HAT832THREE POWER ATS CONTROLLER(DUAL-ATS)USER MANUALSMARTGEN (ZHENGZHOU) TECHNOLOGY CO., LTD.

HAT832 Three Power ATS Controller (Dual-ATS) User ManualCONTENTCONTENT .31 OVERVIEW .52 PERFORMANCE AND CHARACTERISTICS .63 SPECIFICATION .84 MEASURE AND DISPLAY DATA .95 OPERATION.105.1 INDICATORS .105.2 KEY FUNCTION DESCRIPTION . 116 LCD DISPLAY .126.1 MAIN SCREEN .126.2 STATUS DESCRIPTION .136.1 MAIN MENU .187 START/STOP OPERATION .197.1 MANUAL START/STOP.197.2 AUTO START/STOP .218 PARAMETERS CONFIGURATION.268.1 ILLUSTRATION .268.2 PARAMETERS TABLE .268.3 DIGITAL INPUT/OUTPUT FUNCTION DESCRIPTION .368.4 DEFINITE TIME DELAY AND INVERSE DEFINITE MINIMUM TIME SETTING .439 HISTORICAL RECORDS .4410 BLACK BOX RECORDS .4511 SWITCH OPERATION .4611.1 MANUAL OPERATION .4611.2 AUTOMATIC OPERATION .4712 ATS POWER SUPPLY .4813 NEL CONTROL .4913.1 ILLUSTRATION .4913.2 AUTO OPERATION .4913.3 MANUAL OPERATION .4914 COMMUNICATION CONFIGURATION .5015 TERMINALS .5116 TYPICAL WIRING DIAGRAM .55HAT832 Three Power ATS Controller (Dual-ATS)2018-08-21Version1.0Page 3 of 61

HAT832 Three Power ATS Controller (Dual-ATS) User Manual17 INSTALLATION .6018 TROUBLE SHOOTING .61HAT832 Three Power ATS Controller (Dual-ATS)2018-08-21Version1.0Page 4 of 61

HAT832 Three Power ATS Controller (Dual-ATS) User Manual1 OVERVIEWHAT832 Three Power ATS controller (Dual-ATS) is intelligent tri-supply module with configurablefunction, automatic measurement, LCD display, and digital communication. It combines digitization,intelligence and networking. Automatic measurement and control can reduce incorrect operation,which is an ideal option for ATS.The powerful Microprocessor contained within the unit allows for precision voltage (3-way 3-phase)measuring and make accurate judgment and the corresponding volt free digital output port will activewhen there is over/under voltage, over/under frequency, loss of phase, phase sequence wrong andother abnormal condition occurs. It has compact structure, advanced circuits, simple wiring and highreliability, and can be widely used in electric device and automatic control system of electric power,telecommunications, petroleum, coal, metallurgy, railways, municipal administration, intelligentbuilding, etc.HAT832 Three Power ATS Controller (Dual-ATS)2018-08-21Version1.0Page 5 of 61

HAT832 Three Power ATS Controller (Dual-ATS) User Manual2 PERFORMANCE AND CHARACTERISTICS——System type can set as: Mains-Gen-Mains, Gen-Mains-Mains, Mains-Mains-Mains,Gen-Gen-Mains, Mains-Gen-Gen, Gen-Mains-Gen, and Mains-Mains-Gen;——4.3 inchs solid color 240x128 LCD display with white backlight, multilingual interface(including English, Simplified Chinese, Other), push-button operation;——Collect and display 3-way 3-phase voltage, frequency and phase sequence;——Collect and display load active power, reactive power, apparent power, power factor andcurrent;——S1/S2/S3 separated over current warning/ trip alarm;——NEL (Non-essential Load) trip function;——Display S1/S2/S3 total kW energy, total kvar energy, total close times;——Display continuous power supply time and S1/S2/S3 total power supply time;——For Stored-Energy type ATS, its close relay will active after the PF Input is active;——Over/under voltage, over/under frequency, over current, loss of phase, phase sequencewrong protection;——Automatic/Manual mode. In manual mode, can force the switch to close or open;——All parameters can be set on site. Passwords authentication ensures authorized staffoperation only;——The genset can be manual test on site to achieve start/stop operation;——Automatic re-closing;——Closing output signal can be set as on intervals or as continuous output;——Applicable for 3 isolated neutral line;——Real-time clock (RTC); event log function (event log can record 200 items circularly);——Black box function, which can cycle record 5 pieces of log and each log contains 60 groups ofdata including breaker state detailed data of 50s before and 10s after switchover;——Scheduled routing run & scheduled not run (can be set as start genset once aday/week/month whether with load or not);——Can control two generators to work as cycle run mode, master run mode and balance runmode;——Widely DC power supply range allows the controller can bear instantaneous 80V DC input;——Large terminal space allows the controller can bear maximum 625V AC voltage input;——With Dual-RS485 isolated communication interface. With "remote controlling, remotemeasuring, remote communication, remote regulating" function by the ModBus-RTUcommunication protocol. Can remote start/stop the genset and remote control the breaker toclose or open;——Suitable for various AC systems (3-phase 4-wire, 3-phase 3-wire, single-phase 2-wire, andHAT832 Three Power ATS Controller (Dual-ATS)2018-08-21Version1.0Page 6 of 61

HAT832 Three Power ATS Controller (Dual-ATS) User Manual2-phase 3-wire);——Modular design, self extinguishing ABS plastic shell, pluggable terminal, built-in mounting,compact structure with easy installation.HAT832 Three Power ATS Controller (Dual-ATS)2018-08-21Version1.0Page 7 of 61

HAT832 Three Power ATS Controller (Dual-ATS) User Manual3 SPECIFICATIONTable 2 – Performance ParametersItemsContents1. DC8.0V 35.0V, continuous power supplyOperating VoltagePower Consumption2. AC(90 305)V power supply A1N1/A2N2/A3N3 7W(Standby mode: 2W)AC systemAC Voltage InputRated FrequencyProgrammble Output 1 6Relay CapacityProgrammble Output 7 12Relay CapacityATS Power Supply RelayCapacityDigital InputCommunication3P4W (L-L)(80 530)V3P3W (L-L)(80 625)V (DC supply)1P2W (L-N)(50 305)V2P3W (A-B)(80 530)V50/60Hz16A AC250V Volts free output8A AC250V Volts free output16A AC250V Volts free outputGND (B-) connect is active.1.Dual-RS485 isolated interface, MODBUS Protocol2.D-type USB portCase Dimensions260mmx180mmx54mmPanel Cutout242mmx161mmWorking ConditionsTemperature: (-25 70) C;Relative Humidity: (20 93)%RHStorage ConditionTemperature: (-25 70) CProtection LevelIP65: when water proof gasket ring inserted between panel and housing.Apply AC1.5kV voltage between high voltage terminal and low voltageInsulation Strengthterminal;The leakage current is not more than 3mA within 1min.Weight1.2kgHAT832 Three Power ATS Controller (Dual-ATS)2018-08-21Version1.0Page 8 of 61

HAT832 Three Power ATS Controller (Dual-ATS) User Manual4 MEASURE AND DISPLAY DATATable 3 – Display ParametersNo.Measure & Display Data Items1S1/S2/S3 Power Phase Voltage2S1/S2/S3 Power Line Voltage3S1/S2/S3 Power Phase4S1/S2/S3 Power Frequency5Load 3-Phase Current6Load 3-Phase Active Power kW7Load Total Active Power kW8Load 3-Phase Reactive Power kvar9Load Total Reactive Power kvar10Load 3-Phase Apparent Power kVA11Load Total Apparent Power kVA12Load 3-Phase Power Factor PF13Load Average Power Factor PF14Continuous Power Supply Time (Currently)15Continuous Power Supply Time (Last Time)16S1 Total Power Supply Time17S2 Total Power Supply Time18S3 Total Power Supply Time19S1 Total kW Energy kWh20S2 Total kW Energy kWh21S3 Total kW Energy kWh22S1 Total kvar Energy kvarh23S2 Total kvar Energy kvarh24S3 Total kvar Energy kvarh25QS1 Total Close Times26QS2 Total Close Times27QS3 Total Close Times28QS12 Total Close Times29Input/Output Port Status30Real Time Clock31Alarm Status32Communication StatusHAT832 Three Power ATS Controller (Dual-ATS)2018-08-21Version1.0Page 9 of 61

HAT832 Three Power ATS Controller (Dual-ATS) User Manual5 OPERATIONFig.1 – Penal Indication Drawing5.1 INDICATORSTable 4 – Indicators DescriptionIndicator TypeAlarmDescriptionSlow flashing (1time per sec) when warn alarm occurs.Fast flashing (5 times per sec) when fault alarm occurs.ManLight on when the module is in Manual mode.AutoLight on when the module is in Auto mode.Alarm MuteLight on when alarm mute.IOOOIOOOIOOOGensetIlluminated: QS1, QS2closed, S1 supply power for load.Flashing: status switchingIlluminated: QS2, QS12 closed, S2 supply power for load.Flashing: status switchingIlluminated: QS3 closed, S3 supply power for load.Flashing: status switchingIlluminated: QS1, QS2, QS12, QS3 all open, offload.Flashing: status switchingLight on when the Start signal is be initiated.HAT832 Three Power ATS Controller (Dual-ATS)2018-08-21Version1.0Page 10 of 61

HAT832 Three Power ATS Controller (Dual-ATS) User Manual5.2 KEY FUNCTION DESCRIPTIONTable 5 – Buttons Function DescriptionIconButtonsIOOOIOOOIOOOTestFunction DescriptionActive in Manual mode.QS1, QS12 close and S1 supply after pressing this key.Active in Manual mode.QS2, QS12 close and S2 supply after pressing this key.Active in Manual mode.QS3 close and S3 supply after pressing this key.Active in Manual mode.Offload after pressing this key.Press this key to enter to genset manual start/stop operation interface.Alarm MutePress this key to enter into alarm page and mute the alarm.Man/AutoManual mode and Auto mode switching.Alarm ResetPressing this key can reset fault alarm.When setting parameters, press the key to return back.Return/HomepageIn main screen, press the key to return the first screen; in other screen,press the key to return to main screen.In main screen, press the key to enter to menu.Set/ConfirmIn menu screen, press this key can move cursor and confirm settinginformation.In main screen, press the key to scroll up screen.UpIn menu interface, press this key to up cursor or increase value insetting menu.In main screen, press the key to scroll down screen.In menu interface, press this key to down cursor or decrease value inDown/Lamp Testsetting menu.In main screen, press the key for seconds to enter lamp test mode,LCD backlit and all LED lamps are lit and LCD screen display black.HAT832 Three Power ATS Controller (Dual-ATS)2018-08-21Version1.0Page 11 of 61

HAT832 Three Power ATS Controller (Dual-ATS) User Manual6 LCD DISPLAY6.1 MAIN SCREENTable 6 – Screen DisplayItemsDisplay ContentsS1 status, S2 status, S3 status, switch status, generator start status;Supply system diagram, QS1 is side switch for S1, QS2 is side switch for S2, QS12 isside switch for S1 and S2, QS3 is side switch for S3;HomepageS1/S2/S3 voltage and frequency;S1/S2/S3 priority switch;Total active power, maximum loading current.AutoTrans/Restore status.S1S2S3S1 line voltage, phase voltage and frequency, phase angle;S2 line voltage, phase voltage and frequency, phase angle;S3 line voltage, phase voltage and frequency, phase angle.3-phase current (I1,I2,I3);LoadActive Power kW (Sum of P1, P2, P3);3-Phase Reactive Power (sum of Q1,Q2,Q3);3-Phase Apparent Power kVA(sum of S1,S2,S3);3-Phase Average Power Factor PF(average of PF1,PF2,PF3).CUM.3-Phase total active energy and total reactive energy.TIMECurrent continuous power supply time;Last time continuous power supply time.CUM.S1 total power supply time;S2 total power supply time;S3 total power supply time.QS1 Total Close Times;QFQS2 Total Close Times;QS12 Total Close Times;QS3 Total Close Times;I/OProgrammable digital input status and auxiliary status;Programmable digital output status.Comm.RS485-1 Comm. status and baud rate;HAT832 Three Power ATS Controller (Dual-ATS)2018-08-21Version1.0Page 12 of 61

HAT832 Three Power ATS Controller (Dual-ATS) User ManualItemsDisplay ContentsRS485-2 Comm. status and baud rate;USB Comm. status.AlarmsPresent alarm informations (warn alarm and fault alarm)Alarm status/working status;StatusReal-time clock;Status line is showed below in every main screen pages.6.2 STATUS DESCRIPTIONTable 7 – S1 Voltage StatusNo.ItemDescription1S1 AvailableS1 normal delay2S1 UnavailableS1 abnormal delay3S1 AvailablePower supply voltage is within the setting range4S1 BlackoutVoltage is 05S1 Over VoltVoltage is higher than the set value6S1 Under VoltVoltage has fallen below the set value7S1 Over FreqFrequency is higher than the set value8S1 Under FreqFrequency has fallen below the set value9S1 Loss of PhaseLoss of any phase of A, B and C10S1 Phase SeqWrongA-B-C phase sequence is wrongTable 8 – S2 Voltage StatusNo.ItemDescription1S2 AvailableS2 normal delay.2S2 UnavailableS2 abnormal delay.3S2 AvailablePower supply voltage is within the setting range.4S2 BlackoutVoltage is 0.5S2 Over VoltVoltage is higher than the set value.6S2 Under VoltVoltage has fallen below the set value.7S2 Over FreqFrequency is higher than the set value.8S2 Under FreqFrequency has fallen below the set value.9S2 Loss of PhaseLoss of any phase of A, B and C.10S2 Phase SeqWrongA-B-C phase sequence is wrong.HAT832 Three Power ATS Controller (Dual-ATS)2018-08-21Version1.0Page 13 of 61

HAT832 Three Power ATS Controller (Dual-ATS) User ManualTable 9 – S3 Voltage StatusNo.ItemDescription1S3 AvailableS3 normal delay2S3 UnavailableS3 abnormal delay3S3 AvailablePower supply voltage is within the setting range.4S3 BlackoutVoltage is 0.5S3 Over VoltVoltage is higher than the set value.6S3 Under VoltVoltage has fallen below the set value.7S3 Over FreqFrequency is higher than the set value.8S3 Under FreqFrequency has fallen below the set value.9S3 Loss of PhaseLoss of any phase of A, B and C.10S3 Phase SeqWrongA-B-C phase sequence is wrong.Table 10 – Genset StatusNo.ItemDescription1Start DelayDelay time before genset start2Return DelayDelay time before genset stop3Scheduled Not WorkWhen scheduled not run is active, its duration time will be displayed.4Scheduled WorkWhen scheduled run is active, its duration time will be displayed.5S1 Cycle RunS1 cycle run countdown will be terminated when cycle start is active.6S2 Cycle RunS2 cycle run countdown will be terminated when cycle start is active.7S3 Cycle RunS3 cycle run countdown will be terminated when cycle start is active.8S1 Genset WorkingActive only when system has 2 gensets and S1 generating.9S2 Genset WorkingActive only when system has 2 gensets and S2 generating.10S3 Genset WorkingActive only when system has 2 gensets and S3 generating.11Genset WorkingGenset start signal output.12Genset StandbyThere is no start genset signal output.Table 11 – Switch StatusNo.123ItemReady to TransferQS1 ClosingQS1 OpeningDescriptionSwitch transfer begins.QS1 closing delay is in progress.QS1 opening delay is in progress.4QS2 ClosingQS2 closing delay is in progress.5QS2 OpeningQS2 opening delay is in progress.6QS12 ClosingQS12 closing delay is in progress.7QS12 OpeningQS12 opening delay is in progress.8QS3 ClosingQS3 closing delay is in progress.9QS3 OpeningQS3 opening delay is in progress.HAT832 Three Power ATS Controller (Dual-ATS)2018-08-21Version1.0Page 14 of 61

No.Item10Transfer RestHAT832 Three Power ATS Controller (Dual-ATS) User ManualDescriptionInterval time between switch transferIf ―Closing Again Delay‖ is not 0, when the QS1 ―Fail to open‖ condition11Closing QS1 Againoccurs, it’s the delay time before the close relay is active for the secondtime.If ―Opening Again Delay‖ is not 0, when the QS1 ―Fail to close‖12Opening QS1 Againcondition occurs, it’s the delay time before the close relay is active forthe second time.If ―Closing Again Delay‖ is not 0, when the QS2 ―Fail to open‖ condition13Closing QS2 Againoccurs, it’s the delay time before the close relay is active for the secondtime.If ―Opening Again Delay‖ is not 0, when the QS2 ―Fail to close‖14Opening QS2 Againcondition occurs, it’s the delay time before the close relay is active forthe second time.If ―Closing Again Delay‖ is not 0, when the QS12 ―Fail to open‖15Closing QS12 Againcondition occurs, it’s the delay time before the close relay is active forthe second time.If ―Opening Again Delay‖ is not 0, when the QS12 ―Fail to close‖16Opening QS12 Againcondition occurs, it’s the delay time before the close relay is active forthe second time.If ―Closing Again Delay‖ is not 0, when the QS3 ―Fail to open‖ condition17Closing QS3 Againoccurs, it’s the delay time before the close relay is active for the secondtime.If ―Opening Again Delay‖ is not 0, when the QS3 ―Fail to close‖18Opening QS3 Againcondition occurs, it’s the delay time before the close relay is active forthe second time.19Waiting QS1 PF20Waiting QS2 PF21Waiting QS12 PF22Waiting QS3 PFBefore QS1 is closed, it’s the delay time to confirm ―QS1 PF Input‖signal is active.Before QS2 is closed, it’s the delay time to confirm ―QS2 PF Input‖signal is active.Before QS12 is closed, it’s the delay time to confirm ―QS2 PF Input‖signal is active.Before QS3 is closed, it’s the delay time to confirm ―QS3 PF Input‖signal is active.23Elevator DelayElevator control output before ATS transfer.24S1 On LoadQS1, QS2 were already closed and S1 is taking load.25S2 On LoadQS2, QS12 were already closed and S2 is taking load.26S3 On LoadQS3 was already closed and S3 is taking load.27OffloadSwitch was already opened and load is disconnected.HAT832 Three Power ATS Controller (Dual-ATS)2018-08-21Version1.0Page 15 of 61

HAT832 Three Power ATS Controller (Dual-ATS) User ManualWarning alarms are active when controller detects the alarm signals, and alarm indicator will flashslowly (1time per sec). When alarm is reset, indicator is extinguished, which means warn alarms arenot latched.Table 12 – Warning AlarmsNo.123ItemS1 Over CurrentWarnS2 Over CurrentWarnS3 Over CurrentWarn4Forced Open Warn5Battery Under Volt6Battery Over VoltDescriptionWhen the S1 current has exceeded the pre-set value and the actionselect ―Warn‖, it will initiate a warning alarm.When the S2 current has exceeded the pre-set value and the actionselect ―Warn‖, it will initiate a warning alarm.When the S3 current has exceeded the pre-set value and the actionselect ―Warn‖, it will initiate a warning alarm.When the input is active and the action (cut off non-fire supply) select―Warn‖, it will initiate a warning alarm.When the battery voltage has fallen below the pre-set value, it willinitiate a warning alarm.When the battery voltage has exceeded the pre-set value, it will initiatea warning alarm.Fault alarms are active when controller detects the alarm signals. Alarm indicator will flash rapidly(5 times per sec) and the alarm will last until it was removed manually. Fault alarms are latched.Table 13 – Fault AalrmsNo.ItemDescription1QS1 Failed to CloseQS1 fail to close.2QS1 Failed to OpenQS1 fail to open.3QS2 Failed to CloseQS2 fail to close.4QS2 Failed to OpenQS2 fail to open.5QS12 Failed to CloseQS12 fail to close.6QS12 Failed to OpenQS12 fail to open.7QS3 Failed to CloseQS3 fail to close.8QS3 Failed to OpenQS3 fail to open.9S1 Over Current Trip10S2 Over Current Trip11S3 Over Current Trip12Forced Open Fault13S1 Genset FaultWhen the S1 is taking load and its current has exceeded the pre-setvalue, and the action select ―Trip‖, it will initiate a trip alarm.When the S2 is taking load and its current has exceeded the pre-setvalue and the action select ―Trip‖, it will initiate a trip alarm.When the S3 is taking load and its current has exceeded the pre-setvalue and the action select ―Trip‖, it will initiate a trip alarm.When the input is active and the action (cut off non-fire supply) select―Fault‖, it will initiate a fault alarm.Only when system has 2 gensets and S1 generating, S1 fail to start.HAT832 Three Power ATS Controller (Dual-ATS)2018-08-21Version1.0Page 16 of 61

No.ItemHAT832 Three Power ATS Controller (Dual-ATS) User ManualDescription14S2 Genset FaultOnly when system has 2 gensets and S2 generating, S2 fail to start.15S3 Genset FaultOnly when system has 2 gensets and S3 generating, S3 fail to start.16Switch Trip AlarmIt will initiate a fault alarm, when the input is active.The indication information will continuously display for 2s after it is active.Table 14 – Indication InformationNo.1ItemDescriptionPlease Reset TheWhen there is fault alarm occurs, the indication will be displayed whenAlarmchange the genset mode to Auto Mode manually.2S1 Already Closed.3S2 Already Closed.4S3 Already Closed.5Already OpennedAfter S1 was already closed, the indication will be displayed when ―S1close (IOO)‖ button is pressed.After S2 was already closed, the indication will be displayed when ―S2close (OIO)‖ button is pressed.After S3 was already closed, the indication will be displayed when ―S3close (OOI)‖ button is pressed.While in breaker opening status, the indication will be displayed when―Open (OOO)‖ button is pressed.The information displays when panel lock is active and keys are6Panel Lockedpressed (Manual/Auto, Alarm Reset, Alarm Mute, IOO, OIO, OOI,OOO and Genset keys).After pressed close S1(IOO), S2(OIO), and S3(OOI), the indication will7AC System Abnormalbe displayed when power supply is fault and AC system is disable totransfer.Table 15 – Other Status InformationNo.ItemDescription1Start InhibitGenset start Inhibit is active.2S1 Load InhibitS1 Load Inhibit input is active.3S2 Load InhibitS2 Load Inhibit input is active.4S3 Load InhibitS3 Load Inhibit input is active.5NEL 1 TripNEL1 off load signal is output.6NEL2 TripNEL2 off load signal is output.7NEL3 TripNEL3 off load signal is output.8Remote Gen On LoadRemote start (on load) signal is active.9Remote Gen Off LoadRemote start (off load) signal is active.10Gen Start Mains NGStart genset when mains is abnormal.11Gen Start MasterStart when the gens supply and switching to highest priority.HAT832 Three Power ATS Controller (Dual-ATS)2018-08-21Version1.0Page 17 of 61

HAT832 Three Power ATS Controller (Dual-ATS) User ManualNo.ItemDescription12Auto ModeCurrent mode is Auto mode.13Manual ModeCurrent mode is Manual mode.6.3 MAIN MENUIn main screen, presskey will enter into the menu interface.1.Configuration2.Data Calibration3. Historical RecordsPress Up/Down key to choose parameters (the current line was4. Black Box Recordshighlighted with black) and then press Confirm key to enter into the5. AutoCharge/Recovercorresponding display screen.6. Language7. AboutNOTE:Default password is 01234, user can change it in case of others change the parameters setting.Please clearly remember the password after changing. If you forget it, please contact SmartGen services.NOTE:Data Calibration is for factory use only and correct passwords must be input before entered.HAT832 Three Power ATS Controller (Dual-ATS)2018-08-21Version1.0Page 18 of 61

HAT832 Three Power ATS Controller (Dual-ATS) User Manual7 GENSET OPERATION7.1 MANUAL START/STOP7.1.1 PANEL START/STOPIn the main screen, according to different system types, presskey to enter to differentstart/stop menu screens.7.1.1.1 SYSTEM TYPE ―S1 GEN S2 GEN S3 MAINS‖When system type is ―S1 Gen S2 Gen S3 Mains‖, manual start/stop interface is as below:Manual Start GensetReturnS1 Genset StopS1 Genset StartPress ―Up/Down‖ key to choose parameters (the current line washighlighted with black) and then press ―Confirm‖ key to confirm.S2 Genset StopS2 Genset StartS1 Genset Stop:Disconnect the start signal of S1 genset, i.e. stop the running S1 genset.S1 Genset Start:Output the start signal of S1, i.e. start the S1 genset.S2 Genset Stop:Disconnect the start signal of S2 genset, i.e. stop the running S2 genset.S2 Genset Start:Output the start signal of S2, i.e. start the S2 genset.7.1.1.2 SYSTEM TYPE ―S1 GEN S2 MAINS S3 GEN‖When system is ―S1 Gen S2 Mains S3 Gen‖, manual start/stop menu interface is as below:Manual Start GensetReturnS1 Genset StopS1 Genset StartPress ―Up/Down‖ key to choose parameters (the current line washighlighted with black) and then press ―Confirm‖ key to confirm.S3 Genset StopS3 Genset StartS1 Genset Stop:Disconnect the start signal of S1 genset, i.e. stop the running S1 genset.S1 Genset Start:Output the start signal of S1, i.e. start the S1 genset.S3 Genset Stop:Disconnect the start signal of S3 genset, i.e. stop the running S3 genset.S3 Genset Start:Output the start signal of S3, i.e. start the S3 genset.HAT832 Three Power ATS Controller (Dual-ATS)2018-08-21Version1.0Page 19 of 61

HAT832 Three Power ATS Controller (Dual-ATS) User Manual7.1.1.3 SYSTEM TYPE ―S1 MAINS S2 GEN S3 GEN‖When system is ―S1 Mains S2 Gen S3 Gen‖, manual start/stop menu interface is as below:Manual Start GensetReturnS2 Genset StopS2 Genset StartPress ―Up/Down‖ key to choose parameters (the current line washighlighted with black) and then press ―Confirm‖ key to confirm.S3 Genset StopS3 Genset StartS2 Genset Stop:Disconnect the start signal of S2 genset, i.e. stop the running S2 genset.S2 Genset Start:Output the start signal of S2, i.e. start the S2 genset.S3 Genset Stop:Disconnect the start signal of S3 genset, i.e. stop the running S3 genset.S3 Genset Start:Output the start signal of S3, i.e. start the S3 genset.7.1.1.4 OTHER SYSTEM TYPEWhen system is ―S1 Mains S2 Gen S3 Mains‖, ―S1 Gen S2 Mains S3 Mains‖, ―S1 Mains S2 MainsS3 Gen‖, manual start/stop menu interface is as below:Manual Start GensetReturnGenset StopPress ―Up/Down‖ key to choose parameters (the current line washighlighted with black) and then press ―Confirm‖ key to confirm.Genset StartGenset Stop:Disconnect the start signal of genset, i.e. stop the running genset.Genset Start:Output the start signal of genset, i.e. start the genset.7.1.2 REMOTE START/STOPSend remote start/stop signals using MODBUS protocol via RS485 port.Remote Stop:Disconnect the start signal, i.e. stop the running genset.Remote Start:Output the start signal, i.e. start the genset.HAT832 Three Power ATS Controller (Dual-ATS)2018-08-21Version1.0Page 20 of 61

HAT832 Three Power ATS Controller (Dual-ATS) User Manual7.2 AUTO START/STOP7.2.1 START/STOP FOR ONE GENSETWhen system type is ―S1 Gen S2 Mains S3 Mains‖, ―S1 Mains S2 Gen S3 Mains‖, or ―S1 MainsS2 Mains S3 Gen‖, configure input port as ―Remote Start On Load‖ or ―Remote Start Off Load‖, bothcould not be set simultaneously.Remote Start on Load:When the input is active, genset close relay will active after genset isnormal; when the input inactive, genset will stop automatically.Remote Start off Load:When the input is active, mains close relay will active after mains is normal;when the input inactive, genset will stop automatically.Gen Start Mains NG: If one of the mains is the highest priority of the system, the genset is thesecondary priority, when mains fault, genset starts output; or both two ways of mains fault, gensetstarts output.Gen Start Master: If genset is the highest priority of the system, genset starts output; genset isavalibale and ―Auto Charge/Recover‖

21 S3 Total kW Energy kWh 22 S1 Total kvar Energy kvarh 23 S2 Total kvar Energy kvarh 24 S3 Total kvar Energy kvarh 25 QS1 Total Close Times 26 QS2 Total Close Times 27 QS3 Total Close Times 28 QS12 Total Close Times 29 Input/Output Port Status 30 Real Time Clock 31 Alarm Status 32 Communication Status

Related Documents:

Morphy Richards Fastbake Breadmaker 48280 User Manual Honda GCV160 User Manual Canon Powershot A95 User Manual HP Pocket PC IPAQ 3650 User Manual Navman FISH 4200 User Manual - Instruction Guide Jensen VM9021TS Multimedia Receiver User Manual Sanyo SCP-3100 User Manual Honda GC160 User Manual Canon AE-1 Camera User Manual Spektrum DX7 User Manual

Ademco Passpoint Plus User Manual Morphy Richards Fastbake Breadmaker 48280 User Manual Honda GCV160 User Manual Canon Powershot A95 User Manual HP Pocket PC IPAQ 3650 User Manual Navman FISH 4200 User Manual - Instruction Guide Jensen VM9021TS Multimedia Receiver User Manual Sanyo SCP-3100 User Manual Honda GC160 User Manual Canon AE-1 Camera .

E-816 DLL Manual, PZ120E E-621.CR User Manual, PZ160E E-816 LabVIEW Software Manual, PZ121E E-621.SR, .LR User Manual, PZ115E Analog GCS LabVIEW Software Manual, PZ181E E-625.CR User Manual, PZ166E PIMikromove User Manual, SM148E E-625.SR, .LR User Manual, PZ167E E-665 User Manual, PZ127E E-801 User Manual

MSC CAN Isolated, maximum communication length 250m; applying Belden 9841 cable or the equivalence; EMC/CE Certification EN 61326-1:2013 Vibration Test 5 - 8 Hz: 7.5 mm 8 - 500 Hz: 2 g IEC 60068-2-6 Shock Test 50g, 11ms, half-sine, complete shock test from three di

Isolated, maximum communication length 250m; applying Belden 9841 cable or the equivalence EMC/CE Certification EN 61326-1:2013 Vibration Test 5 - 8 Hz: 7.5 mm 8 - 500 Hz: 2 g IEC 60068-2-6 Shock Test 50g, 11ms, half-sine, complete shock test from three directions,

Nov 11, 2010 · User Story 1 User Story 2 User Story 4 User Story 5 User Story 5 (Cont.) User Story 3 User Story 6 User Story 7 rint 1 User Story 8 2 User Story 1 User Story 2 User Story 4 . Process Template Light on security artifacts/documentati on. OWASP Making SDL-Agile Manageable Toolin

manual, icom 718 user manual, icom 7000 user manual, icom 705 user manual, icom bc-160 user manual, icom ic-41pro user manual Your Icom radio generates RF electromagnetic energy . manual contains important operating instructions for the IC-F14/ . FA-SC56VS: 150–162 MHz. EvaluationIcom IC-R30 Handheld Broadband Receiver, Easy to.

Animal nutrition has pronounced direct impact not only on animal health but also indirectly through animal products on human health and through excreta on the environment. Due to increased awareness and concerns about animal health, due to increased incidence and severity of chronic non-communicable diseases in developed world that are linked to nutritional quality of (animal) food and due to .