ADEMCO VISTA SERIES - Site.aesecurity

2y ago
44 Views
2 Downloads
975.83 KB
80 Pages
Last View : 12d ago
Last Download : 3m ago
Upload by : Mia Martinelli
Transcription

Page 2-8 and 8-1 Has been edited by Tech Support. If you have anyquestions call 1.800.645.7492ADEMCO VISTA SERIESVISTA-20P / VISTA-20PSIAVISTA-15P / VISTA-15PSIASecurity SystemsInstallation and Setup GuideK5305-1V5 10/04 Rev. A

RECOMMENDATIONS FOR PROPER PROTECTIONThe Following Recommendations for the Location of Fire and Burglary DetectionDevices Help Provide Proper Coverage for the Protected Premises.Recommendations For Smoke And Heat DetectorsWith regard to the number and placement of smoke/heat detectors, we subscribe to therecommendations contained in the National Fire Protection Association's (NFPA) Standard #72 notedbelow.Early warning fire detection is best achieved by the installation of fire detection equipment in all roomsand areas of the household as follows: For minimum protection a smoke detector should be installedoutside of each separate sleeping area, and on each additional floor of a multi-floor family living unit,including basements. The installation of smoke detectors in kitchens, attics (finished or unfinished), orin garages is not normally recommended.For additional protection the NFPA recommends that you install heat or smoke detectors in the livingroom, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms,basements and attached garages.In addition, we recommend the following: Install a smoke detector inside every bedroom where a smoker sleeps. Install a smoke detector inside every bedroom where someone sleeps with the door partly orcompletely closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outsidemay not wake up the sleeper if the door is closed. Install a smoke detector inside bedroomswhere electrical appliances (such asKITCHENportable heaters, air conditioners orBDRMKITCHEN DININGBEDROOM BEDROOMTV ROOMDININGBDRMhumidifiers) are used.LIVING ROOM Install a smoke detector at both ends of ahallway if the hallway is more than 40feet (12 meters) long.BEDROOMBEDROOMLIVING ROOMSmoke Detectors for Minimum ProtectionSmoke Detectors for Additional ProtectionHeat-Activated DetectorsBEDROOMBEDROOMTOBRBEDROOMKTCHNLVNG RM.CLOSEDDOORGARAGEBASEMENTfloor plan-001-V0 Install smoke detectors in any room wherean alarm control is located, or in any roomwhere alarm control connections to an ACsource or phone lines are made. Ifdetectors are not so located, a fire withinthe room could prevent the control fromreporting a fire or an intrusion.THIS CONTROL COMPLIES WITH NFPAREQUIREMENTS FOR TEMPORAL PULSESOUNDING OF FIRE NOTIFICATIONAPPLIANCES.Recommendations For Proper Intrusion ProtectionFor proper intrusion coverage, sensors should be located at every possible point of entry to a home orcommercial premises. This would include any skylights that may be present, and the upper windowsin a multi-level building.In addition, we recommend that radio backup be used in a security system so that alarm signals canstill be sent to the alarm monitoring station in the event that the telephone lines are out of order(alarm signals are normally sent over the phone lines, if connected to an alarm monitoring station).ii

Table Of ContentsFeatures and Installation Highlights.1-1Capabilities and Functions.1-1Compatible Devices .1-2Important Installation Highlights (Installer Please Read) .1-2Mounting and Wiring the Control .2-1Installing the Control Cabinet and PC Board .2-1Cabinet and Lock .2-1Mounting the PC Board Alone (no RF Receiver) .2-1Mounting Board with RF Receiver.2-1AUXILIARY DEVICE CURRENT DRAW WORKSHEET .2-2AC Power, Battery, and Ground Connections .2-31321 Transformer.2-31361X10 Transformer .2-3Battery Connections.2-3Battery Saver Feature .2-3Earth Ground .2-3Sounder (Bell) Connections .2-4Basic Connections .2-4Supervised output .2-4Connecting the Keypads and Other Addressable Devices .2-4Connections .2-4Supplementary Power (optional).2-4Keypad Notes .2-5Long Range Radio Connections .2-5Table of Device Addresses .2-5Hardwire Zones and Zone Expansion .2-6Hardwire Zones .2-6Double-Balanced Zones.2-6Zone Doubling .2-6Smoke Detectors.2-6Smoke Detector Notes.2-74219/4229 Expansion Zones .2-7Installing the RF Receiver and Wireless Transmitter Zones .2-8Compatible Receivers.2-8Receiver Connections .2-8RF Receiver Notes.2-8Installing a 5800TM Module .2-9Installing the Transmitters .2-9Transmitter Battery Life .2-9Installing a Keyswitch.2-10Keyswitch Connections .2-10Keyswitch Notes.2-10Connecting Relay Modules, Powerline Carrier Devices and Output Triggers.2-114204/4229 Relay Modules .2-11Powerline Carrier Devices .2-11On-Board Triggers .2-12Phone Line/Phone Module, and Audio Alarm Verification (AAV) Connections.2-13Phone Line.2-134285/4286 Phone Module .2-13Phone Module Problems .2-13Audio Alarm Verification Connections.2-14Programming Overview .3-1About Programming .3-1Mechanics of Programming.3-1Data Field Programming Procedures.3-1Interactive Mode Programming ( 56, *57, 58, 79, 80, 81, 82).3-2Loading Factory Defaults/Initializing for Download.3-2Exiting the Programming Mode .3-2Zone Type Definitions.3-2iii

Table Of Contents (continued)Data Field Programming .4-1About Data Field Programming.4-1System Setup Fields ( 20 – 29) .4-1Zone Sounds & Timing ( 31– 39) .4-1Dialer Programming ( 40 – 50) .4-2System Status Report Codes .4-4Miscellaneous System Fields .4-5Pager Programming Fields.4-7Miscellaneous System Fields .4-8Configurable Zone Type Fields .4-9Touch Screen Device (AUI) Enable.4-11Keypad Programming Fields.4-11Menu Mode Programming .5-1Zones and Partitions.5-1About Zone Programming ( 56 and 58 Menu Modes) .5-1 56 Zone Programming Procedure .5-1Completing Zone Programming .5-4 58 Expert Programming Mode Procedures .5-4Wireless Key Programming Templates .5-6About Output Device Programming (*79/*80 Menu Mode) .5-8Programming Output Devices.5-8*79 Menu Mode: Output Device Mapping .5-8*80 Menu Mode: Defining Output Functions .5-10About Zone Lists (*81 Menu Mode) .5-12Zone List Programming.5-12About Function Keys (*57 Menu Mode).5-13Programming Function Keys .5-13About Descriptor Programming (*82 Menu Mode) .5-14Programming Zone Descriptors (Menu Mode 82).5-14Adding Custom Words (will not be annunciated by 4285/4286 Phone Module) .5-15Programming Installer and User Schedules .5-17System Communication and Operation .6-1Panel Communication with Central Station .6-1Report Code Formats.6-1Ademco Contact ID .6-3System Security Codes .6-4Panic Keys.6-6Setting the Real-Time Clock .6-6Various System Trouble Displays .6-7Testing the System.7-1About Test Procedures.7-1System Test.7-1Checking Transmitter Enrollment (Sniffer Mode).7-1Go/No Go Test Mode .7-2Dialer Communication Test and Periodic Test Reports.7-2Automatic Standby Battery Tests.7-2Specifications & Accessories.8-1Security Control.8-1Compatible Devices .8-15800 Series Transmitter Input Loop Identification .8-3Regulatory Agency Statements .9-1Limitations and Warranty .10-7iv

S E C T I O N1Features and Installation HighlightsThis manual applies to the following Honeywell security systems:ADEMCO VISTA-20P/ADEMCO VISTA-20PSIA/ADEMCO VISTA-20PCN (collectively referred to asVISTA-20P series), ADEMCO VISTA-15P/ADEMCO VISTA-15PSIA/ADEMCO VISTA-15PCN(collectively referred to as VISTA-15P series)Features and procedures apply to all, except where differences are noted.SIA Installations: The VISTA-20PSIA and VISTA-15PSIA are certified SIA-compliant controls thatmeet SIA specifications for False Alarm Reduction. The other controls described in this manual arenot certified as SIA compliant, but can be programmed for False Alarm Reduction. To program forFalse Alarm Reduction, follow the SIA Guidelines noted in the applicable programming fields.NOTE: Throughout this manual, device model numbers are ADEMCO model numbersunless otherwise noted.Capabilities and FunctionsFeature/FunctionPartitionsZonesSecurity CodesOne-button armingSchedulesKeypad macrosPagingEvent LoggingZone descriptorsBell supervisionRF jam detectionTelephone LineMonitoringDownloadingADEMCO VISTA-20P SeriesADEMCO VISTA-15P SeriesVISTA-15P is not a partitioned system. 2 partitions, can protect two independentareas Common zone option allows eitherpartition to arm, while leaving a commonarea (ex. lobby or foyer) disarmed foraccess into the other partition.Up to 32 zones plus 8 keyfob zones (zonesUp to 48 protection zones plus 16 keyfob49-56) for total of 40 zones:zones (zones 49-64) for total of 64 zones: 6 basic hardwired zones (zone 1-6) 8 basic hardwired zones (zones 1-8) withoptional zone-doubling feature Up to 16 additional wired zones (zones 924) using up to 2 4219/4229 modules Up to 40 additional wired zones (zones 948) using up to 5 4219/4229 modules Up to 26 wireless transmitter zones(5800 series; zones 9-34) Up to 40 wireless transmitter zones (5800series; zones 9-48) Up to 2 configurable zone types Up to 4 configurable zone typesUp to 48 Security Codes, with separateUp to 32 Security Codes, with separateauthority levels and partition accessauthority levelsDedicated keys can arm the system.Dedicated keys can arm the system.Up to 32; can control devices and/or autoUp to 8; can control devices and/or autoarm/disarmarm/disarmUp to 4; activated by wired keypadsUp to 2; activated by wired keypadsUp to 2 pagers; certain system conditionsUp to 4 pagers; certain system conditionscan report to pagers; can use a dedicatedcan report to pagers; can use a dedicatedkey on keypads to send a signal to a pagerkey on keypads to send a signal to a pager50 events; log display is done via Ademco100 events; log display is done via AdemcoCompass Downloader software orCompass Downloader software orinstaller/master code at Keypadinstaller/master code at KeypadCan assign for all zones (for alpha display keypads and/or 4285/4286 Phone Module).Optional, detects external sounder wiring short or open; causes a trouble condition,keypad display, and sends a report to the central monitoring station, if enabled.Optional, for wireless systems detects a condition that may impede proper RF reception(i.e., jamming or other RF interference); causes keypad display, and sends a report to thecentral monitoring station (if trouble reporting is enabled).Built-in option can monitor the telephone line voltage and can cause a local display, or adisplay and trouble/alarm soundVia an IBM compatible computer, Compass downloading software, and a compatibleHAYES or CIA modem specified by Ademco.1-1

Installation and Setup GuideCompatible DevicesDeviceAddressable KeypadsVISTA-20P8VISTA-15P822Up to 5 forup to 40exp. zonesUp to 40 RFzonesUp to 16Up to 2 forup to 16exp. zonesUp to 26 RFzonesUp to 82Up to 48Partition 1only2Up to 24yesAudio AlarmVerificationUsing AAVmoduleUsing AAVmoduleAlarm output12VDC, 2AMP output12VDC, 2AMP outputAuxiliary Power OutputBackup BatterySee note.See note.See noteSee note.Long Range RadioSee note.See note.AC Power SupplySee note.See note.Touch Screen (AUI)Devices4219, 4229 ZoneExpander Modules5800 Series WirelessOutput relays and/orPowerline CarrierDevices (X-10 type)On-Board TriggersOutput functions4285/4286 PhoneModuleNotes6150 Fixed-Word Keypad, 6160 Alpha Keypad, 6150VFixed-Word Display Voice Keypad, 6160V AlphaDisplay Voice Keypad, 6150RF Keypad/TransceiverTouch Screen (AUI) devices are in addition to the 8addressable keypads. E.g., Symphony, 6270Zone numbers are predefined according to the deviceaddresses used. See Expander Module Addresses tablein Wiring section and set addresses accordingly.Uses 5881/5883 Series Receivers/Transceivers.Use any combination of 4204, 4229 and or PowerlineCarrier Devices.Map output devices via *79 Menu mode.Can be used to reset 4-smoke detectors.Program output functions via *80 Menu mode.Provides access to the system via on premises or offpremises phones for arming, disarming, etc., pluscontrol of relay outputs and Powerline Carrier devices.Use ADEMCO UVS or Eagle Model 1250; can be usedin conjunction with an output trigger to permit voicedialog between an operator at the central station anda person at the premises.Can drive the compatible sounders; steady output forburglary/panic, or temporal pulse (3 pulses – pause –3 pulses – pause – 3 pulses. . .) for fire. Uses currentlimiting circuitry for protection.12VDC, 600 mA maximum; uses fuse for protection.Rechargeable (sealed lead-acid type) 12VDC, 4AHminimum.Primary telephone number messages can be reportedvia ECP connection to various Long Range Radios(check compatibility/availability of specific models)Plug-in 120VAC transformer, ADEMCO 1321(1321CN in Canada) or, if using Powerline Carrierdevices, ADEMCO 1361X10 Transformer ModuleNOTE: All devices and accessories used in a Canadian installation must be Listed for use in Canada.Important Installation Highlights (Installer Please Read) This system uses addressable keypads and Zone Expander Modules (see Table of Addresses inSection 2. Mounting and Wiring – Wiring the Keypads and Other Addressable Devices). Keypads must be set for addresses 16-23 (first keypad is address 16, which is different fromprevious controls) and programmed in data fields *190-*196. Zone Expander Modules must be set for specific addresses (07-11), based on the zone numbers used. 4204 Relay Modules must be set for specific addresses (12-15). This control will not power-up unless AC power is connected (will not power-up on battery alone).However, once the system is powered up, it will operate on battery power in the event of AC loss. Relays have two programming menu modes: Use *79 Menu mode to map module addresses anddevice (output) numbers. Use *80 Menu mode to define the output functions. This system supports programmable function keys. Use *57 Menu mode to define the functionkeys. This system provides various paging features. Refer to the Programming Overview section for asummary on pager programming.1-2

S E C T I O N2Mounting and Wiring the ControlInstalling the Control Cabinet and PC BoardMounting the PC BoardAlone (no RF Receiver)LOCKEDPUSHON LOCKUNTIL ITIS SEATEDSECURELYSNAPTABPUSHUNLOCKEDCABINET DOORBOTTOMSNAPTABSTEP 1STEP 2cab lock snap-001-V02. Remove cabinet door, then removethe lock knockout from the door.Insert the key into the lock.CHECKPOSITIONADEMCO1. Mount the control cabinet to asturdy wall in a clean, dry area,which is not readily accessible tothe general public, using fastenersor anchors (not supplied) with thefour cabinet mounting holes.ADEMCOCabinet and LockFigure 1. Installing the Cabinet Lock3. Position the lock in the hole, making certain that the latch will make contact with thelatch bracket when the door is closed. When correctly positioned, push the lock untilthe snap tabs hold it securely.The cabinet can be secured without a lock by using 2 screws in the cover's edge.Before installing the cabinet's contents, remove the metal cabinet knockouts required forwiring entry. Do not remove the knockouts after the circuit board has been installed.1. Hang two short mounting clips (provided) on the raised cabinet tabs (see Detail B).2. a. Insert the top of the circuit board into the slots at the top of the cabinet. Make surethat the board rests on the correct row (see Detail A).b. Swing the base of the board into the mounting clips and secure the board to thecabinet with the accompanying screws (see Detail B).CIRCUITBOARDCABINETCIRCUITBOARDCABINETDETAIL ASIDE VIEWOF BOARDSUPPORTINGSLOTS DETAIL BSIDE VIEWOF MOUNTINGCLIPSMOUNTING-001-V0Mounting Board with RFReceiverFigure 2. Moun

ADEMCO VISTA SERIES VISTA-20P / VISTA-20PSIA VISTA-15P / VISTA-15PSIA Security Systems Installation and Setup Guide K5305-1V5 10/04 Rev. A . Page 2-8 and 8-1 Has been edited by Tech Support. If you have any quest ions call 1.800.645.7492. File Size: 975KB

Related Documents:

ADEMCO VISTA-10PSIA Security Systems User Guide K0736V3 10/04 Rev. B – 2 – IMPORTANT! . Your Honeywell security system is designed for use with devices manufactured or approved by . The features and procedures described in this manual apply to the ADEMCO VISTA-10P and ADEMCO VISTA-10PSIA. Differences are noted where applicable.

ADEMCO VISTA-48A ADEMCO VISTA-48E Security Systems Installation and Setup Guide K0749-1ENV1 10/05 Rev. A

ADEMCO VISTA-48A ADEMCO VISTA-48E Security Systems User Guide K0750-1EN 11/04 Rev. A

ADEMCO VISTA-48A ADEMCO VISTA-48E Security Systems User Guide ÕðغðóïÛÒ ïïæðì »“ò ß www.msealarms.com.au

About the System (cont’d) 2 Alarm System Maximum Number of Keypads Minimum Software Revision Level VISTA-250FBP-9 3 4.1 VISTA-250BP 3 2.4 VISTA-250FBP 1 3.0 VISTA-250FBP 3 2.0 VISTA-128BPE 3 4.4 VISTA-250BPE 3 4.4 VISTA-128BPEN 3 7.0 VISTA-128BPLT 3 6.0 VISTA-128FBPN 3 5.1 VISTA-128BPT 6 10.1 VISTA-250BPT 6 10.1 VISTA-128BPTSIA 6 10.1 FA148CP 2 3.0 .

ADEMCO VISTA SERIES VISTA-20P / VISTA-20PSIA VISTA-15P / VISTA-15PSIA Security Systems Programming Guide K5305-1PRV5 10/04 Rev. A Downloaded from www.Manualslib.com

ADEMCO VISTA SERIES VISTA-20P / VISTA-20PSIA VISTA-15P / VISTA-15PSIA Se

The dynamics of group size is an important component of group work. A small group is often considered to consist of three or more people (Beebe & Masterson, 2003). Groups of two are called dyads and are not encouraged for group work because there are not a sufficient number of individuals to generate creativity and a diversity of ideas (Csernica et al., 2002). In general, it is suggested that .