Short form catalogueSwitchgearEnclosed switch disconnectors,switch fuses and transfer switches

SwitchgearEnclosed OT switch disconnectors, OS switch fuses,Manual & automatic transfer switchesContentsOFFNF 1OFFNB 1415V415V32A1 / gG63A1 / gG 80kA4Metal enclosed switches5Metal enclosed switch fuses6Fuses7Metal enclosed manual & automatic transfer switches8Functionallity & features10General & technical information12Controller technical information14Selection16Accessories18 80kAMADE IN ABBS04076MADE IN ABBS04075Double insulated enclosed switches & safety switches3 Enclosed Switching Products 0115 ABB Low Voltage

Switchgear - Loadbreak & safety switchesIP65 Double insulated enclosureLoad Break Switches 3 - 4 pole 9.37kWDescription IP65 three and four-pole switch disconnectors suitable for load break switching or isolation. Polycarbonate enclosure. IEC 60947-3Polycarbonate Enclosure 9kW . 11kW 3 poleRating@415v1th ADimensions mmAC22kW32259404011HWD125100107Part NumberProduct Hierarchy 4000002Order -APolycarbonate Enclosure 9kW . 37kW 4 N-AS415KN-AS418KN-AS418KN-AS426KN-AS426KN-ALoad Break Switches 3 - 4 - 6 pole 16.125 ampsDescription IP65 ratedGrey plastic enclosureStandard handle - Red/Yellow (padlockable in the off position)Cable entries top and bottomAll OTP16 (excluding 3p) /25/32 all have 25/20mm reducersRating@415v1th AAC22AC23Dimensions mmkWNo. PolesHWD3 solid 12237454OTP16BA4MSOTP16BA4MSOTP16BA6M3 solid A6MOTP25BA6M3 A6MOTP32BA6M3 solid A6MOTP45BA6M3 solid 0020013013014514560OTP16BA3MOTP16BA6M150130Order CodeOTP16BA3M64150Product Hierarchy 4000002Part Number606090906OTP63BA6MOTP63BA6M3 solid 125BA6UOTP125BA6UProduct Hierarchy 4000002Order Code44002001406Safety Switches 3 pole 16.40 ampsRating@415vDimensions mm1th AAC22AC23kWNo. PolesHWDPart 32B3U4 Enclosed Switching Products 0115 ABB Low Voltage

Switchgear - Loadbreak switchesIP65 Steel enclosureLoad Break Switches 3 - 4 pole 20 . 800A IP65 rated (not suitable for external installation)Powder coated textured finish (RAL 7035)All 3 pole switches include detachable neutral link (OT160 solid link)Hinged lid complete with lockPadlockable pistol grip handle as standardRemovable gland plates fitted top and bottom (see below for knockout configurations)Spreader boxes available see belowRating@415v [A]Dimensions1th 0400400400400400400Spreader BoxesSuitable for Loadbreak Switches150150150150200200200200250250No. Poles3 solid neutral43 solid neutral43 solid neutral43 solid neutral43 solid neutral43 solid neutral43 solid neutral43 solid neutral4Product Hierarchy 4000003Order CodePart AOT200FP-AOT315TPN-AOT315TPN-AOT400FP-AOT400FP-A3 solid neutralOT400TPN-AOT400TPN-A4OT400TPN-AOT400TPN-A3 solid neutralOT630TPN-AOT630TPN-A4OT630FP-AOT630FP-A3 solid oduct Hierarchy 3200003Spreader BoxOrder CodeOT20, OT32, OT63, OT100, OT125Spreader Box GasketOrder CodeNot RequiredOT160, OT200, OT315, OT400SRN5420KOT630, OT800SRN6425KWall Mounting Brackets (Pack of 4)GZ4020GZ4025AA1206Auxiliary Contacts1 N/OOA1G10OA1G101 N/C - only for OT20-125OA1G01OA1G011 N/C - only for OT200 and aboveOA3G01OA3G011 N/O - 1 N/C - OT20-125 and OT160 onlyOA2G11OA2G11Mounting module for OA2G11 - for OT160 onlyOAZX1OAZX15 Enclosed Switching Products 0115 ABB Low Voltage

Switchgear - Switch fusesIP65 Steel enclosure3 - 4 pole 20 . 800A IP65 rated (not suitable for external installation)Powder coated textured finish (RAL 7035)All switches are supplied with fuses and removable gland platesAll 3 pole switches include detachable neutral link (OT160 solid link)Switch Fuses are internally rated IP20 on incoming terminals up to 63AHinged lid complete with lockAC23 0220355450111837557590132220280450560Padlockable pistol grip handle as standardSwitch Fuses 100A are supplied with incoming terminal shrouds(NOT FITTED) to allow customer connections Spreader boxes available see belowDimensions1thA 400V 500V 690V20 0150150150150200250250250300300No. PolesFuse Type3 detach neutralA143 detach neutralA243 detach neutralA2/A343 detach neutralA2/A343 detach neutralA2/A343 solid neutralA3/A443 detach neutralB1/B243 detach neutralB1/B443 detach neutralB1/B443 detach neutralC1/C243 detach neutralC1/C24Part NumberProduct Hierarchy 4000003Order AOS800FP-ANote: OT630 & OT800 TPN/FP products are made to order and are non-stock itemsSpreader BoxesSuitable for Loadbreak SwitchesSpreader BoxPart NumberOS20 - OS125Not RequiredOS160SRN5420KSpreader Box GasketProduct Hierarchy 3200003Order CodePart Number-Not RequiredSRN5420KProduct Hierarchy 3200003Order Code-GZ4020GZ4020OS200 - OS400SRN6425KSRN6425KGZ4025GZ4025OS630 - OS800SRN8530KSRN8530KGZ6030GZ6030AA1206AA1206Wall Mounting Brackets (Pack of 4)Auxiliary Contacts1 N/OOA1G10OA1G101 N/COA3G01OA3G011 N/O - 1 N/COA2G11OA2G111 x CO contact - only for products OS20 /OS32OA4B1COA4B1CMounting frame to fit OA1/OA3 aux on left side of OS20/0S32 switch fuse (only for OS20 /OS32OSZ46 Enclosed Switching Products 0115 ABB Low VoltageOSZ4

Switchgear - BS fusesHRC fuse links, BS-typeBS FusesBS-fuse typeIn [A]Ph [W]Part NumberProduct Hierarchy0002100007 Order CodeTag type: OffsetOFFNA 2OFFNA 1415V415V32A2 / gG32A1 / gGOFFNF 1415V 80kAMADE IN ABBS04082 8R1001101.2OFFNF1GG101SCA107789R1001MADE IN ABBS04075MADE IN ABBS04080 80kA32A1 / FFNF1GG321SCA107793R1001Tag type: Offset, two holes fixing 20OFFNA 4415VOFFNA 3125A4 / gG415V63A3 / gG 80kAMADE IN ABBMADE IN ABBS04081S04082 80kAA1OFFNA3OFFNA4OFFNB 1415V63A1 / gGOFFNB 2415V 80kA200A2 / gGS04076MADE IN ABBA2 80kABMADE IN ABOFFNB1OFFNB2OFFNB 4OFFNB 3415V415VA4400A4 / gG315A3 / gG 80kA 80kABMADE IN ABS04079S04078A3OFFNB3BMADE IN ABOFFNB4B1B2OFFNC 2415VS04083MADE IN A107817R100120016.2OFFNB2GG2001SCA107818R1001Tag type: Central, two holes fixing 10630A2 / gG 825R100180068.0OFFNC3GG8001SCA107826R1001B3Tag type: Central, four holes fixingOFFNC2C37 Enclosed Switching Products 0115 ABB Low Voltage

Enclosedmanualcommitmentand automatic transfer switchesConstantABB low voltage component capabilities for critical power applicationsABB’s solutions and products to ensurecontinuity of operationCriticalpowerapplicationsconstantand reliablepowerCriticalapplicationsrequirerequire a aconstantand reliablepower supplyto keepsupply to keepservicesrunningand preventfundamentalservicesfundamentalrunning and preventseriousconsequencescaused by theinterruptionor absence of the dueelectricalgrid.serious consequencesto interruptionor absence of theelectricalgrid.Thisneed is controleven andstrongernowadaysSelectionof asourceof switching,protectioncapable of becausesustaining theneedsa critical powerapplication is ofparamount,ABBhas a wellandproventrackof theofincreasingsignificancekey role,capacityfeaturesrecordwithinthis environment.of thesesystems.In order to ensure the high level of reliabilityrequested, the system must include generators and UPSequipment which ensure the right power supply to the criticalloads in case of grid failure.48 EnclosedSecuringSwitchingyour powersupplyProducts0115 ABB Low Voltage

In today’s world, electrical power plays a key role in almostIn today’s world, electrical power plays a key role in almost everyeveryactivity of our life. For some equipment a reliable,activity of our life. For some equipment a reliable, uninterruptible anduninterruptibleandfree supplyof disturbancepowersupplyis anfree of disturbancepoweris an absoluteessential.Fromthisabsoluteneed.point of view, a fault in the power supply of communications systems,Fromthispoint ofsecurityview, asystems,fault in thepowersupplyofhospitalapparatus,waterand atus,securitydevices, banking computers and many other crucial applicationssystems,water seriousand gasdistributiondevices, bankingmay bring aboutproblems,with consequencesthat can becomputersandmanyothercrucialappliancemay bring aboutdevastating.serious problems, with consequences that can easily beAll these applications can be identified as “Critical Power” applications:imagined.ABB can offer a wide range of components for on board installationAll these applications can be identified as “Critical Power”and complete power distribution systems.applications: they are specifically designed to leverage aThese and securesupply,for ACU),manualandmotorisedchange-overequipment or power ,Air offerand moulded-caseInthe areaof “CriticalPower” ABB cana wide ,protectiondevicesinstallationagainstproducts, including both components for on boardovervoltages,contactors,current sensorsand many other devices.andcompletepower distributionsystems.These products range from low voltage generators forABB products comply with the most important internationalgeneratorsets (Gen-set) to iPDU (intelligent Power Distributionstandards and European or North American - and with theUnits) switchboards,includeall typesrequirements ofandthe NavyRegistry;they ofareequipmentalso ability:air,and built on the basis of the most modern and otectionsenvironmental standards. ABB products are backed byagainst aovervoltages,isolators andswitch-disconnectors,consolidated experiencein powerand switches,technologies. They are supported through a ticcontroland service network which covers more than 100 units,countries allcurrent sensorsand many other devices.over the world.ABB products comply with the most important internationalstandards - either European or North American - and with therequirements of the Navy Registry; they are also designedand built on the basis of the most modern and advancedenvironmental standards.ABB products are backed by a consolidated experience inpower and automation technologies. They are supportedthrough a global assistance and service network which coversmore than 100 countries all over the world.Securing0115your ABBpowersupply 59 Enclosed Switching ProductsLowVoltage

Enclosed manual & automatic transfer switchesFunctionality & featuresAs industrial processes and IT applicationsdiversify, a secure power supply is becomingan increasingly important asset in the driveto cut production and maintenance costs.In emergency situations, the system logicof power distribution can become complexwith mechanical devices looking after themaking, breaking, conducting and isolatingof power. Loads may sometimes need tobe transferred from one supply to another— this will be the case when energy useis restricted or when the supply source isoverloaded.ATS isolatorBypass supply selection switchClosed transition ATS bypass switchAutomatic transfer controllerAutomatic transfer switchHigh performance levelIn change-over applications where the loaded switchmay need to be operated remotely, adequate durabilityhas been ensured by testing against the IEC 60947-6-1standard in the specification of endurance requirements.Utillisation categories:AC-31for non-inductive or slightly inductive loadABB products for GENSET AC-33 for motor loads or mixed loads including motorsABB change-over switches are rated according toIEC 60947-6-1 standard.Control panel- ATS Panels(Change-over switch,monitoring relays,push buttons)Circuit breaker- ACB, MCCB- MCB10 Enclosed Switching Products 0115 ABB Low Voltage6 GEN SET and UPS manufacturers

Fig. 1 ATS automatic transfer switch with dual supply bypassStandard ATS without bypasswith blank doorwith pilot lights showinghealthy suppliesATS controller mountedon doorOMD300controllerOMD800controller11 Enclosed Switching Products 0115 ABB Low Voltage

Enclosed automatic transfer switchesGeneral informationEnclosed automatic transfer switcheswith current ratings 40A 1600A. Theenclosure complies with IP65 EN 60529and finished in a RAL 7035 colour.The ATS enclosures are designed to allowadequate cabling space to allow installersto terminate oversized cables.Automatic transfer switchesDesign & safetyAutomatic transfer switches comply with the standards listed below.Automatic transfer switches are available as 3 or 4 pole versions.All three positions I, 0 and II shall be stable and keep its positions incase of supply failure or mechanical shocks.The switch mechanism is located on the left hand side to theswitch’s power poles. The operating mechanism is of “quick make /quick break” construction. The position indication markings on themechanism shall always show reliably the true position of the maincontacts. Automatic transfer switchs can be operated by directmounted handle and the handle shall be showing reliably the realposition of the main contacts of the transfer switch. The handle willallow the switch to be padlocked in the off position. IEC 60947-1:Low voltage switchgear and control gear Part 1: General rules IEC 60947-3:Low voltage switchgear and control gear Part 3: Switches,disconnectors, switch-disconnectors and fuse-combination IEC 60947-6-1-PC: Low voltage switchgear and control gearPart 6: Multiple function equipment – Transfer switching equipmentApplicationThe automatic transfer switch is managing different power suppliesto one or more load circuits and guarantees the continuity ofperformance. The automatic transfer switch ensures the switchingand isolation between the primary network supply and the alternatenetwork supply or a standby generator. Type of operation is opentransition, i.e. break-before-make.The automatic transfer switches can be operated in three ways,local manual operation with handle, local manual operation withthe automatic control unit or full automatic operation done bythe automatic control unit. Manual operation, using a handle isthe simplest type of operation. Local manual operation with thecontrol unit enables to operate the switch electrically. Full automaticoperation ensures that loads are transferred automatically to thesecondary source in case of mains failure. Both local operation withthe control unit and full automatic operation enables a short switch-offtime between the normal and the alternative supply.Automatic transfer switches shall be used for switching I, 0 and IIpositions following types of loads: Off load application (AC 20A) Resistive loads (AC 21 or AC31) Mixed resistive and inductive loads (AC 22) Motor loads12 Enclosed Switching Products 0115 ABB Low VoltageThe automatic transfer switch is constructed with a motor operator.The motor operator is protected against overloads with a separateoverload fuse (160A to 1600A). The fuse is situated at the bottomof the Motor. The 40A to 125A motor is protected by a resettableoverload button.The accessories, i.e. terminal shrouds and auxiliary contacts shall bemountable without any special tools (i.e. snap on mounting).The terminals of the 160A to 1600A automatic transfer switch itis possible to connect two parallel cables for easier installationand space saving. All the terminals shall be finger protected withor without separate terminal shrouds. All the metal parts shall beprotected against corrosion. The contact surfaces shall be silverplated to minimise contact resistance. The automatic transferswitches meet the ROHS requirements and only recyclable materialis used. The current carrying plastic parts shall have high thermal,mechanical and electrical properties and have V0 classification.The voltage sensing wiring from the switch’s power poles to theautomatic control unit is done by the automatic transfer switchmanufacturer. Voltage sensing wires are double insulated.

Enclosed automatic transfer switchesGeneral & technical specificationThe handle is a direct mounted type, and it shall bepadlockable in the “0” position with three padlocks with5 6 mm. It is possible to operate switch with themanual handle in case of emergency, regardless of theposition of switch and without any supply power.Bypass RequirementTechnical specifications according toIEC 60947-3 and IEC 60947-6-1The bypass switches consist of the following; A closed transition manual changeover switch is included to allow for theseamless (no 0 position giving no break in supply when moving to bypass)transition to bypass. The front of the panel should indicate that the ATS hasbeen bypassed and is safe to carry out maintenance.Type of equipmentClass of equipmentRated operational voltage,Rated impulse withstand voltage,Rated frequencyEMC environmentATSEPCUe Max. 415 VUimp 6 kV50 - 60 HzA and BIn order to comply with BS8519 which states “Where the availabilityof the life safety and fire-fighting equipment is conditional to theoccupation of the building, a bypass arrangement should beincorporated to enable the changeover device to be maintainedwithout loss of service from the critical plant”.Single or mains bypassDual BypassA closed transition manual changeover switch is included to allow for theseamless (no 0 position giving no break in supply when moving to bypass)transition to bypass. Together with a standard manual changeover switch toallow you to choose between supply 1 or supply 2. The front of the panel shouldindicate that the ATS has been bypassed and which supply is feeding the loadand is safe to carry out maintenance.Specific ratings according to IEC 60947-3 40A to 125ARated free air thermal current (Ith) and operational current in AC20 at 40 C ambient temperatureA406380115125Rated enclosed thermal current (Ith) and operational current in AC20 at 40 C ambient temperatureA406380115125Rated operational current AC 21A and AC 22A at voltages up to 500VA406380100125Rated operational current AC23A at voltages up to 415VA4063808090Rated AC 23 breaking capacity at 415VA320504640640720Rated conditional short circuit current Ip (r.m.s.) at 415V, 50kA netkA16.516.516.516.516.5and corresponding max. allowed cut-off current of gGA125125125125125Rated short time withstand current Icw 690v (1sec), (r.m.s. value)kA2.52.52.52.52.5Rated short time making capacity Icm, peak value 690vkA3.63.63.63.63.6Mechanical endurance / switchOper2000020000200002000020000Rated short-time withstand current Icw (r.m.s.) 690V, 0,1 seckA55555Rated operational current, AC-31B, up to 415VA406380100125Rated operational current, AC-33B, up to 415VA4063808080Rated free air thermal current (Ith) and operational current in AC20 at 40 C ambient temperatureA160200250315400630800100012501600Rated enclosed thermal current (Ith) and operational current in AC20 at 40 C ambient temperatureA16020025031540063080010001201600Rated operational current AC 21A and AC 22A at voltages up to 415VA160200250315400630800100012501600Rated operational current AC23A at voltages up to 415VA160200250315400630800100012501250Rated AC 23 breaking capacity at ted conditional short circuit current Ip (r.m.s.) at 415V, 50kA netkA40.540.540.5595983.583.5100100100and corresponding max. allowed cut-off current of gGA355355355500500800800125012501250Rated short time withstand current Icw 690v (1sec), (r.m.s. value)kA88815152020505050Rated short time making capacity Icm, peak value 690vkA30303065658080929292Mechanical endurance / 0006000Rated short-time withstand current Icw (r.m.s.) 690V, 0,1 seckA15151525253838505050Rated operational current, AC-31B, up to 415VA160200250315400650720100012501600Rated operational current, AC-33B, up to 415VA160200250315400650650100010001000Specific ratings according to IEC 60947-3 160A to 1600A

Enclosed automatic transfer switchesControllers technical specificationComments1) Dual power source allows the motor operator to be supplied by twoseparate voltage supplies. This way the motor operator is always energized.2) Four options: 0, 5, 10 or 30 seconds.3) Delaying the switching sequence before transferring to generator,guaranteeing that in cold locations the generator is properly heated up.4) Two options: the duration of back-switching delay is the same as switchingdelay, i.e. the time delay is same for I - II and II - I, or the back-switchingdelay is fixed 300 seconds.FunctionalityOTM C3DOTM C8D1.1. Automatic control unitOMD300OMD8001.1. Manual operation with handleXX1.2. Local operation with front panel keypadXX1.3. Automatic transfer switching equipment (ATSE)XXoperator 1)XO2.1. Three phase voltage measurement on LINE1XX2.2. Single phase voltage measurement on LINE1XX2.3. Three phase voltage measurement on LINE2XX2.4. Single phase voltage measurement on LINE2XX2.5. Frequency on LINE1XX2.6. Frequency on LINE2XX1. Automatic transfer switch products overview5) Two options: the duration of generator stop delay is the same as Switchingdelay or fixed 5 min.1.4. Dual power source for the motor6) Menus available in eight languages; English, French, German, Italian,Spanish, Russian, Chinese and Finnish.2. Measurements7) Two-way communication, bus communication protocol is Modbus8) In case of source failure, the controller can be supplied with an externalauxiliary supply with 24 110 V DC.9) Automatic control unit requires an external signal before allowing thetransfer to secondary.10) Two options for the operating mode after receiving the alarm: control uniteither works normally, or initiates generator stop with operation to position O.11) Two options: No line priority, or Source 1 is the priority source.12) Three options: No line priority, Source 1 or Source 2 is the priority source.2.7. Possibility to check measurements on LCDX13) Automatic back-switching to primary source is prevented.3. Source failure detections14) Automatic control unit and motor operator must be energized.3.1. No voltageXXX includes as standard3.2. UndervoltageXX3.3. OvervoltageXX3.4. Phase missingXX3.5. Voltage unbalanceXX3.6. Invalid frequencyXXO as an accessory3.7. Incorrect phase sequenceX4. Configuration4.1. By DIP switchesX4.2. By rotary switchesX4.3. By keypad and LCD4.4. Voltage threshold settingXXX4.5. Voltage hysteresis settingX4.6. Frequency threshold settingX4.7. Frequency hysteresis settingX5. Time delays5.1. Switching delayX 2)5.2. Delay on transfer 3)X5.3. Dead band time I-II (stop switching to position O)5.4. Back-switching delayXX 4)5.5. Dead band time II-I (stop switching to position O)5.6. Generator stop delay5.7. Status of time delays on the LCDIn the enclosed ATS the dual power source is included14 Enclosed Switching Products 0115 ABB Low VoltageXXXX 5)XX

Enclosed automatic transfer switchesControllers technical specificationCommentsFunctionalityOTM C3DOTM C8D6.2. Generator start and stopXX6.3. OFF-load test sequenceXX4) Two options: the duration of back-switching delay is the same as switchingdelay, i.e. the time delay is same for I - II and II - I, or the back-switchingdelay is fixed 300 seconds.6.4. ON-load test sequenceXX6.5. Source status via front panelXX5) Two options: the duration of generator stop delay is the same as Switchingdelay or fixed 5 min.6.6. Source status via digital outputs1) Dual power source allows the motor operator to be supplied by twoseparate voltage supplies. This way the motor operator is always energized.2) Four options: 0, 5, 10 or 30 seconds.3) Delaying the switching sequence before transferring to generator,guaranteeing that in cold locations the generator is properly heated up.6) Menus available in eight languages; English, French, German, Italian,Spanish, Russian, Chinese and Finnish.6.1. FeaturesX6.7. Switch position via front panelX6.8. LCD 6)XX7) Two-way communication, bus communication protocol is Modbus6.9. Fieldbus interface8) In case of source failure, the controller can be supplied with an externalauxiliary supply with 24 110 V DC.6.10. Event/alarm logX6.11. Counter for number of operationsX6.12. Auxiliary voltage supply 8)X6.13. Programmable digital inputs (eight) and digital outputs (six)X6.14. Secondary load control (load shedding)X9) Automatic control unit requires an external signal before allowing thetransfer to secondary.10) Two options for the operating mode after receiving the alarm: control uniteither works normally, or initiates generator stop with operation to position O.11) Two options: No line priority, or Source 1 is the priority source.7)X12) Three options: No line priority, Source 1 or Source 2 is the priority source.6.15. Digital input – Allow transfer to13) Automatic back-switching to primary source is prevented.6.16. Digital input - Generator alarm 10)X6.17. Digital input - Remote control to positions I, O and IIX14) Automatic control unit and motor operator must be energized.X includes as standardO as an accessorysecondary 9)X7. Operating mode7.1. Line priority7.2. Manualback-switching 13)7.3. Automatic operation to position O, in case of source failureX 11)X 12)XX14)X8. Applications8.1. Transfer between two transformersXX8.2. Transfer between a transformer and a generatorXXIn the enclosed ATS the dual power source is included15 Enclosed Switching Products 0115 ABB Low Voltage

Enclosed manual & automatic transfer switchesSelectionEnclosed manual transfer switches, I-O-II operation, open transition MTS 4 pole 40 to 800A with blank door, wall mountableEnclosure Size (mm)DescriptionRatedCurrent(A)HWDMTS 40A40400300150OT40FPC-BMTS 63A63400300150OT63FPC-BOrder CodeMTS 80A80400300150OT80FPC-BMTS 100A100500400250OT100FPC-BMTS 125A125500400250OT125FPC-BMTS 160A160600400250OT160FPC-BMTS 200A200600400250OT200FPC-BMTS 250A250600400250OT250FPC-BMTS 315A315800600300OT315FPC-BMTS 400A400800600300OT400FPC-BMTS 630A6301000600400OT630FPC-BMTS 800A8001000600400OT800FPC-BEnclosed automatic transfer switches, I-O-II operation, open transition ATS 4 pole 40 to 1600A with OMD300 & OMD800 controller, blank door, wall mountableDescriptionRatedCurrent(A)ATS 40A40Enclosure Size (mm)Controller OMD300HWDPart NumberOrder Code600600250OTA40E4C3SR1TVC004014S3000ATS 63A63600600250OTA63E4C3SR1TVC006314S3000ATS 125A125600600250OTA125E4C3SR1TVC012514S3000ATS 160A160600600250OTA160E4C3SR1TVC016014S3000ATS 250A250600600250OTA250E4C3SR1TVC025014S3000ATS 400A400800600300OTA400E4C3SR1TVC040014S3000ATS 630A*6301000800400OTA630E4C3AM1TVC063024S3000ATS 800A*8001000800400OTA800E4C3AM1TVC080024S3000ATS S S scriptionRatedCurrent(A)ATS 40A40Enclosure Size (mm)Controller OMD800HWDPart NumberOrder Code600600250OTA40E4C8SR1TVC004014S8000ATS 63A63600600250OTA63E4C8SR1TVC006314S8000ATS 125A125600600250OTA125E4C8SR1TVC012514S8000ATS 160A160600600250OTA160E4C8SR1TVC016014S8000ATS 250A250600600250OTA250E4C8SR1TVC025014S8000ATS 400A400800600300OTA400E4C8SR1TVC040014S8000ATS 630A*6301000800400OTA630E4C8AM1TVC063024S8000ATS 800A*8001000800400OTA800E4C8AM1TVC080024S8000ATS S S 1600A*16001400800500OTA1600E4C8AM1TVC160024S8000* Floor standing - plinths from accessories below.Bypass options

Short form catalogue. 3 Enclosed Switching Products 0115 ABB Low Voltage . 3 Enclosed Switching Products 0115 ABB Low Voltage Switchgear Enclosed OT switch disconnectors, OS switch fuses, Manual & automatic transfer switches Contents D

Related Documents:

A-Drawout AKD-6 switchgear B-Drawout substructure D-Drawout AKD-8 switchgear and substructure S-Stationary Fig. 1. AKR breaker type designation . com 3 BCS Switchgear Inc. Switchgear Circuit Breakers Parts Tech Support bcsswitchgear.com 888.599.0486 Need Help? 888.599.0486 · ;: .

1. A new switchgear architecture for modern technology 1.1 Philosophy The standard IEC 60298 for AC metal-enclosed switchgear and controlgear , 1 - 52 kV, defines three different types of architectures: Metal-clad, compartmented and cubicle switchgear and controlgear. With the new switchgear AX1 a

Switchgear Support Ltd specialise in the supply of components and services for MV/HV legacy switchgear, typically originally manufactured between the 1950’s and 1990’s. Predominantly, these activities are focused on the Brush Switchgear and South Wales Switchgear

Switchgear OS switch fuses Short form catalogue 3 Switch Fuses 0115 ABB Low Voltage 3 Switch Fuses 0115 ABB Low Voltage Switchgear OS Switch fuses Contents Introduction 4 Overview 6 Features 8 OS Switches fuses 20 - 1250A 10 Accessories 17 4 Switch Fuses 0115 ABB Low Voltage 5 Switch Fuses 0115 ABB Low Voltage

38 kV Metal-Clad Switchgear Eaton's VacClad switchgear family is designed for use in applications with distribution voltages up to 38 kV maxi-mum. Typical applications include not only new construction but also replace-ment for older air-break, minimum oil or SF6 switchgear. The circuit breaker and switchgear will meet industry require-

3.12 IEC 62271-100 High-voltage switchgear and controlgear-Part 100: Alternating-current circuit-breakers 3.13 IEC 62271-200 High-voltage switchgear and controlgear - Part 200: AC Metal-Enclosed Switchgear and Controlgear for

Medium-Voltage Switchgear Type NXPLUS C Fixed-Mounted Circuit-Breaker Switchgear up to 24 kV, Extendable Single Busbar, Metal-Enclosed, Gas-Insulated Medium-Voltage Switchgear INSTALLATION AND OPERATING INSTRUCT

Plan and monitor animal diet and nutrition LANAnC46 Plan and monitor animal diet and nutrition 1 Overview This standard covers planning and monitoring the diet and nutrition for animals in your care. You will need to identify the nutritional requirements of the animals and develop feeding plans containing all the necessary information for those responsible for feeding the animals. You will .