Welcome! to“Fire Sprinklers on UC Campuses”To listen to this webinar:One tap mobile 16699006833,,432765947# US (San Jose) 16468769923,,432765947# US (New York)Dial by your location 1 669 900 6833 US Toll (San Jose) 1 646 876 9923 US Toll (New York)*4 (from UCOP office phone)Meeting ID: 432 765 947We will begin shortly.Join Zoom Meetinghttps://UCOP.zoom.us/j/432765947

What you need to know!Webinar: FIRE SPRINKLERS on UC CAMPUSESMarch 7th 2019 10:00 – 11:00amMarch 14th 2019 10:00 – 11:00am2

Today’s PresentersMark Meredith,Senior Counsel, OGCJosephine Ortega, AIA, C.B.OConstruction Specialist, UCOPWebinar: FIRE SPRINKLERS on UC CAMPUSESMarch 7th 2019 10:00 – 11:00amMarch 14th 2019 10:00 – 11:00am3

Learning Objectives: Review the new fire sprinkler certification requirements Learn how the Bulletin impacts UC and who enforces it Learn how the regulation impacts UC contracting

5

CALIFORNIA STATE FIRE MARSHALRESPONSIBILITIES Enforcement of building standards adopted by theState Fire Marshal and published in the CaliforniaBuilding Standards Code relating to fire and panicsafety and other regulations of the State FireMarshal6

CALIFORNIAHealth and Safety Code 13146 Section 13146(e) The SFM shall enforce the building standards and otherregulations of the SFM on all University of Californiacampuses and properties administered or occupied bythe University of California. For each university campusor property the SFM may delegate that responsibility tothe person of his or her choice who shall be known asthe Designated Campus Fire Marshal7

UC FIRE MARSHAL PROGRAM Individuals are hired by the University – UC employees,not OSFM employees MOU delegates authority to Designated Campus Fire Marshal MOU establishes education and experience criteria for DCFMpositions Gives OSFM right to review qualifications and confirm or denyDCFM status8

INFORMATION BULLETIN 17-002 Issued on May 25, 2017 Requires certification for anyone who installs or repairs waterprotection systems All fitters must possess certification card All trainees and apprentices must be registered Describes work covered Sets forth requirements to obtain certification9

INFORMATION BULLETIN 17-002WORK COVERED All UC properties and UC occupied and leased facilities oncampuses and off-site facility locations in California arerequired to comply with the Bulletin Work consisting of the installation, alteration or repair ofall water-based fire protection systems10

INFORMATION BULLETIN 17-002WORK COVERED Includes wet, dry, pre-action, and deluge sprinkler systems,small hose connections, standpipe systems, private fireservice mains and their appurtenances, hydrants andmonitor nozzles, water spray systems, foam water systems,fire pumps, water storage tanks, low, medium, and highexpansion foam systems, and water mist systems.11

FIRE SPRINKLER CERTIFICATIONREQUIREMENTS Be at least 16 years old. Active C-16 holder or have successfully completed a CaliforniaState or federally-approved Fire Sprinkler Fitter ApprenticeshipProgram File a Fire Sprinkler Fitter Certification Application (AES 1005)and pay the 150 application fee Pass written certification examination. This exam is conductedby a third-party CAL FIRE12

FIRE SPRINKLER APPRENTICESHIPREQUIREMENTS Be at least 16 years old. Registered in a State of California or federally-approvedFire Sprinkler Fitter Apprenticeship Program. Proof of employment by a licensed C-16. Work under the direct supervision of a Certified FireSprinkler Fitter. File an Apprentice/Trainee Registration Application(AES 1005A) and pay the 150 application fee.13

SPRINKLER FITTERS CERTIFICATIONInformational Bulletin 17-002 Available /pdf/2017/IB AESCert final 05 25 17.pdf14

Quiz: Test your knowledge.OSFM Certification requirement applies to all UC Facilities andproperties administered or occupied by the University ofCalifornia?A. TrueB. False15

Quiz: Test your knowledge.OSFM Certification requirement applies to all UC Facilities andproperties administered or occupied by the University ofCalifornia?A. TrueB. FalseOSFM Information Bulletin 17-002 applies to all UC Facilities located in theState of California. This regulation applies to all water protection systems workthroughout California.It does not apply to UC Facilities located outside of California and outside ofUSA borders.16

Quiz: Test your knowledge.UC Facilities staff who work on the installation, alteration orrepair of all water-based fire protection systems are requiredto have a C-16 license.A. TrueB. False17

Quiz: Test your knowledge.UC Facilities staff who work on the installation, alteration orrepair of all water-based fire protection systems arerequired to have a C-16 license.A. TrueB. FalseOSFM certification is required to work on water protection systems.A C-16 license is not required.18

SPRINKLER FITTERS CERTIFICATIONInformational Bulletin 17-002 Overview of AES certification timeline? How often AES certifications are renewed. Learn about the two types AES certifications. Where to find a list of OSFM AES certified individuals.19

AB 433September 27, 2013 Legislaturetasked OSFM to adoptregulations to ensurefire safety in buildingand structures. OSFMIssuedBulletin 17-002May 25, 201720

SPRINKLER FITTER’S CERTIFICATION21

SPRINKLER FITTER’S CERTIFICATION22

SPRINKLER FITTER’S CERTIFICATION23

SPRINKLER FITTERSCERTIFICATIONOSFM website: icensinglistings/pdf/aes/AESlisting.pdf24

Quiz: Test your knowledge.I submitted my application to OSFM for Certification inthe Fall 2018 and was told there is a backlog to processapplications. While OSFM processes my application I amable to perform work on water protection systems.A. TrueB. False25

Quiz: Test your knowledge.I submitted my application to OSFM for Certification inthe Fall 2018 and was told there is a backlog to processapplications. While OSFM processes my application I amable to perform work on water protection systems.A. TrueB. FalseYou are not permitted to work on water protection systems until OSFMissues a certification card or a letter similar to what the DMV issues fortemporary driver licenses.26

SPRINKLER FITTERS CERTIFICATIONInformational Bulletin 17-002 How does the OSFM Bulletin 17-002 apply to UCconstruction contracting?o Biddingo Specificationso Blanket Contracts for Fire Protection Systems27

UC CONTRACTS No change to core contract documents28

UC CONTRACTS No change to sub-contractor listing29

UC CONTRACTS Specifications CSI Format Section 21 13 14Automatic Fire Sprinkler System30

UC CONTRACTS Specifications C-16 – include and shall be OSFM Certified31

UC CONTRACTS Blanket Contracts for Fire Protection Systems C-16 . . . . and all pipe fitters shall be OSFM Certified . . . . and all trainees and apprentices on job siteregistered.32

Quiz: Test your knowledge.This new regulation requires one certified sprinkler fitteron each job site.A. TrueB. False33

Quiz: Test your knowledge.This new regulation requires one certified sprinkler fitter oneach job site.A. TrueB. FalseThe regulation requires all fitters on each job site to becertified.34

CONFUSED ABOUT THE REGULATION? Contact your Designated Campus Fire Marshal2019 UC Designated Fire Marshals University of California, BerkeleyAmy W. Chen, Lead DCFM University of California, RiversideScott Leland Jackson, Lead DCFM University of California, DavisJames Patterson, Interim Lead DCFM University of California, San DiegoChuck Strickland, Lead DCFM University of California, Davis HealthMichael Major, Lead DCFM, FSLO II OSHPD University of California, San Diego Medical CenterJimmy Fiero, DCFM (Non-OSHPD) University of California, IrvineDale Saunders MPA AIA, Lead DCFM University of California, San FranciscoJeff Monkman, Interim Lead DCFM University of California, Irvine Medical CenterDavid Adrian, DCFM T19 (Non-OSHPD) University of California, Santa BarbaraJim White, DCFM University of California, Los Angeles & Medical Center University of California, Santa CruzDana C. Johnson, Lead DCFMNick Otis, Lead DCFM University of California, MercedGini Krippner, Lead DCFM Lawrence Berkeley National LaboratoryTodd LaBerge, P.E., Lead DCFM35

CONFUSED ABOUT THE REGULATION? Call UCOP Call your construction counsel at OGC36

Questions?Thank you!37

Fire Sprinkler Fitter Apprenticeship Program. Proof of employment by a licensed C-16. Work under the direct supervision of a Certified Fire Sprinkler Fitter. File an Apprentice/Trainee Registration Application (AES 1005A) and pay the 150 application fee. 13

Related Documents:

FM Global PUBLIC Nonstorage Protection FM Global Data Sheet 3-26 & 2-0 K80 sprinklers or water-mist is acceptable for HC-1 occupancy Minimum K115 sprinklers in manufacturing areas (HC-2) –HC-3 occuancy, minimum K160 sprinklers –Ceiling heights 18 m, use K360 sprinklers Extended coverage (EC) heads allow sprinkler spacingsFile Size: 2MBPage Count: 31Explore furtherPocket Guide For Sprinkler Inspection Requirementsfiresprinklertesting.orgPocket Guide to Automatic Sprinklers - FM Globalwww.fmglobal.comSprinklers in electrical rooms according to NFPA 13 - Fire .www.fps-eg.comFire Pump Room Design, Details and Requirements PDF Noteswww.mepwork.comFire Sprinkler Guide to Fire Sprinklers in the .nfsa.orgRecommended to you b

and fire fighters. Fire sprinklers will also prevent extensive damage to your home in the event of a fire. 4. Fire sprinklers operate by releasing a spray of water droplets to supress or extinguish a fire as soon as the heat from the fire heats the air to a certain temperature. This will be within a short time of the fire starting.

Fire sprinklers in homes, apartments, and commercial buildings are the only way we will drive down fire fatalities. Fire sprinklers save lives. Sprinklers reduce the risk of fire-related death by 80%. When it comes to fire the best water is the fastest water—and the fastest water comes from a fire

FIRE TOPPER Fire Bowl User Manual Home » FIRE TOPPER » FIRE TOPPER Fire Bowl User Manual Contents [ hide 1 FIRE TOPPER Fire Bowl 2 Setting Up Your Fire Topper Fire Bowl 2.1 Set-Up 3 Placement and Location 3.1 Liquid Propane Tank 4 Using your Fire Topper Fire Bowl - For your safety, read before lighting. 5 Cleaning, Maintenance, Storage 6 .

Types I and II. 505.2.1(2) – NFPA 13 . Sprinkled mezzanines in 2 story buildings, other than H and I use, having two or more means of egress are not required to exit into the area of the mezzanine 505.2.3(5)– NFPA 13 . Height Increases Sprinklers permit a height increase of 20 feet. Table 504.3 – NFPA 13 and NFPA 13R . Sprinklers increase stories by one-story. Table 504.4 – NFPA 13 and .

fire sprinkler system, you will find little damage from flames, heat, smoke and water. If you plan to rebuild, now is the time to think about installing sprinklers. Learn more about fire sprinklers at the Home Fire Sprinkler Coalition’s website: www. homefiresprinkler.org.

social or cultural context (livelihoods, festivals, traditional, conflict) and perhaps regulatory framework (permit fires, illegal fires). The terms include fires, wildfires, wildland fire, forest fire, grass fire, scrub fire, brush fire, bush fire, veldt fire, rural fire, vegetation fire and so on (IUFRO 2018). The European Forest Fire

Ordinary Hazard Horizontal Sidewall, Dry-Type Sprinklers are designed for extended coverage use in ordinary hazard occupancies (ECOH) per NFPA 13 Series DS-3 Dry-Type Sprinklers provide protection of coverage areas up to 16 ft x 20 ft (320 ft 2) as compared to standard coverage horizontal side-wall sprinklers having a maximum cov -