AF & AG 7-96 Dry Pipe Valve - Tyco Fire

2y ago
26 Views
2 Downloads
916.27 KB
12 Pages
Last View : 1m ago
Last Download : 3m ago
Upload by : Elise Ammons
Transcription

AF & AG7-96Dry Pipe ValveFlange x Groove - AGFlange x Flange - AFManufactured by: Central Sprinkler Company451 North Cannon Avenue, Lansdale, Pennsylvania 19446OTELEBSThe Central Dry Pipe Valve is a drypipe sprinkler system water-supplycontrol valve that makes possible theinstallation of sprinkler systems inbuildings subject to freezingtemperatures. It is designed so thatair pressure in the piping system willhold back water pressure at the valveuntil such time as a sprinkler isactivated. Upon such activation theair pressure in the system will bedecreased sufficiently to causeautomatic operation of the valve andadmission of water into the system.It is a 5:1 differential type valvehaving a clapper air seat of large arearelative to the water seat. The twoconcentric seats are separated by anintermediate chamber normallymaintained at atmospheric pressure.The Dry Pipe Valve Trim packageincludes the necessary valves,gauges, fittings and nipples to providean air supply connection, primingwater connection, drain connections,alarm connection, acceleratorconnections and alarm test bypass.(Note: Accelerator trim soldseparately). The Dry Pipe Valves areListed/Approved with Central’s Trimonly. Any substitutions or omissionsmay void such Listings andApprovals, without prior approvalfrom Central Sprinkler.Central’s Air Maintenance Devicefor owner’s air supply or automatic aircompressor supply may be easilyconnected to the Dry Pipe ValveTrim.Central’s Accelerator (quickopening device) may also be easilyconnected to the Dry Pipe ValveTrim. It is a NFPA 13 requiredaddition to the valve and trim whenthe capacity of the dry pipe sprinklersystem exceeds 500 gallons.The Dry Pipe Valves are availablein two styles, flange-by-flange ModelAF and flange-by-groove Model AG.Each Valve style is available in the4 inch and 6 inch size.The Valves are Approved byFactory Mutual and Listed by Underwriter’s Laboratories and Underwriters' Laboratories of Canada for use infire sprinkler systems with a maximum working pressure of 175 psi.OProductDescriptionTechnicalDataModel: AF or AGStyle: Flange-x-Flange - AFFlange-x-Groove - AGSize: 4" and 6"Approvals: U.L., F.M., U.L.C.Maximum Working Pressure: 175 psiFactory Hydro Test: 100% at 350 psi(with clapper open)Standard Finish: Blue enamelFlange Specifications:AF Inlet - Class 125 ANSI B16.1AG Inlet - Class 125 ANSI B16.1AF Outlet - Class 125 ANSI B16.1Groove Specifications:AG Outlet - Std. AWWA C-606Piping Take-Out:AF - 4" size 15 1/4", 6" size 18 1/2"AG - 4" size 16 1/4", 6" size 20"4" & 6" DryPipe Valve &ComponentTrimRequired Accessories:Standard Trim (as shown)Optional Accessories:Air Maintenance DeviceAir CompressorAccelerator & TrimPressure Alarm SwitchWater Motor AlarmLow Air Pressure SwitchMfgr. Source: U.S.Weight: Valve - 140 lb. (4" size)235 lb. (6" size)Trim - 45 lb.No. 10-5.0

Figure 1Dry Pipe Valve - Partial SectionsGrooved Outlet OptionModel AGNote: * 4" Dry Pipe Valve** 6" Dry Pipe Valve16 1/4"*20"**Flanged Outlet OptionModel AF1 BodyCoverAir Supply Connection (3/4" NPT)9 Cover Gasket15 1/4"*18 1/2"**TE8Priming Connection (3/4" NPT)10Cover Bolt (3/4")7 ClapperAssemblyMain Drain Connection (2" NPT)3 3/4"OWater 2SeatRingLEAir Seat Ring 36 Pipe Plug (1/2")5Hinge PinInter. ChamberConnection (3/4" NPT)BS7"*8 1/4"**4 Body BushingONote: The Clapper Assembly may be removed from the body of the Dry Pipe Valveby removing the two 1/2" plugs (#6) and removing the hinge pin (#5).Parts List - Dry Pipe ValveModel AF (4" Part No. 2214 — 6" Part No. 2216)Model AG (4" Part No. 2215 — 6" Part No. 91010*Not field replaceable.11112121116 (4")8 (6")Part Number4" SizeDescriptionBodyBodyWater Seat RingAir Seat RingBody BushingHinge PinPipe Plug, 1/2"-14 NPTClapper AssemblyCoverCover GasketCover Bolt 3/4"-10 x 2" LongCover Bolt 3/4"-10 x 2" Long2400-188-00 (AF)400-189-00 2-00400-186-00400-02-000400-04-000600-03-000Part Number6" Size600-188-00 (AF)600-189-00 2-00600-186-00600-02-000600-04-000600-03-000

Figure 2Dry Pipe Valve Clapper 3RubberSealOBolt2ClapperBushing1LE10TE9Parts List - Clapper AssemblyModels AF or AG (4" Assembly No. 400-186-00 — 6" Assembly No. equired12115 (4")6 (6")21121Part Number4" SizeDescriptionClapperClapper Bushing (body)Rubber SealRetaining Plate1/4"-20 x 3/4" Hex Head Bolts1/4"-20 x 3/4" Hex Head BoltsClapper Bushing (latch)LatchLatch PinRetaining RingLatch -21-000Part Number6" -000

Pendent sprinklers in dry pipesystems must be of the dry pendenttype in areas that are subject tofreezing.Dry pipe systems that supplyfreezer areas must be equipped witha local, Low Air Pressure Alarm whichmay be connected to the system riserjust above the Dry Pipe Valve. For“freezer area” systems, a desiccantair dryer should be provided in the airsupply line to remove moisture fromthe compressed air.Dry System CapacityIf the dry pipe system capacityexceeds 500 gallons, the Dry PipeValve must be equipped with aCentral Accelerator. See the appropriate Central Bulletin for details.The capacity (gallons) of the pipingsystem may be calculated using thefollowing table:TEDesignDataDESIGN CONSIDERATIONSLEGeneralThe Central Model AF and ModelAG Dry Pipe Valves must be installedin the vertical position. They shouldbe located in a sprinklered area notsubject to freezing conditions, suchas a well-lighted and heated valvehouse or similar enclosure havingsufficient room to enable ease ofinstallation, care and maintenance.When properly installed, the Trimon the Dry Pipe Valve protrudes thefollowing horizontal distances fromthe center line (C.L.) of the riser:OBSWhen the Dry Pipe Valve is in theset position, the rubber-faced clapperis tightly closed on two concentricseat rings. The inner ring is the waterring and the outer ring is the air ring.The annular space between the twoseat rings (intermediate chamber) isopen to the atmosphere via the alarmconnection trim piping to the normallyopen automatic ball drip valve.Priming water is provided above theclapper up to the level of the primingconnection. Above the priming water,compressed air (or nitrogen) ismaintained at a pressure sufficient tohold the clapper closed. The DryPipe Valve has a differential trip ratioof approximately 5 to 1. Thus thevalve will open (trip) when the airpressure in the system piping isreduced to approximately one-fifth ofthe water supply pressure.The purpose of the priming water isto assist in providing a positive seal atthe air seat ring to prevent air fromescaping into the intermediatechamber and on to the atmosphere.The clapper will remain in the closedposition as long as the air pressure inthe piping system is maintained at theproper level.When a sprinkler operates, the airpressure in the piping system decaysdue to the air escaping from theopened sprinkler. When the airpressure has decayed to the pointthat it is no longer adequate to holdthe clapper shut, the water supplypressure lifts the clapper whichautomatically latches in the openposition. Water flows into the systempiping to the open sprinkler(s). At thesame time, water flows via theintermediate chamber into the alarmconnection trim piping (closing theautomatic ball drip valve) andcontinues on through the alarm line tooperate the pressure actuated alarmswitch and/or the water motor alarm.When a sprinkler opens, theresulting air pressure decay isinversely proportional to the volumeof air in the sprinkler piping. Thelarger the volume, the slower the airpressure decays, which slowsoperation of the Dry Pipe Valve.Central’s Accelerator is an ApprovedQuick Opening Device (QOD) that issensitive to a rapid, small drop insystem air pressure. Its quickoperation directs system air pressureto the underside of the clapper in thearea of the intermediate chamber.Here the air pressure build-up,coupled with the pressure of thewater supply, forces the clapper toopen quickly. The operation of theDry Pipe Valve has been accelerated.The operation of Central’s Accelerator is described in greater detail in aseparate Central bulletin.Diameter(in.)3/411 1/41 1/222 1/23468OOperationTrimProtrusion*4"ValveC.L. to leftC.L. to rightC.L. to rear22 1/2"8 1/2"15"6"Valve23"11"16"* When the observer is facing the valve bodycover plate.DrawingsThe dry pipe system workingdrawings must show:1. The manufacturer, style, modelnumber, and size of the DryPipe Valve.2. The total number of sprinklerson each dry pipe system, and3. The capacity (gallons) of eachdry pipe system.4123Capacity (gal./ft.)Sch. 40Sch. 9.085.115.190.283.433.7401.64912.77620.134" wall pipe0.188" wall pipeSchedule 30 pipeIn accordance with current NFPA13, the maximum allowable capacityof a single dry pipe system is normally 750 gallons. The capacity mayexceed 750 gallons only if water canbe delivered to the inspector’s testconnection in 60 seconds or less.Air CompressorThe compressed air supply for thedry pipe system is usually providedby a continuously available, electrically driven, air compressor which isautomatically controlled to turn onand off at the designed minimum andmaximum pressures, respectively.After initial pressurization of thesystem, the air supply is maintainedthrough an in-line, 1/8" orifice in thepiping of the Air Maintenance Device.

Figure 3 - Set PositionSystemPressureReliefAirAir SupplyFill PortWater LevelTEAlarm Line(to Water tMainDrainOMainSupplyBSFigure 4 - Activated PositionSystemOPressureReliefWaterFill PortAir SupplyAlarm Line(to Water ainSupply5MainDrain

Figure 5Trim Assembly Diagram - 4" & 6" Dry Pipe ValveModel AF Shown (Model AG Similar)IMPORTANT: Assemble Components in Proper Numerical OrderLETE‡BSO‡* Double wrap Teflon tape on threaded ends.All other threaded connections assembledwith Loctite PST pipe sealant.O‡Normal Valve PositionComp. #1Comp. #2Comp. #2Comp. #4Comp. #4 & 12Comp. #6Comp. #7Drain ValvePlug1/4" Globe Valve3/4" Globe Valve3-way Globe Valve1/2" Ball Valve (alarm test)3/4" Ball ValveNormally ClosedNormal Screwed TightNormally ClosedNormally OpenNormally OpenNormally ClosedNormally Sealed Open6Indicates accelerator trim connection point.Note: CL Close Nipple

Bill of MaterialDry Pipe Valve Trim - Model AF & Model AG(See Trim Assembly Diagram on page 6)43/4" x 7 1/2" Nipple3/4" x 5" NippleSub-Assembly3/4" x 3/4" x 1/2" Tee1/2" Pipe Plug3/4" x Close Nipple3/4" x 3/4" x 1/4" Tee1/4" x Close Nipple1/4" 3-way Globe Valve1/4" Pipe Plug1/2" Relief Valve3/4" Globe Valve111111111111111011214111111112141111111/4" Gauge, Air6Sub-Assembly1/2" x Close Nipple1/2" x 1/2" x 1/4" Tee1/2" Ball Valve1/2" X 1 1/2" Nipple21112111Sub-Assembly3/4" Ball Valve3/4" x 5" Nipple3/4" x 1/2" x 3/4" Tee3/4" Close Nipple3/4" Check Valve1/2" x 2" Nipple1/2" x 1/4" x 1/2" Tee1/4" x Close Nipple1/4" Globe Valve111111111111111111O9 578111111Description3/4" x 3 1/2" Nipple3/4" x 2 1/2" NippleSub-Assembly3/4" x 1/2" x 3/4" Tee3/4" x 2 1/2" Nipple3/4" 90 Elbow3/4" x Close Nipple3/4" Union1/2" x Close Nipple1/2" Tee1/2" 90 Elbow1/2" Pipe Plug3/4" x Close Nipple3/4" x 4" NippleTE3Sub-Assembly3/4" x 2 1/2" Nipple3/4" x 3/4" x 1" Tee1" Pipe Plug3/4" x 1/4" Red. Bush.1/4" 90 Street Elbow1/4" x Close Nipple1/4" Globe Valve11111111111121111111111Sub-Assembly1/4" x 14" Nipple1/4" 3-way Globe Valve1/4" Pipe Plug111111131/4" Gauge, Water1114Sub-Assembly1/2" x 6" Nipple1/2" Check Valve1/2" x 5" Nipple1/2" x Close Nipple1/2" 90 Elbow11111111111/2" Drip CupSign, Main DrainSign, Alarm LineSign, Alarm TestSign, Control ValveSign, Inspectors TestSign, Air LineTie Wrap1111111121111111121516171819202122Note: The Trim Kit includes all the valves, nipples and fittings to completely trim either a 4" or 6" Dry Pipe Valve.7111112111111111214" Qty. 6" Qty.Sub-Assembly1/2" x 5 1/2" Nipple1/2" x 1/2" x 1/4" Tee1/4" Pipe Plug1/2" x 1 1/2" Nipple1/2" Drip ValveLE2Sub-Assembly2" x Close Nipple2" MxF Ball Valve2" x 6 1/2" Nipple2" x 2" x 1/2" Tee2" 90 ElbowDetailNumber4" Qty. 6" Qty.O1DescriptionBSDetailNumber

Drainage (per NFPA 13)The dry pipe system must bedesigned so that all portions of thepiping system may be drained. Inorder to assure proper drainage:a. If the trapped section is lessthan 5 gallons capacity,provide a 3/4" valve with plugor with nipple and cap.b. If the trapped section isgreater than 5 gallonscapacity, provide a drum drip(2" x 12" pipe nipple with a 1"valve on each end) with theoutlet valve equipped with aplug or nipple and cap.O4" valve 30 feet6" valve 33 feet2. Trapped sections of piping mustbe equipped with auxiliary drainsas follows:InstallationGeneralDry Pipe Valves must be installed in asprinklered area not subject tofreezing conditions, such as a welllighted and heated valve house orsimilar enclosure having sufficientroom to enable ease of installation,care and maintenance.Prior to installing the Dry PipeValve in the piping system, the watersupply line must be thoroughlyflushed to assure that no foreignmatter is present.The valve must be installed in thevertical position in the system piping.Trim according to the Trim AssemblyDiagram on page 6.Remove the hand hole cover andgasket and check the valve clapperfor freedom of movement.In order to place the Dry Pipe Valveinto operation, the valve must be “set”(see Setting Procedure on page 9).The system side of the valve clapperassembly must be primed with waterto the level of the priming connection.TEFriction LossFor use in hydraulic calculations,the pressure loss through the DryPipe Valve may be expressed inequivalent length of schedule 40,C 120 pipe as follows:1. Branch lines, cross and feedmains shall be pitched inaccordance with NFPA 13, Sec.3-6.1.3.LEAir Compressor (continued)The orifice is small enough thatwhen a sprinkler opens, the air supplywill not interfere with the operation ofthe Dry Pipe Valve by rapidly supplying additional air pressure to theupper chamber of the Dry Pipe Valve.The air compressor must beadequately sized to be able to bringthe system air pressure up to thedesign level in 30 minutes or less.The required size of the air compressor in C.F.M., may be determinedfrom the following equation:C.F.M. 0.012 X System Capacity(gallons), where C.F.M. is the free airdelivery in cubic feet per minutebased on standard air at sea level ata system pressure of 25 psig.BS4"6"Note: Priming water is as follows:6" 4 Gallons4" 2 GallonsOThe system piping must besubsequently pressurized with air (ornitrogen) via the air connection. Afterpriming and pressurization of the DryPipe Valve, the main system watercontrol valve must be opened fully.After initial installation, the alarm test,main drain test and trip test(s) mustbe performed and the system resetand placed in service.It is recommended that Central’sAutomatic Air Maintenance Device bepermanently connected to the systemto avoid the possibility of false valvetrips which may result from smallpiping leaks gradually loweringsystem air pressure.If difficulty in performance isexperienced, Central SprinklerCompany should be contacted if anyfield adjustment is to be made.8

Setting ProcedureStep 1. Close the main water supplycontrol valve to the sprinkler system(OS&Y, PIV or other).Step 2. Close all valves in the DryPipe Valve Trim, except the 1/4"three-way valves at the Air PressureGauge and Water Pressure Gauge(Figure 5).Do not force the clapper in attemptingto make the Dry Pipe Valve tight. Donot use grease or other sealingmaterials on the seat rings orrubber seal.Step 9. Reinstall the valve bodyCover and Gasket, being careful totighten the bolts evenly in astaggered fashion.Step 10. Open the Priming SupplyPlug (subassembly Fig. 5, #2) whilemaking sure that the CondensateDrain Valve (subassembly Fig. 5, #2)is closed. Prime the Dry Pipe Valveby slowly pouring water into thePriming Supply. Stop pouring whenwater remains visible in the PrimingSupply Line.Step 4. After all drainage hasstopped, tightly close all auxiliarydrain valves. Leave the inspector’stest valve and system main drainvalve open.Step 11. Open the CondensateDrain Valve to remove excesspriming water from the Dry PipeValve.LENote: Priming water is as follows:6" 4 Gallons4" 2 GallonsOStep 12. Close the CondensateDrain Valve and replace the PrimingSupply Plug.BSStep 5. Remove the valve bodyCover and Gasket (Fig. 1, #8 & #9).Caution: Never attempt to removethe valve cover while the valve isunder pressure.OStep 6. Lift the clapper assembly(Fig. 1, #7) and carefully inspect thewater seat ring (Fig. 1, #2), air seatring (Fig. 1, #3), rubber seal (Fig. 2,#3), and valve body interior. Clean ifnecessary. Do not use cleaningcompounds which could damage therubber seal. Be careful not to scratchor dent the seat rings. Damaged seatrings are not field-replaceable.Step 7. Verify that the clapperassembly moves freely and that thespring-loaded anti-reseat Latch (Fig.2, #7) moves freely under handapplied pressure.Step 8. Raise the rear portion of theanti-reseat Latch so that it clears thetwo cast-in-body latching positions,and lower the clapper assembly tothe closed and fully-seated position.Step 16. Open the Air SupplyControl Valve (subassembly Fig. 5,#4) and admit air to the system. If thesystem is equipped with an automaticAir Maintenance Device, refer to theappropriate Central Bulletin fordetailed instructions.Note: It is good practice to buildup the air pressure on the systemto 10 psi and then individuallyopen the auxiliary drains to forceany remaining water from the lowpoints in the system. When dry airstarts to discharge, close thevalve(s) tightly and replace theplug or cap.TEStep 3. Open the system main drainvalve, the system inspector’s testvalve, and all system auxiliary drainvalves connected to the piping.Replace any sprinklers which mayhave activated.By keeping the inspector’s testconnection open, the system pipingwill be maintained at atmosphericpressure and the test connection willserve as a vent during systemdrainage and during priming of theDry Pipe Valve.Step 15. Clean the Accelerator, if thesystem is so equipped. Refer to theappropriate Central Bulletin fordetailed instructions. Cleaning theaccelerator may proceed concurrentwith establishing the air pressure inthe system.Step 13. Check the Automatic BallDrip Valve (subassembly Fig. 5, #11)for leakage.a. If there is little or no leakage, theclapper is properly seated.Continue with the “SettingProcedure”.b. If there is leakage, the clapper isnot properly seated, and thepriming water is leaking past theair seat into the intermediatechamber. The Dry Pipe Valvemust be re-opened andrepaired. Replace the rubberseal on the clapper if it is worn.After performing the necessaryrepairs, repeat steps 5 through13 above.Step 14. Close the systeminspector’s test valve.9Step 17. Continue to admit air intothe system until the Air PressureGauge (Fig. 5, #5) registers the airpressure required to hold the DryPipe Valve closed against the watersupply pressure. The recommendedair pressure is a function of the watersupply pressure as shown below:Air (psi)Water 5050* When an accelerator is installed with the DryPipe Valve, a minimum air pressure of 25 psiis required.Step 18. Again, check the AutomaticBall Drip Valve for leakage. Thereshould be none.a. If there is no leakage, theclapper is properly seated.Continue with the “SettingProcedure”.b. If there is leakage, the clapperis not properly seated and isnot holding the priming water.

Step 20. Slowly open the main watersupply control valve to the sprinklersystem. When water starts todischarge from the main drain, slowlyclose the main drain valve(subassembly Fig. 5, #1). Then fullyopen the main water supply controlvalve (OS&Y, PIV or other).Step 21. Perform a Main Drain Test(see Main Drain Test Procedure).Acceptance TestingAfter the installation of a Dry PipeSystem is complete and prior to finalacceptance by the Authority HavingJurisdiction, the installer must conducta Main Drain Test, Alarm Test, andTrip Test. The test results must berecorded on the Contractor’s Materialand Test Certificate.Refer to the Trim AssemblyDiagram (Figure 5) which correlateswith the I.D. numbers noted in thefollowing procedures:BSStep 22. Open the Alarm Test Valve(subassembly Fig. 5, #6) and thenperform an Alarm Test (see AlarmTest Procedure).Air TestThe 40 psi air pressure test of thesprinkler system piping must beconducted to verify there are no leaksthat would allow a pressure loss of1.5 psi or more during the 24-hourtest period.Main Drain Test ProcedureThe purpose of the Main Drain Testis to show whether or not the normalwater supply is available to thesystem. By comparing the static andresidual water pressure readings withany previously established readings,a Main Drain Test can indicate thepossible presence of partially closedvalves or other obstructions in thesupply piping. To avoid propertydamage during testing, provision mustbe made for proper disposal of waterissuing from the test outlet.The procedure for conducting amain drain test is as follows:OStep 23. Seal, lock, or otherwisesecure the Alarm Control Valve(subassembly Fig. 5, #7) and themain water supply control valve in theopen position. The system is nowready for service.Step 24. If alarms connect to acentral station or fire department,notify the signal receiving station thatthe system has been placed inservice.TestingGeneralPrior to completion of the installation of a Dry Pipe System, the pipingmust be tested for strength and waterleakage (hydrostatic test) and for airStep 2. Open the main drain valve(subassembly Fig. 5, #1) slowly untilit is wide open. Verify that a fullsteady flow of water is dischargingfrom the main drain pipe. If a fullsteady stream is not discharging,check the main drain piping forobstructions.Step 3. Allow the water to flow untilthe reading on the Water PressureGauge drops and stabilizes. Thenrecord this reading. This is theresidual pressure.Step 4. Close the main drain valveslowly.Step 5. Compare static and residualpressure readings with any previouslyestablished or normal readings. If thereadings compare favorably, thewater supply may be consideredsatisfactory. If the readings vary toany great extent, the condition shouldbe investigated to determine thecause. Some possible causes are:TEStep 19. Activate the air supply tothe Accelerator, if the system is soequipped. Refer to the CentralAccelerator Bulletin for instructions.To prevent a possible false trip of theDry Pipe Valve, perform thisaccelerator activation step prior toopening the main water supplycontrol valve.Hydrostatic TestThe 2-hour, 200 psi hydrostatic testof the sprinkler system piping must beconducted with the valve clapperlatched in the open position. Therubber seal on the face of the clappermay be ruptured if the valve is testedwith the clapper in the closed position.The test should be conducted asweather permits to prevent freezing ofthe piping.LEPriming water must be retained inthe valve before the system can beplaced in service. After correctingany problems, repeat steps 3 thru18.leakage (air test). The test resultsmust be recorded on the Contractor’sMaterial and Test Certificate.OThe Dry Pipe Valve must bere-opened, inspected, andrepaired or replaced.Step 1. While the Dry Pipe Valve is“set”, and the main drain valve isclosed, note and record the readingon the Water Pressure Gauge (Fig. 5,#13). This is the static pressure.10a. Partially or totally closed watersupply control valves.b. Clogged or frozen water supplymains.c. Serious leakage at water supplyvalves or mains.d. Significant modifications to thewater supply system since theprior test. This may be verifiedwith the local water supply utilityor fire department.Alarm Test ProcedureUnlike wet sprinkler systems, it isnot practical to periodically test theoperation of the alarm connected to adry pipe system by opening theinspectors test valve normally locatedat the most remote position of thesystem piping. The reason being thatthe entire dry system piping would fillwith water, hence necessitating timeconsuming system draining and resetting. If alarms connect to a centralstation or fire department, notify thesignal receiving station prior to and atthe completion of the Alarm Test.The procedure for testing the alarmwithout tripping the system is asfollows:

Trip Test ProcedureDry Pipe Valves should be triptested during warm weather,preferably in the summer to allow allcondensation to drain from thesystem piping before the onset ofcold weather.Before proceeding with any trip testof a Dry Pipe Valve, the water supplyline to the system should bethoroughly flushed. The system maindrain may be used for this purpose. Ifthere is a hydrant on the supply line,it should be used to flush the pipingbefore the main drain is opened.Note: If two-way communication isnot available, the time of openingthe inspector’s test valve may bedetermined by observing when theneedle on the Air Pressure Gaugestarts to move downward.Step 5. When the Dry Pipe Valvetrips, quickly note the time and thereading on the Air Pressure Gauge.Step 6. Allow water to flow into thesystem. Note the time when waterstarts to discharge from theinspector’s test connection.BSNote: Assistance is required toperform some of the operations inthis test procedure.Step 4. While observing the AirPressure Gauge, have the inspector’stest valve opened by an assistant andnote the time.The procedure for conducting a fullflow trip test is as follows:OStep 1. While the dry pipe system is“in service”, open the main drainvalve (subassembly Fig. 5, #1) slowlyuntil it is wide open. Then check tomake sure that a full steady flow ofwater is discharging from the maindrain pipe. Allow the water to flow atfull pressure long enough to clear thewater supply pipe of anyaccumulation of scale or foreignmaterial.Step 2. Slowly close the main drainvalve. The Dry Pipe Valve is nowready for Trip Testing.Step 3. Note and record the readingson the Air Pressure Gauge and onthe Water Pressure Gauge.Caution: Before proceeding, beprepared to record the followingperson and organization performingthe test.The organization performing thetest should maintain separate recordswhich show the test results including:initial air and water pressures, triptime, trip air pressure, water deliverytime to the inspector’s test connectionand operating condition of the DryPipe Valve and accessory devices.Note: If there is an Acceleratorattached to the Dry Pipe Valve,initial acceptance testing mustinclude two trip tests, one with andone without the Accelerator inservice.TEStep 3. Open the Alarm Line DrainValve (subassembly Fig. 5, #7) anddrain the water from the alarm line.When drainage is complete, close theAlarm Line Drain Valve.a. Air Pressure reading when theDry Pipe Valve trips.b. The time when the inspector’stest valve is opened.c. The elapsed time, in seconds,when the Dry Pipe Valve trips.d. The elapsed time, in seconds,when water begins flowing fromthe inspector’s test connection.LEStep 2. Close the Alarm Test Valveto silence the sounding device.information; a watch with a sweepsecond hand will be required.OStep 1. Open the Alarm Test Valve(subassembly Fig. 5, #6). This willpressurize the alarm line, cause thepressure alarm switch (if any) toactivate and the water motor alarm (ifany) to sound.Step 7. Keep the Inspector’s TestValve open until clean water isflowing at the connection. Terminatethe test by closing the Inspector’sTest Valve and then the main watersupply control valve (OS&Y, PIV orother).Step 8. Compare the data on trippoint pressure, trip time, and waterdelivery time to the inspector’s testconnection, with previous testrecords. If the data differs to anygreat extent from previous records,the cause should be investigated, andthe condition corrected.Step 9. Drain the Dry Pipe System,thoroughly clean the Dry Pipe Valve,replace parts as required, and resetthe valve (see Setting Procedure).Step 10. The Dry Pipe Valve shouldbe provided with an attached tagwhich shows the date when the valvewas tripped and the name of the11Care &MaintenanceThe Central Model AF and ModelAG Dry Pipe Valves and their accessory devices (air maintenance device,accelerator, pressure alarm switch,water motor alarm), should be semiannually examined by experiencedand qualified personnel, to ensureproper operation and trouble-freeservice.Warning: Any systemmaintenance or inspection thatinvolves placing a control valve“out-of-service” will eliminate thefire protection normally providedby the system.Prior to proceeding, be certain tosecure permission from all AuthoritiesHaving Jurisdiction and notify allpersonnel who may be affectedduring system shutdown. A fire watchduring maintenance periods is arecommended precaution.The owner is responsible for theproper operating condition of all fireprotection devices and accessories.The NFPA Standard 25 entitled,“Inspection, Testing and Maintenanceof Water-Based Fire ProtectionSystems”, contains guidelines andminimum maintenance requirements.Furthermore, the Authority HavingJurisdiction may have additionalregulations and requirements formaintenance, testing and inspectionthat must be obeyed.

Priming Water Level(Refer to Figure 5) Loss of primingwater, either through evaporation intothe system or by seepage past the airseat ring, could result in operation ofthe Dry Pipe Valve. Conversely,accumulation of additional water fromcondensation in the system couldraise the primi

fire sprinkler systems with a maxi-mum working pressure of 175 psi. Manufactured by: Central Sprinkler Company 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 The Central Dry Pipe Valve is a dry pipe sprinkler system water-supply control valve that makes possible the installation of sprinkler systems in buildings subject to freezing .

Related Documents:

AIR CONTROL REQUIREMENTS FOR DRY CLEANERS WITH EXISTING MACHINES ARE BASED ON PERC PURCHASES Small Area Dry Cleaners Large Area Dry Cleaners Major Dry Cleaner Dry-to-Dry Machines ONLY: Less than 140 gal/yr OR Transfer Machines ONLY: Less Than 200 gal/yr OR Transfer AND Dry-to-Dry Machines: Less Than 140 gal/yr* Dry-to-Dry Machines ONLY:

(MMA)** Ennis - Flint 04/ Richmond, VA 4161 Piedmont Pkwy Greensboro, NC 27410 www.ennisflint americas.com 800-331-8118 336-475-7900 fax Paint Paint Paint High Build Paint (HB) High Build Paint (HB) Thermoplastic Thermoplastic Dry Dry Dry Dry Dry Dry Dry N/A N/A N/A N/A N/A N/A N/A Y W B W Y W Y TRAF87052 TRAF87051 TRAF87041 TRAF87061 TRAF87062 .File Size: 218KB

Class- VI-CBSE-Mathematics Knowing Our Numbers Practice more on Knowing Our Numbers Page - 4 www.embibe.com Total tickets sold ̅ ̅ ̅̅̅7̅̅,707̅̅̅̅̅ ̅ Therefore, 7,707 tickets were sold on all the four days. 2. Shekhar is a famous cricket player. He has so far scored 6980 runs in test matches.

This research aims to develop an innovative electrical discharge machining (EDM) process, i.e., dry and near-dry EDM milling, as the finishing technology for rapid and precision die, mold and tool fabrication. Applied as the post-process of direct metal deposition (DMD), the dry and near-dry EDM milling processes are targeted to finish the

HOOVER H-Wash & Dry 500 [pdf] Instruction Manual H-Wash Dry 500 HOOVER H-Wash & Dry 500 [pdf] User Guide HOOVER, H-Wash, Dry, 500, Wash Dry Related Posts Join the Conversation 1. 2. 2 Comments 1. ISABEL RODRIGUEZ says: June 25, 2021 at 5:35 pm I just bought a Hoover washer-dryer and unfortunately in the manuals it brings and on the website I .

Dry eye is problem of tear quantity, quality or stability, and a process of inflammation is often associated with dry eye. Factors associated with dry eye Diabetes mellitus, autoimmune disease, hepatitis C, HIV infection, radiation therapy and bone marrow transplantation have all been associated with dry eye disease. Medications and dry eye .

5 October: after one dry sunny day, 9 newts 7 October: after three dry sunny days, 6 newts 8 October: light rain all day, 59 newts 10 October: dry sunny day but heavy frost last night, much cooler, 6 newts 11 October: after a second dry sunny day, but also very cool, 5 newts 15 October: after a string of dry days, warming up, 5 newts

fluctuate between the wet months of December to April and dry months of May to October. Sea-sonal precipitation and a rainshadow caused by high mountains results in a dry side of Fiji that once contained large expanses of tropical dry forest. Fiji’s tropical dry forests probably