Ceiling Concealed Chilled Water Fan Coil Unit

2y ago
36 Views
3 Downloads
2.53 MB
19 Pages
Last View : 5d ago
Last Download : 3m ago
Upload by : Sasha Niles
Transcription

Technical ManualCeiling Concealed Chilled WaterFan Coil UnitModels:Air Flow:MCW200 MCW300 MCW400 MCW500MCW600 MCW700 MCW800 MCW1000MCW1200 MCW1400340-2380m3/hEngineered for flexibility and performance. TMMCW-V-2013

Literature No.: TM-MCW-V-1310ASupersedes:Part No.: M08039130028ContentsNomenclature 2Valve Nomenclature 3Features 4Specifications 5Sound Data 6Air Flow vs ESP Curve 7Operating Limits 8Water Flow Rate/Pressure Drop Chart 9Outlines and Dimensions 10Electrical Data 11Wiring Diagrams 12Installation 13NOTE: Installation and maintenance are to be performed only by qualified personnel who arefamiliar with local codes and regulations, and experienced with this type of equipment.Caution: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.Warning: Moving machinery and electrical power hazard. May cause severe personalinjury or death. Disconnect and lock off power before servicing equipment.“McQuay” is a registered trademark of McQuay International. All rights reserved throughout the world. 2013 McQuay International“Bulletin illustrations cover the general appearance of McQuay International products at the time of publicationand we reserve the right to make changes in design and construction at any time without notice.”1

NomenclatureMCW 200V C 3 R C X-A 0 A ESales Region:E: ExportPower Supply:A: 220V /50 HzOther Feature CodesMaterial of Drain PanFilter:X: no filterF: 8mm nylon filterA: 8 mm aluminum filterReturn Air Plenum:C: without return air plenumB: back return air plenumD: bottom return air plenumPipe Connection:R: facing air flow right handL: facing air flow left handExternal Static Pressure: 1: 12 Pa3: 30 Pa5: 50 PaCoil Type:C: 3 rowsUnit Design SNRated Air Volume (CFM, 1 CFM 1.7 m3 /h)McQuay Ceiling Concealed Horizontal Fan Coil Unit2

Valve NomenclatureMCW - 2V 4 Y B R A EE-ExportU-Stick "Made In China"Power Supply:A-220-240V/1Ph/50HzK-208-230V/1Ph/60HzPipe ConnectionR-for Right hand unitL-for Left hand unitValve TypeB-with Ball ValveX-without Ball ValveStrainer TypeY-with Y-StrainerX-without Y-StrainerUnion SizeOmitted-R3/44-R1Valve model2V:2-Way Valve Kit3V:3-Way Valve KitMCW-McQuay FCU(Only 2-pipe system is applicable)3

FeaturesCompact Light-weighted, good-looking appearance, and compact and solid structure. 235 mm height, allowing installation on the ceiling with a limited space.Low-noise Low-noise motor for driving the low speed fan with a wide impeller; strictly tested before delivery.   Precise distance between the impeller inlet/outlet and the heat exchanger for more reasonable air flowdistribution.   Highly efficient sound-absorbing and heat-preserving materials inside to minimize noises produced by the unit.Reliable   Single-phase capacitor motor with the protection grade IP20 and insulation grade B to ensure operation safety.   Permanently lubricated and sealed ball bearing with high precision, which is provided by internationally famousbrands and receives processing including hardening and tempering as well as chroming. Motor power outlet wires protected by metal hoses to ensure its durability.   Working pressure up to 1.6 MPa and test pressure up to 2.0 MPa for the heat exchanger to endure highpressures and prevent leakage.High Efficiency   Heat exchanger with the high-quality mechanically expanded copper pipe and hydrophilic aluminum fins toensure high efficiency.   Intensified air supply using a large air flow fan with a wide impeller to maximize the heat transfer performance. Precise matching of the fan and motor to guarantee the maximum cooling capacity but a low power input.Flexible   Multiple external static pressures designed based on the unit’s cooling capacity, meeting the air supplyrequirements at different distances.   Optional bottom return air plenum or back return air plenum with support for onsite changes, featuring timesaving. Variable accessories for more options.Anti-leakage   Delicate condensate-proof drain pan made of the cold-rolled steel through one-time impact molding, withcoating on both sides and high-quality heat-preserving materials on the exterior.   Unique independent mounting bracket without soldering seams or joints, requiring no bolts for fixing to preventdamages to the drain pan heat-preserving layer or cold bridges. Tilt structure for rapid condensate water drainage.4

SpecificationsGeneral DataMCW-VCMCW200VC MCW300VC MCW400VC MCW500VC MCW600VC MCW700VC MCW800VC MCW1000VC MCW1200VC 00120014003m 049233265682098411483m 00166400500600700EXTERNALPa/in.wgSTATIC PRESSURETOTAL COOLINGCAPACITYSENSIBLECOOLINGCAPACITYTOTAL HEATINGCAPACITYWATER FLOWRATEHEAD LOSS(COOLING)UNIT WEIGHT(WITHOUTPLENUM)DIMENSIONSUNIT GROSSWEIGHT(Without 9.242.845.063.771.478.084.9WithoutReturnAir Plenummm625 465 235 815 465 235 865 465 235 945 465 235 1045 465 235 1095 465 235 1425 465 235 1475 465 235 1675 465 235 1825 465 235With BackReturnAir Plenummm625 516 235 815 516 235 865 516 235 945 516 235 1045 516 235 1095 516 235 1425 516 235 1475 516 235 1675 516 235 1825 516 235With BottomReturnAir Plenummm625 497 235 815 497 235 865 497 235 945 497 235 1045 497 235 1095 497 235 1425 497 235 1475 497 235 1675 497 235 1825 497 235UNIT WEIGHT(With b29.135.336.842.546.749.469.076.783.891.5UNIT GROSSWEIGHT(With TEDRAIN SIZER3/4NOTES:1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL THE UNITS ARE BEING TESTED UNDER FOLLOWING CONTITION: COOLING-27 C DB/19.5 C WB INDOOR AND WATER INLET 7 C OUTLET 12 C HEATING-21 C DB INDOOR AND WATER 60 C INLET.WATER FLOW:WAME WITH COOLING CONDITION.3) SOUND PRESSURE LEVEL ARE ACCORDING TO MICROPHONE POSITION OF THE MEASUREMENT POINTIS 1m IN FRONT AND5

Components DataMCW-VCMCW200VC MCW300VC MCW400VC MCW500VC MCW600VC MCW700VC MCW800VC MCW1000VC MCW1200VC MCW1400VCTYPEGALVANIZED STEEL DOUBLE STAGE IMPELLER CENTRIFUGAL (BLADE: ULATION OPHILIC ALUMINUMTHICKNESSFACE .66ROW3FIN PER INCH17TYPENYLON/ALUMINIUM FRAMELENGTHAIRFILTER(Option) SIZE4COPPERTHICKNESSFIN4IP20/BMATERIALCOIL3SINGLE PHAZE BALL BEARING CAPACITOR RUNNINGQUANTITYTUBE3DIRECT DRIVEDIAMETERMOTOR2GALVANIZED 5764.47mm196in7.71mm8in0.31NOTES:ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.Sound DataMCW-VCModelMCW200VC MCW300VC MCW400VC MCW500VC MCW600VC MCW700VC MCW800VC MCW1000VC MCW1200VC MCW1400VCSoundHighdBAPressure LevelMiddle dBA(ESP: 025.629.827.927.432.633.438.0SoundHighdBAPressure LevelMiddle dBA(ESP: 30 827.327.329.430.636.434.735.5SoundHighdBAPressure LevelMiddle dBA(ESP: 50 331.333.937.331.837.641.741.0NOTES:1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) SOUND PRESSURE LEVEL ARE ACCORDING TO MICROPHONE POSITION OF THE MEASUREMENT POINT IS 1mIN FRONT AND 1m BELOW THE UNIT.6

Air Flow vs ESP CurveAir Flow, m3/hESP, 12PaESP, PaAir Flow, m3/hESP, 30PaESP, PaAir Flow, m3/hESP, 50PaESP, Pa7

Operating LimitsOperating LimitsWater CircuitMax. Water side pressureMin. Entering water temperaturePower supplyOperating voltage limitsOperating frequency limitsMCW-V1.6MPa3ºC (cooling) 10% Volt 2Hz8

Water Flow Rate/Pressure Drop ChartMCW-VCWATER PRESSURE DROP CURVE(3 Rows)65WATER PRESSURE DROP 00.10.20.30.40.50.60.70.80.911.11.21.31.4WATER FLOW m3/h91.51.61.71.81.922.12.22.3

Outlines and DimensionsWITHOUT PLENUMDModelModel40A ADrain PanMCW200V 62514235151143226304435WATER SUPPLYCONNECTIONRc3/4″WATER RETURNCONNECTIONRc3/4″4651052075187CONDENSATE DRAINR3/4″AIR VENTBCA20 8131725MCW200V625MCW300V 815MCW300V815MCW400V 865MCW400V865MCW500V 945MCW500V945MCW600V 1045MCW600V1045MCW700V1095MCW700V1095MCW800V 1425MCW800V1425MCW1000V 1475MCW1000V1475MCW1200V 1675MCW1200V1675MCW1400V 1825MCW1400V1825MOUNTING HOLE 4-10 16242262BStandardLongStandardDrain PanDrain PanLongDrain 02 437592627915592 627642677965642 6777227571045722 7578221145822 857857872 872 90711959071202 1202 1237152512371252 1252 1287157512871452 1452 1487177514871602 1602 163719251637DD440NumberNumberOf FansOf 129014901490164016401222222222223334444WITH BACK PLENUMEFModelModel146TERMINAL BOXMOUNTING HOLE 4-10 16187CONDENSATE DRAINR3/4″AIR VENTBCA3523218023515122614330516WATER SUPPLYCONNECTIONRc3/4″WATER RETURNCONNECTIONRc3/4″131BDrain Pan Drain PanMCW200V 6254044AAStandardDrain Long DrainStandardLongPanPanMCW200V625MCW300V 815MCW300V815MCW400V 865MCW400V865MCW500V 945MCW500V945MCW600V 1045MCW600V 1045MCW700V1095MCW700V 1095MCW800V 1425MCW800V1425MCW1000V 1475MCW1000V1475MCW1200V 1675MCW1200V1675MCW1400V 1825MCW1400V1825725B C C402437DD440EEFF472420725402 437 440 472630 662592627915915592 627 630 662680 712642677965965642 677 680 7121045760 7927227571045722 757 760 79211451145 822822857857 860860 89289211951195 872872907907 910910 94294215251525 120212021237123712401240 1272127215751575 125212521287128712901290 1322132217751775 145214521487148714901490 1522152219251925 160216021637163716401640 16721672Number OfNumberFansOf 127014701470162016201222222222232334444242262WITH BOTTOM PLENUMEModelModel146TERMINAL BOXMOUNTING HOLE 4-10 16BCA497WATER SUPPLYCONNECTIONRc3/4″WATER ONDENSATE DRAINR3/4″AIR VENT131242262( 175)1635217Drain Pan Drain PanMCW200V 6254038AAStandardDrain Long DrainStandardLongPanPan䖛 㔥ᣵᵓG10MCW200V625MCW300V 815MCW300V815MCW400V 865MCW400V865MCW500V 945MCW500V945MCW600V 1045MCW600V1045MCW700V1095MCW700V1095MCW800V 1425MCW800V1425MCW1000V 1475MCW1000V1475MCW1200V 1675MCW1200V1675MCW1400V 440CD402 437 440630630680642 677 680722757760722 757 760822857860822 857 860872910872 907907 910124012021202 12371237 1240125212901252 12871287 1290145214901452 14871487 1490160216401602 16371637 1640592627592 627642677EE472Number OfNumberGG OfFansFans441472 441662581662 581712681712 681792761792 761892861892 861942 9119119421272 1241124112721322 1291129113221522 1491149115221672 16411641167211222222222223334444

Electrical DataMCW-VCMODELMCW200VC MCW300VC MCW400VC MCW500VC MCW600VC MCW700VC MCW800VC MCW1000VC MCW1200VC MCW1400VCINSULATION GRADEPOWERSOURCERATED INPUT12PaPOWERMOTORRATEDRUNNINGCURRENTBV/Ph/Hz220 430.520.610.700.861.12POLES4PINSULATION GRADEBPOWERSOURCERATED INPUT30PaPOWERMOTORRATEDRUNNINGCURRENTV/Ph/Hz220 .490.560.650.801.001.19POLES4PINSULATION GRADEBPOWERSOURCERATED INPUT50PaPOWERMOTORRATEDRUNNINGCURRENTV/Ph/Hz220 .510.600.770.921.091.45POLES4PNOTES:1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL ELECTRIC DATA ARE BEING TESTED UNDER HIGH SPEED.11

Wiring DiagramsMolde: CW 200 1400HBLUEMLFAN SPEED TORCAPACITORL(220V /50Hz)NBLUEYELLOWBLACKBROWNORANGENOTE:HF: FAN SPEED HIGHMF: FAN SPEED MEDIUMLF: FAN SPEED LOW— — — — — FIELD WIRINGFANMOTORBLACK2Only unit 800 1200 have fan motor212MOTORCAPACITOR

InstallationReceivingAll units leaving the McQuay plant have been inspected to ensure the shipment of high quality products andreasonable means are utilized to properly pack the fan coil units to protect them in transit.Carefully inspect all shipments immediately upon delivery. When damage is visible, note this fact on thecarrier’s freight bill and request that the carrier sends a representative to inspect the damage. This may bedone by telephone or in person, but should always be confirmed in writing.The shipment should be unpacked in the presence of the agent so that the damage or loss can bedetermined.The carrier’s agent will make an inspection report and a copy will be given to the consignee for forwardingto the carrier with a formal claim.LocationBefore installation, please check the following:There must be enough space for unit installation and maintenance. Please refer to the unit’s drawings anddimensions and fig.1 for the minimum distance between the unit and obstacle.Please ensure enough space for piping connection and electrical wiring.Please make sure that the hanging rods can support weight of the unit.InstallationThe unit is designed for concealed ceiling installation.There are holes on the top of the unit for hanging. Please refer to Fig.1.Fig.2 and Fig.3.Make sure that the top of the unit is level.Insulation1)2)3)4)Use proper insulation material onlyChilled water pipes and all parts on the pipes should be insulatedIt is also necessary to insulated air ductedAdhesive for insulation should work under range 0 F(-18 C) to 200 F(93.3 C).Fig.1OBSTACLEBACEILINGA 200mmB 400mm13C 265mmCOBSTACLE

Fig.2 WITH AND WITHOUT PLENUM FORM:ATerminal blockCeiling accessPanel with air returnDischarge airReturn airFig.3 DETAIL A:EXP ANSION SCREWNUTRECOMMENDED THEDIAMETER IS 6-8MMHANGING RODFANCOILFLAT WASHERAir Duct ConnectionCirculatory air pressure drop should be within External Static PressureGalvanized steel air ducts are suitableMake sure there is no leak of air.Air duct should be fireproof, refer to concerned country national and local regulations.Pipe ConnectionUsing suitable fittings as water pipe connections. Refer to the specificationThe water inlet is on the bottom while outlet on top.The connection must be concealed with rubberized fabric to avoid leakage.Drainpipe can be PVC or steel.The suggested slope of the drainpipe is at least 1:50.Wiring1) Wiring connection must be done according to the wiring diagram on the unit.2)3)4)5)The unit must be GROUNDED well.An appropriate strain relief device must be used to attach the power wires to the terminal box.A 7/8” knockout hole is designed on the terminal box for field installation of the strain relief device.Field wiring must be complied with the national security regulations.14

Valve KitThe valve kit is applied for 2-pipe system.The kit consists of (refer structure figure 0): 2/3 way valve body is made of brass, maximum working pressure 1.6MPa. Electric actuator has the following specifications:-Power supply: 220V 10%/50/60Hz ( 2Hz)-Activation: ON/OFF Hydraulic kit for the installation of the valve on the heat exchanger, complete with 2 ball valves foradjusting the water flow and for closing the water circuit when perform maintenance to the unit. Y-strainer protects unit from impurity, increases the service life and insolating valves.Figure 0All parts of 2-way valve kit are indicated in the figure 1. ( For right pipe connection unit.)FEA Ball valveB Brass connectorC Y-strainerD Water inlet pipeE Water outlet pipeF 2-way valveABCFigure 1DAll parts of 3-way valve kit are indicated in the figure 2. ( For right pipe connection unit.)GFABCEA Ball valveB Brass connectorC Y-strainerD Connector pipeE Water inlet pipeF 3-way valveG Water outlet pipeDFigure 215

Installation1. Install the 2-way valve kit as indicated in the pictures of figure 3. (For right pipe connection unit.) Asshown as detail A, firstly take apart connector, then install ① to unit with necessary sealing material . Fix② between ① and ③. At last tighten ③, make sure all of connectors are sealed.2. Install the 3-way valve kit as indicated in the pictures of figure 4. (For right pipe connection unit.) Detail isas same as 2-way valve unit.The valve kit has been pre-assembled for easy installation. Where needed the connections are pre-coated with sealing material. The connections are not tightened for easy adjustment. After determining the final position of the valve kit, tighten all connections to obtain water tightness.WATER RETURN CONNECTION Rc3/4WATER SUPPLY CONNECTION Rc3/4209Ĺ22020365ķAĸ146Detail AFigure 32-Way Valve218153300ĹķĸDetail AWATER RETURN CONNECTION Rc3/4WATER SUPPLY CONNECTION Rc3/4120210A16

Insulation1. The insulation design and materials should be complying with local and national codes and regulations.2. Chilled water pipes and all parts on the pipes should be insulated.The flow resistance of the connecting valve/hydraulic kit assembly is obtained from the following formula: PW (QW/100Kv)2PW is the flow resistance (Pa)QW is the water flow rate (m3/h)Kv is the flow rate identified in the tableValve ModelDNConncetionTypeValve TypeKVShut-off PressureDifference (MPa)MC-FCV3335G20Rc3/4"3-way Valve3.40.18MC-FCV2334G20Rc3/4"2-way Valve3.00.18Pipe Connection1.2.3.4.Using suitable fittings as water pipe connections with reference to the outline and dimensions.The water inlet is on the bottom while outlet on top.The connection must be concealed with rubberized fabric to avoid leakage.Tightening torque should not be too high when connecting water pipes, in order to avoid brass deformationor water-leakage by torsion split.Wiring1. Refer to the wiring diagram of the appropriate controller.2. For connection with the McQuay controller, position the water temperature probe into the appropriateposition. Refer to the dedicated controller installation and operation manual.17

ISO 9001Certificate No.: 9601019 2013 McQuay International 1 (800) 432-1342BS-OHSAS 18001Certificate No.: 7644ISO 14001Certificate No.: EMS 80362www.mcquay.comWhile utmost care is taken in ensuring that all details in the publication are correct at the time of goingto press, we are constantly striving for improvement and therefore reserve the right to alter modelspecifications and equipment without notice.Details of specifications and equipment are also subject to change to suit local conditions and requirementsand not all models are available in every market.

Fan Coil Unit Technical Manual Engineered for flexibility and performance.TM MCW-V-2013 . McQuay Ceiling Concealed Horizontal Fan Coil Unit. 3 Valve Nomenclature MCW - 2V 4 Y B R A E MCW-McQuay FCU . ALL THE UNITS ARE BEING TESTED UNDER FOLLOWING CONTITION:

Related Documents:

4"- CTK4ZW Concealed Fixture Trim CONCEALED FIXTURE TRIM: 48" - CTK48ZW Concealed Fixture Trim 6" - CTK6ZW Concealed Fixture Trim 72" - CTK72ZW Concealed Fixture Trim 24" - CTK24ZW Concealed Fixture Trim 96" - CTK96ZW Concealed Fixture Trim 2.6.1 General The edge details on the Optima and Lyra Concealed product are

Fan Coil Systems Fan Coil Systems Cooling only Heating only Heat pump 5 Fan Coil Systems Fan Coil Systems I Fan Coil Units pages 7-40 FAN COIL UNITS PAGE 1 1 FWH(M)/FWV(M) 7 CEILING SUSPENDED UNIT CONCEALED CEILING UNIT LOW WALL UNIT CONCEALED LOW WAL

integrated in narrow ceiling voids Concealed ceiling unit with medium ESP A * For FBQ50D RXS50L * NEW NEW NEW NEW NEW Easy to install and to set-up › Unique Automatic air flow adjustment function selects the most appropriate fan curve to achieve the best comfort. With these concealed ceiling

Exposed Cabinet Fan Coil E2-10 HFI Horizontal Standard, Recessed Ceiling Fan Coil E2-13 HFHP Horizontal Standard, Concealed with Plenum Fan Coil E2-7 HFH Horizontal Standard, Concealed Ceiling Fan Coil E2-4 VPH Vertical Stack, Recessed Hi-Rise Fan Coil E2-56 VPHP / VPHS Vertical Stack, Recessed Primary / Seco

calculation. FAN SPEED 0000 RPM Displays fan real time speed based on the fan frequency reading. FAN OUTPUT FREQUENCY 000.0 Hz Displays the output frequency of the fan inverter. FAN OUTPUT CURRENT 000.0 A Displays the output current of the fan inverter. FAN OUTPUT VOLTAGE 000.0 V Displays output voltage of the fan inverter. FAN OUTPUT POWER

CF E 48 0009 IV MC CF EP 48 0009 BR MC 1200 mm 1200 mm 1200 mm 1200 mm 2550.00 2550.00 2550.00 2550.00 4 4 4 Pearl White earl Gold Pearl Ivory 4 Pearl Brown Ceiling Fan Ceiling Fan Ceiling Fan Ceiling Fan G AIR AIR 9 G BREEZE CRUZE240. CEILING FANS ITEM CODE COLOUR SWEEP MRP PKG Rose Gold Metallic Gold Metallic Silver

Ceiling Cassette Ceiling Convertible Fan Coil Unit Product Catalogue Ducted . Ceiling Convertible Type Ceiling Concealed Type Ducted Blower Type 20 24 Remark: All unit photos in this catalog are solely for illustration purpose, actual outlook may differ slightly. . The unit

(An Alex Rider adventure) Summary: After a chance encounter with assassin Yassen Gregorovich in the South of France, teenage spy Alex Rider investigates international pop star and philanthropist Damian Cray, whose new video game venture hides sinister motives involving Air Force One, nuclear missiles, and the international drug trade. [1. Spies—Fiction. 2. Adventure and adventurers—Fiction .