Technical and Specification InformationGB162 Australia / New ZealandWorcester GB162 & GB162 CascadeWall mounted gas-fired condensing boiler series

2 Technical & Specification Information – GB162 & GB162 CascadeBosch and you, making a ntentsGB162 IntroductionThe features of the Worcester GB162 condensing boiler seriesTechnical dataInside storyInstalling the Worcester GB162 seriesInstallation requirementsSingle boiler installationPump groupWiring diagramHorizontal and vertical flue terminal positioningWorcester GB162 boiler series fluing optionsEnergy management controlsBosch CSM920 boiler managementCascade – quick and simple to installCascade technical informationWorcester GB162 boiler series and accessoriesNotes

Technical & Specification Information – GB162 & GB162 Cascade 3The Worcester GB162 is partof a market leading range ofenergy-saving condensingwall mounted gas-fired boilers.The GB162 is an extremely versatile and compact wallhung condensing boiler that can be installed on its ownor as part of a multi-boiler ‘cascade’ system. The boileris available with individual outputs of 65 and 100kW;outputs of up to 800kW can be achieved when multipleunits are connected as part of a cascade installation.Precise energy managementEach boiler in the GB162 series can automaticallymodulate its output down to 25% or less in order toprecisely match the demand for heat. This llseasonal efficiency.The GB162 is fully compatible with the EnergyManagement System (EMS) modular controls platform.This optimises performance by keeping the boiler incondensing mode for as long as possible. EMS alsoprovides comprehensive heating system functionalityand ensures minimal energy usage at all times.High efficiency, low emissionsThe GB162 provides efficiencies of up to 110% (NetEfficiency) with ultra low class 5 levels of CO2 and NOxemissions.Its compact dimensions make it especially suitable forinstallations where space is restricted, but demand fora modern high output heating solution is high.

4 Technical & Specification Information – GB162 & GB162 CascadeThe Worcester GB162 series at a glanceBoilerPart No.Heat output at 50/30ºCHeat output at 80/60ºCNet efficiencyGB162 65kWGB162 100kW7 746 900 8228 747 025 0.5kW94.5kW108.0%110.0%Natural gas33Single boiler installation33Cascade installation33FeaturesBenefitsCondensing technology with up to110% net efficiencySaves fuel compared to standardefficiency boilerModulation to just 20% of total output†Year round efficiency accordingto seasonal demandCascade outputs up to 800kW perframe kitModular package providing energysaving flexibility and maintenancebackupExtremely compact cascades(400kW in just 1m2)Space savingAward winning ALU-Plus heat exchangerAdded durability and low costservicingUltra low emission levelsCleaner combustion and increasedcarbon savingsQuick and easy installationTime savingIndividual lift weight starting at only 70kgAids installationWhisper quietCan be sited near occupied roomsIntuitive user controlsIncreased system functionalityand reduced running costs

Technical & Specification Information – GB162 & GB162 Cascade 5The features of the WorcesterGB162 condensing boiler seriesWorcester boilers are built to withstand heavy use, so only the most reliableand efficient components are used in the design and manufacture of products.The GB162 benefits from the very latest in high efficiency technology with apatented, award winning ALU-Plus heat exchanger.ALU-Plus heat exchangerThe wide channels on the heat exchanger ensure thatThe precision engineered heat exchanger in thethe flow resistance is minimised and this, combinedGB162 is constructed from a cast aluminium silicatewith its fully insulated case, makes the GB162 incrediblycompound which is lightweight, robust and allows forquiet in operation.a rapid transfer of heat. The heat exchanger also usesthe very latest ALU-Plus technology that has beenPlasma-polymerised heat exchangerdeveloped by Bosch Thermotechnology Ltd. to increaseThe surfaces of the heat exchanger’s tubes are treateddurability and optimise heating efficiency.using a patented plasma-polymerisation process whichFins on the outside of the aluminium tubes increaseleaves the surfaces so smooth that the heat exchangerthe exterior surface area so that more hot flue gaseffectively stays clean as no deposits can adhere tocomes into contact with the heat exchanger.them.A spiral channel on the inside of the tube increases theIts extremely high efficiency is maintained and there isinternal surface area, bringing more water in contactno need for mechanical cleaning; the heat exchangerwith the heating surface and ensuring an optimum heatcan be simply flushed through during servicing.transfer.5 year guarantee heat exchangerThe ALU-Plus heat exchanger in the GB162is eligible for a 5 year guarantee. Subjectto terms and conditions.

6 Technical & Specification Information – GB162 & GB162 CascadeThe features of the WorcesterGB162 condensing boiler seriesMulti-boiler cascade systemsThe GB162 cascade kit includes:For larger heat demands, the GB162 can be easily3 Mounting framescombined as part of a multi-boiler cascade system.3 Support legsAny combination of 1 to 8 boilers can be connected3 Main gas pipeeither in-line (TL) or back-to-back (TR). This providesa condensing boiler output of up to 800kW with theability to modulate down to as low as 2.5% of the totaloutput. This ensures that high levels of efficiency can beachieved all year round, even when demand for heat islow. Boilers can be sequenced to come into and out ofoperation when required.3 Flow and return headers(reversible for either left or right orientation)3 Low loss header3 Boiler connecting pipe work3 Full insulation.The picture below shows each boiler fitted with apump group which is available separately. For fulltechnical details on each individual back-to-back (TR)or in-line (TL) GB162 cascade kit please see pages 2934 at the back of this brochure.Cascade controlsNo minimum flow rate requiredWorcester offers a range of advanced modular controlsGB162 boilers do not require a minimum flow rate,designed specifically for the GB162 cascade system.which makes the design and specification of a heatingThe control systems can be easily wired to the boiler.system much simpler, removing the need for additionalThey can be fixed to a cascade frame kit, or can becomponents and reducing installation time. Modulatingfitted onto a wall of the boiler room. For further detailsfans and pump groups mean that output is preciselyon this control system please see page 24-27.matched to the user’s actual requirements at all timesThe modular control system provides a comprehensiveand, as such, electricity consumption can fall by up tosolution for any heating system and is a cost-effective40% in some cases.alternative to installing a Building Management System.Using Worcester accessories in the system will help toA low loss header should be installed to separate theensure that the best solution is provided for optimumboilers from the rest of the heating system. Fittingenergy savings and reduced installation costs.together with the modulating pump group accessoryensures that flow volumes are balanced, efficiency ishigh and hydraulic performance is optimised.

Technical & Specification Information – GB162 & GB162 Cascade 7Worcester GB162 technical dataBoilerHeight without pump groupH x W x D (with pump group)GB162 65kWGB162 100kW980mm980mm1414x520x465mm1414x520x465mmDry weight (without a pump group)70kg70kgBoiler flow and return connectionsG11/2” union nut freefemale thread enclosedG11/2” union nut freefemale thread enclosed80/125mm dia. or100mm/150mm dia.*100mm/150mm dia.R1”R1”Concentric room sealed flueGas connectionCondensate drainØ 24mmØ 24mmNominal heat output at 80/60ºC14.2 - 60.5kW19.0 - 94.5kWNominal heat output at 50/30ºC15.6 - 65.0kW20.5 - 99.5kWSafety valve connectionRated heat inputR1”R1”14.6 - 62.0kW19.3 - 96.5kWNet efficiency (NCV)108%110%Standby heat loss0.05%0.06%4bar4bar30 - 90ºC30 - 90ºC5l5lPressure drop rate at ΔT 20K170mbar320mbarNoise level at 1m, full load46dB(A)52dB(A)2839Maximum working pressureFlow temperatureWater contentNOx rating at 0% oxygen, dry mg/kWhMaximum flue length 80/125mm7.7mN/AMaximum flue length 100/150mm20m*18mFlue gas mass flow rate, full load27.2g/s44.9g/sFlue gas temperature 80/60ºC, full load64ºC76ºCFlue gas temperature 80/60ºC, part load57ºC57ºCFlue gas temperature 50/30ºC, full load43ºC51ºCFlue gas temperature 50/30ºC, part load33ºC34ºCFree feed pressure of fan120Pa220Pa9.4%9.4%CO2 content at full load, natural gas G20Condensate water rate natural gas G20, 50/30ºCpH value of condensate waterGas pressureGas rating at 15ºC 1013mbarCurrent ratingElectrical supply, number of phasesMaximum fuse ratingElectrical power consumption, full load6.9l/h10.8l/happrox. 4.1approx. 4.111.3 - 24mbar11.3 - 24mbar6.53m3/h10.53m3/h230 VAC, 50 Hz, 10A230 VAC, 50 Hz, 10A11101099W†147W†Electrical power consumption, part load21W†28W†Electrical ingress protectionIPX4DIPX4D248386Nominal gas consumption (MJ/h)*100/150 adaptor required. †Electrical consumption does not include pump group.

8 Technical & Specification Information – GB162 & GB162 CascadeInside storyThe GB162 has been designed to provide engineers with quick and easy access to themain heating components from the front of the boiler. The burner plate is secured to theheat exchanger with quick-clip fastenings so it can be removed for servicing without theneed for special tools.GB162 – 65 & 100kW modelsGas valveFanLow NOx ceramicQuick-clippre-mix burnerburner releaseAutomatic air ventCeramic glow igniter& ionisation electrodeFlow temperature sensorCombustion chamberFinned ALU-Plusheat exchangerCondensatecollector & drainUBA 3 boilermanagement systemBC10 controller withexpansion slot for RC35(EMS) controls

Technical & Specification Information – GB162 & GB162 Cascade 9Installing the Worcester GB162 seriesThe GB162 series is the perfect replacement boiler forWith its compact dimensions, relative light weight andmany installations where old and inefficient heatingmodular design, the GB162 is an excellent choice wheresystems have come to the end of their life. By investingaccess to the boiler or plant room is restricted, or wherein condensing technology with a fully compatible controlsfloor space is limited. A smaller physical footprint for thesystem, fuel savings can be achieved from day one, andheating system will increase planning flexibility, speed upthe higher fuel prices go, the bigger your saving will be.the installation process, improve access for maintenance,and reduce the need for large boiler rooms.465652001525500FGCFGC40135 103.5CFOAICAIC14030013101003103011861280980KeyGAS B CHRAir intakeCHFCentral heating flowCHRCentral heating returnCDOCondensate drain outletFGCFlue gasPFPump group flowPRPump group returnCFODistance from wallbracket to centre ofhorizontal flue bend;337.5mm for 80/125mmdia. flue and 339.5mmfor 100/150mm dia. flue0CHFAIC39 CDO13013035PF/PRCDO138162PFGAS APRClearancesThe minimum clearances shown below should be allowed for installation and servicing.Permanent clearancesGB162 65kWGB162 100kWIn front50mm50mmBelow0mm*0mm*Right side0mm0mmLeft side0mm0mm30mm30mmAbove*250mm with pump groupService clearancesGB162 65kWGB162 100kWIn front550mm550mmBelow350mm350mmRight side0mm0mmLeft side0mm0mmAbove40mm40mm

10 Technical & Specification Information – GB162 & GB162 CascadeInstallation requirementsThese pages provide an overview of the main installation Modulating pump group – 65/100kWand system requirements for the GB162. The full installation instructions supplied with theboiler must be adhered to before any work on the heating system takes place.Frost protectionWiring diagramThe boiler has integrated frost protection whichA detailed wiring diagram showing how to wireswitches the boiler on at a central heating flowthe boiler and controls can be found on page 15.temperature of 7 C and switches it off at a centralWe recommend using either dedicated controls toheating flow temperature of 15 C.maximise efficiency or control the GB162 with anexisting 0 to 10V BMS signal.Designated useThe 65kW boiler incorporates an RTH converterThe boilers may only be used to heat water for sealedallowing 230V controls to be connected (for singleheating systems of up to 4 bar. For greater systemboiler installations only).pressures or open vented systems the boiler must beseparated from the heating system with a plate heatQuality of the pipe workexchanger.When using plastic pipe work in the heating system,e.g. for underfloor heating, it has to be oxygen-tightQuality of the heating system wateraccording to relevant Standards. If the plastic pipesWe strongly recommend thoroughly flushing the systemdo not comply with these standards, the system partsbefore filling it and using only untreated tap watermust be separated using a plate heat exchanger.when filling the system. The use of dirty water willlead to build-ups of sediment and corrosion, which canMaintenance scheduleresult in the boiler malfunctioning and cause damageThe activities to be included in an annual inspectionto the heat exchanger.and maintenance contract can be found in the serviceDO NOT treat the water with products such as pH-section of the installation manual. If an inspectionadjusting substances (chemical additives), antifreezereveals that maintenance activities are necessary, theseor water softeners. Sentinel X100 or Fernox MB-1activities must be carried out.can be used to achieve the desired water quality. Theconcentration of Sentinel or Fernox should be at leastConnection of gas and water1% of the volume of the water in the system.TheThe pH of the heating system water MUST be betweencirculation pump. The boiler should be installed7 and 8.5. If this is not the case, please contact Boschtogether with a GB162 accessory pump group toon 1300 30 70 37 before proceeding.ensure that the pump is appropriately sized for theboilersdonotcontainafactoryinstalledboiler. The pump group also allows for an easier andquicker installation.If the boiler is being wall mounted rather than framemounted, a connection set is required in order toconnect the flow and return.Pump group numbersModulating pump group7 114 070Connection set (for using pumpgroup without cascade set)558 4552

Technical & Specification Information – GB162 & GB162 Cascade 11Modulating pump group – 00015002000250030003500400045005000[l/h]Residual head downstream of the pump group – with and without a non-return valvel/hmbar123Volume flowResidual headResidual head downstream of the pump group without a non-return valve (UPER 25-80) – full loadResidual head downstream of the pump group with a non-return valve (UPER 25-80) – full loadResidual head downstream of the pump group with a non-return valve (UPER 25-80) – partial loadHydraulic resistance – 50005001000150020002500[l/h]Boiler resistance curvel/hmbarVolume flowResidual head30003500400045005000

12 Technical & Specification Information – GB162 & GB162 CascadeSingle boiler installationThe GB162 65kW boiler, when installed on its own,must use a pump group and connection set. For controlof the boiler it can be connected to 230V AC on/offcontrols via the supplied RTH convertor. Alternatively,an RC35 control can be used to control the systemcircuits. Please note this will also require at least a lowloss header and a WM10 module.The GB162 100kW boiler also requires a pump groupand connection set, and must be installed with a lowloss header. Third party circulation pumps will also berequired for the DHW and heating circuits. To monitorthe temperature at the low loss header, a WM10module is required with an RC35 controller. 100kWboilers cannot be connected to 230V AC controls.Part No.GB162 65kW(7 746 900 822)GB162 100kW(8 747 025 0)Modulating pump group7 114 07033Connection set5 584 5523389 200 972*37 747 312 318*330 008 458*35 991 387*3Low loss header c/w insulationRC35 digital boiler controlWM10 low loss header moduleDHW cylinder sensor(if DHW cylinder is present)3 Required accessory*Optional accessory may be required in some installations

Technical & Specification Information – GB162 & GB162 Cascade 13Pump groupThe Worcester GB162 is installed with a modulatingThe pump group is directly mounted under the boiler topump group accessory. The high quality pump groupsfeed a low loss header or in the case of a single 65kWensure quick, easy and reliable connection of the boilerboiler supply the system directly. As the heating circuitsto the main flow, return and gas headers. The Worcesterreach their required temperature and the flow is reducedpump group is correctly sized to ensure that the flow rateby the thermostatic radiator valves, the modulating pumpthrough the GB162 heat cell never exceeds the limit ofwill respond to the reduced demand. This helps keep a5000I/h @ ΔT 20K. Worcester pump group will also helpsystem in balance as well as reducing noise and electricalto prolong the life of the boiler by minimising wear andenergy use.tear on its components. As a result, system efficiency isimproved and installation time and running costs arereduced. When using Worcester pump groups, a low lossheader should also be used to simplify hydraulic designof the heating circuit.Modulating pumpgroup (7 114 070)Modulating 25/80 pump3Gas isolating valve3Flow & return isolating valves3Pressure gauge3Pressure relief valve3Drain valve3Expansion vessel connection point*3Insulated cover3Flow & return thermometers3*Expansion vessel not suppliedGB162 pump group at a glanceFlowGasReturnCondensatedrainage pointGas isolating valve – yellowPressure relief valve(can be rotated)Modulating pumpPressure gaugeConnection for expansion vessel(vessel not supplied)Flow isolating valve – redReturn isolating valve – blueFlow connectionReturn connectionScrew fitting 1¼" connection set (accessory 5 584 552)when using boiler without cascade frame

14 Technical & Specification Information – GB162 & GB162 CascadePump GroupPositioning and termination of the condensate drainpipeThe condensate pipe should be routed internallyto prevent freezing. If an internal routing of thecondensate pipe work is not possible, it is advisableto use a trace heating device or an auxiliary syphon toreduce the prospect of freezing.The condensate pipe should run and connect to theinternal sewage pipe in the building or waste o the rainwater system if connected to a foul waterdraining system.All connecting drainage pipe work should generally havea fall of at least 2.5º to the horizontal, or approximately50mm per metre of pipe run. If this cannot be achieved,you should consider the use of a condensate pump. Itshould be noted that the connection of a condensatepipe to a drain may be subject to local building control.

Technical & Specification Information – GB162 & GB162 Cascade 15Wiring aulic, complete with low loss header. ConnectingEMSEnergy Management Systemthe sophisticated energy saving controls to the GB162EVExternal safety contact, e.g. external safety chainis simplified by the use of colour coded plugs.FAOutdoor temperature sensorThe RC35 programmer is wired back to respectiveFKLow loss header temperature sensorplugs which are then simply clicked into the codedFVFlow temperature sensorconnections on the GB162. For systems with anFWDHW sensoradditional unmixed or mixed heating circuit, the MM10NETZMains connection 230 VAC 50Hz, max. permissible: 10Awith a flow temperature sensor can be used to controlPHHeating pump 230 VAC max. 250Wa pump and mixing valve.PSDHW pump 230VAC max. 250WThe WM10 module for the low loss header andPZDHW circulation pump 230 VAC max. 250Wunmixed heating circuit pump is connected in theRCRoom controller RC and EMS busboiler tray via the EMS bus.SHMixing valveWAOn/off temperature controller, potential freeRC35 wiring diagramFor DHW, 1 x unmixed heating and 2 x mixed heating circuitsE N L E N L 4143 44 61 63EMS EMSNETZNETZ1 2 1 21 2 1 2 1 2RCFAWAFWEV3 core 230vacNorth3 core 230vac2 core shieldedE 24 25 E 13 14PSPZPHE N L E N L 41 43 44 61 631 2 1 2 1 2FVRCEMSNETZNETZSHPH1 2 1 2FVMM10MM10Address 2Address 33 core 230vacFA3 core 230vac2 core shielded2 core shieldedWM10SHFVFW1 2 E N LEMS NETZFKHydraulic layout has been simplified for clarityFV4 core 230vacFK2 core shielded1 2 1 2 1 2PHNETZ4 core 230vac3 core 230vac2 core shieldedNETZ3 core 230vacE N L E N L 61 63RC35 used as roomcontroller, assigned toheating circuit it is to controlRC1 2EMS

16 Technical & Specification Information – GB162 & GB162 CascadeWorcester GB162boiler series fluing optionsThe flexibility of the GB162 series also extends to the fluing options, as shown in thediagram below, allowing the specifier to site the boiler in a number of different positions.The GB162 is suitable for either room sealed or openTheflues. To ensure maximum reliability, quality and safetysystems that can be used for a GB162 installation.all Worcester flue gas systems are rigorously tested toFull installation instructions and relevant buildingthe latest industry standards.regulations must be adhered to prior to installation ofdiagrambelowshowstypicalstandardflueany flue system. Additional fluing solutions are possibleand should be discussed with your fluing specialist.12KeyOpen Flue2Cascade, B23Room Sealed1Vertical, C333Horizontal, C333

Technical & Specification Information – GB162 & GB162 Cascade 17Horizontal and vertical flueterminal positioningONFlue terminal positionsfor boilers in accordancewith AS5601.ACNB,CB,CMFKAFFMGLGEJH, IKLKGDKG3 Pluming will occur at the terminal so terminalpositions where this could cause a nuisance shouldbe avoided.3 The air supply and the flue gas exhaust must meetKey to illustrationBalanced flue terminal positionTerminal PositionMinimumSpacingthe applicable general regulations. Please consultAthe instructions provided with the flue terminal kitsDirectly below, above or alongside an openingwindow, air vent or other ventilation openingBBelow guttering, drain pipes or soil pipes75mmprior to installation.CBelow eaves300mmDBelow balconies or a car port roof*300mmEFrom vertical drain pipes or soil pipes75mmFFrom internal or external corners300mmGAbove adjacent ground, roof or balcony levelHFrom a surface facing the terminal1,500mm3 The boiler must be installed so that the terminal isexposed to the external air.3 It is important that the position of the terminalallows the free passage of air at all times3 Minimum acceptable spacing from the openings1,500mm300mmare specified above, for domestic situations inIFrom a terminal facing the terminal1,200mmaccordance with AS 5601.KVertically from a terminal on the same wall1,500mmLHorizontally from a terminal on the wallMAdjacent to openingNAbove intersection with roof500mmOFor a vertical structure on the roof500mm*Installations in car ports are not recommended300mm1,500mm

18 Technical & Specification Information – GB162 & GB162 CascadeWorcester GB162 boiler serieshorizontal room sealed fluing options80/125mm horizontal room sealed flue accessoriesHorizontal room sealed flueFlue GB162 65kWMaximum flue lengthGB162 100kWMaximum flue lengthN/A18,000mm90º bendHorizontal flue terminalFlue finishing kitPart No.Description7 716 191 11680/125mm dia. horizontal flue kit7 716 191 11880/125mm dia. 1m flue extension(cutable)7 716 191 11780/125mm dia. 0.5m flueextension (cutable)7 716 191 11980/125mm dia. 90º bend7 716 191 12080/125mm dia. 45º bends (pair)T 000 082 13180/125mm dia. flue supportbracket (3 pack)100/150mm horizontal room sealed flue accessoriesComponents80/125mm dia. horizontal flue kit1 x 90º bend1 x horizontal flue terminal1 x flue finishing kitPart No.7 716 191 094100/150mm dia.horizontal flue kit7 716 191 096100/150mm dia. 1m flueextension (cutable)7 716 191 097100/150mm dia. 1m flueextension (non-cutable)7 716 191 095100/150mm dia. 0.5m flueextension (cutable)7 716 191 098100/150mm dia. 90º bend7 716 191 099100/150mm dia. 45º bends (pair)Part No. 7 716 191 116100/150mm dia. horizontal flue kit1 x 90º bend1 x horizontal flue terminal1 x flue finishing kitPart No. 7 716 191 094Description8 720 011 6100/150mm dia. adaptor(GB162 65kW only)7 716 191 102100/150mm dia. flue supportbracket (3 pack)7 716 191 103100/150mm dia. clamp withEPDM seal

Technical & Specification Information – GB162 & GB162 Cascade 19Extension flue horizontalStandard horizontal flue assemblyComponentsComponentsPart No. 125mm7 716 191 116N/APart No. 125mm7 716 191 1167 716 191 118N/APart No. 150mm7 716 191 0948 720 011 6Part No. 150mm7 716 191 0947 716 191 0968 720 011 6Maximum lengths (mm) & no. of components requiredMaximum lengths (mm) & no. of components requiredGB162 65kWGB162 65kW125mm5401N/A125mm77001up to 8N/A150mm55011150mm20,0001up to 2011up to 18N/AGB162 100kW150mmGB162 100kW55011150mm18,000Extension flue horizontal using a second 90º bendComponentsPart No. 125mm7 716 191 1167 716 191 1187 716 191 119N/APart No. 150mm7 716 191 0947 716 191 0967 716 191 0988 720 011 6Maximum lengths (mm) & no. of components requiredGB162 65kW125mm5,8001up to 61N/A150mm17,9001up to 18111up to 161N/AGB162 100kW150mm15,900Note: The short 0.5m flue extension may be used as an alternative tothe standard extension.GB162 65kW80/125mm fluesGB162 65 & 100kW100/150mm flues45º bend0.9m1.2m90º bend1.9m2.1mNote: The maximum flue length must be reduced by the following amountsfor each bend used.

20 Technical & Specification Information – GB162 & GB162 CascadeExtension flue horizontal and upwardsComponentsPart No. 125mm7 716 191 116 7 716 191 118 7 716 191 119N/APart No. 150mm7 716 191 094 7 716 191 096 7 716 191 0988 720 011 6Maximum lengths (mm) & no. of components requiredComponentsGB162 65kW125mm7,7001up to 80*N/A150mm20,0001up to 200*11up to 180*N/AGB162 100kW150mm18,000Extension flue upwards and horizontal using a second90º bendPart No. 125mm7 716 191 116 7 716 191 118 7 716 191 119N/APart No. 150mm7 716 191 094 7 716 191 096 7 716 191 0988 720 011 6Maximum lengths (mm) & no. of components requiredGB162 65kW*Horizontal flue kit includes a 90º bend125mm7,7001up to 61*N/A150mm17,9001up to 181*11up to 161*N/AGB162 100kW150mm15,900*Horizontal flue kit includes a 90º bend, therefore only 1 additional bendneeds to be orderedNote: The short 0.5m flue extension may be used as analternative to the standard extension.GB162 65kW80/125mm fluesGB162 65 & 100kW100/150mm flues45º bend0.9m1.2m90º bend1.9m2.1mNote: The maximum flue length must be reduced by thefollowing amounts for each bend used.

Technical & Specification Information – GB162 & GB162 Cascade 21Worcester GB162 boiler seriesvertical room sealed fluing optionsVertical room sealed flueFlue diameter80/125mm horizontal room sealed flue ntsGB162 65kWMaximum flue lengthGB162 100kWMaximum flue lengthN/APart No.Description7 716 191 11580/125mm dia. vertical flue kit7 716 191 11880/125mm dia. 1m flue extension(cutable)7 716 191 11780/125mm dia. 0.5m flueextension (cutable)7 716 191 11980/125mm dia. 90º bend7 716 191 12080/125mm dia. 45º bends (pair)T 000 082 13180/125mm dia. flue supportbracket (3 pack)18,000mm100/150mm vertical room sealed flue accessoriesComponentsflue terminalsupport bracket80/125mm dia. vertical flue kit1 x flue terminal1 x support bracket1 x sealing clampPart No. 7 716 191 115100/150mm dia. vertical flue kit1 x flue terminal1 x support bracket1 x sealing clampPart No. 7 716 191 093Part No.Description7 716 191 093100/150mm dia. vertical flue kit7 716 191 096100/150mm dia.1m flue extension (cutable)7 716 191 097100/150mm dia.1m flue extension (non-cutable)7 716 191 095100/150mm dia.0.5m flue extension (cutable)7 716 191 098100/150mm dia. 90º bend7 716 191 099100/150mm dia. 45º bends (pair)8 720 011 6100/150mm dia. adaptor(GB162 65kW only)7 716 191 102100/150mm dia. flue supportbracket (3 pack)7 716 191 103100/150mm dia.clamp with EPDM seal

22 Technical & Specification Information – GB162 & GB162 CascadePitcroo hedfPitcroo hedf500mm300mm500mm300mmFlat roofStandard vertical flue assemblyComponentsPart No. 125mm7 716 191 115N/APart No. 150mm7 716 191 0938 720 011 6Maximum lengths (mm) & no. of components requiredGB162 65kW125mm1,3521N/A150mm1,545111,5451N/AGB162 100kW150mmVertical balanced flue system maximum heightComponentsPart No. 125mm7 716 191 1157 716 191 118N/APart No. 150mm7 716 191 0937 716 191 0968 720 011 6Maximum lengths (mm) & no. of components requiredGB162 65kW125mm7,7001up to 7N/A150mm20,0001up to 2011up to 18N/AGB162 100kW150mmNote: The short 0.5m flue extension may be used as analternative to the standard extension.Note: The maximum flue length must be reduced by thefollowing amounts for each bend used.ComponentsGB162 65kW80/125mm fluesGB162 65 & 100kW100/150mm flues45º bend0.9m1.2m90º bend1.9m2.1m18,000

Technical & Specification Information – GB162 & GB162 Cascade 23Extension flue horizontal and upwardsComponentsPart No. 125mm7 716 191 115 7 716 191 118 7 716 191 120N/APart No. 150mm7 716 191 093 7 716 191 096 7 716 191 0998 720 011 6Maximum lengths (mm) & no. of components requiredComponentsGB162 65kW125mm5,9001up to 62N/A150mm17,6001up to 17211up to 152N/AGB162 100kW150mm15,600Extension flue upwards and horizontal using a second90º bendPart No. 125mm7 716 191 115 7 716 191 118 7 716 191 119N/APart No. 150mm7 716 191 090 7 716 191 096 7 716 191 0988 720 011 6Maximum lengths (mm) & no. of components requiredGB162 65kW125mm3,9001up to 42N/A150mm1

18 Worcester GB162 boiler series fluing options 24 Energy management controls 26 Bosch CSM920 boiler management 28 Cascade – quick and simple to install 29 Cascade technical information 35 Worcester GB162 boiler series and accessories 39 Notes Bosch and you, making a difference 2 Technical & Specification Information – GB162 & GB162 Cascade

Related Documents:

Worcester and you, making a difference As part of the Bosch Group, Worcester products are designed and manufactured to . Cascade technical information 34 - 39 GB162 boiler series and accessories 40 - 43 Training 44 - 46 After-sales 47. 4 GB162 condensing boiler series

UK/IE Installation and servicing instructions Wall hung gas fired condensing boiler Worcester Commercial Boiler Series GB162-50/65/80/100 6 720 648 726-000.1TD

UMSL Cascade Content Management System User Guide . Updated 2021 4 . What is Cascade? Cascade is the Content Management System the university uses to create, manage, and publish content to the web. This guide should be referenced to help answer questions regarding features in Cascade. If

5 1. Introduction Figure 1 - Typical cascade configuration (S-cb PX 120 Above). This Cascade manual is intended for the S-CB and the S-CB PX 120 wall-hung high efficiency CH boilers by Strebel Ltd. These boilers are available, in order of ascending output, as S-CB 60, 80, 100, 120, PX120, 150 and 180. The S-CB 60 - 120 (Not including the PX models) can be combined in one cascade set .

UNDERGRADUATE CATALOG 2019-20 WORCESTER POLYTECHNIC INSTITUTE UNDERGRADUATE CATALOG 2019-20 Worcester Polytechnic Institute 100 Institute Road Worcester, MA 01609-2280 wpi.edu Photo by: MacKenzie Hridel, WPI Class of 2019

Open Mic Songbook 2015 Revision 2 . Worcester Ukulele Club 2015 - www.worcester-uke-club.co.uk Page 2 Rev 2 Introduction Welcome to Worcester Ukulele Club’s first Open Mic songbook. The contents of this book are a collection of songs that were submitted by club members after they had bravely performed at one of our wonderful Open Mic nights. .

Worcester State University 486 Chandler Street, Worcester, MA 01602-2597 508-929-8000 www.worcester.edu CATALOG UNDERGRADUATE STUDIES Academic Year 2016—2017 . This catalog was prepared by WSU Publications & Printing Services. REV. 2/16/2017. 2 TABLE OF CONTENTS GENERAL INFORMATION .

Description Logic RWTH Aachen Germany 4. Introduction to DL I A Description Logic - mainly characterised by a set of constructors that allow to build complex concepts and roles from atomic ones, concepts correspond to classes / are interpreted as sets of objects, roles correspond to relations / are interpreted as binary relations on objects, Example: Happy Father in the DL ALC Manu (9has-child .