DGA – Method In The Past And For The Future

3y ago
96 Views
12 Downloads
1.71 MB
46 Pages
Last View : 30d ago
Last Download : 3m ago
Upload by : Noelle Grant
Transcription

DGA - Methodin the Past andfor the FutureIvanka Atanasova-Höhlein Siemens AGFrei verwendbar

Page 2Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

1970Doerenburg introduced the differentiation between electricaland thermal failure mode and introduced ratios for fault gaseswith similar solubility.1973Halstead developed the theoretical thermodynamic theory. The ratiosare temperature dependent. With increasing the hotspot the amountof gases increases in the order: methane-ethane-ethylene.1975The evaluation scheme of the modern Gas-in-Oil Analysis isdeveloped by Rogers, Mueller, Schliesing, Soldner (MSS).1995Development of In-Line MonitoringPage 3Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

Different phenomena in oil take place like:dielectricthermalChange/Ageingdynamicchemical Gas-in-Oil Analysis (DGA Dissolved Gas Analysis)Page 4Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

The measurement of dissolved gasesallow the knowledge on Type Complexity Seriousnessof eventPage 5Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

SamplingPage 6Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

Sampling Container Perfectly cleaned & Dried Free from dust & moisture Airtight Glass or Metal cans, syringesPage 7Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

Protect sample from direct light Avoid moisture & dust contamination Use the sampling containers exclusivelyfor transformer oil samplingPage 8Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

1 Handwheel2 Sealing cap3 Safety chain4 Polyamid gasket5 Nut6 Drain valve7 Hose and screw connector8 Sampling bottle9 Overflow vesselPage 9Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

Page 10Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

Required information concerning oil sample(example)Requested analysis:ColourISO 2049AppearanceIEC 60422Neutralisation valueIEC 62021-1Breakdown voltageIEC 60156Water contentIEC 60814Loss factor at 50 HzIEC 60247Interfacial tensionISO 6295PCB-contentEN 12766-2Furananalysis (DGA)IEC 61198Gas-in-oil-analysisIEC 60567Please fill in the following data:Manufacturer:FTNR (Manufacturing No.):Customer:WNR (Order No.):Location:Sample No.:Year of manufacture:Date sample taken.:Type:Type of oilPower:Quantity of oil:Rating:Oil temperature in the sample taken:Sample taken from:Oil sample valveOil drainage deviceA 22/31/40 DIN 42 rOLTCBushingOLTCOLTC tankBushingOthers:Reason for sample taking:Date of operation fault:Date of repair :Date of oil treatment/reclaimingRoutine checkup:Further informations and previous history:Sample taker:DateLab information:Page 11Consecutive no.:Date sample received:Date sample analysed:Type of sample container:Name in block lettersCompany/ DepartmentPhonespecial features:Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

Extraction of Gasesfrom the OilPage 12Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

DGA. Toepler PumpPage 13Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

DGA. Partial DegassingPage 14Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

DGA. Headspace at Ambient TemperaturePage 15Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

DGA. Headspace at 70 CPage 16Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

Gaschromatographic AnalysisPage 17Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

Gaschromatographic AnalysisSampleinjectionCarrierGasPage 18DetectorDetectorgasIvanka Atanasova-Höhlein Siemens AGSiemens Energy

Failures which can be identified by DGA Partial discharges Electrical discharges Charcoal coating of contacts Accelerated cellulosic degradation Local overheating Untightness of OLTC tank Catalytic reactions of materials Additional information from BHR gasPage 19Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

Failures which can not be identified by DGA Incipient Failures Long lasting temperatures 150 CPage 20Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

Interpretation SchemesPage 21Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

Duvals TrianglePage 22Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

PatternsElectrical DischargesThermal ProblemPartial 04040303030202020101010000COPage 23H2CH4C2H6C2H4C2H2COH2CH4C2H6C2H4Ivanka Atanasova-HöhleinC2H2COH2CH4C2H6C2H4C2H2 Siemens AGSiemens Energy

MSS SchemeRatio ranges 0.30.3 to 1.01.0 to 3.03.0 to 10.0 10.0DiagnosisNormal ageing of insultansDischarge of high energyDischarge of low energyPartial discharge with high energyPartial discharge with low energyLocal overheating up to 300 ºCLocal overheating from 300 ºC to 1000 ºCLocal overheating over 1000 ºCLocal overheating and dischargeLocal overheating and partial discharge[C2H2][C2H6]011220221100110n.i. not indicativePage 24Ivanka Atanasova-HöhleinRatio 13313Number 2[CO2][CO]111020110022222 Siemens AGSiemens Energy

IEC SchemePage 25Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

In case of quotient information it must be clear, that quotientsare only representative, if following values of the fault gases(in ppm) are exceeded:Page 26C2H2 1H2 15 [CXHY] x 1;2;3 50CO 80CO2 200Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

DGAExample – thermal ProblemMSS-Code00120Fault neC3H64824Carbon monoxideCO253Carbon dioxideCO21903OxygenO218222NitrogenN261662Page 27Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

MSS-Code00120Fault 1012Carbon monoxideCO1047Carbon dioxideCO26158OxygenO211805NitrogenN258084Page 28Manufacturing year 1970360 MVACarbon deposits on PLTC Contacts537Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

Gas-in-Oil AnalysisTurn-to-Turn FailureMSS-Code21121Fault neC3H61320Carbon monoxideCO1196Carbon dioxideCO22431OxygenO26743NitrogenN244120Page 29Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

DGAThermal Problem with Partial DischargesMSS-Code00101Fault yleneC2H42187AcetyleneC2H24Carbon monoxideCarbon dioxideCOCO2Page 30Manufacturing year 1991234 MVA, 330 kVDefective welding joint450995Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

DGACatalytical EffectsMSS-Code?3?0Fault gasppmHydrogenH2MethaneCH4EthaneC2H6 1EthyleneC2H4 1AcetyleneC2H2 1PropaneC3H8 1PropyleneC3H6 1Carbon monoxideCO67Carbon dioxideCO2222OxygenO25180NitrogenN223700Page 31Manufacturing year 1977Closed typeColor 0,5 / Acidity 0,014881Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

DGAUntight OLTCMSS-Code22122Fault on monoxideCO143Carbon dioxideCO21920OxygenO224600NitrogenN252000Page 32128Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

DGADiagnostic Importance in ServicePage 33RatiosGasincreaseratesAbsoluteValuesTrendIvanka Atanasova-Höhlein Siemens AGSiemens Energy

Absolute ValuesIEC 60599 (VDE 0370-7)C2H2All transformersNo OLTC2 20CommunicatingOLTC60 280Page 34H2CH4C2H4C2H6COCO250 15030 13060 28020 90400 6002800 14000Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

Ratiosa) Eliminates the effect of the oil volumeb) Eliminates some effects of samplingc) Especially interesting is the ratio formation for faultgases which exhibit similar solubilities, but theirdevelopment is temperature dependent –e. g. the thermodynamic considerations of Halstead.Page 35Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

Thermodynamcal considerations of HalsteadPage 36Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

Gas Increase Rates –information on seriousness of failureC2H2All0,01transformersH2CH4C2H4 C2H6COCO20,360,330,402,9270,25 90% gas increase source: Cigre TF11 in ppm/dayGas increase rates are temperature and volume dependentPage 37Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

Trend AnalysisDevelopment of the Fault Gases After Two Months of On-Line Monitoring6001005008070400ppm CO26030050402003020100ppm H2, CO,CH4, C2H4, C2H6, top oil ( C)90Carbon DioxideHydrogenMethaneCarbon MonoxideEthaneEthylenetop oil temp 0809.9.08Sampling datePage 38Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

Trend Analysis4063554top oil ( C)25203152406Ratio C 2H4/C2H6, CH4/H230101355530top oil ( C)20315201.7.08Ratio C 2H4/C2H6, CH4/H242511.7.0821.7.08Top oil Temperature ( C)31.7.0810.8.0820.8.0830.8.0809.9.08Sampling dateC2H4/C2H6CH4/H210 Trendanalysis is important not only with absolute values,but also with the 830.8.0809.9.08Sampling datePage 39Ivanka Atanasova-Höhlein Siemens AGSiemens EnergyTopC2CH

On-Line Monitoring Early failure recognition Diagnosis is only possible with the sofisticated types – where IECratios can be builtCigre TF 15 DGA did a comparison between On-Line monitoringsystems and Off-Line analyses. The brochure is on the way.Evaluated are: Precision Longterm stability RepeatabilityIn case of Routine concentrations, d.h. 5 * Detection Limit Low Concentrations, d. h. 2-5*Detection LimitPage 40Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

Recommendation of Cigre A2.27for On-LineMonitoring Necessary in case a problem has been identified Often, however, difficult to maintain Interfaces can lead to problems Able to deliver important informationin a short time Does not automatically lead to higher reliabilityPage 41Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

What can be measured on-line: Temperature Current, Voltage OLTC Oil level Gas-in-Öl Analysis Humidity in oil Bushings Acoustic Signals Magnetic Circuit CoolersPage 42Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

More Data does not mean automaticallymore InformationData Explosion1) (Total Exabytes)20015010050020022003200420051) Exa 1016 10 Mil of BillionsPage 43Ivanka Atanasova-Höhlein20062007 Siemens AGSiemens Energy

Transformer Failure Rate Failure rateFailure atComissioningFailure becauseof agingConstant failure ratePage 44Ivanka Atanasova-HöhleinAging / years Siemens AGSiemens Energy

Future Developments Further development of the On-Line analysiswith decision criteria Gas-in-oil analysis in OLTC Gas-in-oil analysis in alternative insulation fluidsand high temperature insulating materialsPage 45Ivanka Atanasova-Höhlein Siemens AGSiemens Energy

Thank youfor your attention! Siemens AG

Appearance IEC 60422 Neutralisation value IEC 62021-1 Breakdown voltage IEC 60156 Water content IEC 60814 Loss factor at 50 Hz IEC 60247 Interfacial tension ISO 6295 PCB-content EN 12766-2 Furananalysis (DGA) IEC 61198 Gas-in-oil-analysis IEC 60567 Please fill in the following data: Manufacturer: FTNR (Manufacturing No.): Customer: WNR (Order No.):

Related Documents:

May 02, 2018 · D. Program Evaluation ͟The organization has provided a description of the framework for how each program will be evaluated. The framework should include all the elements below: ͟The evaluation methods are cost-effective for the organization ͟Quantitative and qualitative data is being collected (at Basics tier, data collection must have begun)

Silat is a combative art of self-defense and survival rooted from Matay archipelago. It was traced at thé early of Langkasuka Kingdom (2nd century CE) till thé reign of Melaka (Malaysia) Sultanate era (13th century). Silat has now evolved to become part of social culture and tradition with thé appearance of a fine physical and spiritual .

D IRECTION G N RALE DE LÕA RMEMENT La DGA prend une nouvelle direction D IRECTION G N RALE DE LÕA RMEMENT 7-9 rue des Mathurins - 92 221 Bagneux cedex T l phone : 33 (0)1 46 19 50 00 - Fax : 33 (0)1 46 19 50 01 Site institutionnel DGA : www.defense.gouv.fr Portail industrie : www.ixarm.com DGA/Comm - 01 - 10.2009 - Photos : DGA/Comm - F .

On an exceptional basis, Member States may request UNESCO to provide thé candidates with access to thé platform so they can complète thé form by themselves. Thèse requests must be addressed to esd rize unesco. or by 15 A ril 2021 UNESCO will provide thé nomineewith accessto thé platform via their émail address.

̶The leading indicator of employee engagement is based on the quality of the relationship between employee and supervisor Empower your managers! ̶Help them understand the impact on the organization ̶Share important changes, plan options, tasks, and deadlines ̶Provide key messages and talking points ̶Prepare them to answer employee questions

Dr. Sunita Bharatwal** Dr. Pawan Garga*** Abstract Customer satisfaction is derived from thè functionalities and values, a product or Service can provide. The current study aims to segregate thè dimensions of ordine Service quality and gather insights on its impact on web shopping. The trends of purchases have

Chính Văn.- Còn đức Thế tôn thì tuệ giác cực kỳ trong sạch 8: hiện hành bất nhị 9, đạt đến vô tướng 10, đứng vào chỗ đứng của các đức Thế tôn 11, thể hiện tính bình đẳng của các Ngài, đến chỗ không còn chướng ngại 12, giáo pháp không thể khuynh đảo, tâm thức không bị cản trở, cái được

fat, saturated fat and cholesterol" were part of the 1980 Dietary Guidelines for Americans (DGA), and in 1985, recommendations were added to "use skim or low-fat milk or milk products" to help meet this DGA guidance (2, 3). . more aggressive regarding saturated fat recommendations than the DGA. In 2006 the American Heart Association