IEC 60364-6: Low Voltage Electrical Installations – Part 6 .

3y ago
365 Views
37 Downloads
3.62 MB
33 Pages
Last View : 1m ago
Last Download : 2m ago
Upload by : Dani Mulvey
Transcription

IEC 60364-6: Low voltage electricalinstallations – Part 6: Verification

Electrical installation safetyThe risks linked to incorrect use of electricity may include:- life-threatening danger for people,- threat of damage to electrical installations and property,- harmful effects on systems operation and equipment life spans.So the purpose of electrical installation testing is primarily to ensure that people andgoods are kept safe and are protected in the event of a fault. It also facilitatespreventive maintenance of installations, preventing serious faults which mightprove expensive. To guarantee people's safety with regard to these installationsand the electrical equipment connected to them, standards have naturally beendeveloped and updated to take changes into account. The IEC 60364 standardand its various national equivalents specify the requirements concerningelectrical installations in buildings. Chapter 6 describes the requirements fortesting the compliance of an installation.The effectiveness of the safety measures implemented can only be guaranteed ifregular tests prove they are operating correctly. This is why the standards covernot only the initial verifications when installations are commissioned, but alsoperiodic testing.

Electrical installation safetyEvery installation shall be verified during erection, as far as reasonably practicable,and on completion, before being put into service. Precautions shall be taken toensure that the verification shall not cause danger to persons or livestock and shallnot cause damage to property and equipment even if the circuit is defective.It shall be verified that an extension, addition or alteration to an existing installationcomplies with the IEC 60364 series and does not impair the safety of thatinstallation, and that the safety of the new installation is not impaired by the existinginstallation.The electrical testing is divided into 2 parts:1.Visual inspection to guarantee that the installation complies with the safetyrequirements (presence of an earth electrode, protective devices, color of the cables,etc.) and does not show any visible evidence of damage.2.MeasurementsMeasuring instruments and monitoring equipment and methods shall be chosen inaccordance with the relevant parts of the IEC 61557 series. If other measuringequipment is used, it shall provide no less a degree of performance and safety.

Installation safety testsThe following tests shall be carried out where relevant and should preferably bemade in the following sequence:a) continuity of conductors;b) insulation resistance;c) insulation resistance testing to confirm the effectiveness of protection by SELV,PELV or electrical separation;d) insulation resistance testing to confirm the effectiveness of floor and wallresistance/impedance;e) polarity test;f) testing to confirm effectiveness of automatic disconnection of supply;g) testing to confirm the effectiveness of additional protection;h) test of phase sequence;i) functional tests;j) voltage drop.In the event of any test indicating failure to comply, that test and any preceding test,the results of which may have been influenced by the fault indicated, shall berepeated after the fault has been rectified.

a) Continuity of conductorsThe continuity of conductors and connection to exposed-conductive-parts, if any,shall be verified by a measurement of resistance on protective conductors, includingprotective bonding conductors, exposed-conductive-parts, and in the case of ringfinal circuits, live conductors. The continuity shall be measured:a)between the earth electrode and the earth collector,b)between the earth collectors (if there are more than one),c)between the exposed-conductive-parts and the earth collector(s),d)between the exposed-conductive-parts (if there are more than one).If the measurement is carried out by generating AC current, it is advisable tocompletely unwind the test cables to avoid variations of their impedance that wouldaffect the compensation performed.If the measurement is carried out by generating DC current, it is advisable to use aninstrument that can reverse the polarity and carry out two tests, providing bothmeasures.

b) Insulation resistanceGood insulation is essential to prevent electric shocks. The insulation resistanceshall be measured between live conductors, and live conductors and the protectiveconductor connected to the earthing arrangement.The power must be switched off and the installation must be disconnected beforeperforming this test to ensure that the test voltage will not be applied to otherequipment electrically connected to the circuit to be tested.To measure the insulation resistance the test voltage is applied between conductors.The stray capacitance between active conductors and ground slows the voltagechange, hence test voltage time rises.Test instrument shall generate voltage for a sufficient time for the transients to dieout so that a steady test voltage value is reached.

c) Insulation resistance testing to confirm the effectivenessof protection by SELV, PELV or electrical separationThe separation of live parts from those of other circuits (protection by PELV) andfrom earth (protection by SELV or electrical separation) shall be confirmed by ameasurement of the insulation resistance.The resistance value obtained shall be at least that of the circuit with the highestvoltage present in accordance with the following table.Nominal circuit voltageDC test voltage [V]Insulation resistance [MΩ]SELV and PELV250 0,5Up to and including 500 V,including FELV500 1,0Above 500 V1.000 1,0

d) Insulation resistance/impedance of floors and wallsWhen it is necessary to comply with the requirements of IEC 60364-4-41:2005,Clause C.1, at least three measurements shall be made in the same location, one ofthese measurements being approximately 1 meter from any accessible extraneousconductive-part in the location. The other two measurements shall be made atgreater distances. The measurement of resistance/impedance of insulating floorsand walls is carried out with the system voltage to earth at nominal frequency.The above series of measurements shall be repeated for each relevant surface ofthe location.Current I is fed through an ammeter to the test electrode from the output of thevoltage source or from the phase conductor L. The voltage U at the electrode ismeasured by means of a voltmeter with internal resistance of at least 1 MΩ towardsPE. The impedance of the floor insulation will then be ZX UX / IThe measurement for ascertaining the impedance shall be carried out at as manypoints as deemed necessary, selected at random, with a minimum of three.

e) PolarityWhere relevant, the polarity of the supply at the origin of the installation shall beverified before the installation is energized.Where single pole switching devices are not permitted in the neutral conductor, atest shall be made to verify that all such devices are connected in the lineconductor(s) only.During the polarity test, it should be verified that:a) every fuse and single-pole control and protective device is connected in the lineconductor only, andb) except for E14 and E27 lamp-holders according to IEC 60238, in circuits havingan earthed neutral conductor center contact bayonet and Edison screw lampholders, the outer or screwed contacts are connected to the neutral conductor,andc) wiring has been correctly connected to socket-outlets and similar accessories.

f) Protection by automatic disconnection of supplyIn the protection against indirect contactsby automatic interruption of the powersupply, the protection device (RCD /MCB / FI / fuse) must trip in case ofground fault so that a contact voltagehigher than the limit indicated by theregulation can not persist for adangerous time for people.For the purpose of coordinatingprotection against indirect contacts, thestructures of the plants and thedistribution systems have to beconsidered. Tests depend on thecomposition of the fault circuit.Special conditionsOrdinary conditions

Automatic disconnection of supply – TNFor a TN system the following tests shall be performed:1. Measurement of the earth fault loop impedance.2. Verification of the characteristics and/or the effectiveness of the associatedprotective device. This verification shall be made:- for overcurrent protective devices, by visual inspection or other appropriatemethods (i.e. short time or instantaneous tripping setting for circuit-breakers,current rating and type for fuses);- for RCDs, by visual inspection and testing.The effectiveness of automatic disconnection by RCDs shall be verified usingsuitable test equipment according to IEC 61557-6 confirming that the relevantrequirements in IEC 60364-4-41 are met taking into account the operatingcharacteristic of the device. The effectiveness of the protective measure isverified if disconnection occurs with a fault current lower than or equal to therated residual operating current IΔn.It is recommended that the disconnection times required by IEC 60364-4-41 beverified.

Automatic disconnection of supply – TNThe fault circuit always involves the protective conductor, while it does not involvethe earthing electrodes.Power centerLoadPowerdistributorFaultcurrent

Automatic disconnection of supply – TNThe fault loop impedance value shall be coordinated to the rated current/curve andthe short circuit breaking capacity of the protection device. To check the specifics ofthe protective devices such as fuses or MCBs, a fault loop impedance measurementis carried out to calculate the corresponding short-circuit/fault current.The condition ISC Ia shall be fulfilled in any part of the circuit. The prospective shortcircuit current ISC is given by Uo / Zs where Uo is the nominal voltage and Zs is thefault loop impedance. Ia is the current triggering the active protections within 0.4 s.Prospective short-circuit currentEvaluation of the measureFault loop impedanceType C MCB, 16 A

Automatic disconnection of supply – TTFor a TT system the following tests shall be performed:1) Measurement of the resistance RA of the earth electrode for exposedconductive-parts of the installation.2) Verification of the characteristics and/or the effectiveness of the associatedprotective device. This verification shall be made:- for overcurrent protective devices, by visual inspection or other appropriatemethods (i.e. short time or instantaneous tripping setting for circuit-breakers,current rating and type for fuses);- for RCDs, by visual inspection and testing.The effectiveness of automatic disconnection by RCDs shall be verified usingsuitable test equipment according to IEC 61557-6 confirming that the relevantrequirements in IEC 60364-4-41 are met taking into account the operatingcharacteristic of the device. The effectiveness of the protective measure isverified if disconnection occurs with a fault current lower or equal to the ratedresidual operating current IΔn.It is recommended that the disconnection times required by IEC 60364-4-41 beverified.

Automatic disconnection of supply – TTThe fault circuit always involves the ground between the user earth electrode andthe center of the secondary winding of the power transformer. The current closesthrough the ground to the generator by the grounded center of the secondarywinding.The earth resistance value shall be coordinated to the rated differential current of theactive protection device. The earth resistance value of the typical TT system (lowvoltage consumer) should not exceed the product of 50 V / IΔn.P o w e rtransformerearthingL o c a learthingFault current

Automatic disconnection of supply – TTThe RCD is a device designed to quickly and automatically disconnect a circuitwhenever the current is not balanced between the supply and return conductors(indicating leakage current), which presents a shock hazard.IEC 60755 defines three types of RCD depending on the waveforms and frequencyof the fault current:-type AC RCD that trips on sinusoidal residual currents,-type A RCD also responding to pulsating or continuousdirect currents of either polarity,-type B RCD also responding to higher frequency currentsor for combinations of alternating and direct currents.There are three groups of devices according to the trip time:-G general RCDs (must not trip at ½ of the nominalcurrent rating, maximum trip time 300 ms for rated current),-S selective RCDs (must not trip at ½ of the nominal currentrating, providing a delay of tripping at rated current),-R time-delayed RCDs (must not trip at ½ of the nominal currentrating, providing a user-selectable delay of tripping at rated current)

Automatic disconnection of supply – TTThe RCD tripping time test shall be performed on a live installation. Where the circuitincludes equipment that is likely to influence the results, such equipment shall bedisconnected.The suitable test equipment shall operate according to IEC 61557-6 confirming thatthe relevant requirements in IEC 60364-4-41 are met.Measured tripping timesEvaluation of the measure according to the IEC 60364-4-41General RCDType AC RCD, 30mA

Automatic disconnection of supply – ITFor a IT system compliance with the rules shall be verified by calculation ormeasurement of the current Id in case of a first fault of a live conductor. Precautionsare to be taken while making the measurement in order to avoid the danger due to adouble fault.In the case of a double earth fault, the fault loop impedance shall be verified bycalculations or by measurements. Where the condition is similar to that of a TTsystem, verification shall be made as for a TT system. Where conditions are similarto that of a TN-system, verification by measurement shall be made as for TNsystems.

Automatic disconnection of supply – IT systemsFirst fault circuit closes through the protective conductor and, through the groundand the parasitic capacitances on the two live cables not involved in t

requirements in IEC 60364-4-41 are met taking into account the operating characteristic of the device. The effectiveness of the protective measure is verified if disconnection occurs with a fault current lower than or equal to the rated residual operating current IΔn. It is recommended that the disconnection times required by IEC 60364-4-41 be .

Related Documents:

MS IEC 60364–7–710 Water Features and Fountains IEC 60364–7–702 Swimming Pool IEC 60364–7–702 Agriculture & Horticulture IEC 60364–7 705 Marina’s: IEC 60364–7–709 Bath room: IEC 60364–7–701 Masuk Sakit, Keluar Mati Masuk Lebih Kurang Mati, Keluar Sahat

IEC has formed IECRE for Renewable Energy System verification - Component quality (IEC 61215, IEC 61730, IEC 62891, IEC 62109, IEC 62093, IEC 61439, IEC 60947, IEC 60269, new?) - System: - Design (IEC TS 62548, IEC 60364-7-712, IEC 61634-9-1, IEC 62738) - Installation (IEC 62548, IEC 60364-7-712)

IEC 60634-1 IEC 60050-826 IEC 60364-4-41 IEC 60364-4-42 IEC 60364-5-52 IEC/DIS 64(CO)9173 IEC 60204-32 IEC 60529-1989; IEC 60529 IEC 60529 Accident prevention regulation "Electrical systems and apparatus" Accident prevention regulatio

IEC 60634-1 IEC 60050-826 IEC 60364-4-41 IEC 60364-4-42 IEC 60364-5-52 IEC/DIS 64(CO)9173 IEC 60204-32 IEC 60529-1989; IEC 60529 IEC 60529 Accident prevention regulation "Electrical systems and apparatus" Accident prevention regulation "Cranes" Safety instructions "Monorails"

IEC 61215 IEC 61730 PV Modules Manufacturer IEC 62941 IEC 62093 IEC 62109 Solar TrackerIEC 62817 PV Modules PV inverters IEC 62548 or IEC/TS 62738 Applicable Standard IEC 62446-1 IEC 61724-1 IEC 61724-2 IEC 62548 or IEC/TS 62738 IEC 62548 or IEC/TS 62738 IEC 62548 or IEC/TS 62738 IEC 62548 or IEC/

02 Basics of IEC 62446 Overview of sub standards . IEC 62446. IEC 60364 (all parts) IEC 60364-6 IEC 60364-7-712:2002 . IEC/TR 60755:2008 . IEC 61557 (all parts) IEC 61730-1 - Clause 4 - System documentation requirements - Clause 5 - Verification . 4.1 General . 4.2 System data . 4.3 Wiring diagram . 4.4 Datasheets . 4.5 Mechanical design .

IEC 60364-1 (mod) 2005 Low-voltage electrical installations - Part 1: Fundamental principles, assessment of general characteristics, definitions HD 60364-1 2008 IEC 60364-4-41 (mod) 2005 Low-voltage electrical installations - Part 4-41: Protection for safety - Protection against electric shock HD 60364-

Különleges berendezések MSZ HD 60364-7-712:2006 2. Napelemes (PV) energiaellátó rendszerek MSZ HD 60364-7-714:2013 Szabadtéri világítóberendezések (IEC 60364- 7-714:2011) MSZ HD 60364-7-715:2012 Törpefeszültségű világítási berendezések MSZ HD 60364-7-717:2010 Mobil vagy szállítható egységek MSZ HD