Controls— Options DDC

2y ago
285 Views
2 Downloads
466.43 KB
23 Pages
Last View : 1d ago
Last Download : 8m ago
Upload by : Annika Witter
Transcription

Controls—DDCOptionsControls By Others (All Unit Types)Unit HeatControlDD00FM00FM01ENONDescriptionTrane Actuator for Field-Installed DDC ControlsFactory Installation of Customer Supplied Actuators and DDC ControlsTrane Actuator w/ Factory Installation of Customer-Supplied DDC ControlsNo Controls or Actuator—Field-Installed DDC or Analog ControlsPage #C8C9C9—Single-Duct Terminal Unit (VCCF, VCWF, and VCEF)Unit HeatCooling Only(VCCF)Hot 05DD07DD02DD03DD07DD04DD05DescriptionCooling OnlyCooling With Remote Normally-Closed On/Off Hot Water Valve (Normally-Open Outputs)Cooling With Remote Proportional Hot Water Valve with Optional Spare On/Off OutputCooling With Remote Staged On/Off Electric HeatCooling With Remote Pulse-Width Modulation Electric HeatCooling With Remote Normally-Open On/Off Hot Water Valve (Normally-Closed Output)Cooling With Normally-Closed On/Off Hot Water Valve (Normally-Open Outputs)Cooling With Proportional Hot Water Valve with Optional Spare On/Off OutputCooling With Normally-Open On/Off Hot Water Valve (Normally-Closed Output)Cooling With Staged On/Off Electric HeatCooling WIth Pulse-Width Modulation Electric HeatPage #C 10C 10C 10C 10C 10C 10C 11C 11C 11C 12C 12Dual-Duct Terminal Unit (VDDF)Unit HeatControlNone(VDDF)DD00DD01DD08DescriptionTrane Actuator for Field-Installed DDC ControlsCooling (No Remote Heat) and Heating ControlCooling (No Remote Heat) and Heating—Constant-Volume ControlPage #C8C 13C 14Fan-Powered Terminal Units with PSC Motor (VPCF, VPWF, VPEF, VSCF, VSWF, and VSEF)Low-Height Fan-Powered Terminal Units with PSC Motor (LPCF, LPWF, LPEF, LSCF, LSWF, and LSEF)Unit HeatCooling Only(VPCF, VSCF,LPCF, LSCF)Hot Water(VPWF, VSWFLPWF, LSWF)Electric(VPEF, VSEFLPEF, 04DD05DescriptionCooling OnlyCooling With Remote Normally-Closed On/Off Hot Water Valve with Normally-Open OutputsCooling With Remote Proportional Hot Water ValveCooling With Remote Staged On/Off Electric HeatCooling With Remote Pulse-Width Modulation Electric HeatCooling With Remote Normally-Open On/Off Hot Water Valve with Normally-Closed OutputsCooling With Normally-Closed On/Off Hot Water Valve with Normally-Open OutputsCooling With Proportional Hot Water ValveCooling With Normally-Open On/Off Hot Water Valve with Normally-Closed OutputsCooling With Staged On/Off Electric HeatCooling With Pulse-Width Modulation Electric HeatPage #C 15C 16C 16C 15C 15C 16C 16C 16C 16C 15C 15Fan-Powered Terminal Units with ECM (VPCF, VPWF, VPEF, VSCF, VSWF, and VSEF)Unit HeatCooling Only(VPCF, VSCF)Hot Water(VPWF, VSWF)Electric(VPEF, D02DD03DD07DD04DD05DescriptionCooling OnlyCooling With Remote Normally-Closed On/Off Hot Water Valve with Normally-Open OutputsCooling With Remote Proportional Hot Water ValveCooling With Remote Staged On/Off Electric HeatCooling With Remote Pulse-Width Modulation Electric HeatCooling With Remote Normally-Open On/Off Hot Water Valve with Normally-Closed OutputsCooling With Normally-Closed On/Off Hot Water Valve with Normally-Open OutputsCooling With Proportional Hot Water ValveCooling With Normally-Open On/Off Hot Water Valve with Normally-Closed OutputsCooling With Staged On/Off Electric HeatCooling With Pulse-Width Modulation Electric HeatPage #C 17C 17C 17C 17C 17C 17C 17C 17C 17C 17C 17C3

Controls—DDCTrane DDC–UCMControl Logic—DDC controllers are today’s industrystandard. DDC controllers providesystem-level data used to optimizesystem performance. Variables such asoccupied/unoccupied status, minimumand maximum airflow setpoints,temperature and temperaturesetpoints, valve position, fan status (onor off, and mode of operation: series orparallel), reheat status (on or off), boxtype and air valve size, temperaturecorrection offsets, flow correctionvalues, ventilation fraction, etc. areavailable on a simple twisted-shieldedwire pair.Trane DDC controllers provide Tranedesigned, solid-state electronicsintended specifically for VAVtemperature control in space comfortapplications. DDC control capabilitiesinclude: Proportional plus integral control loopalgorithm for determining requiredairflow needed to control roomtemperature. Airflow is limited byactive minimum and maximumairflow setpoints. Pressure-independent (PI) operation,which automatically adjusts valveposition to maintain required airflow.In certain low-flow situations or incases where the flow measurementhas failed, the DDC controller willGeneralLogicoperate in a pressure-dependent (PD)mode of operation. Cooling and heating control action ofair valve. In cooling control action, theDDC controller matches cooling airflowto cooling load. In heating controlaction, the DDC controller matches theheating airflow to control heating load.The DDC controller will automaticallychange over to cooling control action ifthe supply air temperature is below theroom temperature and willautomatically change over to heatingcontrol action if the supply airtemperature is 10 F or more above theroom temperature. If the supply airtemperature is between the roomtemperature and the roomtemperature plus 10 F, then the DDCcontroller will provide the activeminimum airflow.The DDC controllerfirst chooses theTracer Summitsupplied supply air temperature valueto use for auto changeover. If this is notavailable, it uses the temperatureprovided by the optional auxiliarytemperature sensor. If this is also notavailable, it uses the heating/coolingmode assigned byTracer Summit orthe DDC controller’s service tool(Everyware TM or RoverTM V4). Multiple reheat control optionsincluding staged electric, staged hotwater (normally on or normally off),proportional hot-water, and slowpulsed width modulation. Modulatingreheat options utilize a separate reheatproportional-plus-integral control loopfrom that controlling airflow into theroom. Staged reheat options utilize acontrol algorithm based on heatingsetpoint and room temperature. 24 VAC binary input that can beconfigured as a generic input or asoccupancy input. When the DDCcontroller is operation withTracerSummit, the status of the input isprovided toTracer Summit for itsaction. In stand-alone operation andwhen configured for an occupancyinput, the input will control occupancystatus of the DDC controller. Auxiliary temperature analog inputthat can be configured for an auxiliarytemperature sensor or a 2-to-10 VDCCO2 sensor. When configured fortemperature, the value of the input isused as status-only by Tracer Summit ifTracer Summit is providing a supply airtemperature to the DDC controller.Otherwise, the input will be used fordetermining control action of the DDCcontroller. When configured for a CO2sensor, the value of the input is used asa status-only input by Tracer Summit. Dual-duct support with two DDCcontrollers. One DDC controllercontrols the cooling air valve and theother controller controls the heating airvalve. With constant-volumesequences, the discharge air volume isheld constant by controlling dischargeair volume with the heating UCM.Flow Sensor Signal vs. Airflow Delivery5Flow Sensor DP (In. wg)14"5"6"8"10"12" 14" 16"0.10.01101001,00010,000CfmC4Note: Flow sensor DP (in. wg) is measured at the flow ring to aid in system balancing and commissioning. See "Valve/Controller AirflowGuidelines" in each section for unit performance.VAV-PRC008-EN

Controls—DDCDDC Remote HeatControl OptionsWhen heat is added to the primary airat the VAV unit before it enters thezone, the air is said to be reheated. Theoperating characteristics of the fourbasic types of VariTrane DDC terminalreheat are discussed.Single-Duct: On/Off Hot WaterReheat—Three stages of on/off hotwater reheat are available. The watervalves used are 2-position and areeither fully-opened or fully-closed. Theheating minimum airflow setpoint isenabled during reheat.Stage 1 energizes when the spacetemperature is at or below the heatingsetpoint. When the zone temperaturerises above the active heating setpointby 0.5 F (0.28 C), stage 1 is deenergized. Stage 2 energizes when thespace temperature is 1 F (0.56 C) ormore below the active heatingsetpoint, and is de-energized when thespace temperature is 0.5 F (0.28 C)below the active heating setpoint.Stage 3 energizes when the zonetemperature is 2 F (1.11 C) or morebelow the active heating setpoint, andde-energizes when the spacetemperature is 1.5 F (0.83 C) below theactive heating setpoint. When reheat isde-energized, the cooling minimumairflow setpoint is activated.VCEFSingle-Duct: Proportional HotWater Reheat—Proportional hotwater reheat uses 3-wire floating-pointactuator technology.The heatingminimum airflow setpoint is enabledduring reheat.The water valve opens as spacetemperature drops below the heatingsetpoint. Water valve position isdependent on both the degree thatspace temperature is below the activeheating setpoint and the time that thespace temperature has been below theactive heating setpoint. If not alreadyclosed, the water valve fully closeswhen the zone temperature risesabove the active heating setpoint by0.5 F (0.28 C). An additional on/offremote heat output is available andenergized when the proportional valveis driven 100% open and de-energizedwhen the proportional valve reaches50% open. When reheat is deenergized, the cooling minimumairflow setpoint is activated.Single-Duct: On/Off ElectricReheat—Three stages of stagedelectric reheat are available. Theheating minimum airflow setpoint isenabled during reheat.Stage 1 is energized when the spacetemperature falls below the activeheating setpoint and minimum airflowrequirements are met. When the zoneDDCReheatControltemperature rises above the activeheating setpoint by 0.5 F (0.28 C),stage 1 is de-energized. Stage 2energizes when the space temperatureis 1 F (0.56 C) or more below the activeheating setpoint, and is de-energizedwhen the space temperature is 0.5 F(0.28 C) below the active heatingsetpoint. Stage 3 energizes when thezone temperature is 2 F (1.11 C) ormore below the active heatingsetpoint, and de-energizes when thespace temperature is 1.5 F (0.83 C)below the active heating setpoint.When reheat is de-energized, thecooling minimum airflow setpoint isactivated.Single-Duct: Pulse-WidthModulation of Electric Heat—Electric heat is modulated byenergizing for a portion of a threeminute time period. The heatingminimum airflow setpoint is enabledduring reheat. This allows exact loadmatching for energy efficientoperation, and optimum zonetemperature control. One or twostages can be used.The amount of reheat supplied isdependent on both the degree thatspace temperature is below the activeheating setpoint and the time that thespace temperature has been below theactive heating setpoint. If not alreadyoff, reheat de-energizes when the zonetemperature rises more than 0.5 F(0.28 C) above the heating setpoint.The Stage 1 “on” time is proportionalto the amount of reheat required. Forexample, when 50% of stage 1capacity is required, reheat is on for 90seconds and off for 90 seconds. When75% of stage 1 capacity is required,reheat is on for 135 seconds and off for45 seconds. When 100% of stage 1capacity is required, reheat is oncontinuously.Stage 2 uses the same “on” time logicas stage 1 listed above, except stage 1is always energized. For example,when 75% of unit capacity is required,stage 1 is energized continuously, andstage 2 is on for 90 seconds and off for90 seconds. When reheat is deenergized, the cooling minimumairflow setpoint is activated.VAV-PRC008-ENC5

Controls—DDCFan-Powered Terminal Units:On/Off Hot Water Reheat—Twostages of on/off hot water reheat areavailable. The water valves used are2-position and are either fully-openedor fully-closed. The heating minimumairflow setpoint is enabled duringreheat.On parallel-configured fan-poweredunits, the fan is energized when thespace temperature falls below theactive fan on/off point (active heatingsetpoint plus fan offset). The parallelfan is turned off when the spacetemperature rises above the active fanon/off point (active heating setpointplus fan offset) plus 0.5 F (0.28 C).DDCReheatControlVPEFVSEFSeries configured fan-poweredterminal units utilize continuous fanoperation during all occupied settingsand while unoccupied when minimumairflows are being enforced.When the zone temperature falls belowthe active heating setpoint, the UCMmodulates the primary airflow to theminimum heating airflow setpoint.Stage 1 energizes when the spacetemperature is below the activeheating setpoint, and is de-energizedwhen the space temperature is 0.5 F(0.28 C) above the active heatingsetpoint. Stage 2 energizes when thezone temperature is 1 F (0.56 C) ormore below the active heatingsetpoint, and de-energizes when thespace temperature is 0.5 F (0.28 C)below the active heating setpoint.When reheat is de-energized, thecooling minimum airflow setpoint isactivated.Fan-Powered Terminal Units:Proportional Hot Water Reheat—Proportional hot water reheat uses3-wire floating-point-actuatortechnology.The heating minimumairflow setpoint is enabled duringreheat.When the zone temperature falls belowthe active heating setpoint, the UCMmodulates the primary airflow to theminimum heating airflow setpoint.When the zone temperature falls belowthe active heating setpoint, the UCMmodulates the primary airflow to theminimum heating airflow setpoint.The water valve opens as spacetemperature drops below the heatingsetpoint.The degree to which the hotwater valve opens is dependent onboth the degree that spacetemperature is below the activeheating setpoint and the time that thespace temperature has been below theactive heating setpoint. If not alreadyclosed, the water valve fully closeswhen the zone temperature risesabove the active heating setpoint by0.5 F (0.28 C). When reheat is deenergized, the cooling minimumairflow setpoint is activated.Stage 1 energizes when the spacetemperature is below the activeheating setpoint, and is de-energizedwhen the space temperature rises0.5 F (0.28 C) above the active heatingsetpoint. Stage 2 energizes when thespace temperature is 1.0 F (0.56 C) ormore below the active heatingsetpoint, and is de-energized when thespace temperature is 0.5 F (0.28 C)below the active heating setpoint.When reheat is de-energized, thecooling minimum airflow setpoint isactivated.Fan-powered Terminal Units:On/Off Electric Reheat—Two stagesof staged electric reheat are available.The heating minimum airflow setpointis enabled during reheat.On parallel-configured fan-poweredunits, the fan is energized when thespace temperature falls below theactive fan on/off point (active heatingsetpoint plus fan offset). The parallelfan is turned off when the spacetemperature rises above the active fanon/off point (active heating setpointplus fan offset) plus 0.5 F (0.28 C).On parallel-configured fan-poweredunits, the fan is energized when thespace temperature falls below theactive fan on/off point (active heatingsetpoint plus fan offset). The parallelfan is turned off when the spacetemperature rises above the active fanon/off point (active heating setpointplus fan offset).Series-configured fan-poweredterminal units utilize continuous fanoperation during all occupied settingsand while unoccupied when minimumairflows are being enforced.Series-configured fan-poweredterminal units utilize the continuous fanoperation during all occupied settingsand while unoccupied when minimumairflows are being enforced.C6Fan-powered Terminal Units:Pulse-Width Modulation ofElectric Heat—Electric heat ismodulated by energizing for a portionof a three-minute time period. Theheating minimum airflow setpoint isenabled during reheat. This allowsexact load matching for energyefficient operation, and optimum zonetemperature control. One or two stagescan be used.On parallel-configured fan-poweredunits, the fan is energized when thespace temperature falls below theactive fan on/off point (active heatingsetpoint plus fan offset). The parallelfan is turned off when the spacetemperature rises above the active fanon/off point (active heating setpointplus fan offset) plus 0.5 F (0.28 C).VAV-PRC008-EN

Controls—DDCSeries-configured fan-poweredterminal units utilize the continuous fanoperation during all occupied settingsand while unoccupied when minimumairflows are being enforced.When the zone temperature falls belowthe active heating setpoint, the UCMmodulates the primary airflow to theminimum heating airflow setpoint.The amount of reheat supplied isdependent on both the degree thatspace temperature is below the activeheating setpoint and the time that thespace temperature has been below theVAV-PRC008-ENactive heating setpoint. If not alreadyoff, reheat de-energizes when thespace temperature rises 0.5 F (0.28 C)above the active heating setpoint. TheStage 1 “on” time is proportional to theamount of reheat required. Forexample, when 50% of stage 1capacity is required, reheat is on for 90seconds and off for 90 seconds. When75% of stage 1 capacity is required,reheat is on for 135 seconds and offfor 45 seconds. When 100% of stage 1capacity is required, reheat is oncontinuously.DDCReheatControlStage 2 uses the same “on” time logicas stage 1 listed above, except stage 1is always energized. For example,when 75% of unit capacity is required,stage 1 is energized continuously, andstage 2 is on for 90 seconds and off for90 seconds. When reheat is deenergized, the cooling minimumairflow setpoint is activated. Whenreheat is de-energized, the coolingminimum airflow setpoint it activated.C7

Controls—DDCControlDrawingsDD00—Available for all VariTrane Units(Trane actuator for field-installed DDC controls)A unit controller is not provided. The air damper actuator is provided with an integral screw terminal block.The fan contactor (fan-powered units), 24-VAC control power transformer (optional for single- and dual-ductunits), and factory-installed electric heater contactor wires are attached to the outside of the unit for fieldconnection of controls. A second actuator is provided with an integral screw terminal for dual-duct units.CCW24-VACDamper ControlsBy OthersCOMMDamperActuatorLoad: 4 VACWY24-VAC toCustomerControlsLine VoltageBLTransformer24 VAC, 50 VA2FAN RELAY3Fan1Load: 6.5 VA224-VAC Fan/StagedHeat ControlsHEATER CONTROL BOX14CLoad: 10 VA (MAGN)21stLoad: 12 VA (MERC)32nd43rd55.CCW24-VACDamper ControlsBy OthersCOMMDamperActuatorLoad: 4 VACWNOTES:1.Factory-installedField WiringOptional or installed by others2.Located in Heater Terminal Box for electric heat on single-duct units.Located in Control Box for cooling only and hot water heat on single-duct units.Located in Control Box on all fan-powered units.3. Only available with fan-powered units.4. Located in Heater Terminal box.5. Only available with dual-duct units.C8VAV-PRC008-EN

Controls—DDCControlDrawingsAvailable on all VariTrane UnitsFM00 – Customer-supplied actuator and DDC controller factory-installed.FM01 – Trane actuator and customer-supplied DDC controller factory-installedAll customer furnished controllers and actuators are installed and wired per control manufacturer's specifications. Metal controlenclosure is standard.CCWCOMActuatorCustomer-furnishedor Trane-suppliedFanRelayTrane-supplied(Fan-powered only)CW24 VACComBL1st stage - 24 VACElectricReheatContactorsTransformer2nd stage - 24 VACCustomer-furnishedControllerYTrane-supplied3rd stage - 24 VAC24 VAC, 50vaStandard – (Fan-powered)Optional –LOHITrane-suppliedHot r valvefield-wiredto controllerNOTES:1.Factory-installedField WiringOptional or installed by others2. NEMA-1 Enclosure provided.VAV-PRC008-ENC9

Controls—DDCControlDrawingsVCCF—Single-Duct Terminal Units(Normal Operation: Cooling Only with Reheat Capabilities)DD01 – Cooling OnlyDD02 – Cooling with Remote Normally-Closed On/Off Hot Water Valve (Normally-Open Outputs)DD03 – Cooling with Remote Proportional Hot Water Valve with Optional Spare On/Off OutputDD04 – Cooling with Remote Staged On/Off Electric HeatDD05 – Cooling with Remote Pulse-Width Modulation Electric HeatDD07 – Cooling with Remote Normally-Open On/Off Hot Water Valve (Normally-Closed Outputs)See "General Logic" and "DDC Reheat Control" sections for Sequence of Operation.24 VAC 60HZNEC CLASS-2Control CircuitLoad 12 VA(Without heat)DamperActuatorWiringTB2-6TB3-1TB2-5 TB3-2TB3-38.543213.G-OPENR-CLOSEW-HOTW-HOTZone Sensorw/ Comm. JackRemote MTD.4.Optional Field-InstalledZone SensorTB3-2 TB3-1OptionalTransformer50 VATB1-1D.D.C.\U.C.M.CONTROL BOARDAddressSwitch14.PressureTransducerBIP GND 24VJ3RPRESSTB1-2 YBLTB1-1TB1-21ACTTB4-1J7J1J8J9J11J102Zone SensorRemote MTD.BKGOptional Field-InstalledZone Sensor VOUT-1STB3-6TB3-5TB3-3TB3-2YEL GRNTB3-1TB2-6 TB2-5TB2-4 TB2-3TB2-2TB2-1 7.TO J10TO J9TO J8ZONE GND SET A/CO2 GNDOUTW (HOT)TO J8BK (CLOSE)TO J9R (OPEN)TO J10Shielded Twisted PairCommunications Wiring5.R (HOT)(TB1-1) 24VACO (COMMON)GR (NC CONTACT)TB3-5TB3-6NOT CONNECTEDOPTIONAL FIELD INSTALLEDOCCUPANCY SENSOR(TB1-1) 24VCO2(TB3-6) GNDSENSOR GND(TB1-1) 24VACBK (RETURN)Y6.Optional Field-InstalledAuxillary Temperature SensorOUT (TB3-5) A/CO2OPTIONAL FIELD INSTALLEDCO2 SENSORTO J9TO J8ON–OFFWATER VALVE24 VAC12 VA MAXOptional Field-InstalledOn-Off Water ValveNOTES:1.PROP.WATERVALVE24 VAC12 VA MAXOptional Field-InstalledProportional Water Valve6.24V(TB4-1) BIPHEATER STAGECONTACTOR(S)24 VAC, 12 VAMAX/COILOptional Field-InstalledElectric HeaterD.D.C.\U.C.M.Control BoxOUTININ9.2ND STG.1ST STG.HOTFactory WiringField WiringOptional or Alternate Wiring2. 1/4" quick connect required for all field connections.3. Zone sensor terminals 4 and 5 require shielded twisted pair wiring for zone sensorequipped with communications jack. Zone sensor with LCD requires a sixth wirewith 24 V from a transformer.4. No additional wiring required for night setback override (On/Cancel).5. The optional binary input connects between TB4-1 (BIP) and 24 VAC (Hot) from thetransformer. The binary input can be reconfigured as an occupancy input via thecommunications interface.6. As shipped, the AUX input is configured as an Auxiliary Temperature Input. The AUXinput can be reconfigured as a CO2 Sensor Input via the communications interface.7. S-terminal is not to be used with VariTrane.8. If unit-installed transformer is not provided, polarity from unit to unit must bemaintained to prevent permanent damage to control board. If one leg of 24 VACsupply is grounded, then ground leg must be connected to TB1-2.9. Connect shielding from each communication cable together and insulate.C 10VAV-PRC008-EN

Controls—DDCControlDrawingsVCWF—Single-Duct Terminal Units(Normal Operation: Cooling with Hot Water Reheat)DD02 – Cooling with Normally-Closed On/Off Hot Water Valve (Normally-Open Outputs)DD03 – Cooling with Proportional Hot Water Valve with Optional Spare On/Off OutputDD07 – Cooling with Normally-Open On/Off Hot Water Valve (Normally-Closed Outputs)See "General Logic" and "DDC Reheat Control" sections for Sequence of Operation.ON–OFFWater Valve24 VAC12 VA Max.24 VAC 60HZNEC CLASS-2Control CircuitLoad 12 VA(Without 8.543G-OPENR-CLOSEW-HOT3.W-HOT21Zone Sensorw/ Communication JackRemote MTD.4.Optional Field-InstalledZone SensorTB3-2TB3-121D.D.C.\U.C.M.Control BoardAddressSwitchJ3RPRESSY4.PRESSURETRANSDUCERGND 24VBIPBLTB1-1ZONE SENSORREMOTE Transformer50 VAOptional Field-InstalledZone Sensor VOUT-BKG1Optional Field-InstalledZone SensorSTB3-6TB3-5GRNTB3-3YELTB3-2TB2-5TB3-1 TB2-6TB2-4 TB2-3TB2-2TB2-1 7.ZONE GND SET A/CO2 GNDTO J8TO J95.R (HOT)O (COMMON)TB3-5(TB1-1) 24VACTB3-6Y6.24V(TB4-1) BIP(TB1-1) 24VCO2SENSOR(TB1-1) 24VACBK (RETURN)Prop.WaterValve24 VAC12 VA Max.Optional Field-InstalledProportional Water ValveD.D.C.\U.C.M.Control BoxShielded Twisted PairCommunications WiringR (OPEN)TO J10OUTOUTININ9.W (HOT)BK (CLOSE)(TB1-2) GND6.OUT (TB3-5) A/CO2NOT CONNECTEDOPTIONAL FIELD INSTALLEDOCCUPANCY SENSOROPTIONAL FIELD INSTALLEDAUX. TEMPERATURE SENSOROPTIONAL FIELD INSTALLEDCO2 SENSORNOTES:1.Factory WiringField WiringOptional or Alternate Wiring2. 1/4" quick connect required for all field connections.3.Zone sensor terminals 4 & 5 require shielded twisted pair wiring for communications jack equipped zone sensor options.Zone sensor with LCD requires a sixth wire with 24 V from a transformer.4.No additional wiring required for night setback override (ON/CANCEL).5.The optional binary input connects between TB4-1 (BIP) and 24-VAC (HOT) from transformer. The binary input can bereconfigured as an occupancy input via the communications interface.6.As shipped, the Aux. Input is configured as an Auxillary Temperature Input. The Aux. Input can be reonconfigured as aCO2 sensor input via the communications interface.7. S Terminal not to be used with VariTrane.8. If unit-installed transformer is not provided, polarity from unit to unit must be maintained to prevent permanent damageto control board. If one leg of 24-VAC supply is grounded, the ground leg must be connected to TB1-2.9. Connect shielding from each communication cable together and insulate.VAV-PRC008-ENC 11

Controls—DDCControlDrawingsVCEF—Single-Duct Terminal Units(Normal Operation: Cooling with Electric Reheat)DD04 – Cooling with Staged On/Off Electric HeatDD05 – Cooling with Pulse-Width Modulation Electric HeatSee "General Logic" and "DDC Reheat Control" sections for Sequence of Operation.Heater StageContactor(s)OptionalTransformer9.3RD 2ND24-VAC 60 HZNEC Class–2Control CircuitLoad 12 VA(Without heat)DamperActuatorWiring1ST8.TB2-6TB3-1TB2-5 ressSwitchTB3-11Zone SensorRemote MTD.TB1-1TB1-2TB4-1J8J74.PressureTransducerBIP GND 24VJ3D.D.C.\U.C.M.Control BoardRPRESSJ9J10J111ACT14.2J12Optional Field-InstalledZone SensorBRTB1-2HOT4Zone Sensorw/ Comm. JackRemote MTD.BL1ST STG.ORV2ND STG.3RD STG.5BKGOptional Field-InstalledZone Sensor VOLT-1ZONE GND SET A/CO2STB3-6TB3-5TB3-3GRNTB3-2YELTB3-1-TB2-6 TB2-5-TB2-4 TB2-3-TB2-2TB2-1 7.GNDD.D.C.\U.C.M.Control BoxOUTOUTININ10.Shielded Twisted PairCommunications Wiring5.R (HOT)O (COMMON)GR (NC CONTACT)BK (RETURN)Y(TB1-1) 24VACTB3-5TB3-6TB3-6 TB3-5(TB4-1) BIP(TB1-1) 24VAC6.(TB1-2) GND6.NOT CONNECTEDOPTIONAL FIELD INSTALLEDOCCUPANCY SENSORFIELD INSTALLEDAUX. TEMPERATURE SENSOR1.0–10.0VDC OUTCOMOPTIONAL FIELD INSTALLEDCO2 SENSORNOTES:1.Factory WiringField WiringOptional or Alternate Wiring2. 1/4" quick connect required for all field connections.3. Zone sensor terminals 4 and 5 require shielded twisted pair wiring for zone sensor equipped withcommunications jack. Zone sensor with LCD requires a sixth wire with 24 V from a transformer.4. No additional wiring required for night setback override (On/Cancel).5. The optional binary input connects between TB4-1 (BIP) and 24 VAC (Hot) from the transformer.The Binary input can be reconfigured as an occupancy input via the communications interface.6. As shipped, the AUX input is configured as an Auxiliary Temperature Input. The AUX input can bereconfigured as a CO2 Sensor Input via the communications interface.7. S-terminal is not to be used with VariTrane.8. If unit-installed transformer is not provided, polarity from unit to unit must be maintained to preventpermanent damage to control board. If one leg of 24 VAC supply is grounded, the the ground legmust be connected to TB1-2.9. Contactors are 24 VAC: 12 VA max./coil (mercury contactors) and 10 VA max./coil (magnetic coils).10. Connect shielding from each communication cable together and insulate.C 12VAV-PRC008-EN

Controls—DDCControlDrawingsVDDF – Dual-Duct Terminal Units(Normal Operation: Cooling and Heating)DD01 – Cooling (No Remote Heat) and Heating ControlSee "General Logic" and DDC Reheat Control" sections for Sequence of Operation.24VACFROM TB4 ONHEATING VALVE TG-OPENR-CLOSEW-HOTCOOLING VALVETB2-6TB3-1TB2-5 TB3-2TB3-35PRESSURETRANSDUCERBIP GND 24VD.D.C.\U.C.M.CONTROL BOARDJ3PRESSR3.TB1-2 0J11J13212ZONE SENSORW/ COMM. JACKREMOTE MTD.Y24VAC4TB3-2 TB3-11ZONE SENSORREMOTE MTD.4.4.OPTIONAL FIELDINSTALLED ZONE SENSOROPTIONAL FIELDINSTALLED ZONE SENSOR VOUT-BKG1-7.TB3-6TB3-5TB3-3TB3-2GRNSZONE GND SET A/CO2 GNDYELTB3-1 TB2-5TB2-2TB2-1-TB2-6 TB2-4-TB2-3 5.R (HOT)O (COMMON)GR (NC CONTACT)BK (RETURN)OUTOUTININD.D.C.\U.C.M.CONTROL BOXBLBKRY(TB1-1) 24VACTB3-5TB3-66.(TB1-1) 24V(TB4-1) BIPCO2(TB3-6) GNDSENSOR GND(TB1-1) 24VAC(TB1-2) GNDNOT CONNECTEDOPTIONAL FIELD INSTALLEDOCCUPANCY SENSOROUT (TB3-5) A/CO26.OPTIONAL FIELD IAUX TEMP SLEDOPTIONAL FIELD INSTALLEDCO2 SENSORSHIELDED TWISTED PAIRCOMMUNICATIONS WIRING FROM TB3 ONHEATING VALVE UCMHEATING VALVE24VACTO TB1 ONCOOLINGVALVE UCM24VAC 50/60 HZNEC CLASS-2CONTROL CIRCUITLOAD ETB1-21ACTTB4-1344. No additional wiring required for night setback override (On/Cancel).BIP GND 24VPRESSURETRANSDUCERD.D.C.\U.C.M.CONTROL BOARDJ3-TB3-5TB3-3TB3-2GRNRBKG VOUT-1ZONE GND SET A/CO2 GNDYELTB3-1TB2-6 TB2-5-TB2-4 DRESSSWITCH 5SJ8J7J9J10J11J12BL1YTB4FACTORY WIRINGFIELD WIRING2. 1/4" quick connect required for all field connections.3. Zone sensor terminals 4 and 5 require shielded twisted pair wiring forzone sensor equipped with communications jack. Zone sensor with LCDrequires a sixth wire with 24 V from a transfomer.TB1-1W-HOT1.YBL7.5. The optional binary input connects between TB4-1 (BIP) and 24 VAC(Hot) from the transformer. The binary input can be reconfigured as anoccupancy input via the communications interface. Occupancy sensoris connected to both UCM's.6. As shipped, the AUX input is configured as an Auxiliary TemperatureInput. The AUX input can be reconfigured as a CO2 Sensor Input viathe communications interface.7. S-terminal is not to be used with VariTrane.OUTOUTININ9.BLBKRFROM TB

room temperature and will automatically change over to heating control action if the supply air temperature is 10 F or more above the room temperature. If the supply air temperature is between the room temperature and the room temperature plus 10 F, then the DDC controller will provide the ac

Related Documents:

DDC Controls-Use Open Networks BacNet (don't be confused with multiple systems) 20 DDC Controls-Use Open Networks BacNet (View all controls from one network) 21 DDC Control Intervention is the Key. 22 DDC Controls Be Sure Your DDC Controls Vendor is Using BacNet. 23 DDC Controls BacNet. 24

to access the DDC. See figure 2. A55 Prodigy control board DDC ASSEMBLY DDC Figure 2. 036, 060, 120 Units Accessing DDC (Top View) 5. 240 Units:Attach the hat section provided in the kit to the DDC assembly using two 5/8" screws (see figure 3.) HAT SECTION USED ON 240 UNITS ONLY DDC HINGED MOUNTING PANEL Figure 3. 240 Units .

MPC Multi-Protocol/DDC Controls 3 THE SMART SOLUTION FOR ENERGY EFFICIENCY MPC Multi-Protocol DDC Controls August 18, 2021 3 The Multi-Protocol (MPC) Heat Pump controller is a dual purpose controller. It contains the logic to perform as an advanced customizable thermostat when combined with a wall sensor and is designed to allow the integration of

1 Video -5HG 2 Video -Green 3 Video -Blue 4 GND 5 Self -test 6 GND -R 7 GND -G 8 GND -B 9 Computer 5V/3.3V 10 GND -sync 11 GND 12 DDC data 13 H-sync 14 V-sync 15 DDC clock Pin Number 24 -pin Side of the Connected Signal Cable 1 TMDS RX2 - 2 TMDS RX2 3 TMDS Ground 4 Floating 5 Floating 6 DDC Clock 7 DDC Data 8 Floating

VZG Verbundzentrale des GBV (VZG) 32nd Annual Conference of the German Classification Society (ul, July 17, 2008, p. 2) VZG Project Colibri/DDC Fundy National Parc 25 May 2008 by Flo Contents Preface Assignment of DDC* numbers to - Bibliographic title records-N on-DDC terms -

accept Direct Digital Controls (DDC) for VAV pressure independent operation. The terminal unit controls are supplied by the controls contractor and either factory or field mounted and wired. For information concerning controls, components, sequence of operation, etc., please refer to the documentation provided by the controls contractor.

DDC 23 Summaries History and Current Use The Dewey Decimal Classification (DDC) system is a general knowledge organization tool

DUC/DDC Compiler v3.0 7 PG147 February 4, 2021 www.xilinx.com Chapter 1: Overview specifications, and EVM is further limited to 1.6% or less (standard/bandwidth dependent) to provide maximum flexibility in other areas of the wireless digital front end (DFE). The DUC/DDC Compiler co