Circuit-breakers, switch-disconnectorsfrom 630 A to 6300 A11/0efesotomasyon.com - Klockner Moeller - inverterIZM circuit-breakers, IN switch-disconnectorsMoeller HPL0211-2004/2005

efesotomasyon.com - Klockner Moeller - inverter11/1Moeller HPL0211-2004/2005Circuit-breakers, switch-disconnectorsfrom 630 A – 6300 ADescriptionPage11/2Technical overview11/4Overview of functions for electronic release11/6System overview11/10IZM circuit-breakers3-poleIZM.1-.For distribution circuit protection (A)For selective protection (V)For universal protection (U)With digital release (D)IZM.2-.IZM.3-.For distribution circuit protection (A)For selective protection (V)For universal protection (U)With digital release (D)4-poleIZM.1-4-.For distribution circuit protection (A)For selective protection (V)For universal protection (U)With digital release (D)IZM.2-4-.IZM.3-4-.For distribution circuit protection (A)For selective protection (V)For universal protection (U)With digital release (D)IN switch-disconnectorsThree and K4810-1143G“Type tested switchgear systems up to 4000 cessoriesIncreasing the rated operational voltage to 1000 V ACElectronic overcurrent releaseManual test device for overcurrent release11/2811/2911/29Rated current module/rating plugEarth-fault protection and 4-line display11/3011/31Current transformer for N conductor and earth-faultprotectionAccessories for overcurrent releaseComponents for communicationsDescriptionParameter definition systemsCommunication modulesMeasurement modulesVoltage transformerExpansion moduleAuxiliary contactsMotor operatorsMotor cut-off switchOperations counterControl circuit connectionsClosing releasesShunt releaseUndervoltage releaseElectrical ONEmergency-Stop actuatorMounting brackets for fixed mounted circuit-breakerDoor sealing frames to IP41Protective cover to IP55Control circuit plug terminal assignment plan11/32Locking facilitiesLocking arrangementsWithdrawable unitsWithdrawable unitReserve switch for withdrawable unitFixed mounting conversion kitfor withdrawable unitPosition signalling switchfor withdrawable unitShutterArcing chamber coverfor withdrawable unitCoding system for withdrawable unitConnection systems for fixed mountingConnection system for withdrawable 1/5511/5611/58Selectivity table11/57Tripping characteristics11/72Technical data11/74Dimensions11/88Circuit-breakers, switch-disconnectorsfrom 630 A to 6300 AContentsIZM circuit-breakers, IN switch-disconnectors

efesotomasyon.com - Klockner Moeller - inverterDescriptionIZM circuit-breakers, IN switch-disconnectorsCircuit-breakers, switch-disconnectorsfrom 630 A to 6300 A11/2Moeller HPL0211-2004/2005IZM circuit-breakersThe IZM from Moeller embodies a concept for open circuit-breakers that exceeds thestandard throughout the world. Based on state-of-the-art system engineering, theseswitches open up a new dimension in the rated current range from 630 to 6300 A.They excel not only for their performance, but also for their functionality, especiallyin their communications capabilities and their ease of handling and installation.A comprehensive operator manual is supplied with each device.Application areasCoupler switches: Beside the IZM circuit-breakers, IN switch-disconnectors areavailable. These are used, for example, as coupler switches between different powersupplies.Main switches: You can use both IN switch-disconnectors and IZM circuit-breakersas mains isolating switches. In combination with a lockable handle, all IZM circuitbreakers (IN switch-disconnectors) fulfil the main switch and isolatingcharacteristics to IEC/EN 60204-1. Four main applications: Dependent on the typeof equipment to be protected, the circuit-breaker tasks are divided into four mainareas of application: System protection Motor protection Transformer protection Generator protection.These key applications make different demands on the switches, which are met witha range of control units.Standard versionIZM circuit-breaker has the following standard equipment: Mechanical ON and mechanical OFF switch Manual drive for charging the spring-operated stored energy mechanism Switch position indication 0 / I Ready to switch on display OK Charge state display Auxiliary circuit switch 2 M 2 B Horizontal main terminals on rear with fixed mounted and with withdrawableunits up to 5000 A and on rear with vertical main terminals at 6300 A With 4-pole switches the 4th pole (N) is fitted on the left and can be loaded to 100% Display of the contact erosion of the main contacts Auxiliary current plug system with screw terminations. The switch is alwaysequipped with the required number of auxiliary current plugs. Mechanically tripped display of the overcurrent release system Mechanical reclosing lockout after trip Operating manualAdditional with withdrawable units: Main contacts: Laminated contacts on the back plate of the withdrawable unit,contact pin on basic unit Position display with operating console of the plug-in switch Captive crank handle for switch movement with withdrawable system Withdrawable unit with guide rails for simple handling Locking facility for switch movement in the withdrawable unit The switch cannot be moved in the withdrawable unit in the on state Rated current coding between the withdrawable unit and the switch.Safety and reliabilityNumerous locking features are provided or can be fitted by the user, on the onehand to protect the switch and system from unauthorised switching, and on theother for the protection of maintenance and operating personnel.Further safety features are: Power feed from top or bottom as required Standard locking facility for the withdrawable unit when the switch is removed Standard locking facility for the switch in withdrawable unit to prevent removal High degree of protection with IP 55 terminal cover Standard with mechanical closing lockout after overload or short-circuit release The operating panel cannot be removed when the switch is operational Delivery including all auxiliary circuit connectors corresponding to built-infeatures including coding device to prevent mix-up of plug-connectors with fixedmounted breakers Devices with IZM-XCOM-DP communication interfacing feature temperaturesensors on the built-in microswitch detection units (XBSS) and on thecommunication module.DesignThe compact design of the circuit-breakers provides optimum utilization of theavailable space, allowing control panels to be equipped more efficiently. The IZMfor a rated current up to 6300 A, for example, can be installed in am 800 mm widecontrol panel field. Switches with a rated current of 1600 A need only a 400 mmfield.Operating consoleThe operating panel is designed to ensure that it can protrude through a cut-out inthe door and that all operation elements and displays can be accessed when thecontrol panel door is closed. The operating panels of all switches (fixed mounted/withdrawable, 3/4-pole) have identical dimensions. The operating panel providesIP20 degree of protection.

DescriptionIZM circuit-breakers, IN switch-disconnectors11/3Moeller HPL0211-2004/2005Current rangeThe new IZM open circuit-breakers cover the entire range from 800 – 6300 A withjust two frame sizes. The compact IZM1 frame size extends the rated current rangedownwards from 630 A. If required, the range can be extended to 250 A byexchanging the rating plug. And all this with a setting range of 0.4 – 1 x In.DimensionsThe IZM devices have the same height and depth across their entire current range.Only their device varies depending on the number of poles and the frame size.TerminationsAs standard, IZM circuit-breakers are fitted with horizontal connections. Optionally,the following connections are possible: vertical connections, connections that areaccessible from the front and flanged connections.Trip electronicsThe IZM units are equipped with microprocessor-controlled control units asstandard. Five different control units are available for selection and thus offeroptimum protection for your system: From simple system protection with overloadand short-circuit release extending to a digital circuit-breaker with graphic displayand the option of setting up time-discriminating networks.Control circuit connectionsThe built-in auxiliary switches are connected to the male connector on the switch.Irrespective of the mounting type, the customer connects the auxiliary power circuitsto the control circuit plugs at the top of the circuit-breaker. The standard terminalsare screw-type; spring-loaded terminals are optional.ON fixed mounting units, the control circuit plugs are fitted directly to the plugconnectors on the switch and are coded against accidental reversal.To allow withdrawable units to be moved, a sliding contact module is fitted betweenswitch and mounting. The sliding contact module allows a secure connection of thecontrol circuit cable connectors in the “connected” and “test” positions of theswitch.ModularityBecause components are installed from the front, retrofitting accessories isespecially quick and easy. This allows you to respond flexibly to changingrequirements within your system.Communication capabilityWith their communication-capability, the IZM circuit-breakers open up newpossibilities in power distribution. Providing and transmitting all importantoperational information, they increase system transparency and shorten theresponse times to states such as overcurrent, phase asymmetry and overvoltage. Arapid intervention in a process can, for example, prevent downtimes and help toschedule maintenance activities and therefore boost plant availability.Internal system busThe IZM universal and digital circuit-breakers contain an internal system bus asstandard, which connects all intelligent components of the circuit-breaker.Through the communications interface, the information from the intelligentcomponents can then be transmitted through PROFIBUS-DP, for example with theIZM-XCOM communication module.Expansion modules for the internal system bus:External add-on modules can be connected to the IZM circuit-breakers through theinternal system bus without extensive additional wiring. Digital input modules anddigital and analog output modules are available for this purpose. A further moduleimplements reduced-time selectivity control between IZM circuit-breakers.Selection criteria for the IZM circuit-breakersFundamental criteria for the selection of circuit-breakers: Max. short-circuit current at the point of installation of the circuit-breaker Ik“max: this value determines the short-circuit breaking capacity or the short-circuitcurrent carrying capacity of the circuit-breaker. It is compared with the value Icu,Ics, Icw of the switch and mainly determines the size of the switch a technicaldata. Rated current In which should flow through the respective branch circuit: Thisvalue may not be greater than the maximum switch rated current of the circuitbreaker. The rated current is defined with the IZM with the rated current module(Exception: XZMA overcurrent release for system protection). Ambient temperature of the circuit-breaker: This is generally the internaltemperature in the control panel. Observe the derating table with increasedambient temperature a technical data. Circuit-breaker type: fixed mounted or withdrawable, 3 or 4-pole. Minimum short-circuit current, which flows through the switchgear: The releasemust recognize this value as a short-circuit and may react with a trip. Protection functions of the circuit-breaker: This is determined by the selection ofthe respective overcurrent release.NotesOperating manual AWB1230-1407D/GB, Article no. 232792Approved performance dataDetails of UL and CSA a chapter 19, ApprovalsCircuit-breakers, switch-disconnectorsfrom 630 A to 6300 Aefesotomasyon.com - Klockner Moeller - inverter

efesotomasyon.com - Klockner Moeller - inverterTechnical overviewIZM circuit-breakersMoeller HPL0211-2004/2005Circuit-breakerswith main switch and isolating characteristics(in combination with the “interlock in OFF” facility ),from 630 – 6300 ARated current rated uninterruptedcurrentIn IuABasicswitching capacity (B)Normal switching capacity(N)High switching capacity (H)1000 VIcu IcskAIcu IcskAIcu IcskAIcu IcskAIcu IcskAIcu IcskAMoeller HPL0211-2004/2005Switch-disconnector:with main switch and isolating characteristics(in combination with the “interlock in OFF”facility ), from 630 – 6300 ARated ultimate short-circuit breaking capacity Icu with rated operational voltage Ue440 V690 V440 V690 V440 V690 VIcu IcskATechnical overviewIZM circuit-breakersRated current In rated uninterrupted current IuRated short-circuit making capacity IcmRated short-time withstand current Icw t 1 sINIZMIZM.1(-4)-.INB1(-4)-.630 – 160050426550In 630 – 1600 w/kA22080100a page 11/24a page 11/12, 11/18IZM.2(-4)-.INN1(-4)-.800 – 3200555080751008545In 630 – 1600 Aa page 11/24a page 11/14, 11/20IZM.3(-4)-.INB2(-4)-.4000 – 63001008550In 800 – 3200 Aa page 11/26a page 11/14, 11/20INN2(-4)-.In 800 – 3200 Aa page 11/26INH2(-4)-.In 800 – 3200 AIn 800 – 3800 Aa page 11/26INH3(-4)-.In 4000 – 6300 AIn 4000 – 5000 AIn 6300 Aa page 11/26Optional electronic releasefor IZM circuit-breakers:Standard circuit-breaker ASelectively-operating circuit-breaker VUniversal circuit-breaker UDigital circuit-breaker Da page 11/611/5Circuit-breakers, switch-disconnectorsfrom 630 A to 6300 ACircuit-breakers, switch-disconnectorsfrom 630 A to 6300 A11/4

Moeller HPL0211-2004/2005Functional overview of the electronic releaseIZM circuit-breakersMoeller HPL0211-2004/2005IZM .-A.IZM .-V.IZM .-U.IZM .-D.IZM .-D. IZM-XZMRElectronic release for distribution circuitprotection630 – 3200 AElectronic release for selectively-openingcircuit-breakers630 – 6300 AElectronic release for universal protection630 – 6300 ADigital release630 – 6300 ADigital release for externalparameterization only630 – 6300 K–––Comm k–K–K–––OtherConnection feature for an external 24 V DC power supply––KKKNotes1)Basic protective functionsOverload protection IrAdjustable delay trShort-time delayed short-circuit protection IsdNon-delayed short-circuit protection IiNeutral conductor protectionEarth-fault protectionLSINGAdditional functionsN conductor protection can be activated/deactivatedShort time delayed short-circuit protection can beactivated/deactivatedNon-delayed short-circuit protection can beactivated/deactivatedThermal memory can be activated/deactivatedLoad monitoringLeading “L” trip signal, 200 msShort-time delayed short-circuit protectionconvertible to I2tOverload protection convertible to I4tOverload protection can be activated/deactivatedN conductor protection adjustableEarth-fault protection convertible to I2tEarth fault alarmSelectable parameter setsZone-selective interlockingParametric programming and visualizationParametric programming via rotary coding switchParametric programming via communication(absolute values)Parametric programming via communication(absolute values)Remote parameter definition of the basic functionsRemote parameter definition of additional functionsSetting through IZM-XEM-PG parameter assignmentmodule or PROFIBUS-DP1)Menu-assisted setting directly on release1)Alphanumeric LCD (4-line display)Graphic LCDStep width for Menu/Comm or Comm settingSetting rangeStep width0.10–111 – 1005100 – 50010500 – 1000501000 – 16001001600 – 10 000100010 000 – max.2) Fixed at I f 20 x I , max. 50 kAinK standardk optional11/7Circuit-breakers, switch-disconnectorsfrom 630 A to 6300 Aefesotomasyon.com - Klockner Moeller - inverterFunctional overview of the electronic releaseIZM circuit-breakersCircuit-breakers, switch-disconnectorsfrom 630 A to 6300 A11/6

Moeller HPL0211-2004/2005Functional overview of the electronic releaseIZM circuit-breakersMoeller HPL0211-2004/2005IZM .-A.IZM .-V.IZM .-U.IZM .-D.IZM .-D. IZM-XZMRElectronic release for distribution circuitprotection630 – 3200 AElectronic release for selectively-openingcircuit-breakers630 – 6300 AElectronic release for universal protection630 – 6300 ADigital release630 – 6300 ADigital release for externalparameterization only630 – 6300 AMeasuring functions“power” measuring function“harmonic” measuring function––––kkkkkkCommunicationInternal system busPROFIBUS-DP communicationCommunication using Ethernet––––––KkkKkkKKkLED display featuresRelease activeAlarmControl unit error messageOverload tripShort-time delayed short-circuit tripNon-delayed short-circuit tripNeutral conductor fault protection tripG–Earth-fault protection alarmG–KKKKKKK(only possible with IZM-XT option)K(only possible with IZM-XT option)–––––K(only possible with ( )IZMU-XT option)K(only possible with ( )IZMU-XT(A) option)KKK(only possible with ( )IZMD-XT option)K(only possible with ( )IZMD-XT(A) option)KKK(only possible with ( )IZMD-XT option)K(only possible with ( )IZMD-XT fault protection tripG––G––––––K(only possible with ( )IZMD-XT option)K(only possible with ( )IZMD-XT(A) option)KKKEarth-fault protection alarmK(only possible with ( )IZMU-XT option)K(only possible with ( )IZMU-XT(A) option)KKTrip by extended protective functionCommunicationSignals via signalling switch with external systembus modules (optocoupler or relay)Overload warningLoad shedding, load pick-upLeading overload signal, 200 msTemperature alarmPhase imbalanceOverload tripShort-time delayed short-circuit tripNon-delayed short-circuit tripNeutral conductor tripAuxiliary relayControl unit error messageNotesK standardk optionalKKK11/9Circuit-breakers, switch-disconnectorsfrom 630 A to 6300 Aefesotomasyon.com - Klockner Moeller - inverterFunctional overview of the electronic releaseIZM circuit-breakersCircuit-breakers, switch-disconnectorsfrom 630 A to 6300 A11/8

efesotomasyon.com - Klockner Moeller - inverterSystem overviewIZM circuit-breakersCircuit-breakers, switch-disconnectorsfrom 630 A to 6300 A11/10Moeller HPL0211-2004/200555555776234218817161590 169 51014111111111312

System overviewIZM circuit-breakers11/11Moeller HPL0211-2004/2005Basic UnitsIZM circuit-breakersRated current from 630 – 6300 A4-stage switching capacity4 release types for different protection andindication function3 and 4 pole designAdd-on functions1a page 11/12CommunicationPosition switchModules for withdrawable unitsModule 1 Connected position: 1 changeovercontact Test position: 1 changeover contact Disconnected position: 1 changeovercontactModule 2 Connected position: 3 changeovercontacts Test position: 2 changeover contacts Disconnected position: 1 changeovercontactMounting accessories43a page 11/38External expansion modulesControl circuit plugsScrew terminalsSpringloaded terminalsa page 11/447Auxiliary contactsNormal auxiliary contacts with 2 breakcontacts and 2 make contacts (standard)2 make contacts and 2 break contactadditionally possibleReady-to-close auxiliary contactsTrip indicationSpring energy store status signalVoltage release status signal82a page 11/40Electronic releases11Standard protection functionsOptional protection functionsAdditional functionsParametric programming and visualizationMeasuring functionsCommunicationWithdrawable unitReplacing the circuit-breakers by insertionand withdrawal3 positions, lock

The IZM devices have the same height and depth across their entire current range. Only their device varies depending on the number of poles and the frame size. Terminations As standard, IZM circuit-breakers are fitted with horizontal co nnections. Optionally, the following connections are possible: vertical connections, connections that are accessible from the front and flanged connections .

Related Documents:

efesotomasyon.com -Toshiba inverter,drive,servo,plc. Toshiba inverter VT130G1 G1 Manual

REDI-TANKS PRODUCT LIST Moeller Marine Products 801 N. Spring Street Sparta, TN 38583 www.moellermarine.com 800-432-8344 Custom Performance, CARB Certification, and Moeller Quality at an Aftermarket Price In response to builder input, Moeller launched a line of standard-sized EPA/CARB Certified fuel tanks in 2012. The tanks are available in

Switches the inverter ON or OFF, resets the inverter 5.2 Inverter Status LED's 5.2.1 Inverter Switched Off 5.2.2 Inverter Switched ON 5.2.3 Overload "STATUS LED" Blinking indicates that the inverter is switched off. "STATUS LED" steady ON and the other LEDS rotating in a clockwise direction indicates that the inverter is switched on a

CTC 2200 and 2600 Series Profibus GE Fanuc Series 90 SNP/SNPX Reliance Automate 15/20/30/40 GE Genius I/O Square D Symax IDEC Siemens/TI Series 5x5 Keyence Siemens/TI Series 100 Klockner-Moeller PS 306/316 Siemens S7 Klockkner-Moeller PS4-201-MM1 Texas Instruments Koyo (PLC Direct) Toshiba Magnetek UTICOR Director 6001 1.2 Easy,

Moeller Wiring Manual 02/05 2-3 2 The three-phase asynchronous motor is the world's most common electric motor. Its popularity is the result of a rugged, simple construction, high degrees of protection, standardized sizes and low cost. Three-phase motors have typical starting characteristics, with tightening torque M A, pull-out torque M

Then Lenze is the partner you are looking for. For more than 60 years, drive and automation systems have been our core competence. 3 Contents Inverter Drives 8400 4 Inverter Drives 8400 motec 18 Inverter Drives 8400 protec 20 8200 vector frequency inverter 24 8200 motec frequency inverter 54 9300 vector frequency inverter 60. Price list .

LK/LW Series Power Star inverters Ensure that the inverter is switched off during the installation. It is recommended that you always connect the inverter to the battery bank first, as the battery power ultimately starts the inverter. If the inverter is connected to the AC input only, with the batteries disconnected or too low, the inverter .

ASTM C167-15 – Standard Test Method for Thickness and Density of Blanket or . Batt Thermal Insulations. TEST RESULTS: The various insulations were tested to ASTM C518 and ASTM C167 with a summary of results available on Page 2 of this report. Prepared By Signed for and on behalf of. QAI Laboratories Ltd. Robert Giona Matt Lansdowne Senior Technologist Business Manager . Page 1 of 8 . THIS .