EXECUTIVE SUMMARY IEEE 1584-2002 Arc-lash Study Good .

2y ago
13 Views
2 Downloads
2.18 MB
9 Pages
Last View : 24d ago
Last Download : 3m ago
Upload by : Troy Oden
Transcription

EXECUTIVE SUMMARYIEEE 1584-2002 Arc-Flash Study:Good Enough for a Post IEEE1584-2018 Risk Assessment? The IEEE 1584-2018 guide raises risk analysis questions for organizations.IEEE 1584-2018 calculates the impact of arc-flash differently than the 2002version.New variables in IEEE 1584-2018 arc-flash studies affect arcing currentcalculations and protective device response time.Time is an important factor when it comes to incident energy.The constant energy boundary is a tool that organizations can use to evaluatewhether their previous PPE choices are adequate considering what a 2018study might predict.This analysis may clarify whether existing PPE selections are adequate orwhether more attention is required.OCTOBER 29, 2020Marcelo E. Valdes, P.E., Application & Standards Engineering Manager, Marketing, ABBin partnership with

EXECUTIVES U M M A RYIEEE 1584-2002 Arc-Flash Study: Good Enough for aPost IEEE 1584-2018 Risk Assessment?OverviewIEEE 1584-2018 (IEEE Guide for PerformingArc-Flash Calculations) is substantially different from and more accurate than the 2002version of this guide. Many organizations arenow wondering whether PPE selectionsbased on IEEE 1584-2002 arc-flash studies arestill safe for workers. In some cases, incidentenergy levels calculated with the 2002 modeland the 2018 model are different by more thana factor of two. Fortunately, organizations canevaluate their concerns about PPE and workerrisk with assessment methodologies thatrequire only a few known variables. Thisanalysis may clarify whether existing PPEpractices are adequate or whether moreattention is required.ContextMarcelo Valdes shared a methodology hedeveloped that organizations can use toassess whether PPE selections made basedon IEEE 1584-2002 are still suitable, given thenew approach to arc-flash calculations used inIEEE 1584-2018. The presentation was basedon a paper presented at the IEEE 2020Electrical Safety Workshop in March 2020.Key TakeawaysThe IEEE 1584-2018 guide raises riskanalysis questions for organizations.IEEE 1584 is the standard of care for predicting the impact of an electrical explosion,known as arc flash, on workers under a set ofspecific conditions. The 2002 version of thisIEEE guide was revolutionary in its ability toquantify arcing current and incident thermalenergy in a useful manner. Organizations usedthe data to properly set overcurrent protectionand select PPE. In 2018, a newer and betterversion of this guide was published: IEEE1584-2018.IEEE 1584-2018 is prompting organizations toreconsider their old arc-flash studies and PPEselections. Common questions include: What should organizations do with their oldarc-flash studies and PPE selections? Is it ok to continue using 2002 arc-flashstudies and PPE selections until the organization conducts a 2018 arc-flash study? What are the risk assessment and controlimplications of ignoring IEEE 1584-2018? Based on the new science, do workershave adequate PPE for the potential severity of an arc-flash event?Although IEEE 1584-2018 may raise legal andregulatory compliance concerns for organizations, it also should raise concerns regardingrisk analysis for specific work tasks that mayneed to be accomplished. In recent years,many employers have been implementingrisk-based workplace injury and illness prevention programs, to better meet OSHArequirements.Risk management in the NFPA 70E standardfocuses on monitoring and reviewing risks. Acentral part of risk management is a riskassessment that analyzes risk sources toestimate overall risk level. A risk level includesthe potential that a dangerous event will occurand the potential severity of that event. Thesetwo factors must be considered together.Based on the risk level, organizations determine how to control the risk.PAGE 2

EXECUTIVES U M M A RYIEEE 1584-2002 Arc-Flash Study: Good Enough for aPost IEEE 1584-2018 Risk Assessment?According to NFPA 70E, a risk analysis has thefollowing characteristics: Systematic, structured, and timely Based on the best available information Dynamic, iterative, and responsive tochangeIEEE 1584-2018 calculates the impactof arc-flash differently than the 2002version.2. Gap and enclosure. These are now twoexpanded variables in IEEE 1584-2018.Changes to the gap and enclosure parameters will affect arc-flash calculations. Inmost cases, however, organizations continue to use the gap and enclosure valuessuggested as typical by the IEEE guide.Those values did not change between the2002 and 2018 versions.Figure 2: Parameters for IEEE 1584-2002 vs.IEEE 1584-2018IEEE 1584-2018 is more accurate than IEEE1584-2002. It is based on thousands of tests,rather than hundreds. It was also created in amore scientific way with multiple variables.Two major differences between IEEE 15842018 and IEEE 1584-2002 are:1. Electrode configuration and arc environment. These parameters were not considered in IEEE 1584-2002. In the old model,all input data was based on arc-flash conductors being vertical or parallel to theworkers (referred to as VCB). The 2018standard also considers horizontal orperpendicular orientations (referred to asHCB) and vertical or parallel into barrierorientations (referred to as VCBB).Figure 1: Electrode Configurations and Arc EnvironmentPAGE 3

EXECUTIVES U M M A RYIEEE 1584-2002 Arc-Flash Study: Good Enough for aPost IEEE 1584-2018 Risk Assessment?New variables in IEEE 1584-2018arc-flash studies affect arcing currentcalculations and protective deviceresponse time.In 2002 arc-flash studies, VCB was the onlyelectrode orientation and the enclosure wasalways standard. In 2018 arc-flash studies,however, electrode configuration has become abig factor. Although gap and enclosure size arealso variables, those are less likely to change.Electrode configuration, however, affects arcingcurrent (Iarc) and incident energy (Ei) directly.Organizations must keep the following points inmind when conducting 2018 arc-flash studies: If you are unsure about the size of the gap,use a larger one to be conservative. In mostcases, organizations use the same gap in2018 arc-flash studies as in prior 2002 studies.If the organization decides that a larger gap isneeded, it is important to recognize this willresult in less arcing current, which is harder todetect, and also results in more energy perunit of time, which is potentially a morehazardous situation. If the gap is smaller orthe same, organizations can ignore its impacton the suggested analysis.real-world commercial and industrial systems.Most industrial commercial systems tend tobe 55kA and below.With 208 volts, a 25-millimeter gap, and astandard low-voltage box, the arcing currentvalues are higher than the 2002 model, butthey flatten out (see Figure 4) at higheravailable fault current. When calculating anarc-flash for very high fault current systems,the overcurrent protection may act substantially differently than expected. In the middlerange, however, the 2018 model will produce higher arcing currents than the 2002model for almost all voltages and gaps andhence the protection can be expected to befaster, or at worst case the same speed asfor the 2002 calculated arcing current.Figure 3: The Impact of Gap on Arcing Current at 480V Generally speaking, the 2018 arcingcurrent predicted is higher than the 2002calculations would have predicted. This istrue for VCB, HCB, and VCBB electrodeorientations. Higher arcing current willengender faster or equal protection timefrom the overcurrent protective device, butit should never cause slower protection.Figure 4: The Impact of Gap on Arcing Current at 208VWith very high fault current, the arcing currentin the 2018 model may be lower than the2002 model would have predicted. This occursat currents that aren’t commonly found inPAGE 4

EXECUTIVES U M M A RYIEEE 1584-2002 Arc-Flash Study: Good Enough for aPost IEEE 1584-2018 Risk Assessment? When comparing 2002 and 2018 arc-flashstudies, protective devices will clear at thesame time or faster, never slower. Whenlooking at protective devices like circuitbreakers or fuses, the circuit breaker and fusetime current curves are steeper than theconstant energy boundary (see Figure 5).When arcing current is higher, protectiondevices will clear faster. If protection hits thehorizontal portions of the circuit breaker timecurrent curve, it will be the same speed.Without looking at the time current curve orknowing the exact value of the arcing current,it is evident that protective devices will clearat the same time or faster, never slower.Time is an important factor when itcomes to incident energy.For VCBB and VCB electrode orientations, the2002 model may be adequate or even conservative over a wide range of situations.However, that is not always the case. For HCBelectrode orientations, the 2018 modelindicates more incident energy in all scenariosthan the 2002 model.Figure 6: Incident Energy Calculations Using the 2002and 2018 ModelsFigure 5: The Impact of Increasing Arcing Current onProtective DevicesThe electrode orientationis the variable with thegreatest impact on 2018versus 2002 arc-flashstudy calculations.Marcelo E. Valdes, ABBTime is a very important factor for incidentenergy. Arcing current decreases as gapdimensions increase. Lower arcing current isharder to detect and protection may slow.Incident energy, however, increases as gapdimensions increase because the arc islonger. Although the effects may be small,they can add up—especially if protectionslows.PAGE 5

EXECUTIVES U M M A RYIEEE 1584-2002 Arc-Flash Study: Good Enough for aPost IEEE 1584-2018 Risk Assessment?The constant energy boundary is atool that organizations can use toevaluate whether their previous PPEchoices are adequate.study should still be accurate. The new IEEE1584-2018 arc-flash calculations haven’tchanged the way bolted fault current isderived.When people don’t have exact values ofbolted fault currents, they sometimes use atool for arc-flash analysis called the constantenergy boundary. For any one value of arcingcurrent, the constant energy boundary showsthe time needed to produce a specific valueof incident energy. For the same incidentenergy target, the IEEE 1584-2018 modelallows more time at the same value of arcingcurrent than the IEEE 1584-2002 model. Thechallenge in using the chart in Figure 7,however, is that one must know the exactarcing current.Figure 8: Transposing Arcing Current to BoltedFault CurrentFigure 7: Constant Energy Boundary – A ToolThe solution to this issue is to transpose theclearing time from arcing current to boltedfault current. The bolted fault current is knownto most organizations. If systems haven’tchanged since the last time an organizationconducted an arc-flash study, the bolted faultcurrent values shown in the 2002 arc-flashIn the region between the two vertical blacklines in Figure 8, the data is comparable. Thevertical lines bound the range of bolted faultcurrent where the 2018 arcing current will belarger than the 2002 arcing current calculations. One can assume that the time, gap,working distance, and enclosure variables arethe same. Therefore, from the graph before,since we know the OPCD protected at theblack line or faster, the incident energy forVCB exposure predicted with the 2018 modelwill be less.PAGE 6

EXECUTIVES U M M A RYIEEE 1584-2002 Arc-Flash Study: Good Enough for aPost IEEE 1584-2018 Risk Assessment?Figure 9: Incident Energy for VCB, VCBB, and HCBAs shown in Figure 9, for VCBB, the incidentenergy depends on the exact bolted faultcurrent. And for HCB, it is always worse.However, this assumes that the incidentenergy target performance is the same for the2002 and the 2018 arc-flash studies.In reality, there is a high likelihood that 2002arc-flash studies resulted in PPE selectionsthat could accommodate more incidentenergy than the actual exposure. Usually thePPE level selected or recommended is greaterthan the calculated incident energy. Typicalvalues of PPE may be 8, 25, or 40 calories.The open question is whether the margin isbig enough to cover the difference betweenthe 2002 arc-flash calculations and whatcalculations using the new 2018 model wouldpredict. As outlined in Figure 10, using theright graphs can help answer this question.Figure 10: Assessing Risk With a Few Variables Is PossiblePAGE 7

EXECUTIVES U M M A RYIEEE 1584-2002 Arc-Flash Study: Good Enough for aPost IEEE 1584-2018 Risk Assessment?The results of plotting graphs for a series of comparative scenarios are summarized in thefollowing tables.The method outlined in this presentation was solely created by M. E. Valdes and is not a product of the ABB company nor is itendorsed or promoted by ABB in any way. The method is not intended to replace a well performed arc flash study by qualifiedpersonnel using the latest applicable standards and generally accepted practices.The method is solely intended to provide an estimating tool that may be useful in the process of risk analyses associated withevaluating if PPE has a high enough arc rating, under certain identified limited conditions, to exceed the incident energy that maybe calculated by an Arc Flash study performed using IEEE 1584-2018 under the same identified limited conditions.PAGE 8

EXECUTIVES U M M A RYIEEE 1584-2002 Arc-Flash Study: Good Enough for aPost IEEE 1584-2018 Risk Assessment?BiographyMarcelo E. Valdes, P.E.Application & Standards EngineeringManager, Marketing, ABBAfter 41 years with GE Mr. Valdes joined ABBElectrical Products division in July 2018. Mr.Valdes has held position in field engineering,equipment sales, application engineering, andproduct marketing. He is past chair of variousIEEE PES and IAS chapters in NorthernCalifornia as well as past chair of the 2014IEEE Electrical Safety Workshop (IEEE-ESW).Mr. Valdes chaired the IEEE 1683-2014 working group “IEEE P1683 Guide for Specificationand Selection of Low Voltage Motor ControlCenters with Enhanced Safety Features” andis active in various other IEEE working groups,mostly in electrical safety and electricalsystems protection. Mr. Valdes has receivedmultiple recognitions from the IEEE forvarious contributions in the area of overcurrent protection and electrical safety. Hereceived the IEEE IAS Applications Magazine“First Prize Article Award” for the 2014 article,“Assessing Solutions to Electrical Hazards: AnAnalytical Tool to Reduce Hazards in ElectricalFacilities.” Mr. Valdes has authored or coauthored over 35 technical papers for IEEE &other engineering forums. He participates inCSA Z462, the Canadian Electrical SafetyStandard, the NEC & NFPA70B NFPA’sElectrical Maintenance Standard. Mr. ValdesBioNameNoSpaceholds 28 patents in the field electricalBioTitleCompanydistribution and control.bioTextPAGE 9 2020 Endeavor Business Media. All rights reserved.

Oct 29, 2020 · IEEE 1584-2018 is more accurate than IEEE 1584-2002. It is based on thousands of tests, rather than hundreds. It was also created in a more scientific way with multiple variables. Two major differences between IEEE 1584-2018 and IEEE 1584-2002 are: 1. Electrode configuration and arc enviro

Related Documents:

IEEE Std 1307-2004, IEEE Standard for Fall Protection for Utility Work. IEEE Stds 1584-2002, 1584a-2004 (Amendment 1 to IEEE Std 1584-2002), and 1584b-2011 (Amendment 2: Changes to Clause 4 of IEEE Std 1584-2002), IEEE Guide for Per-forming Arc-Flash Hazard Calculations. IEEE C2-2012, National Electrical Safety Code.

IEEE 1584-2002 Figure 3 Example Comparison 1584-2002, 1584-2018 Page 3 Qual-Tech Engineers, Inc. 13.8 CT-M GND 50/5 o 13.8 CT-M 1200/5 o OCR 13.8 SWGR RLY-M T1 9 %Z 138/13.8 kV 20 MVA U lity 3585.345 MVAsc 0.54699 j2.73497 % 480 SWGR CB-2 65 kA 800 A C 48

IEEE 1584-2002 vs. IEEE 1584-2018 November 12, 2019 Slide 6 IEEE 1584-2002 (version 1.0) calculation variables: Gap (G) (equipment type driven) Working distance (D) Operating voltage (V oc) Available short circuit current (I bf) Grounding (yes/no) (not new model) Box (yes/no) New IEEE 1584-2018 (version 2.0) adds: Electrode .

IEEE 3 Park Avenue New York, NY 10016-5997 USA 28 December 2012 IEEE Power and Energy Society IEEE Std 81 -2012 (Revision of IEEE Std 81-1983) Authorized licensed use limited to: Australian National University. Downloaded on July 27,2018 at 14:57:43 UTC from IEEE Xplore. Restrictions apply.File Size: 2MBPage Count: 86Explore furtherIEEE 81-2012 - IEEE Guide for Measuring Earth Resistivity .standards.ieee.org81-2012 - IEEE Guide for Measuring Earth Resistivity .ieeexplore.ieee.orgAn Overview Of The IEEE Standard 81 Fall-Of-Potential .www.agiusa.com(PDF) IEEE Std 80-2000 IEEE Guide for Safety in AC .www.academia.eduTesting and Evaluation of Grounding . - IEEE Web Hostingwww.ewh.ieee.orgRecommended to you b

IEEE 1584-2018 (IEEE Guide for Performing Arc-Flash Calculations) is substantially differ-ent from and more accurate than the 2002 version of this guide. Many organizations are now wondering whether PPE selections based on IEEE 1584-2002 arc-flash studies are still safe for workers. In some cases, incident

Jul 19, 2010 · This presentation is a based on a paper presented at the IEEE 2020 Electrical Safety Workshop in March 2020. CONSIDERATIONS FOR ADAPTING IEEE 1584 -2002 ARC FLASH STUDY RESULTS TO A POST IEEE 1584-2018 RISK ASSESSMENT. Marcelo E. Valdes, PE, IEEE Fellow Marcelo.E.Valdes@IEEE.OR

History of Arc-Flash Hazard Safety Standards. 2002 -IEEE publishes a new standard to provide an . IEEE Guide for Performing Arc-Flash Hazard Calculations (IEEE 1584). IEEE 1584 amended in 2004 and 2011. 2007 - ANSI/IEEE C2, NESC first detailed an arc-flash hazard assessment method. Revised in 2012.

Otago: Rebecca Aburn, Anne Sutherland, Gill Adank, Jan Johnstone, Andrea Dawn Southland: Mandy Pagan, Carolyn Fordyce, Janine Graham Hawkes Bay: Wendy Mildon As over 30 members of the New Zealand Wound Care Society were in attendance at the AGM a quorum was achieved. Apologies: