Product catalogIndoor liquid chillerCGWH Packaged Water-cooledliquid chillerCCUH Condenserless liquid chillerSizes: 115 - 120 - 125 - 225 - 230 - 235 - 240 - 250CG-PRC008-E4

IntroductionThe CGWH/CCUH chillers rangeequipped with Scroll compressorscombines the latest technologiesavailable to offer an optimumanswer for today s air-conditioningand process cooling applications:- Scroll compressor technology,with high performance, limitedmaintenance and longer life timedesign- Latest generation of Trane controls,with user friendly graphicalinterface and integral autoadaptive to guarantee maximumdependability- High efficiency heat exchangers,allowing significant savings onoperating cost- Integrated hydraulic packages,to shorten installation andcommissioning time.2 Trane 2013 CG-PRC008-E4

ContentsCG-PRC008-E4Introduction2Features and benefits5Options description7Application considerations9Control13Selection Procedures16Performances20General data21Hydraulic data23Sound performances24Units schematics253

Features and benefitsApplications: Operation and controladvantages for any applicationThe Scroll compressor technology,with fewer moving parts, lessrotating mass and less internalfriction, associated with CH530 andAdaptive Controls , allow the CGWH/CCUH range to be used in a widevariety of applications including:- Comfort cooling: designed forreliability, energy efficiency, andsystem-design optimisation,whether the heat is rejected viaan open cooling tower or a closedloop device (dry-cooler)- Industrial process cooling: reliableoperation with tight control oftemperatures- Ice/thermal storage- Heat recovery- Low-temperature process cooling.System design and control: Greaterapplication flexibility for increasedsavingsFirst-cost and operating costminimising system-design conceptsare catching on as their validityis proven through applications.These designs can provide lowerequipment costs and loweroperating costs than those possiblewith the traditional design methodsand past chiller technologies. Theconcepts of the CGWH/CCUH rangeinclude:- Heat exchangers with reducedwater pressure drops and widerwater flow/delta capability- Thermal storage capability- Variable primary (evaporator)chilled-water flow capability- Series evaporator and/orcondenser arrangementsThe CGWH/CCUH range is designedfor a wide range of applications andis especially suited for the dynamicsof these system saving job designs.The dynamic benefits include:- Efficient lift capability- Tight temperature control.CH530 controls mean that theCGWH/CCUH series chillers canmaintain tight leaving-watertemperature control in almost4any application. These benefits fitespecially well with the systemdesign savings ideas listed above.As the compressor reaches theoperating temperatures for theapplication, the controls, make sureyou have total temperature control,even with chilled-water flow and/orload changes.- Commissioning: Water cooledunits (CGWH) come from factoryfully charged with refrigerantand oil, condenserless version(CCUH) with nitrogen holdingcharge. Extensive factory testinghelps ensure trouble-free start-up,resulting in lower installation costsand faster job completion.Sound: Lower sound levels throughcompressor and chiller designTrane has a proven track recordof continuously improving thesound levels of water chillers. Withthe CGWH/CCUH range Trane hasdesigned a fully hermetic cabinetdesign which minimises soundradiation in the neighbourhood ofthe unit. The space around the chillercan be utilised without requirementof additional sound insulation. Onlythe sound produced by the remotecondenser fans can be perceived inthe surrounding of the installation,the sound of compressor isattenuated by the building structure.The Integrated comfort systemThe water-cooled CGWH/CCUHchiller, with the CH530, makes apowerful combination with theTrane Tracer Summit BuildingManagement System to becomepart of a Trane Integrated Comfortsystem (ICS). An Integrated Comfortsystem is a building comfortsystem composed of Trane HVACequipment, integral unit controllers,and building management. It isall designed and commissionedwith Trane application expertise toprovide comfort, efficiency, andreliability, as well as single-sourcewarranty and service. Whether youare replacing a chiller or adding oneto any centrally controlled plant,the Tracer CH530 chiller controlleroffers a wide range of interfaceoptions. Its ability to communicatewith other systems using industrystandard control signals allowsyou to upgrade the control of yourchiller plant regardless of yourcurrent control system.Minimised job time forcontractors through designand testingEase of installation- Footprint: Central to the designof any project is the operatingenvelope of the chiller. With thisin mind, Trane builds the chillersto make the most efficient use ofthe available installation space.The compact CGWH/CCUH rangechiller is an excellent choice forany retrofit or replacement job.It is smaller than most chillers itmight replace, and easier to fitinto existing buildings. All units fitthrough a standard single door.- Weight: Furthermore, thedecreased weight reduces therequirements for lifting, rigging,and installation. Installation timeand effort are reduced whendealing with a significantly smallerand lighter unit.Single-source responsibilityA wide range of products designedfor complete compatibility areavailable with the CGWH/CCUHscroll chillers. Your entire buildingcomfort system can be completedusing components from Trane.The added value of applicationsexpertiseYou get a quality chiller, properlyselected and applied in a properlydesigned system. That means acomfort system that works, the firsttime!CG-PRC008-E4

Features and benefitsReduced total life cycleoperating cost for buildingowner.Energy efficiency: Reduced annualoperating expensesThe CGWH/CCUH chiller designhas been optimized in order toachieve record efficiency levels.With the CH530 chiller controlmodule, control over the chilledwater temperature is increased,simultaneously reducing annualoperating costs. CGWH/CCUHchillers offer superior full-loadperformance and optimised partload performance.Reduced maintenance: Less timeand money every yearThe only recommendedmaintenance for a CGWH/CCUHchiller is an annual oil analysis.The hermetic design allows thecompressor to be driven by a zeromaintenance motor. The installationof strainers upstream the evaporatorand condenser (Option) eliminatesthe need for cleaning the heatexchangers tubes. The AdaptiveControl microprocessor also helpsreduce unnecessary maintenance bymonitoring, protecting, and takingcorrective action so that the chillerstays on-line when you need it themost. Service calls for nuisance tripouts are virtually eliminated.ReliabilityTrane has designed the CGWH/CCUH chiller range to be a leader inreliability for all applications:- Simple design with 64 percentfewer parts than equal capacityreciprocating compressor.- Advanced microelectronics protectboth compressor and motor fromtypical electrical fault conditions.- Scroll compressors have less thana third the torque variations of areciprocating compressor.- Years of laboratory testing haveoptimised compressor and chillersystems reliability.- Water-cooled scroll chillers arefactory tested.CG-PRC008-E4Comfort cooling: designed forreliability, energy efficiency, andsystem design optimisationMost comfort-cooling applicationsconsider reliability and energyefficiency above all else in thedesign requirements. Withproven reliability and high chillerefficiency, the CGWH/CCUH chillersare perfectly suited for theseapplications.Easy serviceabilityTrane CGWH/CCUH chillers aredesigned with service personnelin mind. All major components arereplaceable without complete unitdisassembly. Plus, CH530 providesdiagnostic capability to aid servicepersonnel in analysing problems.Therefore, in case a problem doesoccur, the chiller can be up andrunning in a shorter period of time.Industrial process cooling / Lowtemperature process: Reliableoperation with tight control oftemperaturesThe Trane CGWH/CCUH chillershave the proven reliability requiredto keep the process running,eliminating concerns for chiller andresulting process downtime. Thechiller matches system requirementsand rapidly adjusts to match thechanges seen by most processes.Ice / thermal storageThe Trane CGWH/CCUH chillers canbe used in partial or full thermalstorage applications because of theirexcellent compressor lift (operatingtemperature range) capability. Highreliability and low maintenancemeans thermal storage applicationsare possible without a full-timeoperation/maintenance staff, andTrane Integrated Comfort SystemControls can notify a computer orpager of any system issues.Heat recoveryThe Trane CGWH chillers compressorlift capabilities also play well in heatrecovery, or just high-temperaturecondenser applications. Buildingenergy saving initiatives such asusing condenser water for reheat(dehumidification), preheating boilerwater, and providing domestichot water are compatible with itstemperature capabilities.5

Options descriptionHydraulic pump control: Single or dual pump contactor.Hot water controlThis option allows the control of theunit capacity based on the leavingcondenser water temperature toprovide heat recovery capability.Phase protection deviceInhibits operation of chiller in caseof phase reversalSetpoint and temperature offsetand display cardAllows to offset chilled watersetpoint temperature based oneither ouside air, chilled waterreturn or zone temperature andprovides inlet/outlet condenserwater temperature information.Ice MakingThe unit controls are factory setto handle ice making for thermalstorage applications.Communication InterfacePermits bi-directionalcommunication to the TraneIntegrated Comfort system andprovides the LonMark chiller profileinput/outputs for use with a genericBAS (Building Automation System)Low Noise VersionThe unit is equipped withcompressor sound jackets.Pressure GaugesA set of two pressure gauges perrefrigerant circuit, one for lowpressure and one for high pressure.High Efficiency OptionThis option provides oversized heatexchangers to allow the unit to bemore energy efficient.6CG-PRC008-E4

Application considerationsOptimum performance of CGWHand CCUH units will be achievedonly if proper application guidelinesare followed.Where the application varies fromthe guidelines presented, it shouldbe reviewed with your local Tranesales engineer.Unit sizingUnit capacities are listed inthe Performance Data section.Intentionally oversizing a unit toassure adequate capacity is notrecommended. Erratic systemoperation and excessive compressorcycling are often a direct resultof an oversized unit. In addition,an oversized unit is usually moreexpensive to purchase, install andoperate. If oversizing is desired,consider using two units.FoundationsA special foundation is not required,provided the floor is flat, level andstrong enough to support the unit'sweight (see "General data" tables).Table 1 - Standard Operating Limitations - See performance data for specific informations.CGWHCCUHR407CR407CMin. leaving water temperature CDS 20 C 30 CMin. Sat discharge temperature CDS(Dew point)Max. leaving water temperature CDS 50 C 55 CMax. Sat discharge temperature CDS(Dew point)Min. leaving water temperature EVP-12 CMax. leaving water temperature EVP 12 CHP limitations in the tables 24.5 bar. (Limitation module 23 /- 1 bar / HP pressostat 26 bar).Discharge temperature limitations in the tables 130 C.CG-PRC008-E47

Application considerationsGround isolatorsWater treatment4 isolators are supplied as standard.They will protect the unit from anycontact with the ground.The use of untreated or improperlytreated water in chillers may resultin scaling, erosion, corrosion oralgae. It is recommended thatthe services of a qualified watertreatment specialist be obtained todetermine what water treatment,if any, is advisable. Trane assumesno responsibilty for the results ofuntreated, or improperly treatedwaterWater drainEnsure that near the unit is a largeenough drain to evacuate the waterwhen from the system emptying theunit for shutdown or repair.Water connectionWater connections are threaded ISOR7 type, location and diameter areindicated on the submittals availableon request.Minimum water volumeThe minimum recommended watervolume depends on the type ofapplication.Flow rate limitsThe minimum and maximum flowrates are indicated in the "Hydraulicdata" charts section. Too low a flowrate may cause freezing of theevaporator. Too high a flow rate maycause erosion of the evaporator andvery substantial pressure losses.If necessary, provide a buffer tank.The control and safety devices areonly certain to operate correctlyif the system's water volume issufficient.Table 2 - Minimum water loopCGWH ChillersDataSizes115120125225230235240250Cooling Capacity51 kW64 kW77 kW91 kW103 kW116 kW127 kW155 kWBiggest step50%60%50%42%38%34%30%25%Biggest step26 kW38 kW39 kW38 kW39 kW39 kW38 kW39 kWMinimum water loop forcomfort244 l368 l368 l365 l375 l377 l365 l371 lThis table is estimated withCondenser : Water 30 /35 CEvaporator : Water 12 /7 CDead Band of 3 CCCUH ChillersDataSizes115120125225230235240250Cooling Capacity51 kW64 kW77 kW90 kW102 kW115 kW127 kW153 kWBiggest step50%60%50%42%38%34%30%25%Biggest step26 kW38 kW38 kW38 kW39 kW39 kW38 kW38 kWMinimum water loop forcomfort244 l367 l367 l363 l371 l374 l365 l366 lThis table is estimated withCondensing temp : 45 C with sub cooling 5 CEvaporator : Water 12 /7 CDead Band of 3 C8CG-PRC008-E4

Application considerationsSplit systems pipingrecommendationsMaximum distances and refrigerantline diameters between unitsmust be checked according to theconfiguration and system operatingconditions (Chilled water temperatureand subcooling). Tables 3 to 7 providethe maximum acceptable heightaccording to subcooling availableand recommended diameters fordischarge liquid lines.Figure 1 - Installation configuration - CCUH and condenser at the same levelCCUHcondenser1: Discharge line2: Liquid lineFigure 2 - Installation configuration - CCUH below condenser1:condenserCCUHDischarge line2: Liquid lineCG-PRC008-E49

Application considerationsFigure 3 - Installation configuration - CCUH above condensercondenserH1: Discharge line2: Liquid lineTable 3 - Maximum elevation (H) of CCUH above condenserSubcooling C20 C4 C6 C8 C10 C12 C4m8m12 m16 m20 mCondensing dew temperature C35 C50 C6m12 m17 m23 m28 m8m16 m23 m30 m38 m65 C1020304049mmmmmTable 4 - REQUIRED DISCHARGE LINE DIAMETER CCUH circuit 1 (for vertical risers)Unit Leaving chilled water 1/87/8"7/8"1"1/8Table 5 - REQUIRED DISCHARGE LINE DIAMETER CCUH circuit 2 (for vertical risers)Unit size22523023524025010-12-10-8-6Leaving chilled water "1/81"1/81"1/881012141"3/81"3/8CG-PRC008-E4

Application considerationsTable 6 - REQUIRED LIQUID LINE DIAMETER CCUH circuit 1 (either vertical or horizontal)Unit size115120125225230235240250-12-10-85/8"-6Leaving chilled water 8"1"1/87/8"1"1/8Table 7 - REQUIRED LIQUID LINE DIAMETER CCUH circuit 2 (either vertical or horizontal)Unit "5/8"5/8"-6Leaving chilled water 81"1/811

ControlSafety ControlsA centralized microcomputeroffers a higher level of machineprotection. Because the safetycontrols are smarter, they limitcompressor operation in order toavoid compressor or evaporatorfailures, thereby minimizingnuisance shutdowns. Tracer ChillerControls directly senses the controlvariables that govern the operationof the chiller: evaporator pressure,condenser pressure. When anyone of these variables approachesa limit condition at which the unitmay be damaged or shut downon a safety, Tracer Chiller Controlstakes corrective action to avoidshutdown and keep the chilleroperating. It does this throughcombined actions of compressorstaging and pump staging. It hasalso the capability to control theremote condenser fan staging forcondenserless unit (CCUH). TracerChiller Controls optimizes totalchiller power consumption duringnormal operating conditions. Duringabnormal operating conditions,the microprocessor will continueto optimize chiller performanceby taking the corrective actionnecessary to avoid shutdown. Thiskeeps cooling capacity availableuntil the problem can be solved.Whenever possible, the chiller isallowed to perform its function:make chilled water. In addition,microcomputer controls allow formore types of protection, like winterfreeze protection; the safety controlshelp keep the building or processrunning and out of trouble.Stand-alone controlsInterfacing to stand-alone units isvery simple: only a remote auto/stopfor scheduling is required for unitoperation. Signals from the chilledwater pump contactor auxiliary, or aflow switch, are wired to the chilledwater flow interlock. Signals froma time clock or some other remotedevice are wired to the externalauto/stop input.12TracerTM Chiller Control human interfacesAdditional Features that May BeAdded (require some optionalfactory-installed hardware) Ice-making card Tracer communication card Chilled water and remote currentlimit set point card (note: allwiring outside the unit is suppliedby the contractor).Easy Interface to a GenericBuilding ManagementSystemStandard Features External Auto/StopA job-site-provided contact closurewill turn the unit on and off.Chilled Waterflow InterlockUnit is equipped with a water flowcontrol, it will allow unit operation ifa load exists. This feature will allowthe unit to run in conjunction withthe pump system.External InterlockA job-site-provided contact openingwired to this input will turn the unitoff and require a manual reset ofthe unit microcomputer. This closureis typically triggered by a job-siteprovided system such as a firealarm.Chilled Water Pump Control (Option)Unit controls provide an output tocontrol the chilled-water pump(s).One contact closure to the chilleris all that is required to initiate thechilled-water system.Alarm Indication ContactsFour factory-installed contactswith the following preset defaultassignments: Alarm Chiller running Maximum capacity Chiller limit.Controlling the Indoor CGWH/CCUHchillers with building managementsystems is state-of-the-art, yetsimple with either:- the LonTalk CommunicationsInterface for Chillers (LCI-C)- or Generic Building ManagementSystem Hardwire Points.Simple Interface with Other ControlSystemsMicrocomputer controls affordsimple interface with other controlsystems, such as time clocks,building automation systems, andice storage systems. This meansyou have the flexibility to meet jobrequirements while not having tolearn a complicated control system.This setup has the same standardfeatures as a stand-alone waterchiller, with the possibility of havingadditional optional features.What are LonTalk, Echelon,and LonMark?LonTalk is a communicationsprotocol developed by theEchelon Corporation. The LonMarkassociation develops control profilesusing the LonTalk communicationprotocol. LonTalk is a unit levelcommunications protocol, unlikeBACNet used at the system level.CG-PRC008-E4

ControlWhat are LonTalk, Echelon,and LonMark?LonTalk is a communicationsprotocol developed by theEchelon Corporation. The LonMarkassociation develops control profilesusing the LonTalk communicationprotocol. LonTalk is a unit levelcommunications protocol, unlikeBACNet used at the system level.LonTalk Communications Interfacefor Chillers (LCI-C)LonTalk Communications Interfacefor Chillers (LCI-C) provides ageneric automation system withthe LonMark chiller profile inputs/outputs. The inputs/outp

CG-PRC008-E4 Product catalog Indoor liquid chiller CGWH Packaged Water-cooled liquid chiller CCUH Condenserless liquid chiller Sizes: 115 - 120 - 125 - 225 - 230 - 235 - 240 - 250

Related Documents:

The chiller plant in consideration served a medium-scale commercial building in Dubai and consisted of three air-cooled twin-circuit screw chillers - Chiller-1 which is the redundant chiller, Chiller-2 which is the lag chiller and Chiller-3 which is the lead chiller. Chiller-3 started first and ran for 6 minutes.

Standard Chiller/HP modulare per compressore a vite Generico/Bitzer con driver CAREL Cod.: 030221296 - Rel. 1.4 11/09/08 7 1. Applications and functions performed by the software Type of control unit AIR / WATER CHILLER Chiller only Chiller Heat pump Chiller Freecooling WATER / WATER CHILLER Chiller only

The highest peak in chiller technology VZ Chiller series Water cooled inverter chiller. 2 The highest peak in chiller technology EWWD-VZ chiller series An increasing demand for high efficient HVAC systems drives our product development mission. By answering market demands and offering new opportunities we anticipate on the future HVAC market needs. 8.0 7.1 7.7. 3 7.9 ESEER up to 8.5 Top .

In this mode, the chiller is the sole source of cooling. For example, to cool the building after all ice is produced but before high electric al-demand charges take effect, Tracer sets the air-cooled chiller leaving-fluid set point to its most efficient setting and starts the chiller, chiller pump, and load pump. When electrical demand is high, the

The average operating current of the chiller is small, but the instantaneous operating current could be up to 10 amps. Please make sure there is a stable and normal voltage for the working chiller! The standard operating voltage for the chiller is 220 V. Mismatched power frequency can cause damage to the chiller! Be sure you can run a machine with 50 Hz. To protect the pump, it is strongly .

chiller is released into the room, but is significantly less heat than an air-cooled chiller. By using the electrical data from the chiller and heat load data from the process, the amount of heat added to the room by a chiller can easily be calculated. To calculate the energy usage, refer to the chiller’s serial number tag that should also have the electrical specifications on it or request .

Chiller 200kW to 3000kW. 2 TurboChill Hydro pairs the latest in water cooling technology with the highly efficient Turbocor compressor range, to deliver our highest capacity, highest efficiency chiller with reduced risk to our planet. TurboChill Hydro Turbocor , Turbo Charged 200kW to 3000kW Water-Cooled Chiller TurboChill Hydro is a highly efficient water cooled chiller that offers .

Albert woodfox Arthur Kinoy Award A Message from NYU PILC At every NLG #Law4thePeople Convention, we honor members and friends of the Guild whose exemplary work and activism capture the spirit of “law for the people,” and speak to the Guild’s philosophy of human rights over property interests. Please join us in congratulating our 2016 honorees! Workshops Tentative Schedule Felon .