Adapting IEEE 1584-2002Arc Flash Study Results To A Post .

2y ago
18 Views
2 Downloads
1.26 MB
31 Pages
Last View : 17d ago
Last Download : 3m ago
Upload by : Lilly Andre
Transcription

—Adapting IEEE 1584-2002Arc Flash Study Results to a PostIEEE 1584-2018 Risk AssessmentMarcelo E. Valdes, PE, IEEE Fellow CopyrightABB. All rights reserved.Document ID.:Rev.:

—This presentation is a based on a paper presented at the IEEE 2020 Electrical Safety Workshop in March 2020.CONSIDERATIONS FOR ADAPTING IEEE 1584-2002 ARC FLASH STUDY RESULTS TO A POST IEEE 1584-2018 RISKASSESSMENTMarcelo E. Valdes, PE, IEEE FellowMarcelo.E.Valdes@IEEE.ORG, ABB&H. Landis Floyd, PE, IEEE Life FellowUniversity of Alabama at BirminghamThe method outlined in this presentation was solely created by M. E. Valdes and isnot a product of the ABB company nor is it endorsed or promoted by ABB in any way.The method is not intended to replace a well performed arc flash study by qualifiedpersonnel using the latest applicable standards and generally accepted practices.The method is solely intended to provide an estimating tool that may be useful inthe process of risk analyses associated with evaluating if PPE has a high enough arcrating, under certain identified limited conditions, to exceed the incident energy thatmay be calculated by an Arc Flash study performed using IEEE 1584-2018 under thesame identified limited conditions.

—Old AF study New AF science PPE was selected with an IEEE 1584-2002 AF studyPPE good enough for my task now that IEEE 1548-2018 hasestablished a new science?Am in conformance with the legal requirements? Is ignoring IEEE 1584-2018 the right thing to do from a “riskAssessment and control perspective? Does the worker have adequate PPE for the potential severity ofan AF event based on the “new” science?

—A Paradigm Shift“Ensuring that American workplaces are safe will require a paradigm shift, with employers going beyond simply attempting to meet OSHA standards, to implementing risk-based workplace injury and illness preventionprograms.”Assistant Secretary David Michaelsletter to the OSHA staffJuly 19, 2010

—Is that, really, the right question?Is this a legal matter? PerhapsIs it a safety matter? DefinitelyPrimarily it is a “Risk Analysis” question!

—“Risk” in 70E Risk Management, Needs:1. Communication & consultation2. Establishing risk assessment context &objectives3. Risk assessment4. Risk treatment5. Recording/reporting risk assessment results& treatment decisions6. Monitoring & reviewing risks

—“Risk” in 70E Risk Assessment, Part of risk management involving:1.Identifying sources of risk2.Analyzing risk sources to estimate risk level3.Evaluating risk determine if risk treatment is required

—“Risk” in 70E Risk Analysis, must be:1. Integral to organizational processes & decisions2. Systematic, structured, & timely3. Use best available information4. Accounts for human & cultural factors5. Dynamic, iterative & responsive to change6. Facilitates continual organization improvement

—Why bother asking?ParameterIEEE 1584 2018 is very different from 2002 version2002 version was good, the 2018 version is betterInputs for the calculations are different Electrode orientation & arc environment werenot considered beforeVoltage (Voc) 208 - 600 V & 1kV - 13.8 kVFrequency50 - 60 HzCurrent @ LV (Ibf)700A - 106kACurrent @ MV (Ibf)700A-63kAGap (G) @ LV10 - 40 mmGap (G) @ MV13 - 152 mmWorking Distance (D)Typically 15-36 InchesSystem groundingUsed20182018 model208 V - 15 kV50 - 60 Hz 600 V 500 A - 106 kA 600 V 200 A - 65 kA 600 V 6.35 - 76.2 mm 600 V 19.05 - 254 mm 12 inchesIgnoredvariable, 49" maximum forEnclosure Assumed per voltage & gapany 1 dimensionElectrodeVCB, VOA VCB, VOA (vertical only)configurationsVCBB, HCB & HOAVertical orparallel intobarrierVCBBHorizontal orperpendicularHCBVertical orparallelVCB2002 & 20182002 model2018

—Why bother asking?And gap is now a variableIs the arc pointing at the worker or not?Is the arc constrained or free?Is it an itty-bitty arc, or a great big long one?Are the differences important ? Do we care?Parameter2002 modelVoltage (Voc) 208 - 600 V & 1kV - 13.8 kVFrequency50 - 60 HzCurrent @ LV (Ibf)700A - 106kACurrent @ MV (Ibf)700A-63kAGap (G) @ LV10 - 40 mmGap (G) @ MV13 - 152 mmWorking Distance (D) Typically 15-36 InchesSystem groundingUsed2018 model208 V - 15 kV50 - 60 Hz 600 V 500 A - 106 kA 600 V 200 A - 65 kA 600 V 6.35 - 76.2 mm 600 V 19.05 - 254 mm 12 inchesIgnoredvariable, 49" maximum forEnclosure Assumed per voltage & gapany 1 dimensionElectrodeVCB, VOA VCB, VOA (vertical only)configurationsVCBB, HCB & HOA

—Relationships are not simpleEquations are complex, no need to go there for this analysis if one can make some assumptions!65342𝐼𝐼𝑎𝑎𝑎𝑎𝑎𝑎 𝑉𝑉𝑉𝑉𝑉𝑉 10(𝑘𝑘1 𝑘𝑘2𝑙𝑙𝑙𝑙𝐼𝐼𝑏𝑏𝑏𝑏 𝑘𝑘3𝑙𝑙𝑙𝑙𝐺𝐺) (𝑘𝑘4 𝐼𝐼𝑏𝑏𝑏𝑏 𝑘𝑘5 𝐼𝐼𝑏𝑏𝑏𝑏 𝑘𝑘6 𝐼𝐼𝑏𝑏𝑏𝑏 𝑘𝑘7 𝐼𝐼𝑏𝑏𝑏𝑏 𝑘𝑘8 𝐼𝐼𝑏𝑏𝑏𝑏 𝑘𝑘9 𝐼𝐼𝑏𝑏𝑏𝑏 𝑘𝑘10 ) )𝐸𝐸𝑉𝑉𝑉𝑉𝑉𝑉 12.55250𝑇𝑇 10𝑘𝑘3 ��𝑉1𝑘𝑘1 𝑘𝑘2 𝑙𝑙𝑙𝑙𝐺𝐺 𝑘𝑘11 𝑙𝑙𝑙𝑙𝐼𝐼𝑏𝑏𝑏𝑏 𝑘𝑘12 𝑙𝑙𝑙𝑙𝐷𝐷 𝑘𝑘13 ��𝑉𝑉𝑉𝑉𝑉 𝑙𝑙𝑙𝑙765342𝐶𝐶𝐶𝐶𝑘𝑘4 𝐼𝐼𝑏𝑏𝑏𝑏 𝑘𝑘5 𝐼𝐼𝑏𝑏𝑏𝑏 𝑘𝑘6 𝐼𝐼𝑏𝑏𝑏𝑏 𝑘𝑘7 𝐼𝐼𝑏𝑏𝑏𝑏 𝑘𝑘8 𝐼𝐼𝑏𝑏𝑏𝑏 𝑘𝑘9 𝐼𝐼𝑏𝑏𝑏𝑏 𝑘𝑘10 𝐼𝐼𝑏𝑏𝑏𝑏

—2002 study (VCB)System Voltage (Voc)Fault current (Ibf)Risk analysisTCCIarc timeArcing Gap (G)Grounding methodArcing Gap (G)IarcRisk analysisEi PPE2002timeWork DistanceOnly 1 electrode description VCB, box is always standard There is open as well but ignoring in this situationIn 2018 electrode description became a big factor!Grounding method no longer a factorGap & box size also factors but will those change?

—2002 study (VCB)System Voltage (Voc)Fault current (Ibf)System Voltage (Voc)Fault current (Ibf)Arcing Gap (G)Risk analysisTCCIarc timeHCB, VCB or VCBBArcing Gap (G)IarctimeRisk analysisEi Work DistanceHCB, VCB or VCBBBox sizeVCB, VCBB or HCB impact Iarc & Ei directly, & Iarc impacts time which also impacts Ei !Electrode orientation is now “a” big factor!Gap & box size also factors but will those change? Larger box will lower EiPPE2018

—Gap and electrode orientation IarcGap probably will not change unless it’s recognized the gap needs to be larger than previously used. If alarger gap is needed it’s a more complex problem.If the gap is smaller than what was used in calculation then analysis is conservative, for this purpose itcan be ignored.In a 2018 Arc Flash study, if not sure about “gap” use a larger gap

—Impact of gap on arcing current!480V, 32mm gap, Std LV boxHigher Iarc equal or faster speed protection neverslower!Iarc (kA)Over an important region the 2018 Iarc is the 2002Iarc!!!1584-2018,VCBBHCBVCB1584-2002, VCBIbf (kA)

—208V, similar to 480V except arcing current really flattens out208V, 25mm gap, Std LV boxSimilar relationships at 208V. Its alsosimilar at 600VWhat happens at 200kA Ibf ?Iarc (kA)Flattening of the arcing current atsome point more Ibf drives little morearcing current1584-2018,VCBBHCBVCB201510Arcing current can be much lowerthan traditionally calculated faultcurrents, specially at very high valuesof fault current and in lower voltagesystems!1584-2002, VCB50Ibf (kA)05101520253035404550556065707580859095100

—Important point100.00Fuse TCCCB TCC Protection will be equal or faster over that range ofIbf Never slower!Fuse curve’s & CB’s TOC portion of curves are steeperthan constant energy boundaries If Iarc increases the protection will never be slower!10.00Time (Sec.)For a useful range of Ibf , same Voc & gap, for allVCB/HCB/VCBB; Iarc will be higher in a 2018 study1.00Constant EnergyBoundary0.10Increasing Iarc0.0101Iarc(kA)10100

—Ei not so clear480V, 32mm gap, Std LV box, 18 in, cm2151050cal/cm220208V, 25mm gap, Std LV box, 18 in, 100ms101584-2002, VCB1584-2002, VCBIbf (kA)051015202530354045505560657075808590951000Ibf (kA)05101520253035404550556065707580859095For VCBB & VCB, all else equal, the 2002 study may be adequate or even conservative over a wide range of situations, butnot alwaysHCB, on the other hand but there are more variables in the new equationsBut above assumes time is equal! If the 2002 vs 2018 time are different .100

—Gap, 25, 32 & 51mm (1, 1.25 & 2 inches), VCB, 480V5020Incident energy (Ei)Increases with gap45Arcing current (Iarc)Decreases with gap403515Gap EiIarc (kA)2510cal/cm2302015Gap10Gap5 Iarc Ei50Ibf (kA)051015202530354045500556065707580859095100Ibf (kA)0510Lower Iarc is harder to detect, may cause protection to slowRegardless the decreasing Iarc, Ei increases because the arc is longerEffects may be small, but they may add up specially if protection slows1520253035404550556065707580859095 100

—Constant Energy Boundary, A tool1000A CB100.00480V, 32mm, 18”, VCB8 cal/cm210.00Time (Sec.)1584-2018 For any one value of Iarc, curve shows the time needed toproduce a specific value of Ei. Notice, for same target Ei, 2018 allows more time at thesame value of Iarc But the AF study may tell you Iarc for a 2018 based AFstudy, we do not know what it would be for a 2018calculation But we know that for a certain range of IbF the 2018 Iarc willbe higher hence the OCPD will be equal speed or faster!1.001584-20020.100.0101Iarc(kA)10100

—Transpose to Ibf5010.00.4540 Since we do not need OCPD clearing time wedo not need actual Iarc. The vertical lines bound the range of Ibfwhere we know the 2018 Iarc will be largerthat the 2002 Iarc. If the gap, working distance & voltage are thesame & Ibf is the same between 5kA to85kA the Ei will be less for VCB with thesame OCPD.30252015.1051.000Ibf (kA)01020304050Time (Sec.) Plotting at Ibf allows the two lines to becompared to each other.Iarc (kA)350.100.011Ibf(kA)1010060708090100

10.00 2018 VCB is always easier but for VCBB it dependson the exact Ibf And for HCB it is always worse!!1.00 But this assumes the Ei target performance is thesame for 2002 & 2018 studies Time (Sec.)—VCB, VCBB & HCB1584-2002 Energyboundary/ vs IbfVCBHCBChances are that the 2002 PPE decision selected a PPEhigher than the actual exposure because PPE choicesare limited by choice & availability there is a margin0.100.01VCBB1Ibf(kA)10100

—One more consideration Generally a PPE level selected or recommended is than the Ei calculated. Table above: 9.5 25, 11.8 25, 38 40, 31.1 40 Can the margin absorb the extra energy the new exposure may cause?

—15.6 calories calculated; 25 calorie PPE identified An almost 10 calorie margin, enough toaccommodate the new calculations?Improperly identified as HRC here!

—With the right graph any situation can be analyzed6Time (Sec.)81.0058Time (Sec.)1.00If Ei calculated was 6 cal/cm2 but 8 PPE wasselected. A task that may now have VCB orVCBB exposure is still covered by the 8 cal/cm2PPE. For HCB, for some Ibf range, Ei may exceedPPE selected. A more exact calculation will beneeded to make sure!0.100.10If Ei calculated was 5 cal/cm2 & 8 call PPEwas selected. HCB energy may not exceedselected PPE!8 c/cm 2 480V, G 32mm, WD 457.2mm, VCB Std LV box8 c/cm 2 480V, G 32mm, WD 457.2mm, VCBB Std LV box1584-2002 6 c/cm 2 480V, G 32mm, WD 457.2mm, VCB Std LV box8 c/cm 2 480V, G 32mm, WD 457.2mm, HCB Std LV box0.011Ibf(kA)101008 c/cm 2 480V, G 32mm, WD 457.2mm, VCB Std LV box8 c/cm 2 480V, G 32mm, WD 457.2mm, VCBB Std LV box1584-2002 5 c/cm 2 480V, G 32mm, WD 457.2mm, VCB Std LV box8 c/cm 2 480V, G 32mm, WD 457.2mm, HCB Std LV box0.011Ibf(kA)10Without Iarc or understanding the OCPD the method allows determination if a new electrode exposure presentsunacceptable risk using only the 2002 based study!. But one needs a chart to represent the specific scenario!100

8 c/cm 2 480V, G 32mm, WD 457.2mm, VCB Std LV box8 c/cm 2 480V, G 32mm, WD 457.2mm, VCBB Std LV box1584-2002 5 c/cm 2 480V, G 32mm, WD 457.2mm, VCB Std LV box8 c/cm 2 480V, G 32mm, WD 457.2mm, HCB Std LV box—Table format for multiple scenarioVocGap G in mmHRG1325208 V32401325480 V32401325600 V3240 2.7kVNotes:IEEE 1584-2018Electrode 18 Ia-1584-2002Ibf from - to 106691067710684106100106476156776490741061584-2002 Ei calculated must be identified level for PPE selection to be sufficient1584-2018 calculated Ei over the range of Ibf identified1584-2018 8 1584-2018 25 272321183025221938302723HCB1584-2018 40 1362825Time (Sec.)Ibf range where 1584-2018 minimum Ia is 1584-2002 minimum Ia10.0021430.103329251584-2018 always yields lower Iarc1VCB & HCB have similar Ia so they are grouped in this table.2Ia not calculated for 106 kA Ibf.3Bolded numbers are the highest minimum & lowest maximum in the voltage range0.011Ibf(kA)10100

—Ibf range where 1584-2018 minimum Ia is 1584-2002minimum IaGap G inmmVocHRG1325208 V32401325480 V32401325600 V3240IEEE 1584-2018ElectrodeConfig.Ia-1584-2018 Ia-1584-2002Ibf from - to CBB390VCB/HCB674VCBB31061584-2002 Ei calculated must be identified level for PPE selection to besufficient 1584-2018 calculated Ei over the range of Ibf identified1584-2018 8 cal/cm21584-2018 25 9105 2.7kV 1584-2018 always yields lower IarcNotes:1VCB & HCB have similar Ia so they are grouped in this table.2Ia not calculated for 106 kA Ibf.356Bolded numbers are the highest minimum & lowest maximum in the voltage 336492733216927724293082741386323417HRG/ Floating 2134381059189112021614VCB2368HCB2769VCBB1584-2018 40 cal/cm2522536Calories/cm2 from 2002 study for HRG orungrounded system. If PPE is or higherrated than the arc rating identified at columntop for identified conditions, then PPE shouldhave higher arc rating than what a 2018study would predict for the same identifiedconditions. Which include the same arcinggap, 18 inches working distance, standardbox and electrode configuration of VCB in2002 AF study and as identified in the columnheading for the 2018 AF study.

—Solidly Grounded SystemsIbf range where 1584-2018 minimum Ia is 1584-2002minimum IaVoc (Solidly Gap G IEEE 1584-2018 Ia-1584-2018 Ia-1584-2002Grounded) in mm Electrode Config.1584-2002 Ei calculated must be identified level for PPEselection to be sufficient for 1584-2018 calculated Ei over therange of Ibf identified1584-20181584-20181584-20188 cal/cm225 cal/cm240 cal/cm2Ibf from - to (kA) VCB VCBB HCB VCB VCBB HCB VCB VCBB HCB208/120 V321325324013600/347 VNotes 2.7kV 1584-2018 always yields lower Ia1) VCB & HCB have similar Ia so they are grouped in this table.2) Ia not calculated for 106 kA Ibf.3) Bolded numbers are the highest minimum & lowest maximumin the voltage range2540480/277 VCalories/cm2 from 2002 study for solidly grounded system. If PPE is or rated than the arc rating identified at column top foridentified conditions then PPE should have higher arc rating thanwhat a 2018 study would predict for the same identifiedconditions. Which include the same arcing gap, 18 inches workingdistance, standard box & electrode configuration of VCB in 2002 AFstudy & as identified in the column heading for the 2018 AF study.13253240VCB/HCB (1)8VCBB6VCB/HCB11VCBB7VCB/HCB12 VCB/HCB7VCBB3VCB/HCB6VCBB368 (3)8872106 5 233195.5 334273.5 243216.5 405324.5 293.5 2119162821191633252219

—Summary At LV, creating plots is not difficult for the Excel & math inclined that is what interns are for! Electrical system analysis software may be able to help, consult with your favorite vendor. Most softwarewill plot constant Ei curve against Iarc but not Ibf Risk management principles would seem to dictate that old PPE selections should be questioned based onthe new IEEE guide. Specially if HCB electrodes may be found. Doing the entire arc flash study over again by the time the task needs execution may be unreasonable Assessment with a few known variables is possible! Existing PPE practices may be good enough, sometimes,prioritize where more attention is needed!

—Marcelo E. Valdesmarcelo.valdes@us.abb.com

Jul 19, 2010 · This presentation is a based on a paper presented at the IEEE 2020 Electrical Safety Workshop in March 2020. CONSIDERATIONS FOR ADAPTING IEEE 1584 -2002 ARC FLASH STUDY RESULTS TO A POST IEEE 1584-2018 RISK ASSESSMENT. Marcelo E. Valdes, PE, IEEE Fellow Marcelo.E.Valdes@IEEE.OR

Related Documents:

Oct 29, 2020 · IEEE 1584-2018 is more accurate than IEEE 1584-2002. It is based on thousands of tests, rather than hundreds. It was also created in a more scientific way with multiple variables. Two major differences between IEEE 1584-2018 and IEEE 1584-2002 are: 1. Electrode configuration and arc enviro

History of Arc-Flash Hazard Safety Standards. 2002 -IEEE publishes a new standard to provide an . IEEE Guide for Performing Arc-Flash Hazard Calculations (IEEE 1584). IEEE 1584 amended in 2004 and 2011. 2007 - ANSI/IEEE C2, NESC first detailed an arc-flash hazard assessment method. Revised in 2012.

IEEE Std 1307-2004, IEEE Standard for Fall Protection for Utility Work. IEEE Stds 1584-2002, 1584a-2004 (Amendment 1 to IEEE Std 1584-2002), and 1584b-2011 (Amendment 2: Changes to Clause 4 of IEEE Std 1584-2002), IEEE Guide for Per-forming Arc-Flash Hazard Calculations. IEEE C2-2012, National Electrical Safety Code.

Considerations for Adapting IEEE 1584-2002 Arc Flash Study Results to a Post IEEE 1584-2018 Risk Assessment Technical Panels 3 Applying Continuous Monitoring & Diagnosis (M&D) to Critical Rotating Machines With no Additional Device to Install 4 Implications of IEEE Guide 1584 (dec. 2018) Arc Flash Calculations

IEEE 3 Park Avenue New York, NY 10016-5997 USA 28 December 2012 IEEE Power and Energy Society IEEE Std 81 -2012 (Revision of IEEE Std 81-1983) Authorized licensed use limited to: Australian National University. Downloaded on July 27,2018 at 14:57:43 UTC from IEEE Xplore. Restrictions apply.File Size: 2MBPage Count: 86Explore furtherIEEE 81-2012 - IEEE Guide for Measuring Earth Resistivity .standards.ieee.org81-2012 - IEEE Guide for Measuring Earth Resistivity .ieeexplore.ieee.orgAn Overview Of The IEEE Standard 81 Fall-Of-Potential .www.agiusa.com(PDF) IEEE Std 80-2000 IEEE Guide for Safety in AC .www.academia.eduTesting and Evaluation of Grounding . - IEEE Web Hostingwww.ewh.ieee.orgRecommended to you b

IEEE 1584-2002 vs. IEEE 1584-2018 November 12, 2019 Slide 6 IEEE 1584-2002 (version 1.0) calculation variables: Gap (G) (equipment type driven) Working distance (D) Operating voltage (V oc) Available short circuit current (I bf) Grounding (yes/no) (not new model) Box (yes/no) New IEEE 1584-2018 (version 2.0) adds: Electrode .

IEEE 1584-2018 (IEEE Guide for Performing Arc-Flash Calculations) is substantially differ-ent from and more accurate than the 2002 version of this guide. Many organizations are now wondering whether PPE selections based on IEEE 1584-2002 arc-flash studies are still safe for workers. In some cases, incident

fructose, de la gélatine alimentaire, des arômes plus un conservateur du fruit – sorbate de potassium –, un colorant – E120 –, et deux édulco-rants – aspartame et acésulfame K. Ces quatre derniers éléments relèvent de la famille des additifs. Ils fleuris-sent sur la liste des ingrédients des spécialités laitières allégées .