Technical Data Submittal Document - Tornatech

2y ago
33 Views
3 Downloads
1.84 MB
13 Pages
Last View : Today
Last Download : 2m ago
Upload by : Aliana Wahl
Transcription

Project:Customer:Engineer:Pump Manufacturer:Technical Data Submittal DocumentModel GPYFull Service Reduced VoltageWye-delta OpenElectric Fire Pump ControllerContents: Data Sheets Dimensional Data Wiring Schematics Field ConnectionsNote: The drawings included in this package are for controllers covered under our standard offering.Actual AS BUILT drawings may differ from what is shown in this package.July 2016

Technical DataModel GPY Electric Fire Pump Controller1M3L3From normalincoming power throughDisconnecting T62M1S1SGPY6003L2Across-the linestartingOpen transitionLine current% of full loadLocked rotor currentStarting Method: Reduced VoltageWye-delta open210Wye delta startingTypical Voltage Applied at Start: 100%Inrush Current: 33% of normal load currentStarting Torque: 33%20Motor Type: Wye-deltaNo. of Contactors: 2 at 58%, 1 at 33% of motor FLCMin. ampacity of motor conductors: 6 at 125% x 58% of FLCTransition currentFull load current406080100Percent of motor speed (%)Built to NFPA 20 (latest edition)Standard,Listings,Approvals andCertificationsUnderwriters Laboratory (UL) UL218 - Fire Pump Controllers CSA C22.2 No. 14 Industrial Control EquipmentFM GlobalClass 1321/1323New York CityAccepted for use in the City of New York by the Department of BuildingsSeismic CertificationSee page 5 for detailsOptional CE MarkEnclosureProtection Rating Standard: NEMA 2 (IP31)Optional NEMA 12 NEMA 3 NEMA 3R NEMA 4Accessories Bottom entry gland plate Lifting Lugs Keylock handleVarious EN, IEC & CEE directives and standards NEMA 4X-304 sst painted NEMA 4X-304 sst brushed finish NEMA 4X-316 sst painted NEMA 4X-316 sst brushed finish IP54 IP55 IP65 IP66Paint Specifications Red RAL3002 Powder coating Glossy textured finish*Please see Disconnecting Means details on page 3.July 20162

Technical DataModel GPY Electric Fire Pump ControllerShortcircuitWithstandRating Standard 100kA200V to 208V60Hz220V to 240V60Hz380V to 416V50 Hz / 60Hz440V to 480V60Hz575V to 600V60HzHP (kw)5-150 (3.7 - 110)5-200 (3.7 - 147)5-300 (3.7 - 220)5-450 (3.7 - 335)n/a Standard 50kA200 (147)250 (184)350 - 450 (257 - 335)500 (373) Optional 100kAn/an/an/an/a5-500(3.7- 373) Optional nnectingMeansStandard: 5 C to 40 C / 41 F to 104 FSurge arrestor rated to suppress surges above line voltage Isolating switch and circuit breaker assembly:- Door interlocked in the ON position- Isolating switch rated not less than 115% of motor full load current- Circuit breaker continuous rating not less than 115% of motor full load current- Overcurrent sensing non-thermal type, magnetic only- Instantaneous trip setting of not more than 20 times the motor full load current Common flange mounted operating handleService EntranceRatingSuitable as service entrance equipmentEmergency StartHandle Flange mounted Pull and latch activationLocked RotorProtectorOptional: 5 C to 55 C / 41 F to 131 F Integrated limit switch Across the line start (direct on line) Operate shunt trip to open circuit breaker Factory set at 600% of motor full load currentElectricalReadings Voltage phase to phase (normal power) Amperage of each phase when motor is runningPressureReadings Continuous system pressure display Cut-in and Cut-out pressure settingsPressure andEvent recorderPressure SensingJuly 2016 Trip between 8 and 20 seconds Pressure readings with date stamp Event recording with date stamp Under regular maintained operation, events can be stored in memory for up to 5 years. Data viewable on operator interface display screen Downloadable by USB port to external memory device Pressure transducer and run test solenoid valve assembly for fresh water application Pressure sensing line connection 1/2” Female NPT Drain connection 3/8” Rated for 0-500PSI working pressure (standard display at 0-300psi) Externally mounted with protective cover3

Technical DataModel GPY Electric Fire Pump ControllerAudible AlarmVisual Indications& AlarmsRemote AlarmContactsViZiTouchOperator InterfaceCommunicationProtocolCapability4” alarm bell - 85 dB at 10ft. (3m) Power available Phase reversal Motor run Pump room alarm Motor trouble Phase loss Phase unbalance Low water level Manual start Deluge valve start Remote automatic start Remote manual start Overcurrent Undercurrent Undervoltage OvervoltageSPDT-8A-250V.AC Power available Phase reversal Motor run Common pump room alarm (field re-assignable)** Overvoltage Undervoltage Low pump room temperature High Pump room temperature Common motor trouble (field re-assignable)** Overcurrent Fail to start Undercurrent Ground fault Free (field programmable)** Phase unbalance Embedded microcomputer with software PLC logic 4.2” color touch screen (HMI technology) Upgradable software Expandable storage Multi-language Protocol: Modbus Connection type: Shielded female connector RJ45 Frame Format: TCP/IP Addresses: See bulletin MOD-GPxAutomatic StartManual StartOperation Locked rotor Periodic test Fail to start Low discharge pressure Low pump room temperature Pump room temperature (ºF or ºC) Pump on demand/Automatic start Emergency startStoppingTimers Start on pressure drop Remote start signal from automatic device Start pushbutton Run test pushbutton Deluge valve start Remote start from manual device Manual with Stop pushbutton Automatic after expiration of minimum run timer ***Field Adjustable &Visual CountdownActuationVisual IndicationMode Minimum run timer ***(off delay) Sequential start timer (on delay) Periodic test timer Pressure Non-pressure Automatic Non-automatic**Tornatech reserves the right to use any of these three alarm points for special specific application requirements.***Can only be used if approved by the AHJJuly 20164

Technical DataModel GPY Electric Fire Pump ControllerSeismicTRU Compliance, LLCCertificationA Tobalski Watkins sRigid base and wall mountingBuildingCodeSeismicInformationTWEI Project No.: 15014IBC2015,CBC2016TestSeismicCriteria ParametersICCESAC156AFLX-H ARIG-H AFLX-V 201.282.130.85ASCE 7-10Chapter 13RRS for Nonstructural Components TestingSpectral Response Acceleration (g)10.01.00.10.11.010.0Frequency, f (Hz)Horiz. Level 1Vert. Level 1Notes: Components are tested in accordance with ICC-ES AC156, IBC 2015 & CBC 2016. OSHPD Special Seismic Certification Preapproval (OSP)July 20165

Technical DataModel GPY Electric Fire Pump ControllerFlow switch provisionC20Manual start alarm contact (Form C-SPDT)A8Foam pump application w/o pressure transducer and runtest solenoid valveC21Deluge valve start alarm contact (Form C-SPDT)C22Remote automatic start alarm contact (Form C-SPDT)A9Low zone pump control functionC23Remote manual start alarm contact (Form C-SPDT)A10Middle zone pump control functionC24High pump room temperature alarm contact (Form C-SPDT)A11High zone pump control functionC25A13Non-pressure actuated controller w/o pressure transducerand run test solenoid valveSecond set of standard alarm contacts (Form C-SPDT)(Typical for city of Los Angeles and Denver)CxA16Lockout/interlock circuit from equipment installed inside thepump roomAdditional visual and alarm contact(specify function) (Form C-SPDT)D1Low suction pressure transducer for fresh water rated at0-300PSI with visual indication and alarm contactB11Built in alarm panel (120V.AC supervisory power) providingindication for: Audible alarm & silence pushbutton for motor run, phasereversal, loss of phase. Pilot lights for loss of phase & supervisory power availableD1ALow suction pressure transducer for sea water rated at0-300PSI with visual indication and alarm contactD5Pressure transducer and run test solenoid valve for freshwater rated for 0-500PSI (for factory calibration purposes only)D5DPressure transducer and run test solenoid valvefor sea water rated for 0-500PSID10Omit mounting feet (when applicable)D13High withstand rating for (normal power section) 208V to 480V 150kA 600V 100kAD14Anti-condensation heater & thermostatD14AAnti-condensation heater & humidistatA4B11BBuilt in alarm panel same as B11 but 220-240VACsupervisory powerB19AHigh motor temperature c/w thermoster relay and alarmcontacts (Form C-SPDT)B19BHigh motor temperature c/w PT100 relay and alarmcontacts (Form C-SPDT)B21Ground fault alarm detection c/w visual indication and alarmcontact (Form C-SPDT)C1Extra motor run alarm contact (Form C-SPDT)D14BAnti-condensation heater & thermostat & humidistatC4Periodic test alarm contact (Form C-SPDT)D15TropicalizationC6Low discharge pressure alarm contact (Form C-SPDT)D18CE Mark with factory certificateC7Low pump room temperature alarm contact (Form C-SPDT)D26Modbus with RTU frame format and RS485 connectionC10Low water reservoir level alarm contact (Form C-SPDT)C11High electric motor temperature alarm contact(Form C-SPDT)D27Motor heater connection (external single phase powersource and heater on/off contact)C12High electric motor vibration c/w visual indication and alarmcontact (Form C-SPDT)D27AMotor heater connection (internal single phase powersource and heater on/off contact)D28Customized drawing setC14Pump on demand / automatic start alarm contact(Form C-SPDT)D34Field programmable I/O board - 8 Input / 5 outputC15Pump fail to start alarm contact (Form C-SPDT)D35Field programmable I/O board - 8 Input / 10 outputC16Control voltage healthy alarm contact (Form C-SPDT)D36Redundant pressure transducer for fresh water rated for0-500PSIC17Flow meter valve loop open c/w visual indication and alarmcontact (Form C-SPDT)D36ARedundant pressure transducer for sea water rated for0-500PSIC18High water reservoir level c/w visual indication and alarmcontact (Form C-SPDT)D37Window kit for operator interfaceC19Emergency start alarm contact (Form C-SPDT)Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.July 20166

Technical DataModel GPY Electric Fire Pump ControllerL01Other language and English ote: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.July 20167

Technical DataModel GPY Electric Fire Pump ControllerViZiTouch Operator Interface31PMS 295PMS 361Noir24568789101112?1 - Power on LED2 - Color touch screen3 - Alarm LED4 - HOME page button5 - ALARM page button6 - CONFIGURATION page button7 - HISTORY page buttonJuly 2016138 - USB port9 - START button10 - Contextual navigation pad11 - STOP button12 - RUN TEST button13 - HELP button8

Electric Fire Pump ControllerModel: GPA/GPP/GPYDimensionsBuilt to the latest edition of the NFPA 20 standard33 3/8" [846]32 3/8" [823]30" [762]21 3/4" [552]Ø7/8" [Ø23] X228 3/4" [730]Ø3/8" [Ø10] X418" [457]See Notes69 1/8" [1756]68" [1727]65 7/8" [1675]62" [1576]22 3/4" [576]27 5/8" [702]1" [25] Adjustable Feet34" [864]32" [813]Sensing Line Connection - 1/2 " F.NPTØ1/2" [Ø13] X4Drain - 3/8 " M.TUBE10" [255]Voltage / Power TableVoltageMin HPMax HP20875150220 - 24075200380 - 400 - 415150300440 - 4802004006002005001 1/4" [31]1" [25]NormalPowerand11" [279]Motor LeadsEntrance11 5/8" [294]Notes:11" [279]3 1/2" [89]16" [406]3" [76]1" [25]- Standard NEMA: NEMA 2- Standard Paint : Textured Red RAL 3002.- All Dimensions are in Inches [Millimeters].- Center of ViZiTouch Screen: 62-5/8" [1589] from Bottom.- Bottom Conduit Entrance Through Removable Gland Plate Recommended.- Use Watertight Conduit and Connector Only.- Protect Equipment Against Drilling Chips.- Door Swing Equal to Door Width.- Seismic mounting to be rigid wall and base only.Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.Contact manufacturer for "As Built" drawing.ProjectionREV.NYCDpt of BuildingApproved2016121110DESCRIPTIONMODIFIED TORNATECH & SEISMIC LOGOADDED SEISMIC LOGOGENERAL REVISIONDrawing numberDD/MM/YY22/12/1519/08/1516/06/14GPX-DI311 /ECDLAll right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.

Model: GPYElectric Fire Pump ControllerReduced Voltage / Wye-Delta (Open Transition)Built to the latest edition of the NFPA 20 standardCBSA3To 11411141112CommonPump ack6468672M*691STo J76To WhiteWiring 37TB3J14J39TB4J15( )AI4-IN(-)( )AI3-IN(-)J41TB5( )J16White(-)BlackPressuretransducertype 0-5VPT1RedPT1-IN( )J17PT2-IN(-)J43Green / YellowGSV1-1BrownSV1SV1-2BlueSV1NGNDJ45ST232To shunt tripGNDJ44 1NJ47XTR11REC3LX124VAC3 X2H2H13L23L1J8LS1-18J1627Red 8( )(-)641J53J3P2To 8DI5DELUGE J2*VALVEVIZITOUCHMAIN BOARD696TM1GND72728TemperatureProbe 1J6COM2526REMOTE J1*AUTOMATIC STARTWATER RESERVOIRLOWP124COMLOCKOUTJ1123DI6REMOTEMANUAL STARTJ1P12122COMLS1-2DI7LS1*3L36J57543L2To 3L1-2-332I/O RELAY BOARD* REMOVE JUMPER TO USE THIS FEATURE13L1REV.NYCDpt of BuildingApproved2016Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.Contact manufacturer for "As Built" drawing.* Contact closed when Emergency Start is in ON position543DESCRIPTIONModified Tornatech & Seismic LogoAdded Seismic LogoGeneral RevisionDrawing numberDD/MM/YY14/04/1619/08/1507/01/15GPY-WS500 /ECDLAll right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.

Model: GPXElectric Fire Pump ControllerBuilt to the latest edition of the NFPA 20 standardTerminals Diagram and SizingBondingGroundPower TerminalsModels :GPA, GPR & GPS3 PhasesIncoming PowerL1 L2 L3ISGnd1MGndT1 T2 T3Notes:1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC(Canada) or local code.2 - Controller suitable for service entrance in USA.3 - For more accurate motor connections refer to motor manufacturer ormotor nameplate.4 - Controller is phase sensitive. Incoming lines must be connected in ABCsequence.5 - Field wiring and lug sizes base on copper conductors only.Do not use aluminium conductors.M(Use Copper Conductors Only)Isolating Switch (IS) Field Wiring according to Bending Space (AWG or MCM). TERMINALS L1 - L2 - L3BendingSpaceHP5 " (127 mm)58 " (203 mm)7.51015202530405060Voltage2081x (10 to 1/0)1x (8 to 1/0)1x (8 to 1/0)1x (6 to 1/0)1x (4 to 1/0)1x (3 to 1/0)1x (2 to 1/0)1x (1/0 to 250)1x (3/0 to 250)1x (4/0 to 250)220 to 2401x (10 to 1/0)1x (10 to 1/0)1x (8 to 1/0)1x (6 to 1/0)1x (4 to 1/0)1x (4 to 1/0)1x (3 to 1/0)1x (1 to 250)1x (2/0 to 250)1x (3/0 to 250)380 to 4161x (10 to 1/0)1x (10 to 1/0)1x (10 to 1/0)1x (8 to 1/0)1x (8 to 1/0)1x (6 to 1/0)1x (6 to 1/0)1x (4 to 1/0)1x (3 to 1/0)1x (3 to 1/0)440 to 4801x (10 to 1/0)1x (10 to 1/0)1x (10 to 1/0)1x (10 to 1/0)1x (8 to 1/0)1x (8 to 1/0)1x (6 to 1/0)1x (6 to 1/0)1x (4 to 1/0)1x (3 to 1/0)6001x (10 to 1/0)1x (10 to 1/0)1x (10 to 1/0)1x (10 to 1/0)1x (10 to 1/0)1x (8 to 1/0)1x (8 to 1/0)1x (6 to 1/0)1x (6 to 1/0)1x (4 to 1/0)BendingSpaceHP16 " (406 mm)12 " (305 mm)751001251502002503003504004505001x (500)2x (4/0 to 500)2x (250 to 500)1x (350 to 500)2x (3/0 to 500)2x (4/0 to 500)2x (400 to --2x (350 to 500)2x (500 to 600)----------------------------------------2x (4/0 to 500)2x (300 to 500)2x (400 to 500)2x (400 to 500)2x (500 to 600)2x (600)--------Voltage2081x (300 to 500)220 to 240 1x (250 to 500)380 to 4161x (1/0 to 250)1x (3/0 to 250)1x (250)1x (300 to 500)2x (3/0 to 250)440 to 4801x (1 to 250)1x (2/0 to 250)1x (3/0 to 250)1x (4/0 to 250)1x (350 to 500)2x (3/0 to 250)2x (4/0 to 500)2x (300 to 500)2x (350 to 500)2x (400 to 600)2x (500 to 600)6001x (3 to 1/0)1x (1 to 250)1x (2/0 to 250)1x (3/0 to 250)1x (250 to 500)1x (350 to 500)2x (3/0 to 250)2x (4/0 to 500)2x (250 to 500)2x (300 to 500)2x (350 to 500)BendingSpace5 " (127 mm)8 " (203 mm)12 " (305 mm)(Use Copper Conductors Only)Wiring Size for motor connection for Models GPA, GPR & GPS (AWG or MCM). TERMINALS T1 - T2 - T3HP57.510152025304050602081x (10)1x (10)1x (8 to 2)1x (6 to 2)1x (4 to 1/0)1x (3 to 1/0)1x (2 to 1/0)1x (1/0 to 3/0)1x (3/0)1x (4/0 to 300)Voltage220 to 2401x (12 to 10)1x (10)1x (8 to 2)1x (6 to 2)1x (4 to 1/0)1x (4 to 1/0)1x (3 to 1/0)1x (1 to 3/0)1x (2/0 to 3/0)1x (3/0)380 to 4161x (14 to 10)1x (12 to 10)1x (10)1x (8 to 2)1x (8 to 2)1x (6 to 2)1x (6 to 1/0)1x (4 to 1/0)1x (3 to 1/0)1x (3 to 1/0)440 to 4801x (14 to 10)1x (14 to 10)1x (12 to 10)1x (10)1x (8 to 2)1x (8 to 2)1x (6 to 2)1x (6 to 2)1x (4 to 1/0)1x (3 to 1/0)6001x (14 to 10)1x (14 to 10)1x (14 to 10)1x ( 10)1x (10)1x (8 to 2)1x (8 to 2)1x (6 to 2)1x (6 to 2)1x (4 to 1/0)751001251502002503003504004505001x (300)2x (2/0 to 300)2x (4/0 to 300)2x (250 to 300)2x (400 to --2x (2/0 to 300)2x (3/0 to 300)2x (4/0 to 300)2x (350 to 500)2x (500 to age208220 to 240 1x (250 to 300)380 to 4161x (1/0 to 3/0)1x (3/0)1x (250 to 300)1x (300)2x (3/0 to 300)2x (4/0 to 300)2x (300)2x (400 to 500)2x (500 to 600)2x (600)440 to 4801x (1 to 2/0)1x (2/0 to 3/0)1x (3/0)1x (4/0 to 300)2x (1/0 to 300)2x (3/0 to 300)2x (4/0 to 300)2x (300)2x (350 to 500)2x (400 to 600)2x (500 to 600)6001x (3 to 1/0)1x (1 to 2/0)1x (2/0 to 3/0)1x (3/0)1x (250 to 300)2x (2/0 to 300)2x (3/0 to 300)2x (4/0 to 300)2x (250 to 300)2x (300)2x (350 to 500)Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.For drawing for approval or installation, please contact manufacturer.REV.NYCDpt of BuildingApproved2016876DESCRIPTIONModified Tornatech & Seismic LogoAdded Terminal Torque RatingsAdded Seismic LogoDD/MM/YY14/04/1614/09/1519/08/15Drawing numberGPX-TD500 1/3 /EAll right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.

Model: GPXElectric Fire Pump ControllerBuilt to the latest edition of the NFPA 20 standardTerminals Diagram and SizingPower Terminals3 PhasesIncoming PowerBondingGroundL1 L2 L3ISGndGnd2M1MT7 T8 T9T1 T2 T33 PhasesIncoming PowerBondingGroundL1 L2 L3ISGndGndNotes:1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC(Canada) or local code.2 - Controller suitable for service entrance in USA.3 - For more accurate motor connections refer to motor manufacturer ormotor nameplate.4 - Controller is phase sensitive. Incoming lines must be connected in ABCsequence.5 - Field wiring and lug sizes base on copper conductors only.Do not use aluminium conductors.2M1MT6 T4 T5T1 T2 T3MMModels :GPPModels :GPW & GPY(Use Copper Conductors Only)Isolating Switch (IS) Field Wiring according to Bending Space (AWG or MCM). TERMINALS L1 - L2 - L3BendingSpaceHP5 " (127 mm)58 " (203 mm)7.51015202530405060Voltage2081x (10 to 1/0)1x (8 to 1/0)1x (8 to 1/0)1x (6 to 1/0)1x (4 to 1/0)1x (3 to 1/0)1x (2 to 1/0)1x (1/0 to 250)1x (3/0 to 250)1x (4/0 to 250)220 to 2401x (10 to 1/0)1x (10 to 1/0)1x (8 to 1/0)1x (6 to 1/0)1x (4 to 1/0)1x (4 to 1/0)1x (3 to 1/0)1x (1 to 250)1x (2/0 to 250)1x (3/0 to 250)380 to 4161x (10 to 1/0)1x (10 to 1/0)1x (10 to 1/0)1x (8 to 1/0)1x (8 to 1/0)1x (6 to 1/0)1x (6 to 1/0)1x (4 to 1/0)1x (3 to 1/0)1x (3 to 1/0)440 to 4801x (10 to 1/0)1x (10 to 1/0)1x (10 to 1/0)1x (10 to 1/0)1x (8 to 1/0)1x (8 to 1/0)1x (6 to 1/0)1x (6 to 1/0)1x (4 to 1/0)1x (3 to 1/0)6001x (10 to 1/0)1x (10 to 1/0)1x (10 to 1/0)1x (10 to 1/0)1x (10 to 1/0)1x (8 to 1/0)1x (8 to 1/0)1x (6 to 1/0)1x (6 to 1/0)1x (4 to 1/0)BendingSpaceHP12 " (305 mm)7516 " (406 mm)1001251501x (500)2x (4/0 to 500)2x (250 to 500)1x (350 to 500)2x (3/0 to 500)2x (4/0 to 500)2002503003504004505002x (400 to --2x (350 to 500)2x (500 to 600)----------------------------------------2x (4/0 to 500)2x (300 to 500)2x (400 to 500)2x (400 to 500)2x (500 to 600)2x (600)--------Voltage1x (300 to 500)208220 to 240 1x (250 to 500)380 to 4161x (1/0 to 250)1x (3/0 to 250)1x (250)1x (300 to 500)2x (3/0 to 250)440 to 4801x (1 to 250)1x (2/0 to 250)1x (3/0 to 250)1x (4/0 to 250)1x (350 to 500)2x (3/0 to 250)2x (4/0 to 500)2x (300 to 500)2x (350 to 500)2x (400 to 600)2x (500 to 600)6001x (3 to 1/0)1x (1 to 250)1x (2/0 to 250)1x (3/0 to 250)1x (250 to 500)1x (350 to 500)2x (3/0 to 250)2x (4/0 to 500)2x (250 to 500)2x (300 to 500)2x (350 to 500)BendingSpace5 " (127 mm)8 " (203 mm)12 " (305 mm)(Use Copper Conductors Only)Wiring Size for motor connection for Models GPP, GPW & GPY (AWG or MCM). TERMINALS T1 - T2 - T3 - T4 - T5 - T6 - T7 - T8 - T9HP57.510152025304050602081x (14 to 10)1x (12 to 10)1x (10)1x (8 to 2)1x (8 to 2)1x (6 to 2)1x (6 to 1/0)1x (4 to 2/0)1x (2 to 3/0)1x (1 to 3/0)Voltage220 to 2401x (14 to 10)1x (12 to 10)1x (10)1x (8 to 2)1x (8 to 2)1x (6 to 2)1x (6 to 1/0)1x (4 to 2/0)1x (3 to 2/0)1x (2 to 3/0)380 to 4161x (14 to 10)1x (14 to 10)1x (14 to 10)1x (12 to 10)1x (10)1x (10)1x (8 to 2)1x (6 to 2)1x (6 to 2)1x (4 to 1/0)440 to 4801x (14 to 10)1x (14 to 10)1x (14 to 10)1x (12 to 10)1x (12 to 10)1x (10)1x (10 to 2)1x (8 to 2)1x (6 to 2)1x (6 to 2)6001x (14 to 10)1x (14 to 10)1x (14 to 10)1x (14 to 10)1x (12 to 10)1x (12 to 10)1x (10)1x (10 to 2)1x (8 to 2)1x (8 to 2)751001251502002503003504004505002081x (2/0 to 3/0)1x (3/0)1x (250 to 300)2x (1/0 to 300)2x (3/0 to --220 to 2401x (1/0 to 3/0)1x (3/0)1x (4/0 to 300)1x (300)2x (2/0 to 300)2x (4/0 to 350)----------------------------------------380 to 4161x (4 to 2/0)1x (2 to 2/0)1x (1/0 to 3/0)1x (2/0 to 3/0)1x (4/0 to 300)1x (300)2x (2/0 to 300)2x (3/0 to 300)2x (4/0 to 350)2x (4/0 to 350)--------440 to 4801x (4 to 2/0)1x (3 to 2/0)1x (2 to 3/0)1x (1/0 to 3/0)1x (2/0 to 3/0)1x (4/0 to 300)1x (300)2x (1/0 to 300)2x (2/0 to 300)2x (3/0 to 350)2x (4/0 to 350)6001x (6 to 2)1x (4 to 2/0)1x (3 to 2/0)1x (2 to 3/0)1x (1/0 to 3/0)1x (2/0 to 3/0)1x (4/0 to 300)1x (250 to 300)1x (300)2x (1/0 to 300)2x (2/0 to 300)HPVoltageDrawing for information only.Manufacturer reserves the right to modify this drawing without notice.For drawing for approval or installation, please contact manufacturer.REV.NYCDpt of BuildingApproved2016876DESCRIPTIONModified Tornatech & Seismic LogoAdded Terminal Torque RatingsAdded Seismic LogoDD/MM/YY14/04/1614/09/1519/08/15Drawing numberGPX-TD500 2/3 /EAll right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.

Model: GPXElectric Fire Pump ControllerBuilt to the latest edition of the NFPA 20 standardTerminals Diagram and SizingRemote Alarm Terminals (I/O board)Control Terminals (I/O board)Terminals Wire Size:12 - 24 AWG0.5 NmPhaseReversalNormally closedOpens to alarmPumpRoomAlarmNormally closedOpens to alarmMotorTroubleNormally closedOpens to alarmMOTOR RUNJ19 - 1223Close to start pump24J25LockoutNormally closedOpens to alarmJ40 - 14J40 - 1125Close to block startTB1Normally openCloses to alarm(Fail Safe)J19 - 11Remote Manual leJ19 - 14RemoteAutomaticStartOpen to start pumpIf used, remove jumper J1DelugeValveSignalOpen to start pumpIf used, remove jumper J226J25J40 - 12Normally openCloses to alarmJ42 - 14J42 - 11Automatic StartJ12728J25J42 - 12Normally openCloses to alarm(RE-ASSIGNABLE)J37 - 14J37 - 11TB3Normally closedOpens to alarmNormally openCloses to alarmDeluge ValveJ22930J25J37 - 12Normally openCloses to alarm(RE-ASSIGNABLE)Field Connections for External Devices(I/O board)J39 - 14J39 - 11TB4MotorRunningTerminals Wire Size:12 - 24 AWG0.5 NmJ39 - 12Terminals Wire Size:12 - 24 AWG0.5 NmNormally closedOpens to alarmNormally openCloses to alarmJ41 - 14J41 - 11TB5(Field*Programmable)J41 - 12Water Reservoir LowWater ReservoirLowSignalClose to signal alarmFlow / ZoneStart / StopSignalClose to signal alarmJ25Flow / ZoneDrawing for information only.Manufacturer reserves the right to modify this drawing without notice.For drawing for approval or installation, please contact manufacturer.3334J25*Not Available in GPS ModelsREV.NYCDpt of BuildingApproved20163132876DESCRIPTIONModified Tornatech & Seismic LogoAdded Terminal Torque RatingsAdded Seismic LogoDD/MM/YY14/04/1614/09/1519/08/15Drawing numberGPX-TD500 3/3 /EAll right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.

New York City Accepted for use in the City of New York by the Department of Buildings . 200V to 208V 60Hz 220V to 240V 60Hz 380V to 416V 50 Hz / 60Hz 440V to 480V . (Form C-SPDT) C17 Flow meter valve loop open c/w visual indication and alarm contact (Form C-SPDT) .

Related Documents:

DPP Submittal 4 This is mostly an issue with model corrections Example: 1 DPP could be a seasonal model . *If there is a discrepancy in data between the DPP Submittal Form and the IDEV file, the IDEV data is used. . o 46% - DPP Submittal Form issues

Vertical eries FAN COIL TECHNICAL CATALO 3 Table of Contents 4-5Portfolio 6Features and Benefits 7Unit Model Key 8-9Ratings and Listings 10Air Delivery 11-12 Motor Data 13 Sound Data 14 Electric Heating 15-26 Submittal Data – F*Y 27 Air Flow Arrangements - F*Y 28-31 Submittal Data – L** 32 Submittal Data – ST* 33-34 Pip

and cut sheets of all devices and panels. REVISIONS : - Need Revision Submittal form - Need Architect's Narrative - Need clouds and deltas - Signature is required. www.davie-fl.gov Deerfield Beach (8/27/2015) EPD submittal / Approval required prior to Bldg Dept submittal. Apply 'on-line' for Security Code & Application Number. Walk-thru review .

The submittal items managed for a project can be packaged in the e-Builder system. The packages can be categorized by trade or CSI code, depending on the needs of the user managing the items. Once a Submittal Package is created, items contained in the Submittal Register can be added to their perspective package and transmitted for a formal .

Provide the following in a sealed envelope or package as indicated above in Submittal Check List item C.: Paper Copies One original copy of your complete submittal, arranged as indicated in Sections 3.01 and 3.02. Twelve copies of the complete original submittal. Electronic copies (USB drive, labeled with company name): One electronic copy of the complete submittal in either Word or PDF

Milestone Period: The period for the 2016-2017 Programmatic Milestones covers the two calendar years from January 1, 2016 – December 31, 2017. Submittal and Reporting Process: New Programmatic Milestone Submittal: The State is requesting submittal of Programmatic Milestone commitments by January 29, 2016. Submit to Paul.Emmart@Maryland.gov.

that the submittal does not meet the contract requirements, the government may disapprove or otherwise require re-submittal, as applicable. If systemic weaknesses are found in the contractor's QC process for FlO submittals, corrective action must be pursued promptly. 8. Submittal

Mother’s and Father’s Day Assemblies School Choir School Leaders Elections Development of School Advisory Board Development of Parents and Friends Group (PFA) Movie Night Experience Music Soiree Christmas Carols Night Athletics Carnival Camp for Years 5/6 Thank you to all the staff for their commitment, passion and care of our children. Thank you to .