Molded case circuit breakersTmaxLow Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltageTmaxMolded case circuit breakersIntroductionABB is once again demonstrating itscommitment to new product developmentand its superiority in product technology.Never before has the industry seen such highperformance, versatility and standardizationin a range of molded case circuit breakers.The ABB Tmax line of circuit breakers, with arange up to 3000A, has several key featuresthat go along with its very small size: Double insulation – this constructioncharacteristic allows for the UL Listedfield installation of internal accessorieswithout exposure to energized parts. Complete range of electrical andmechanical accessories Positive operation – breakers from ABBensure that the toggle indicates theprecise position of the moving contacts.This guarantees safe and reliablesignaling by the device. Installation – Tmax molded case circuitbreakers can be installed in panels andswitchboards in either the horizontalor vertical planes while being fed fromeither end without any derating of theirperformance characteristics. Interrupting ratings at 480VAC up to150kAIC. Compact size All Tmax molded case circuit breakersare UL Listed and IEC rated for globalapplication and acceptance. All versions of the Tmax family aresuitable for reverse feed applications.15TM maCC xBsThe ABB Tmax product line has theperformance and accessories to satisfy allindustry requirements in the 600VAC to 600VDCranges.Frame sizes — Eight basic sizesThe ABB Tmax series includes eight basic framesizes as well as the T1 single pole with therange rated from 15A to 1200A at 480VAC. Thevarious versions carry the following interruptingcapacities: B Basic breaking capacity N Normal breaking capacity S Standard breaking capacity H High breaking capacity L Extra high breaking capacity V Very high breaking capacityDerived versions 16Thermal magneticElectronicMolded case switchesMotor circuit protectors (MCPs)Direct current (DC) ratedABB Tmax versions Fixed: all models Drawout or plug-in: T2, T3, Ts3, T4, T5, T6and T7 UL File #E93565 (breakers and MCPs)#E116596 (Accessories)#E116595 (Molded case switches)16.11SXU000023C0202

15Selection GuideCircuit breakers for power distributionT1 – Ts3ax sTm CBCMT1 1PT1TypeT3Ts3Tmax T1 1pTmax T1Tmax T2Tmax T3Tmax Ts3[A]100100100225150225[Nr]13-43-43-42-3-42-3-4AC 0Frame sizeNumber of polesRated voltageT2500Interrupting ratingsBTmax Ts3500NSHNSNHLNHL50 265150506565100150651001503565255085 5255065141425203550240V AC[kA rms]277V AC[kA rms]18 1347V AC[kA rms]14 1480V AC[kA rms]22 22535600Y/347V AC[kA rms]101010600V AC[kA rms]250V DC (2 poles in series)[kA rms]252535500V DC (3 poles in series)[kA rms]252535500V DC (2 poles in series)[kA rms]355065600V DC (3 poles in series)[kA rms]203550Trip unitsTMF TMD/TMADimensionsELT MA Electronic 170W 103.5250002500025000250002500025000D16Mechanical life12345[No. operations]In15A 10kA@277VAC 10kA@347VACIn15A 35kA@240VAC 14kA@480Y/277 VACT5 600 with electronic trip units only and in three pole version2p breakers: available only in N interrupting ratingIn from 15A up to 30A 65kA@480V AC16.21SXU000023C0202Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

15Selection GuideCircuit breakers for power distributionT4 – T8T4T5T6TypeFrame sizeNumber of polesRated voltageT7T8Tmax T4Tmax T5Tmax T6Tmax T7[A]250400-600 38001000-1200[Nr]2-3-4 42-3-4 43-43-4AC (50-60Hz)[V]600600600600DC[V]Interrupting ratings600NS600HLVNSLVNSHL[kA rms] 65 100 150 200 200 65 100 150 200 200 65 100 200 200277V AC[kA rms]347V AC[kA rms]480V AC[kA rms] 25600Y/347V AC[kA rms]600V AC[kA rms] 18250V DC (2 poles in series)[kA rms]500V DC (3 poles in series)[kA rms]Insulated caseT8 / S81600, 2000,2500 & 30003600T8S8SHLT8VS8V65100150125125600H240V AC3565 100 150 253565 100 150 355065 1005065100125100253565 100 18253565 100 2025354225506510085500V DC (2 poles in series)[kA rms] 25355065 100 25355065 100 35355065600V DC (3 poles in series)[kA rms] 16253550253550203550Trip unitsTM maCC xBsTMF TMD/TMA 6516 652025 6 ELTMAElectronicDimensionsMechanical life123456 H[in/mm]8.07/2058.07/20510.55/26810.55/268W 6/154 (toggle)7/178 (motor)10,000[No. operations]15 / 38215.75 / 40016.8 / 427 15.98 / 40611.2 / 2829.53 / 24215,00010,000In15A 10kA@277 VAC 10kA@347 VACIn15A 35kA@240 VAC 14kA@480Y/277 VACT5 600 with electronic trip units only and in three pole version2p T4N250 and T5N400 available only in N interrupting capacity.In from 15A up to 30A 65kA@480 VACApplies to MCS only.Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage16.31SXU000023C020216

15General informationCatalog number explanationax sTm CBCMT3 S 080 T W - 4   xxxAccessories (added in alpha-numeric order) 1A Auxiliary SwitchS Shunt trip with voltage codeU Undervoltage release with voltage codeNumber of poles-1 1 pole (T1 only)-2 2 pole-4 4 poleNone 3 poleType connectorsW NoneL Lugs includedTrip unit functionBDTME5CE LS/I (AC only)Molded Case Switch (MCS)Thermal-magneticMagnetic only (MCP)Electronic MCP (AC only)LSI (AC only)LSIG (AC only)Current rating015 15A080 80A100 100A225 225A250 250A400 400A600 600A800 800A1200 1200AInterrupting rating class16BNSHLV BasicNormalStandardHighExtra HighVery highFrame sizeT1T2T3Ts3T4T5T6T7 100A 100A 225A 225A 250A 400A, 600A 600A, 800A 1000A, 1200A1 Consult ABB for factory installed accessories.16.41SXU000023C0202Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

15T1100A, 600Y/347V, 480V Thermal-magneticTM maCC xBsDimensions3P Fixed Version 5.12H x 3.00W x 2.76DWeight2.34 (Ibs)T1GeneralThe T1 breaker family ranges from 15 through 100 amperes. The T1 trip unitsare non-interchangeable and use the very latest technology in electromagneticrelays for overcurrent trip protection. Thermal overload protection is provided byheat sensitive bimetals. Short circuit protection for the breaker is accomplishedusing a precise magnetic coil. State of the art construction in contacts and arcingchambers aid in limiting damaging fault currents through the protected circuits.StandardsThe UL489/CSA 22.2 version of T1 also carries an IEC-60947-2 rating.VersionsThe T1 frame is available in two versions:T Thermal-magnetic, fixedD Molded case switchUL489 / CSA C22.2 Interrupting capacity (kA RMS)VoltageContinuous ratingB (1 pole)N240VAC15 – 100A—50 1347VAC15A20 – 100A1014——480VAC 15A 220 – 100A——1422600Y/347VAC15 – 100A—10250VDC 2 pole series15 – 100A—25500VDC 3 pole series15 – 100A—25Performance levelsThe T1 breaker has two performance levels available:B Basic single poleN Normal three poleIEC 60947-2 Interrupting capacity (kA RMS)VoltageContinuous ratingB (1 pole)NNumber of poles230VAC15 – 100A25 350The T1 molded case circuit breaker is available in single, three and four poleversions. Estimate 4 pole pricing by adding 35% to the 3 pole price and contactyour ABB sales person for details.415VAC15 – 100A—36690VAC15 – 100A—6500VDC 2 pole series15 – 100A—36Molded case switchesUL489 switches include no overcurrent protection except for a high instantaneoustrip mechanism for self protection.161 In 15A 35kA @ 240VAC.2 15A available in 480/277 VAC only.3 Interrupting capacity for 16-20A is 16kALow Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage16.51SXU000023C0202

15T1100A, 600Y/347V, 480V Thermal-magnetic/Molded Case Switchax sTm CBCMT1B TMF — Single pole thermal magnetic fixedBreakerIC atRating277VACMagnetictrip1 pole, 277VACcatalog 90TL-1T1B100TL-1Magnetictrip3 pole, 600Y/347VAC/500VDCcatalog numberListprice 230262T1N TMF — 3 pole thermal magnetic fixedBreakerIC 0TLListprice 402479T1N TMF — 100% Rated thermal-magneticBreakerIC at480VAC14kAT1N22kARating15 120253040506070809010016Magnetictrip3 pole 600Y/347 500VDCcatalog LT1NQ100TLMagnetictrip480VAC/500VDCcatalog numberListprice 442527T1N-D — Molded case switchBreakerT1-DInterruptingRatingcapacity 2240V, 50kA100A1000AT1N100DLListprice 4311 Rated 480V/277 VAC for 15A.2 When protected by a OCPD with appropriate ratings.16.61SXU000023C0202Discount schedule S1TLow Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

T2100A, 480V Thermal-magnetic/electronic/current limitingDimensions3P Fixed Version 5.12H x 3.54W x 2.76DWeight2.84 (Ibs)15TM maCC xBsT2GeneralThe T2 breaker family ranges from 15 through 100 amperes. The T2 trip units arenon-interchangeable and use the very latest technology in electromagnetic relaysfor overcurrent trip protection as well as a version with microprocessor-basedelectronic trip unit. Thermal overload protection is provided by heat sensitivebimetals. State of the art construction in contacts and arcing chambers aid inlimiting damaging fault currents through the protected circuits.StandardsThe UL489/CSA 22.2 version of T2 also carries an IEC-60947-2 rating.VersionsThe T2 frame is available in four versions:T Thermal-magnetic, fixedB Adjustable LS/I electronicM Magnetic only (MCP)E5 Electronic instantaneous only (MCP)UL489 / CSA C22.2 Interrupting capacity (kA RMS)VoltageContinuous ratingSH240VAC15 – 100A65100480VAC 15 – 100A3565IEC 60947-2 Interrupting capacity (kA RMS)VoltageContinuous ratingB (1 pole)N230VAC15 – 100A85100415VAC15 – 100A5070690VAC15 – 100A78500VDC 2 pole series15 – 100A5070Trip functionsThese tripping functions are available:L Long timeS Short timeI - InstantaneousPerformance levelsThe T2 breaker has two performance levels available:S StandardH High - UL Current Limiting16Number of polesThe T2 is available in three and four pole versions. Estimate 4 pole pricing byadding 35% to the 3 pole price and contact your ABB sales person for details.Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage16.71SXU000023C0202

15T2100A, 480V Thermal-magnetic/current limitingax sTm CBCMT2 — 100A TMF thermal magnetic fixedBreakerIC atRating480VACMagnetictrip3 pole, 480VACcatalog 0TWT2S040TWT2S050TWT2S060TW 2S090TWT2S100TW7933 pole, 480VACcatalog numberListpriceBreakerIC atRating480VACMagnetictripT2H65kAUL T2H070TWT2H080TWT2H090TWT2H100TW 9421,153T2 – 100A TMF, 100% rated thermal magnetic fixedBreaker16IC atRating480VACMagnetictrip3 pole, 480VACcatalog SQ030TWT2SQ040TWT2SQ050TWT2SQ060TW WT2SQ090TWT2SQ100TW872BreakerIC atRating480VACMagnetictrip3 pole, 480VACcatalog numberListpriceT2HUL 30TWT2HQ040TWT2HQ050TWT2HQ060TW unt schedule S2TLow Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

15T2100A, 480V , 100% ratedElectronic/Current limiting/MCPTM maCC xBsT2 — 100A Frame, electronic trip unit (AC only)CTrating3 pole, 480VACcatalog WT2S100BW 1,2401,2401,343T2HUL 2H060BWT2H100BW1,4921,4921,7033 pole, 480VACcatalog numberListpriceBreakerIC at480VACTrip unittypeListpriceT2 – 100A Frame 100% rated, electronic trip unit (AC only)BreakerIC at480VACTrip unittypeT2S35kAPR221DS-LS/IT2H65kAPR221DS-LS/IUL CurrentLimitingCTrating25A60AT2SQ025BWT2SQ060BW 40100AT2HQ100BW1,873T2 — 100A Frame, instantaneous only (MCP)BreakerIC at480VACTrip unitRatingtypeAdjustmentrange3 pole, 480VACcatalog numberListpriceT2S35kAMag only20A50A100A120 - 240300 - 600600 – 1200T2S020MWT2S050MWT2S100MW 598670804T2H65kAMag only20A50A100A120 - 240300 - 600600 – 1200T2H020MWT2H050MWT2H100MW6737549043 pole, 480VACcatalog numberListpriceT2 — 100A Frame, instantaneous only, electronic (MCP - AC only)BreakerIC at480VACTrip nly25A60A100A25 - 25060 - 600100 - 1000T2S025E5WT2S060E5WT2S100E5W 5 - 25060 - 600100 - te: For terminal connection options see page 16.43Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltageDiscount schedule S2T16.91SXU000023C0202

15ax sTm CBCMT3225A, 600Y/347V, 480V Thermal-magneticDimensions3P Fixed Version 5.9H x 4.13W x 2.76DWeight5.45 (Ibs)T3GeneralThe T3 breaker family ranges from 60 through 225 amperes. The T3 trip units arenon-interchangeable and use the very latest technology in electromagnetic relaysfor overcurrent trip protection. Thermal overload protection is provided by heatsensitive bimetals. Short circuit protection begins at 10 times the thermal rating ofthe breaker using a precise magnetic coil. State of the art construction in contactsand arcing chambers aid in limiting damaging fault currents through the protectedcircuits.StandardsUL489 / CSA C22.2 Interrupting capacity (kA RMS)VoltageContinuous ratingNS240VAC60 – 225A5065480VAC 60 – 225A2535600Y/347VAC60 – 225A1010250VDC 2 pole series60 – 225A2535500VDC 3 pole series60 – 225A2535The UL489/CSA 22.2 version of T3 also carries an IEC-60947-2 rating.VersionsThe T3 frame is available in three versions:T Thermal-magnetic, fixedM Magnetic only (MCP)D Molded case switchPerformance levelsThe T3 breaker has two performance levels available:N NormalS StandardIEC 60947-2 Interrupting capacity (kA RMS)VoltageContinuous ratingB (1 pole)N230VAC60 – 225A5085415VAC60 – 225A3650690VAC60 – 225A58750VDC 3 pole series60 – 225A3650Number of polesThe T3 molded case circuit breaker is available in three and four pole versions.Estimate 4 pole pricing by adding 35% to the 3 pole price and contact your ABBsales person for details.16Molded case switchesUL489 switches include no overcurrent protection except for a high instantaneoustrip mechanism for self protection.16.101SXU000023C0202Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

15T3225A, 600Y/347V, 480V Thermal-magneticTM maCC xBsT3 — 225A Frame TMF, thermal magnetic fixedBreakerIC atRating480VACMagnetictrip3 pole, 480VAC/500VDCcatalog numberListprice60A600AT3N060TW 3N200TWT3N225TW1,560Magnetictrip3 pole, 480VAC/500VDCcatalog numberBreakerIC atRating480VACListprice60A600AT3S060TW 3S200TWT3S225TW2,160T3 – 225A Frame TMF, 100% rated thermal magnetic fixedBreakerIC atRating480VACMagnetictrip3 pole, 600/347V VAC/500VDCcatalog numberListprice60A600AT3NQ060TW A2250AT3NQ200TWT3NQ225TW1,717Magnetictrip3 pole, 600/347V VAC/500VDCcatalog numberBreakerIC atRating480VACListprice60A600AT3SQ060TW 00A2250AT3SQ200TWT3SQ225TW2,399Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltageDiscount schedule S3T1616.111SXU000023C0202

15T3225A, 600Y/347V, 480V MCP/Molded case switchax sTm CBCMT3 — 225A Frame instantaneous only, (MCP)BreakerIC at480VACTrip unitRatingtypeAdjustmentrange3 pole, 480VACcatalog numberListprice100A600 – 1200T3S100MW 1,074T3S35kAMag only125A150A200A750 - 1500900 - 18001200 - 2400T3S125MWT3S150MWT3S200MW1,1081,2991,382T3S-D — Molded case switchBreakerInterrupting 1RatingcapacityT3S-D240V, 65kA480V, 35kA150A225AMagnetictrip1500A2250A3 pole, 480VAC/500VDCcatalog numberT3S150DWT3S225DWListprice 1,0781,515Note: For terminal connection options see page 16.43161 When protected by a OCPD with appropriate ratings.16.121SXU000023C0202Discount schedule S3TLow Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

15Ts3150A, 600V , 225A, 480V Thermal magneticDimensions3P Fixed Version 6.7H x 4.13W x 4.07DWeight6.75 (Ibs)TM maCC xBsTs3GeneralThe Ts3 breaker family ranges from 15 through 225 amperes. The Ts3 tripmechanisms are non-interchangeable and use sensitive electromagnetic relaysfor overcurrent trip protection. Heat sensitive bimetals are used for thermalovercurrent protection. Short circuit current protection begins at 10 times thethermal rating of the breaker and uses a magnetic coil principle.StandardsThe UL489/CSA 22.2 version of Ts3 also carries an IEC-60947-2 rating.VersionsTo meet all application needs, the Ts3 is available in various versions:T Thermal-magneticD Molded case switchM Magnetic only (MCP)Performance levelEach version is also available in different maximum fault interrupting levelsN NormalH HighL Extra highUL/CSA Interrupting capacity (kA RMS)UL489 / CSA C22.2VoltageN150AF, 15A-150A240 VAC65480 VAC25600 VAC14500 VDC35600 VDC20225AF, 175A-225A240 VAC65480 VAC25600 VAC–500 VDC20600 VDC–IEC-60947-2 Interrupting capacity (kA RMS)230 VAC65415 VAC35690 VAC1420750 VDC 2HL1005014503515085 0Number of polesThe Ts3 is available in two, three and four pole versions. Estimate 4 pole pricingby adding 35% to the 3 pole price and contact your ABB sales person for details.Molded case switchesUL489 switches include no overcurrent protection except for a high instantaneoustrip mechanism for self protection.161 15-30A are 65kA at 480VACLow Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltageDiscount schedule S3T16.131SXU000023C0202

15Ts3150A, 600V , 225A, 480V Thermal magneticax sTm CBCMTs3150A 600VAC/225A 480VACThermal Magnetic Trip UnitsBreakerTs3NBreakerTs3HIC at 480VACkA25IC at 480VACkA50RatingMagnetictrip2 pole,600VAC/500VDCcatalog etictrip2 pole,600VAC/500VDCcatalog etictrip2 pole,600VAC/500VDCcatalog W-2Ts3L150TW-2List price 8149481,471List price 9391,0712,3233 pole, 600VAC/DCcatalog number3 pole, 600VAC/DCcatalog numberList price 9581,1151,610List price 1,1051,2602,73316BreakerIC at 480VAC65Ts3L8516.141SXU000023C0202kAList price3 pole, 600VAC/DCcatalog numberList priceTs3L015TW 1,5181,5181,6923,636Discount schedule TWTs3L125TWTs3L150TW 1,7861,7861,9904,278Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

Ts3150A, 600V , 225A, 480V , 100% ratedThermal magnetic15TM maCC xBsTs3150A 600VAC/225A 480VACThermal Magnetic Trip Units 100% RatedBreakerTs3NQBreakerTs3HQBreakerIC at480VAC25IC at480VAC50kAIC at480VAC65kATs3LQ85kALow Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltageMagnetictrip3 pole 600VAC/DCcatalog RatingMagnetictrip3 polecatalog A700A800A900A1000A1250A1500A3 polecatalog Q080TWTs3LQ090TWTs3LQ100TWTs3LQ125TWTs3LQ150TWList price 1,0541,2271,771List price 1,2161,3863,00616List price 1,9652,1894,706Discount schedule S3T16.151SXU000023C0202

15Ts3150/225A 600VACMCP/Molded case switchax sTm CBCMMagnetic only (MCP)BreakerTs3LTs3LIC at 480VACTrip unit type25252525858585856565Magnetic onlyMagnetic onlyMagnetic onlyMagnetic onlyMagnetic onlyMagnetic onlyMagnetic onlyMagnetic onlyMagnetic onlyMagnetic onlyRating35102550100125150175 1200 1Adjustmentrange3 pole 600VACCatalog 3L150MWTs3L175MWTs3L200MW 7267267267269201,0951,4481,4481,4481,5173 pole 600Vcatalog numberListpriceTs3H150DWTs3H225DW 1,0601,188Molded Case Switch 2TypeIC at 480V (2)Magnetic tripTs3H505015002250Amps150225 1Note: For terminal connection options see page 16.43161 When protected by a OCPD with appropriate ratings.2 480 VAC maximum16.161SXU000023C0202Discount schedule S3TLow Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

15T4250A, 600V Electronic and thermal magneticTM maCC xBsDimensions3P Fixed Version 8.07H x 4.13W x 4.07DWeight6.18 (Ibs)T4GeneralThe T4 breaker is a 250 amp frame with either a microprocessor based overcurrent protective trip system or a thermal magnetic trip unit.StandardsThe UL489/CSA 22.2 version of T4 also carries an IEC-60947-2 rating.VersionsTo meet all application requirements, the T4 is available in the following versions:T Thermal-magneticB Selectable & adjustable LI or LSC Adjustable LSIE Adjustable LSIGD Molded Case SwitchE5 Electronic instantaneous only (MCP)Trip functionsThese trip functions are available:L Long timeS Short timeI InstantaneousG Ground faultUL489 / CSA C22.2 Interrupting capacity (kA 0150600VAC18253565100500VDC 125355065100600VDC 21625355065IEC 60947-2 Interrupting capacity (kA 200690VAC2025407080750VDC 21625365070Performance levelsEach version is also available in different maximum fault interrupting levels:N NormalS StandardH High - UL Current LimitingL Extra highV Very high - UL Current Limiting16Number of poles 3The T4 is available in two, three and four pole versions. Estimate 4 pole pricing byadding 35% to the 3 pole price and contact your ABB sales person for details.1 2 poles in series.2 3 poles in series.3 2 pole breakers available in N version only. 4 pole breakers available in N and H version only.Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage16.171SXU000023C0202

15T4250A, 600V Adjustable thermal magneticax sTm CBCM20A - 250A FrameBreakerIC at480VACT4N25T4ST4HUL CurrentLimitingT4LT4VUL CurrentLimiting3565100150RatingMagnetictrip2 pole, 600VAC/600VDCcatalog price ––3 pole, 600VAC/600VDCcatalog T4V200TWT4V250TWListprice 1616.181SXU000023C0202Discount schedule S4TLow Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

15T4250A, 600V 100% ratedAdjustable thermal magneticTM maCC xBs30A - 250A Frame 100% ratedBreakerT4NT4SIC at 480 VACkA2535T4HUL CurrentLimiting65T4L100T4VUL 00625-1250750-15001000-20001250-25003 pole,600VAC/600VDCCatalog T4VQ125TWT4VQ150TWT4VQ200TWT4VQ250TWListprice 16Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltageDiscount schedule S4T16.191SXU000023C0202

15T4250A, 600V Electronic (AC only)ax sTm CBCM100A Frame, electronic trip unit (AC only)BreakerIC at 480VACkAT4N25T4S35T4HUL CurrentLimiting65T4L100T4VUL CurrentLimiting150TripUnit2 pole, 600Vcatalog numberListprice3 pole, 600Vcatalog numberListpricePR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 LSIGT4N100BW-2T4N100CW-2T4N100EW-2- 00CWT4L100EWT4V100BWT4V100CWT4V100EWTripUnit2 pole, 600Vcatalog numberListprice3 pole, 600Vcatalog numberPR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 LSIGT4N150BW-2T4N150CW-2T4N150EW-2- 50CWT4L150EWT4V150BWT4V150CWT4V150EW 6,2887,3548,8729,55510,326TripUnit2 pole, 600Vcatalog numberListprice3 pole, 600Vcatalog numberListpricePR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 LSIGT4N250BW-2T4N250CW-2T4N250EW-2- 6,0637,0918,5559,2139,957150A Frame, electronic trip unit (AC only)BreakerIC at 480VACkAT4N25T4S35T4HUL CurrentLimiting65T4L100T4VUL CurrentLimiting150Listprice250A Frame, electronic trip unit (AC only)BreakerIC at 480VACkAT4N25T4S35T4HUL CurrentLimiting65T4L100T4VUL CurrentLimiting1501616.201SXU000023C0202 2,0062,6783,511-Discount schedule 4V250BWT4V250CWT4V250EW 6,4167,5049,0539,75010,537Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

T4250A, 600V , 100% RatedElectronic (AC only)15TM maCC xBs100A Frame - 100% rated, electronic trip unit (AC only)BreakerIC at 480VACkAT4N25T4S35T4HUL CurrentLimiting65T4L100T4VUL CurrentLimiting150TripUnit3 pole, 600Vcatalog numberPR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 0CWT4LQ100EWT4VQ100BWT4VQ100CWT4VQ100EWListprice 6,7377,8799,50610,23711,063150A Frame - 100% rated, electronic trip unit (AC only)BreakerIC at 480VACkAT4N25T4S35T4HUL CurrentLimiting65T4L100T4VUL CurrentLimiting150TripUnit3 pole, 600Vcatalog numberPR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 0CWT4LQ150EWT4VQ150BWT4VQ150CWT4VQ150EWListprice 6,9878,1719,85810,61611,473250A Frame - 100% rated, electronic trip unit (AC only)BreakerIC at 480VACkAT4N25T4S35T4HUL CurrentLimiting65T4L100T4VUL CurrentLimiting150Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltageTripUnit3 pole, 600Vcatalog numberPR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 LSIGPR221 LS/IPR222 LSIPR222 LSIGPR221

Motor circuit protectors (MCPs) Direct current (DC) rated ABB Tmax versions Fixed: all models Drawout or plug-in: T2, T3, Ts3, T4, T5, T6 and T7 UL File #E93565 (breakers and MCPs) #E116596 (A

Related Documents:

World Super Series MCCBs (16-125) NF125, (150-250) NF250 41 World Super Series ELCBs (16-125) NV125, (150-250) NV250 42 World Super Series Accessories 43 - 44 Mitsubishi Electric MCCBs, ELCBs and Switch Disconnectors (DSN) World Super Series MCCBs (200-1600 A) NF 45 World Super Series ELCBs (250-800 A) NV 46 World Super Series Accessories 47 - 48

In most electrical systems, the MCCBs are rated for operation at 80% of t heir rated current. However, certain application use MCCBs rated for 100% operation. This document defines certain terms applicab le to circuit breakers, explains the rati ngs for 100% versus 80% operation, and pro vides cases where 100% rated MCCBs could be beneficial.

Switchgear OS switch fuses Short form catalogue 3 Switch Fuses 0115 ABB Low Voltage 3 Switch Fuses 0115 ABB Low Voltage Switchgear OS Switch fuses Contents Introduction 4 Overview 6 Features 8 OS Switches fuses 20 - 1250A 10 Accessories 17 4 Switch Fuses 0115 ABB Low Voltage 5 Switch Fuses 0115 ABB Low Voltage

ABB Control SECRL - 1 2001-06-19 A New Contactor Range from ABB New Generation ABB Contactors. ABB Control SECRL - 2 2001-06-19 The ABB range of A The ABB range of A contactorscontactors A 9, A 12, A 16 A 26, A 30, A 40 A 50, A 63, A 75 A 95, A

ABB - global market and technology leader in AC drives ABB (www.abb.com) is a leader in power and automation technologies that enable utility and industry customers to improve their performance while lowering environmental impact. ABB is the world's largest drives manufacturer. The ABB Group of companies operates in around 100 countries

E-bypass. The ABB E-Clipse Bypass has taken these developments to the next level. In addition to the benefits of the previous ABB design, ABB has added new capabilities focused upon the changing and evolving customer and market requirements. This brochure will give the user a brief overview

In 1994, ABB pioneered serial communications for VFDs in the HVAC industry. Today ABB has installed over 150,000 units (in the U.S. alone) connected to building automations systems using the various HVAC communications protocols. The ABB E-Clipse Bypass includes serial communications in the bypass mode. Now, going to bypass does not mean losing

In recent years technologies like Artificial Intelligence (AI) is been proved immensely valuable to SCM. As the name suggests AI defined as the ability of a computer to independently solve problems that they have not been explicitly programmed to address. The field of AI came to existence in 1956, in a workshop organized by John McCarthy (McCarthy Et al., 2006). In successive years the .