1746 SLC I/O to Compact 5000I/O Conversion SystemBulletin Number 1492Selection GuideOriginal Instructions

1746 SLC I/O to Compact 5000 I/O Conversion System Selection GuideWhat’s InsideTopicConversion System Product SelectionConversion Chassis Approximate DimensionsDigital InputsDigital OutputsAnalog Inputs and OutputsConversion Module DimensionsSpecificationsAssembled System DimensionsConversion Module Wiring DiagramsAdditional Resources2Page35910111214151931Rockwell Automation Publication 1492-SG010B-EN-P - February 2021

1746 SLC I/O to Compact 5000 I/O Conversion SystemConversion System Product SelectionI/O conversion modules provide a fast and efficient method for converting 1746 SLC I/O to Compact 5000 I/O. The I/O conversion is accomplishedwithout removing any field wires from the existing terminal block, virtually removing the risk of wiring errors and reducing wiring/installation time. Theexisting removable terminal block fits directly into the new 1492 conversion modules.The cables are pre-wired and have a connector for the conversion module on one end and a removable terminal block (RTB) on the other end. The I/Osignals are routed through the conversion module and the cable to the appropriate terminals on the Compact 5000 I/O module.The I/O Conversion System Includes:Conversion Modules (Example: Cat No: 1492-CM1746-M01)Conversion ModuleProvides interface from the 1746 SLC I/O removable terminal blockto the Compact 5000 I/O system.Conversion Chassis(a) (Example: Cat No: 1492-CH1746-7)Upper Mounting PlateTo mount the Compact 5000 I/O system modules and to protect the conversionmodules.Lower Mounting PlateTo mount conversion modules.Chassis Mounting HardwareTo attach the upper mounting plate to the lower mounting plate.(a) The conversion chassis includes the upper and lower mounting plates and hardware. Two 1492-EAHJ35 end anchors (not included) are needed to secure the Compact 5000 I/O system to thedin rail.Rockwell Automation Publication 1492-SG010B-EN-P - February 20213

1746 SLC I/O to Compact 5000 I/O Conversion SystemConversion System Product SelectionConversion Chassis Selection InstructionsConversion Modules must be installed in a 1492 Conversion Chassis. Use the following steps to select the proper conversion chassis:1.Determine the quantity of each type of 1746 SLC I/O modules to be converted to Compact 5000 I/O.IMPORTANT2.In some cases two Compact 5000 I/O modules may be required for one 1746 SLC I/O module.Review the Max Slots for I/O and chassis width data table below, and select a 1492 Conversion Chassis which meets your conversionneeds from step 1.The combined depth of the conversion chassis with the CompactLogix 5380 & Compact 5000 I/O system mounted is 8.75 inches.Dimension drawings are included in the System Installation Manual that ships with the conversion chassis assembly.1746 SLC I/O to Compact 5000 I/O Conversion Chassis41746 Chassis1492 Conversion 1492-CH1746-71492-CH1746-101492-CH1746-131746 SLC I/OMaximum Slots471013Chassis Lengthin. (mm)9.25 (235)13.33 (339)17.88 (454)22 (559)Rockwell Automation Publication 1492-SG010B-EN-P - February 2021Usable Length8 (203)12.08 (307)16.63 (422)20.75 (527)Maximum Number ofCompact 5000 I/O Cards491419

1746 SLC I/O to Compact 5000 I/O Conversion SystemConversion Chassis Approximate DimensionsConversion Chassis Approximate DimensionsApproximate dimensions are shown in inches (millimeters) and are not intended to be used for manufacturing purposes.1492-CH1746-49.26 (235.20)2.76 (70.00)4 mounting holes7.50(190.47)10-32 ScrewQty. 4Torque 21 lb in (2.37 N m)6.22(158)Ø .22 (5.50)2 holes8.67 (220.16)3.25(82.57)3.77(95.85)Rockwell Automation Publication 1492-SG010B-EN-P - February 20215

1746 SLC I/O to Compact 5000 I/O Conversion SystemConversion Chassis Approximate Dimensions1492-CH1746-713.34 (338.80)6.89 (175.01)4 mounting holes10-32 ScrewQty. 4Torque 21 lb in (2.37 N m)6.22(158)7.50(190.47)Ø .22 (5.51)2 holes12.84 (326.13)3.77(95.85)3.25(82.57)6Rockwell Automation Publication 1492-SG010B-EN-P - February 2021

1746 SLC I/O to Compact 5000 I/O Conversion SystemConversion Chassis Approximate Dimensions1492-CH1746-1017.87 (453.90)5.51 (140.00)5.51 (140.00)7.50(190.47)10-32 ScrewQty. 4Torque 21 lb in (2.37 N m)6.22(158)R.11 (2.76)3 holes17.37 (441.14)3.77(95.85)3.25(82.57)Rockwell Automation Publication 1492-SG010B-EN-P - February 20217

1746 SLC I/O to Compact 5000 I/O Conversion SystemConversion Chassis Approximate Dimensions1492-CH1746-1322.00 (558.80)5.51(140.00)4.13(104.98)10-32 ScrewQty. 4Torque 21 lb in (2.37 N m)5.51(140.00)7.50(190.47)6.22(158)R.11 (2.75)4 holes21.50 (546.09)3.77(95.85)3.25(82.57)8Rockwell Automation Publication 1492-SG010B-EN-P - February 2021

1746 SLC I/O to Compact 5000 I/O Conversion SystemDigital InputsDigital InputsIMPORTANT1.2.Column 1: find the catalog number of the 1746 SLC I/O you are converting from.Column 2: find the catalog number of the compatible Compact 5000 I/O module you are converting to. Determine the number ofCompact 5000 I/O modules required.IMPORTANT3.Check the technical specification of the respective Compact 5000 I/O electrical specification before proceeding with theconversion to confirm the new modules is able to support the users' field devices.In some cases two Compact 5000 I/O modules may be required for one 1746 SLC I/O module. Select the applicable 1492conversion modules from the Conversion Module Selection Table below.Column 3: find the catalog number of the Conversion Module.1746 SLC I/O ModuleCatalog 32Compact 5000 I/O ModulesCatalog 6 (Qty. 2)Conversion ModuleCatalog Number1492-CM1746-M011492-CM1746-M12Rockwell Automation Publication 1492-SG010B-EN-P - February 20211746 SLC I/ODescription120V AC Input Module240V AC Input ModuleCurrent Sinking DC Input ModuleFast Response DC Sinking Input ModuleCurrent Sinking DC Input Module9

1746 SLC I/O to Compact 5000 I/O Conversion SystemDigital OutputsDigital OutputsIMPORTANT1.2.Column 1: find the catalog number of the 1746 SLC I/O module you are converting from.Column 2: find the catalog number of the compatible Compact 5000 I/O module you are converting to. Determine the number ofCompact 5000 I/O modules required.IMPORTANT3.Check the technical specification of the respective Compact 5000 I/O electrical specification before proceeding with theconversion to confirm the new modules is able to support the users' field devices.In some cases two Compact 5000 I/O modules may be required for one 1746 module. Select the applicable 1492 conversionmodule from the following table.Column 3: find the catalog number of the Conversion Module.1746 SLC I/O ModuleCatalog 321746-OB32E10Compact 5000 I/O ModulesCatalog 6 (Qty. 2)5069-OB16 (Qty. 2)Conversion ModuleCatalog 41492-CM1746-M13Rockwell Automation Publication 1492-SG010B-EN-P - February 20211746 SLC I/ODescription120/240V AC Output ModuleCurrent Sourcing DC Output ModuleCurrent Sourcing DC Output ModuleAC/DC Relay Output ModuleCurrent Sourcing DC Output ModuleCurrent Sourcing DC Output Module

1746 SLC I/O to Compact 5000 I/O Conversion SystemAnalog Inputs and OutputsAnalog Inputs and Outputs1.2.3.Column 1: find the catalog number of the 1746 SLC I/O module you are converting from.Column 2: find the catalog number of the compatible Compact 5000 I/O module you are converting to. Determine the number of 1746I/O modules used in the 1746 I/O Chassis to be converted to Compact 5000 I/O. Select the applicable 1492 conversion modules fromthe Conversion Module Selection Table below.Column 3: Find the conversion module catalog number.1746 SLC I/O ModuleCatalog 6-NO4V1746-NO8I1746-NO8VCompact 5000 I/O ModulesCatalog 069-OF45069-OF85069-OF8Conversion ModuleCatalog NumberConversion 2-CM1746-MO71492-CM1746-MO9High Resolution (8) Analog Input ModuleHigh Resolution (4) Analog Input ModuleSLC 500 RTD/Resistance Input Module4-Channel Thermocouple/mV Input Module4-Point Analog Output Module (Current)4-Point Analog Output Module (Voltage)8-Point Analog Output Module (Current)8-Point Analog Output Module (Voltage)1492-CM1746-M101492-CM1746-M11(1) Catalog numbers 5069-IF8 and 5069-IY4 support differential inputs only.Rockwell Automation Publication 1492-SG010B-EN-P - February 202111

1746 SLC I/O to Compact 5000 I/O Conversion SystemConversion Module Approximate DimensionsConversion Module Approximate DimensionsApproximate dimensions are shown in inches (millimeters) and are not intended to be used for manufacturing purposes.1492-CM1746-M01, -M02, -M03, -M04, -M05, -M07, M09, M11 5 Connector1.35(34.22)1.64(41.75)1492-CM1746-M10 7 Connector1.35(34.22)1.64(41.75)(a) Total length of the conversion module is approximately 23 in. (584.2 mm)12Rockwell Automation Publication 1492-SG010B-EN-P - February 2021

1746 SLC I/O to Compact 5000 I/O Conversion SystemConversion Module Approximate Dimensions1492-CM1746-M06 8 Connector1.35(34.22)1.64(41.75)1492-CM1746-M12, -M13(a)Contains two 5069-RTB18 38.00).55(13.85)N3 Connector1.64(41.75)(a) Total length of the conversion module is approx 23 in. (584.2 mm)Rockwell Automation Publication 1492-SG010B-EN-P - February 202113

1746 SLC I/O to Compact 5000 I/O Conversion SystemSpecificationsSpecificationsAttributeStorage TemperatureOperating TemperatureOperating HumidityShock (non-operating)Shock (operating)Standards ComplianceCertificationsEnvironmental Rating14Value-40. 85 C (-40. 185 F)0. 60 C ( 32. 140 F)5.95% at 55 C ( 131 F)50 g30 gUL Classified (UL File No. E113724)Compliant for all applicable directivesRoHS/EACRockwell Automation Publication 1492-SG010B-EN-P - February 2021

1746 SLC I/O to Compact 5000 I/O Conversion SystemAssembled System Approximate DimensionsAssembled System Approximate DimensionsApproximate dimensions are shown in inches (millimeters) and are not intended to be used for manufacturing purposes.1492-CH1746-4 Assembly with 5380 CompactLogix8.67(220.16).54(13.71)2.76 (70.00)Mounting Holes1.88(47.64)10-32 ScrewQty. 4Torque 21 lb in (2.37 N m)6.227.34(158.00)(186.51) MountingHolesØ .217 (5.50)2 holes8.68(220.48)7.58(192.64)3.25(82.57)Rockwell Automation Publication 1492-SG010B-EN-P - February 202115

1746 SLC I/O to Compact 5000 I/O Conversion SystemAssembled System Approximate Dimensions1492-CH1746-7 Assembly with 5380 CompactLogix12.84 (326.13).54(13.71)6.89 (175.01)Mounting Holes1.89(48.00)10-32 ScrewQty. 4Torque 21 lb in (2.37 N m)6.22(158.00)Mounting7.34 Rockwell Automation Publication 1492-SG010B-EN-P - February 2021

1746 SLC I/O to Compact 5000 I/O Conversion SystemAssembled System Approximate Dimensions1492-CH1746-10 Assembly with 5380 CompactLogix17.37 (441.14)5.51 (140)Mounting Holes.54(13.71)5.51 (140)Mounting Holes2.29(58.2)10-32 ScrewQty. 4Torque 21 lb in (2.37 N m)7.34(186.51)6.22(158.00)MountingHolesØ .217 (5.51)3 holes8.68(220.48)7.58(192.64)3.25(82.57)Rockwell Automation Publication 1492-SG010B-EN-P - February 202117

1746 SLC I/O to Compact 5000 I/O Conversion SystemAssembled System Approximate Dimensions1492-CH1746-13 Assembly with 5380 CompactLogix21.50 (546.09)5.51 (140)Mounting Holes.54(13.71)4.13 (104.98)5.51 (140)Mounting Holes2.29(58.1)10-32 ScrewQty. 4Torque 21 lb in (2.37 N m)7.34(186.51)6.22(158.00)MountingHolesØ .217 (5.51)8 holes8.68(222.48)7.58(192.64)3.25(82.57)18Rockwell Automation Publication 1492-SG010B-EN-P - February 2021

1746 SLC I/O to Compact 5000 I/O Conversion SystemConversion Module Wiring DiagramsConversion Module Wiring DiagramsIMPORTANT See Additional Resources on page 31 for a list of complete installation instructions.1492-CM1746-M01 Conversion ModuleThis conversion module may be used to connect signals from 1746 SLC I/0 modules to Compact 5000 I/O modules. The conversion module directly acceptsthe 1746 removable terminal block. One end of the 1492 conversion module is an 18 point removable terminal block that installs directly to the Compact5000 I/O modules. The other end is a female connector to which the 1746 removable terminal block is installed directly.IMPORTANT AC COM signals are not required/connected for the Compact 5000 I/O system.A 5069-FPD is required when different voltages are used.Verify that the conversion module is matched correctly to the appropriate I/O module.Route power supply wires (not provided for the Compact 5000 I/O system) manually to the controller or field potentialdistributor (FPD).Wiring DiagramConversion module - 1492-CM1746-M01Field sideconnectorInput 0Input 1Input 2Input 3Input 4Input 5Input 6Input 7Input 8Input 9Input 10Input 11Input 12Input 13Input 14Input 15AC COMAC 15Input 0Input 1Input 2Input 3Input 4Input 5Input 6Input 7Input 8Input 9Input 10Input 11Input 12Input 13Input 14Input 15Conversions1746 SLC I/O ModuleCatalog Number1746-IA161746-IM161746-IB161746-ITB16Compact 5000 I/O ModuleCatalog Number5069-IA165069-IA165069-IB165069-IB16Rockwell Automation Publication 1492-SG010B-EN-P - February 202119

1746 SLC I/O to Compact 5000 I/O Conversion SystemConversion Module Wiring Diagrams1492-CM1746-M02 Conversion ModuleThis conversion module may be used to connect signals from 1746 SLC I/0 modules to Compact 5000 I/O modules. The conversion module directly acceptsthe 1746 removable terminal block. One end of the 1492 conversion module is an 18 point removable terminal block that installs directly to the Compact5000 I/O modules. The other end is a female connector to which the 1746 removable terminal block is installed directly.IMPORTANT See Additional Resources on page 31 for a list of complete installation instructions.VAC 1 and VAC 2 signals are not connected/required for the Compact 5000 I/O system.A 5069-FPD is required when different voltages are used.Verify that the conversion module is matched correctly to the appropriate I/O module.Wiring DiagramConversion module - 1492-CM1746-M02Field sideconnectorVAC1Out 0Out 1Out 2Out 3Out 4Out 5Out 6Out 7VAC2Out 9Out 8Out 11Out 10Out 13Out 12Out 15Out 415Conversions1746 SLC I/O ModuleCatalog Number1746-OA1620Compact 5000 I/O ModuleCatalog Number5069-OA16Rockwell Automation Publication 1492-SG010B-EN-P - February 2021Out 0Out1Out 2Out 3Out 4Out 5Out 6Out 7Out 8Out 9Out 10Out 11Out 12Out 13Out 14Out 15

1746 SLC I/O to Compact 5000 I/O Conversion SystemConversion Module Wiring Diagrams1492-CM1746-M03 Conversion ModuleThis conversion module may be used to connect signals from 1746 SLC I/0 modules to Compact 5000 I/O modules. The conversion module directly acceptsthe 1746 removable terminal block. One end of the 1492 conversion module is an 18 point removable terminal block that installs directly to the Compact5000 I/O modules. The other end is a female connector to which the 1746 removable terminal block is installed directly.IMPORTANT See Additional Resources on page 31 for a list of complete installation instructions. Verify that the conversion module is matched correctly to the appropriate I/O module.Wiring DiagramConversion module - 1492-CM1746-M03Field sideconnectorVDCOut 0Out 1Out 2Out 3Out 4Out 5Out 6Out 7Out 8Out 9Out 10Out 11Out 12Out 13Out 14Out 15DC teBlack/RedWhite/RedOrange/RedBlack & WhiteBlue/Red & Red/GreenRTB1801234567891011121314151617Out 0Out1Out 2Out 3Out 4Out 5Out 6Out 7Out 8Out 9Out 10Out 11Out 12Out 13Out 14Out 15LA LA-Conversions1746 SLC I/O ModuleCatalog Number1746-OB161746-OB16ECompact 5000 I/O ModuleCatalog Number5069-OB165069-OB16Rockwell Automation Publication 1492-SG010B-EN-P - February 202121

1746 SLC I/O to Compact 5000 I/O Conversion SystemConversion Module Wiring Diagrams1492-CM1746-M04 Conversion ModuleThis conversion module may be used to connect signals from 1746 SLC I/0 modules to Compact 5000 I/O modules. The conversion module directly acceptsthe 1746 removable terminal block. One end of the 1492 conversion module is an 18 point removable terminal block that installs directly to the Compact5000 I/O modules. The other end is a female connector to which the 1746 removable terminal block is installed directly.IMPORTANT See Additional Resources on page 31 for a list of complete installation instructions. A 5069-FPD is required when different voltages are used. Verify that the conversion module is matched correctly to the appropriate I/O module.Wiring DiagramConversion module - 1492-CM1746-M04Field sideconnectorVAC-VDC 1Out 0Out 1Out 2Out 3Out 4Out 5Out 6Out 7VAC-VDC 2Out 9Out 8Out 11Out 10Out 13Out 12Out 15Out /BlackBlack & /RedWhite/RedRed/GreenBlue/RedBlue/Black & Black/WhiteConversions1746 SLC I/O ModuleCatalog Number1746-OW1622Compact 5000 I/O ModuleCatalog Number5069-OW16Rockwell Automation Publication 1492-SG010B-EN-P - February 202101234567891011121314151617VOut 0VOut1VOut 2VOut 3VOut 4VOut 5VOut 6VOut 7Common0Vout 8Vout 9Vout 10Vout 11Vout 12Vout 13Vout 14Vout 15Common1

1746 SLC I/O to Compact 5000 I/O Conversion SystemConversion Module Wiring Diagrams1492-CM1746-M05 Conversion ModuleThis conversion module may be used to connect signals from 1746 SLC I/0 modules to Compact 5000 I/O modules. The conversion module directly acceptsthe 1746 removable terminal block. One end of the 1492 conversion module is an 18 point removable terminal block that installs directly to the Compact5000 I/O modules. The other end is a female connector to which the 1746 removable terminal block is installed directly.IMPORTANT See Additional Resources on page 31 for a list of complete installation instructions. Verify that the conversion module is matched correctly to the appropriate I/O module. Single-ended sensors are not supported.Wiring DiagramConversion module - 1492-CM1746-M05Field sideconnectorShieldCh 0 Ch 0Ch 1 Ch 1Ch 2 Ch 2Ch 3 Ch 3Ch 4 Ch 4Ch 5 Ch 5Ch 6 Ch 6Ch 7 Ch reen & RedDrain wire01234567891011121314151617Ch 0 Ch 0Ch 1 Ch 1Ch 2 Ch 2Ch 3 Ch 3Ch 4 Ch 4Ch 5 Ch 5Ch 6 Ch 6Ch 7 Ch 7ShieldShieldConversions1746 SLC I/O ModuleCatalog Number1746-NI8Compact 5000 I/O ModuleCatalog Number5069-IF8Rockwell Automation Publication 1492-SG010B-EN-P - February 202123

1746 SLC I/O to Compact 5000 I/O Conversion SystemConversion Module Wiring Diagrams1492-CM1746-M06 Conversion ModuleThis conversion module may be used to connect signals from 1746 SLC I/0 modules to Compact 5000 I/O modules. The conversion module directly acceptsthe 1746 removable terminal block. One end of the 1492 conversion module is an 18 point removable terminal block that installs directly to the Compact5000 I/O modules. The other end is a female connector to which the 1746 removable terminal block is installed directly.IMPORTANT See Additional Resources on page 31 for a list of complete installation instructions. Verify that the conversion module is matched correctly to the appropriate I/O module. Route power supply wires (not provided for the Compact 5000 I/O system) manually to the controller or field potentialdistributor (FPD).Wiring DiagramConversion module - 1492-CM1746-M06Field sideconnectorInput 0 Input 0ANL COMInput 1 Input 1ANL COMInput 2 Input 2ANL COMInput 3 Input 3ANL VioletGrayWhiteWhite/BlackWhite/BrownDrain wireConversions1746 SLC I/O ModuleCatalog Number1746-NI424Compact 5000 I/O ModuleCatalog Number5069-IY4Rockwell Automation Publication 1492-SG010B-EN-P - February 202123456789101314151617Input 0 Input 0RTDInput 1 Input 1RTDInput 2 Input 2RTDInput 3 Input 3RTDShieldShield

1746 SLC I/O to Compact 5000 I/O Conversion SystemConversion Module Wiring Diagrams1492-CM1746-M07 Conversion ModuleThis conversion module may be used to connect signals from 1746 SLC I/0 modules to Compact 5000 I/O modules. The conversion module directly acceptsthe 1746 removable terminal block. One end of the 1492 conversion module is an 18 point removable terminal block that installs directly to the Compact5000 I/O modules. The other end is a female connector to which the 1746 removable terminal block is installed directly.IMPORTANT See Additional Resources on page 31 for a list of complete installation instructions. Verify that the conversion module is matched correctly to the appropriate I/O module.Wiring DiagramConversion module - 1492-CM1746-M07Field sideconnectorShieldShieldCh0 RTDCh1 RTDCh0 SenseCh1 SenseCh0 ReturnCh1 ReturnShieldShieldCh2 RTDCh3 RTDCh2 SenseCh3 SenseCh2 ReturnCh3 lack & Red & WhiteWhite/Gray &White/Black &Wh-Bl/Brown &234567891013141516Input 0 Input 0RTDInput 1 Input 1RTDInput 2 Input 2RTDInput 3 Input 3RTDShield17ShieldDrain wireConversions(1)1746 SLC I/O ModuleCatalog Number1746-NR4Compact 5000 I/O ModuleCatalog Number5069-IY4(1) In Studio 5000, configure all RTD channels in use (2-wire or 3-wire) in 3-wire mode. Refer toRockwell Automation publication 5069-UM005 for I/O module 5069-IY4 configuration.Rockwell Automation Publication 1492-SG010B-EN-P - February 202125

1746 SLC I/O to Compact 5000 I/O Conversion SystemConversion Module Wiring Diagrams1492-CM1746-M09 Conversion ModuleThis conversion module may be used to connect signals from 1746 SLC I/0 modules to Compact 5000 I/O modules. The conversion module directly acceptsthe 1746 removable terminal block. One end of the 1492 conversion module is an 18 point removable terminal block that installs directly to the Compact5000 I/O modules. The other end is a female connector to which the 1746 removable terminal block is installed directly.IMPORTANT See Additional Resources on page 31 for a list of complete installation instructions. Verify that the conversion module is matched correctly to the appropriate I/O module. Route Analog COM signal (not provided for the Compact 5000 I/O system) manually.Wiring DiagramConversion module - 1492-CM1746-M09Field sideconnectorCJC A CH 0 CJC ACH 0ShieldCH 1 ShieldCH 1ShieldCH 2 ShieldCH 2ShieldCH 3 CJC B CH 3CJC BANALOG ite/GrayWhite/GreenWhite/VioletGreen & Violet & WhiteWhite/Red &White/Yellow &Drain wireConversions1746 SLC I/O ModuleCatalog Number1746-NT426Compact 5000 I/O ModuleCatalog Number5069-IY4Rockwell Automation Publication 1492-SG010B-EN-P - February 2021012356891112131416CJC A CJC AInput 0 Input 0Input 1 Input 1Input 2 Input 2CJC B CJC BInput 3 Input 3Shield17Shield

1746 SLC I/O to Compact 5000 I/O Conversion SystemConversion Module Wiring Diagrams1492-CM1746-M10 Conversion ModuleThis conversion module may be used to connect signals from 1746 SLC I/0 modules to Compact 5000 I/O modules. The conversion module directly acceptsthe 1746 removable terminal block. One end of the 1492 conversion module is an 18 point removable terminal block that installs directly to the Compact5000 I/O modules. The other end is a female connector to which the 1746 removable terminal block is installed directly.IMPORTANT See Additional Resources on page 31 for a list of complete installation instructions. Verify that the conversion module is matched correctly to the appropriate I/O module. Route power supply wires (not provided for the Compact 5000 I/O system) manually to the controller or field potentialdistributor (FPD).Wiring DiagramConversion module - 1492-CM1746-M10Field sideconnector--------Out 0ANL COMOut 1ANL COMOut 2ANL COMOut 3ANL hiteBlackGreenBlackBlueBlackDrain wire0123456716Out 0 Out 0Out 1 Out 1Out 2 Out 2Out 3 Out 3ShieldConversions1746 SLC I/O ModuleCatalog Number1746-NO4I1746-N04VCompact 5000 I/O ModuleCatalog Number5069-OF45069-OF4Rockwell Automation Publication 1492-SG010B-EN-P - February 202127

1746 SLC I/O to Compact 5000 I/O Conversion SystemConversion Module Wiring Diagrams1492-CM1746-M11 Conversion ModuleThis conversion module may be used to connect signals from 1746 SLC I/0 modules to Compact 5000 I/O modules. The conversion module directly acceptsthe 1746 removable terminal block. One end of the 1492 conversion module is an 18 point removable terminal block that installs directly to the Compact5000 I/O modules. The other end is a female connector to which the 1746 removable terminal block is installed directly.IMPORTANT See Additional Resources on page 31 for a list of complete installation instructions.24V DC and DC COM signals are not required/connected for the Compact 5000 I/O system.A 5069-FPD is required when different voltages are used.Verify that the conversion module is matched correctly to the appropriate I/O module.Route power supply wires (not provided for the Compact 5000 I/O system) manually to the controller or field potentialdistributor (FPD).Wiring DiagramConversion module - 1492-CM1746-M11Field sideconnectorIout0 /Vout0ANL COM0Iout1/Vout1ANL COM1Iout2/Vout2ANL COM2Iout3/Vout3ANL COM3Iout4/Vout4ANL COM4Iout5/Vout5ANL COM5Iout6/Vout6ANL COM6Iout7/Vout7ANL COM724VDCDC te-------Conversions1746 SLC I/O ModuleCatalog Number1746-NO8I1746-N08V28Compact 5000 I/O ModuleCatalog Number5069-OF85069-OF8Rockwell Automation Publication 1492-SG010B-EN-P - February kYellowBlackBrownBlackOrangeRedWhiteDrain wire012345678910111213141516Out 0 Out 0Out 1 Out 1Out 2 Out 2Out 3 Out 3Out 4 Out 4Out 5 Out 5Out 6 Out 6Out 7 Out 7Shield

1746 SLC I/O to Compact 5000 I/O Conversion SystemConversion Module Wiring Diagrams1492-CM1746-M12 Conversion ModuleThis conversion module may be used to connect signals from 1746 SLC I/0 modules to Compact 5000 I/O modules. The conversion module directly acceptsthe 1746 removable terminal block. One end of the 1492 conversion module is an 18 point removable terminal block that installs directly to the Compact5000 I/O modules. The other end is a female connector to which the 1746 removable terminal block is installed directly.IMPORTANT See Additional Resources on page 31 for a list of complete installation instructions.COM signals are not required/connected for the Compact 5000 I/O system.A 5069-FPD is required when different voltages are used.Verify that the conversion module is matched correctly to the appropriate I/O module.Route COM signals (not provided for the Compact 5000 I/O system) manually to the controller or field potential distributor (FPD).Wiring DiagramConversion module - 1492-CM1746-M12Field sideconnectorCOMCOMInput 0Input 1Input 2Input 3Input 4Input 5Input 6Input 7Input 8Input 9Input 10Input 11Input 12Input 13Input 14Input 15COMCOMCOMCOMInput 16Input 17Input 18Input 19Input 20Input 21Input 22Input 23Input 24Input 25Input 26Input 27Input 28Input 29Input 30Input /BlackGreen/Black

Conversion Modules must be installed in a 1492 Conversion Chassis. Use the following steps to select the proper conversion chas sis: 1. Determine the quantity of each type of 174

Related Documents:

SLC 500 4-Channel Analog I/O Modules (Catalog Numbers 1746-NI4, 1746-NIO4I, 1746-NIO4V, 1746-NO4I, and 1746-NO4V) User Manual. . Publication 1746-UM005B-EN-P - June 2004 Summary of Changes The information below summarizes the changes to this manual since the last printing.

sourcing modules with removable terminal blocks, including 1746-IB16, 1746-ITB16, 1746-IV16, 1746-ITV16, and 1746-IN16 modules. The input simulator provides 16 switches for simulating inputs to the SLC 500. 1746 Analog I/O Modules Analog I/O modules feature user-selectable voltage or current inputs, backplane

500 100/120V ac 1746-IA16 Input 16 120V ac Input 15 101 200/240V ac 1746-IM4 Input 4 240V ac Input 15 301 200/240V ac 1746-IM8 Input 8 240V ac Input 15 501 200/240V ac 1746-IM16 Input 16 240V ac Input 15 2703 100/120V ac 1746-OA8 Output 8 120/240V ac Output 17

Allen-Bradley SLC 500 SLC 5/03 Allen-Bradley SLC 500 SLC 5/04 Allen-Bradley SLC 500 SLC 5/05 Allen-Bradley VersaView 1500P Andover Controls Continuum Infinet II i2810 Andover Controls Infinity SCX 920 APC AP7960 APC PNET 1 APC Back-UPS BE350R APC Back-

Insert a new battery into the battery retaining clips. 6. Plug the battery connector into the socket as shown above. 7. Re-insert the module into the SLC 500 chassis. 8. Restore power to the SLC 500 power supply. 9. Cl

Mobile Application Development (SLC - Program) Partnership with Business Project (SLC - Report) Public Service Announcement (RLC - Video Production) Publication Design (RLC & SLC - Entry Social Media Campaign (RLC - PDF of slides) Website Design (RLC & SLC - Website Entry Form/URL) Who's Who in FBLA (SLC - Nomination Materials)

for details about SLC. The SLC Command Line Interface (SLC-CLI) tool resolves project and component dependencies and generates a project for a specified embedded target and build system (for example, IAR Embedded Workbench or GNU tools via a Makefile), among other things. SLC-CLI is provided as a downloadable .zip file for three operating systems:

Texts of Wow Rosh Hashana II 5780 - Congregation Shearith Israel, Atlanta Georgia Wow ׳ג ׳א:׳א תישארב (א) ׃ץרֶָֽאָּהָּ תאֵֵ֥וְּ םִימִַׁ֖שַָּה תאֵֵ֥ םיקִִ֑לֹאֱ ארָָּ֣ Îָּ תישִִׁ֖ארֵ Îְּ(ב) חַורְָּ֣ו ם