.The definition of a LU/LA elevator is one that is limited by size, capacity, speed and rise. The ElvoronLU/LA elevator provides a code compliant automaticelevator with a variety of platform configurations andcan service up to 6 landings. The wide selection ofcab finishes and options ensure that it will blend intoany setting.Car WallsCar walls are covered in wood veneer or plasticlaminate panel sections. Available wood veneerspecies include maple, red oak, cherry, mahogany,birch, walnut, hickory, makore and bamboo. Eightstandard colors of plastic laminate are offerred, andany exisiting plastic laminate can be accomodated.What are the limitations of an Elvoron Stella? Travel – 32 feet (9.75 m) with 1400 lb. (635 kg)capacity, 36 feet (10.9 m) with 1000 lb. (455 kg)capacity Speed – 40 fpm Maximum Platform Size – 18 square feet (1.67square meters) Maximum Capacity – 1400 lbs (635 kg), optional1000 lbs (455 kg)Want to customize your elevator car to match theinterior of your home? Cars with walls of unfinishedfibercore board, to be finished by others, are alsopopular.Car Wall TrimCar Wall Trim separates the car wall panels and addsthe finishing touch to your elevator cab. The standardtrim is available in black or white. Custom colors andstainless steel trims are optional.Why an Elvoron Stella?Fully Automatic Doors - Standard home elevatorshave accordian-style cab gates and are interlockedto standard swinging hoistway entrance doors. TheElvoron Stella features commercial-quality two-speedautomatic sliding doors. These are heavy-duty elevator doors which are extremely reliable.Entrance Door and Car DoorsLike a commercial elevator, the Elvoron Stella isequipped with two-speed horizontal sliding landingentrances and car doors. The car doors are finished tomatch your car wall trim. The landing entrance doorsare primed and ready to be painted to match yourbuilding décor. All doors can be supplied in brushedstainless steel (optional).Heavy-duty Lifting Components - The ElvoronStella is equipped with heavy-duty structural components. The machinery is the same as is used for theElvoron LU/LA commercial elevator and allows for anincreased carrying capacity of 1400 lbs. (635 kg).Ceiling and Halogen LightingAll Elvoron Stella elevators are equipped with fourrecessed low-voltage halogen lamps that illuminateautomatically when the doors open. Ceiling choicesare white, black, stainless steel or custom. Whitelamps are fitted into white ceilings and black into allother options.Design AssistanceWith over 40 years of experience, Garaventa Lift hasthe expertise to overcome almost any design challenge you face. Please call our Design Hotline.1-800-663-6556orHandrailAll Elvoron Stella cars are equipped with one brushedstainless steel handrail on the control wall. Additionalhandrails can be mounted on the other car walls.1-604-594-0422ELVORON STELLA Design & Planning Guide77932-D-DPCustom Car FinishesYour car interior can be customized to whateverunique design best suits your home. Our customshop offers a wide variety of wall, ceiling and fixturealternatives. We can also create elegant stainlesssteel and panoramic glass cars.-4-

Design Hot Line: 1-800-663-6556 or 1-604-594-0422How It Works-5-www.garaventalift.com

Design Hot Line: 1-800-663-6556 or 1-604-594-0422HoistwayThe walls of the elevator hoistway can be constructedof wood, poured concrete or concrete block. Thewall behind the cylinder and guide rails must be loadbearing and able to withstand the loads imposed bythe elevator.capacity, size of cab and travel height. Please seefinal elevator shop drawings for actual locations.All the walls of the hoistway, especially the wall behindthe rails and the entrance walls, need to be flush andplumb from floor to ceiling to within /- 1/8”. This isto allow for the required running clearances.The cylinder and guide rails are mounted to the wallwith steel brackets. These rail brackets are fastenedto the load bearing wall at regular intervals.No light is required at the top of the hoistway as thecar top is equipped with a standard caged light fixturefor use by the mechanic during his maintenancevisits. A light is required in the pit (see Constructionof Pit for details).The rail bracket spacing is determined during thedesign phase. The rail brackets are generally every4’ apart, measured vertically, depending on the loadRail Brackets attached towall - locations indicatedon shop drawingELVORON STELLA Design & Planning Guide77932-D-DP-6-

Design Hot Line: 1-800-663-6556 or 1-604-594-0422Construction of PitA pit ladder is required only if the pit depthexceeds 35” (900mm). Consult your Garaventa Liftrepresentative for details as changes to finishedhoistway are required.The pit must be the same width and length as thehoistway. The majority of the weight of the lift isborne by the plunger (ram). Reactions are indicatedon each project’s shop drawings. A minimum 14”(355 mm) pit is required.Pit LightingA pit light and GFI duplex receptacle, supplied by theGeneral Contractor, are required in the pit of yourElvoron Stella for use by the mechanic during hismaintenance visit. Consult Garaventa Lift dealer forlocation and routing of conduit.Overhead Clearance (Refuge Space)135” (3429mm) is required above the upper landinglevel finished floor to the ceiling above to meetthe refuge space required by code. On existingconstruction, a car top prop can be used to reducethe overhead to 114” (2997mm). If your overheadspace is less than 114” (2997mm) please contactGaraventa Lift.Habitable space below hoistway will require the pit tobe increased in depth to a minimum 16” (406mm) toaccommodate the required buffer springs.It is preferable tofill concrete blockswith concreteTypical construction shown:For alternate construction methods (wood or steelstud walls), refer to a structural engineer to ensureconstruction method will support the loads shown onthe loading diagram, page 8.Dimensions shown are for REFERENCE ONLY andshould not be used for site preparation or construction.-7-www.garaventalift.com

Design Hot Line: 1-800-663-6556 or 1-604-594-0422Loading DiagramREFER TO JOBSPECIFICDRAWINGS FORRAIL BRACKETLOCATIONSELVORON STELLA Design & Planning Guide77932-D-DP-8-

Design Hot Line: 1-800-663-6556 or 1-604-594-0422Car Sizes & ConfigurationsThe Elvoron Stella is available in 5 different configurations to suit your home. Each configuration hasspecific car sizes. Limited custom car sizes are available - please contact Garaventa Lift.Style 1RStyle 1LStyle 3Style 2Style 4Style 1L & 1R Car sizes: 48” x 54” (1220 x 1372 mm) 42” x 60” (1067 x 1524 mm)Style 2 Car sizes: 48” x 54” (1220 x 1372 mm) 42” x 60” (1067 x 1524 mm)Style 3 & 4 Car sizes: 51” x 51” (1295 x 1295 mm)-9-www.garaventalift.com

Design Hot Line: 1-800-663-6556 or 1-604-594-0422Layouts & Clearances**66” may be feasible. Consult with yourlocal Garaventa Lift Representative.48 x 54 Cab - Style 1LStyle 1L shown - Dimensions apply to both Style 1L & 1RDimensions shown are for REFERENCE ONLY andshould not be used for site preparation or construction.ELVORON STELLA Design & Planning Guide77932-D-DP-10-

Design Hot Line: 1-800-663-6556 or 1-604-594-0422Layouts & Clearances**66” may be feasible. Consult with yourlocal Garaventa Lift Representative.42 x 60 Cab - Style 1LStyle 1L shown - Dimensions apply to both Style 1L & 1RDimensions shown are for REFERENCE ONLY andshould not be used for site preparation or construction.-11-www.garaventalift.com

Design Hot Line: 1-800-663-6556 or 1-604-594-0422Layouts & Clearances**66” may be feasible. Consult with yourlocal Garaventa Lift Representative.48 x 54 Cab - Style 2Dimensions shown are for REFERENCE ONLY andshould not be used for site preparation or construction.ELVORON STELLA Design & Planning Guide77932-D-DP-12-

Design Hot Line: 1-800-663-6556 or 1-604-594-0422Layouts & Clearances**66” may be feasible. Consult with yourlocal Garaventa Lift Representative.42 x 60 Cab - Style 2Dimensions shown are for REFERENCE ONLY andshould not be used for site preparation or construction.-13-www.garaventalift.com

Design Hot Line: 1-800-663-6556 or 1-604-594-0422Layouts & Clearances51 x 51 Cab - Style 3Dimensions shown are for REFERENCE ONLY andshould not be used for site preparation or construction.ELVORON STELLA Design & Planning Guide77932-D-DP-14-

Design Hot Line: 1-800-663-6556 or 1-604-594-0422Layouts & Clearances51 x 51 Cab - Style 4Dimensions shown are for REFERENCE ONLY andshould not be used for site preparation or construction.-15-www.garaventalift.com

Design Hot Line: 1-800-663-6556 or 1-604-594-0422Operating ControlsHall StationsThe Hall Station buttons illuminate when pushed.The push button itself is always made of stainlesssteel for maximum durability. For increased safetyand security, an optional key switch allows the entireelevator to be deactivated.The controls of the Elvoron Stella are the same aswould be found on a commercial elevator. Operationis fully automatic.Car Operating Panel (COP)The Elvoron Stella COP is equipped with a digital floorindicator, illuminated floor buttons, alarm button,door open and door close buttons and a keyedemergency stop switch. An optional integratedphone is available.Car Direction LanternMounted in the car to the car slam post opposite theCOP, the Car Direction Lantern is an audio and visualsignaling device that indicates direction of travel andarrival at the floor.Hall StationsCar Direction LanternCar Operating Panel (COP)ELVORON STELLA Design & Planning Guide77932-D-DP-16-

Design Hot Line: 1-800-663-6556 or 1-604-594-0422Doors - Entrance and Car DoorsThe Elvoron Stella uses commercial elevator entranceand car doors. When open, the doors provide a 36”(915mm) x 80” (2032mm) clear opening. Theyare two-speed horizontal doors and are equippedwith full height photo-electric presence/obstructionsensors. The doors have an hour and a half fire rating.The car doors are finished to match your car wall trimand the entrance doors are primed and ready to bepainted to match your building décor. All doors can besupplied in brushed stainless steel.-17-www.garaventalift.com

Design Hot Line: 1-800-663-6556 or 1-604-594-0422Door Details - Masonry WallsGaraventa Lift recommends that the walls on the entrance side of the hoistway be left open until the door framesare set. Or a rough opening can be left to accommodate for the doors to be placed. This allows the doors to bealigned with the centerline of the car.Contact your local authorized Garaventa Lift representative for further details.See Layouts & Clearances for door centerlinesELVORON STELLA Design & Planning Guide77932-D-DP-18-

Design Hot Line: 1-800-663-6556 or 1-604-594-0422Door Details - Wood and Drywall WallsGaraventa Lift recommends that the walls on the entrance side of the hoistway be left open until the door framesare set. This allows the doors to be aligned with the centerline of the car.Contact your local authorized Garaventa Lift representative for further details.See Layouts & Clearances for door centerlines-19-www.garaventalift.com

Design Hot Line: 1-800-663-6556 or 1-604-594-0422Technical InformationSafety Features:Uninterruptible Power Supply (UPS) emergencybackup power lowering system, emergency manuallowering valve, safety brake system, 2 speed dooroperators with integral gate switch, automatic bidirectional floor leveling, emergency alarm button incar, emergency keyed stop switch in car, overspeedvalve, final limit switch and low oil protection timercircuitCar Sizes:48” x 54” (1220 x 1372mm) Style 1 2 only42” x 60” (1067 x 1524mm) Style 1 2 only51” x 51” (1295 x 1295mm) Style 3 4 onlyRated Load: 1400 lbs (635 kg) Option 1000 lbs(455 kg)Speed: 40 fpm (0.2 m/s) nominal speedUnique Standard Features:Car direction lantern comes with audio and visualsignals, full height photo-electric presence/obstructionsensors, automatic home park featureTravel Range:Standard: 32 ft (9.8 m) with 1400 lb (636 kg)capacity. 36 ft (10.9 m) with 1000 lb capacityStops: Up to 6 stopsCode ComplianceASME A17.1, Section 5.2 LU/LA ElevatorsCSA B-44, Section 5.2 LU/LA ElevatorsADA (Americans with Disabilities Act)Pit Depth: Recommended pit depth of 14” (355mm), Pit Prop standard equipment with elevator.16” if Buffer Springs are required.Popular Options:Integrated telephone, custom car finishes, poweroperated car gate, additional handrails, car top prop,buffer springs (increases your pit depth).Overhead Clearance (Refuge Space):135” (3429mm) min. standard overhead*114” (2895mm) min. overhead in existingconstruction with the use of a Car Top PropDrive System: 1:2 Cable Hydraulic,Heavy Duty car sling with roller guide shoesrunning on 8 lb. per foot steel T-rails, Quietsubmersed pump and motor (5 HP), Factory preset and tested 2-speed valve for smooth start andstop.Power Supply:Elevator:Standard: 230 VAC single phaseOptional: 208 VAC three phaseLighting: 110 VAC single phase, 15 ampsControls:Fully automatic push button operation, PLCController, integrated self-diagnostics. Digital floorindicator in car, automatic car lighting upon entry,illuminated push buttons, car arrival lanterns incar door jamb.Doors:36” x 80” (914 x 2032mm) two-speed horizontalsliding hoistway and car doors with 1.5 hour firerating*Contact Garaventa LiftELVORON STELLA Design & Planning Guide77932-D-DP-20-

Design Hot Line: 1-800-663-6556 or 1-604-594-0422Machine Room RequirementsThe optimum location for your machine room is at thelowest level of the building, adjacent to the hoistway,preferably on the same side as the guide rails. Thedimensions of the pump unit are 30” wide x 19 ½”deep x 66 ¼” high (762 x 495 x 1683 mm).The controller pump assembly can be located up to25’ (7.6 m) from the hydraulic jack.In order to meet the code requirements, thehydraulic pump unit, GFI duplex receptacle andfused disconnect switches (elevator lighting) must belocated in a dedicated machine room with a minimumoverhead of 7’ (2134 mm). Adequate working spacein the machine room includes, clearance in front ofthe pump unit and the proper location of the lightswitch and disconnect switches. Please refer to yourjob specific shop drawings or contact your localauthorized Garaventa Lift representative for furtherdetails.The controller and pump tank can be separated fromeach other by a maximum of 10’.Please contact your Local Garaventa Lift representative for specificMachine Room Code Requirements.-21-www.garaventalift.com

Design Hot Line: 1-800-663-6556 or 1-604-594-0422Machine Room LayoutsCANADIAN MACHINE ROOM PLANLIGHTSW. & DUPLEX GFCIRECEPTACLE230V-1PH 60Hz 40AmpDISCONNECT FUSED 30A (NOM.)clw AUXILLIARY CONTACT.120 1PH 60Hz DISCONNECTFUSED15APOWER AND OIL LINESLEEVES TO HOISTWAYMACHINE ROOM HEIGHTIS MIN. 79" OR 2m CLEARABOVE FINISHED FLOORUSA MACHINE ROOM PLANLIGHTSW. & DUPLEX GFCIRECEPTACLE230V-1PH 60Hz 40AmpDISCONNECT FUSED 30A (NOM.)clw AUXILLIARY CONTACT.120 1PH 60Hz DISCONNECTFUSED15APOWER AND OIL LINESLEEVES TO HOISTWAYMACHINE ROOM HEIGHTIS MIN. 79" OR 2m CLEARABOVE FINISHED FLOORPlease contact your Local Garaventa Lift representativefor specific Machine Room Code Requirements.ELVORON STELLA Design & Planning Guide77932-D-DP-22-

Design Hot Line: 1-800-663-6556 or 1-604-594-0422Machine Room Layouts(Continued)Two dedicated PVC sleeves, at least 3” (76 mm) indiameter, will be required between the hoistway andthe machine room, one sleeve for the hydraulic hoseand one for the electrical conduit. This is to enablethe installers to make the connection between thecylinder and the pumping unit. The sleeves shouldenter the hoistway at either corner of the supportwall.The fused disconnect switch rating and fuse rating forthe lift will be shown on the shop drawings for yourproject.At least one GFCI duplex receptacle connected to a 15amp branch circuit shall be installed in the machineroom.Ventilation Requirements:No special requirements. The elevator drive unitwill generate approximately 3200 BTU per hourunder normal operating conditions. Recommendedtemperature for elevator equipment is 50º – 90º F(15º – 32º C) and 5% – 90% non-condensing.Contact your local authorized Garaventa Liftrepresentative for code specific requirementsand further details.Lighting:The machine room must be provided with at least100 lx lighting over the pumping unit and disconnectswitches.Mains Power RequirementsThe standard motor on the pump unit is 5 HP and itcan be ordered to suit either three phase or singlephase power.Standard: 230 VAC Single phase 40 ampsOptional: 208 VAC Three phase 30 ampsEmergency Battery LoweringIn case of a power outage the elevator is providedwith a second power source that allows the car to belowered to the lowest landing. While descending, thecar can stop and the passenger can exit the car onany landing along the way.Electrical Disconnects:In the machine room you will need to provide twolockable fused disconnects – one 15 amp for lightingand one 40 amp for the pumping unit. Disconnectswitches should be located on the strike (lock) side ofthe machine room door. In accordance to the electricalcode, you must provide a minimum of 36” (915mm)in the United States and 39 ⅜” (1000mm) in Canadaof working space in front of each disconnect switch.The 40A disconnect switch for the pump unit requiresan auxiliary contact.-23-www.garaventalift.com

Creating An Accessible WorldPrinted in Canada77932-D-DP G a ra v e n t a L i f t . A s w e a r econtinuously improving our products,specifications outlined in this brochureare subject to change without notice.Authorized Garaventa Lift Representativewww.garaventalift.com

The Elvoron Stella is a luxury residential elevator with sliding elevator doors. it utilizes the same drive and control systems as a Lu/LA (limited use, limited ap-plication) commercial elevator. A Lu/LA elevator is a power passenger elevator. The use of these products is limited

Related Documents:

the finishing touch to your elevator cab. The standard trim is available in black or white. Custom colors and stainless steel trims are optional. Entrance Door and Car Doors Like a commercial elevator, the Elvoron LU/LA is equipped with two-speed horizontal sliding landing entrances and ca

The full STELLA development tree is quite large, since for every STELLA source file there are three to four translated versions and as many compiled versions thereof. The actual STELLA libraries that you have to ship with an application, however, are quite small. For example, the Java jar file ‘stella.jar’ is only about 1.3 MB in size.File Size: 710KBPage Count: 130

18-V-189 NCCD-Claremont Properties, LLC Elevator GRANT 18-V-190 1950 Addison Apartment Joint Venture, LLC Elevator GRANT 18-V-191 3400 Sunset LLC Elevator GRANT 18-V-192 Sutter Medical Center Elevator GRANT 18-V-193 Chalmers Investment LLC Elevator GRANT 18-V-197 1716 Lofts, LLC Elevator GRANT

meets the elevator code standards existing at the time the elevator was installed. V. F. "Substantial Alteration" shall means any alteration to a elevator covered by these . W. "Temporary Elevator Mechanic License" means a license issued by the state elevator. inspector to an individual, not currently licensed as an elevator mechanic, who meets

Emulator (Z26 or Stella) Stella Programmer's Guide Bookmarks to AtariAge and the #Stella mailing list That's it for this session. Have a read of the Stella Programmer's Guide (don't worry about understanding it yet), and try installing your emulator (an

Emulator (Z26 or Stella) Stella Programmer's Guide bookmarks to AtariAge and the #Stella mailing list. That's it for this session. Have a read of the Stella Programmer's Guide (don't worry about understandin

PG 18-10 – ELEVATOR DESIGN MANUAL October 1, 2020 . 1 . 1.0 GENERAL REQUIREMENTS . A. An elevator machine room shall be provided for each individual elevator or group of elevators. The elevator drive machine and elevator controller shall be in the same code approved machine room. B.

Auditing and Assurance Services, 15e, Global Edition (Arens) Chapter 2 The Audit Standards’ Setting Process Learning Objective 2-1 1) The legal right to perform audits is granted to a CPA firm by regulation of: A) each state. B) the Financial Accounting Standards Board (FASB). C) the American Institute of Certified Public Accountants (AICPA). D) the Audit Standards Board. Answer: A Terms .