BEE CODE -TRANSFORMERS - NREDCAP

3y ago
45 Views
2 Downloads
231.59 KB
34 Pages
Last View : 22d ago
Last Download : 3m ago
Upload by : Ronnie Bonney
Transcription

BEE CODETRANSFORMERSPrepared forBureau of Energy Efficiency,(under Ministry of Power, Government ofIndia)ndHall no.4, 2 Floor,NBCC Tower,Bhikaji Cama Place,New Delhi – 110066.Indian Renewable Energy DevelopmentAgency,Core 4A, East Court,st1 Floor, India Habitat Centre,Lodhi Road,New Delhi – 110003.ByDevki Energy Consultancy Pvt. Ltd.,405, Ivory Terrace,R.C. Dutt Road,Vadodara – 390007.2006

CONTENTS1OBJECTIVE & SCOPE. 31.11.22DEFINITIONS AND DESCRIPTION OF TERMS. 42.12.23DATA COLLECTION & ANALYSIS . 23UNCERTAINTY ANALYSIS . 257.17.27.38SEQUENCE OF TESTS . 16CHRONOLOGICAL ORDER OF MEASUREMENTS AND CALCULATIONS . 16FORMAT OF TEST RESULTS. 236.17MEASUREMENTS/ESTIMATION OF PARAMETERS . 9POWER INPUT . 9VOLTAGE . 12FREQUENCY . 13W INDING TEMPERATURE . 13COLD WINDING RESISTANCE . 14COMPUTATION OF RESULTS. 165.15.26SAFETY PRECAUTIONS . 7SOURCES OF ERRORS AND PRECAUTIONS . 7ESTIMATION OF TRANSFORMER EFFICIENCY . 8INSTRUMENTS AND METHODS OF MEASURENMENTS. 94.14.24.34.44.54.65BASIC UNITS AND SYMBOLS . 4DEFINITION & DESCRIPTION OF TERMS . 5GUIDING PRINCIPLES . 73.13.23.34OBJECTIVE . 3SCOPE . 3INTRODUCTION . 25METHODOLOGY . 25UNCERTAINTY EVALUATION OF TRANSFORMER EFFICIENCY TESTING: . 27GUIDELINES FOR ENERGY CONSERVATION OPPORTUNITIES . 30ANNEXURE 1: EFFECT OF HARMONICS. 31ANNEXURE-2: REFERENCES . 34LIST OF FIGURESFIGURE 4-1: NO LOAD TEST SET UP FOR SINGLE PHASE TRANSFORMERS. 10FIGURE 4-2: NO LOAD TEST SET UP FOR 3 PHASE TRANSFORMERS . 10FIGURE 4-3: CONNECTION DIAGRAM USING 3-PHASE 4 WIRE ENERGY METER . 10FIGURE 4-4: LOAD LOSS TEST USING LOW VOLTAGE SUPPLY . 11LIST OF TABLESTABLE 2-1: BASIC UNITS AND SYMBOLS . 4TABLE 2-2: SUBSCRIPTS. 4TABLE 5-1: TRANSFORMER EFFICIENCY ESTIMATION AT FULL LOAD . 20TABLE 5-2: TRANSFORMER EFFICIENCY ESTIMATION AT ACTUAL LOAD . 21TABLE 7-1: UNCERTAINTY EVALUATION SHEET-1 . 26TABLE 7-2: UNCERTAINTY EVALUATION SHEET-2 . 26TABLE 7-3: UNCERTAINTY EVALUATION SHEET-3 . 26TABLE 7-4: TEST TRANSFORMER SPECIFICATIONS . 27TABLE A1-0-1: SAMPLE CALCULATION-K FACTOR. 32TABLE A1-0-2: SAMPLE CALCULATION FACTOR K . 332

1OBJECTIVE & SCOPE1.1Objective1.1.1The objective of this BEE Code is to establish rules and guidelines for conducting testson electrical distribution transformers used in industrial, commercial and such other loadcenters at site conditions.1.1.2The overall objective is to evaluate the energy losses in the transformers at differentoperating conditions. The energy losses in a transformer consist of relatively constantiron losses and dielectric losses, and variable load losses; which vary with the load.1.1.3In general, matching the levels of precision of instruments available during testing atworks is difficult and costly. Data from test certificates from manufacturers can be used inmajority of the cases. Tests in this code are minimised and simplified so that it can beconducted by easily available instruments under site conditions.1.2Scope1.2.1This standard covers electrical power distribution transformers of single phase/threephase and oil cooled or dry type but restricted to those having secondary voltages in theL.T distribution range of 415 V/240 V. The ratings covered are 25 kVA and upwards.1.2.2The standards applicable for testing transformers a manufacturer’s works are as under:1. IS 2026- 1977– Specifications for Power Transformers2. IEEE Standard C57.12.90 – 1993: IEEE Standard Test Code for Dry TypeDistribution Transformers3. IEC 60726: Dry type power Transformers4. IEC 60076: Power transformers - general5. IEC 61378: Converter transformers1.2.3Tests described in this code are as under:1.2.3.4.Measurement of winding resistanceMeasurement of no load lossesMeasurement of load lossesMeasurement of operating load and winding temperature3

22.1DEFINITIONS AND DESCRIPTION OF TERMSBasic Units and SymbolsThe basic units and symbols used in this code are given in Table-2.1. Subscripts areexplained in Table –2.2.Table 2-1: Basic Units and -LP cu-LRFDescriptionRated outputRated primary voltageRated secondary voltageRated primary currentRated secondary currentImpedanceLine currentNo load line currentLine current during short circuit testReading of true r.m.s voltmeterReading of average reading voltmeterApplied line voltage during short circuit testWattmeter readingEnergy consumptionTime taken during initial and final reading of energy meterRatio of hysteresis loss to total iron lossRatio of eddy current loss to total iron lossOperating winding temperatureTotal power loss at temperature TStray losses at temperature TCopper losses at temperature TWinding ResistanceTemperature coefficient of resistanceTable 2-2: d valueMeasured at no loadMeasured during short circuit testAt actual loadAt reference temperatureReferred to primaryReferred to secondaryPer phase valueLine to line valueReferred to R phaseReferred to Y phaseReferred to B CWattsWattsWattsΩ

2.2Definition & Description of termsPrimary winding: The winding where incoming power supply is connected. Usually thisrefers to High Voltage side in distribution transformersSecondary winding: the winding where the principal load is connected. Usually thisrefers to Low Voltage side in Distribution transformers.No load loss: The losses taking place in a transformer when only primary winding isenergized and all secondary windings are open. They represent constant losses in atransformer.Dielectric loss: The losses taking place in a stressed dielectric medium (insulation)subjected to stress reversals.Iron losses: The losses taking place in the magnetic core. There are two types;hysterisis losses and eddy current losses.Hysteresis losses: This loss depends upon the area of the hysteresis loop, which isdepending upon the maximum flux density, the type of material and frequency. It isindependent of the waveformEddy current losses in core: This is loss due to circulating currents induced by voltagein the thickness of core laminations. It depends upon thickness of lamination, pathresistance which is depended upon the type of material, R.M.S. flux density i.e. waveformand square of frequencyEddy losses in a conductor: For a thick conductor, the induced voltage within theconductor cross section due to self linkage and due to current in other conductor varies.The difference in induced voltage in the local path in the thickness of the conductorcauses extra eddy current loss. This loss varies with square of current and square offrequency.2Stray losses: All current dependant losses in a winding other than the basic I R losses.Stray losses include eddy loss in the conductor, eddy losses in structural paths in closeproximity to outgoing conductor and the eddy loss in general in the structural parts. In drytype transformers, the last two mentioned types of stray losses are absent.Form factor: It is the ratio of the r.m.s. value of a waveform to the average value overone half cycle. For a sine wave the value of form factor is 1.11. For distorted waves withhigher peak values, the form factor is higher.Harmonics: Frequencies other than the main fundamental frequency of current orvoltage which are present in a distorted wave as multiples of base fundamentalfrequency.Transformer Polarity: This refers to the relative direction of the induced voltagesbetween the high voltage terminals and the low voltage terminals. During the AC halfcycle when the applied voltage (or current in the case of a current transformer) is from H1to H2 the secondary induced voltage direction will be from X1 to X2. In practice, Polarityrefers to the way the leads are brought out of the transformer.Burden: The load on an instrument transformer is referred to as a “burden”.5

Short circuit impedance & Impedance voltage: The impedance voltage of atransformer is the voltage required to circulate rated current through one of the twospecified windings; when the other winding is short circuited with the winding connectedas for rated operation. The short circuit impedance is the ratio of voltage and currentunder above conditions.The resistive component of short circuit impedance, gives a parameter for estimating loadlosses. These losses include eddy current losses in the conductors and structure as asmall portion. Their contribution is materially enhanced due to harmonic currents in load.Exact determination by test is difficult and simplified test at low current suffers from thedisadvantage of a high multiplying factor; but it is expected to give representative values.6

33.1GUIDING PRINCIPLESSafety precautionsThe tests require operation on the HV side of a transformer. Extreme caution should beexercised in consultation with the plant personnel to see that HV system is deactivatedand discharged safely prior to access. Similarly while energizing from LV side, the reachof induced HV side voltage should be restricted to prevent damage to personnel/equipment through inadvertent access.Some simple minimum steps for ensuring safety are as follows.1. Qualified engineers should be conducting the test. Safety work permit should beissued to the person.2. The transformer should be on normal tap3. Before conducting the tests, the HT area should be clearly demarcated to set upa suitable physical barrier to prevent inadvertent entry /proximity of personnel inthe HT zone.4. The HT supply should be switched off by the primary breaker visibly and thendisconnected by the isolator; followed by disconnection on the LT side.5. The HT side terminals should be discharged by a proper grounding rod, which iscompatible with the voltage level on the HT side.6. The primary terminals should then be physically disconnected and left open.7. It should be remembered that application of even 4 volts on the secondary LTside can induce more than 100 volts on the 11 kV HT side, as per transformerratio. Similarly abrupt breaking of relatively small D.C. currents can give largevoltage spikes on the HT side.3.23.2.1Sources of errors and precautionsRatio and phase angle errorsFor no load test, the circuit power factor is very low. (0.05 to 0.15). Hence more sensitiveenergy meters calibrated for preferably 0.1 or 0.2 pf should be used. Indicating metersshould be so selected as to give an indication in 20% to 100% full scale. Digital meterscan give more reliable low end readings.Electro-dynamic watt meters have a small angle of lag for the pressure coil circuit bywhich the pressure coil flux lags the applied circuit voltage. This angle of lag should beadded to measured angle like CT phase angle error. Electronic energy meters/wattmeters may not have this error.CTs used will have a ratio error within 0.5%. The phase angle of the CT secondarycurrent with respect to real current can be leading by phase angle error ‘cd’ stated inminutes. This error causes a very significant effect on measured power and tends to givea higher reading. It is recommended that the CT’s used should be calibrated to haveknown ratio and phase angle errors over the working range and for the intended burdenof the wattmeter and the ammeter.7

Recommendations:It is recommended to use portable power analysers or digital energy meters calibratedwith CTs of suitable range and the errors be known in the entire current range.3.3Estimation of transformer efficiencyThe total losses in a transformer at base kVA as well as at the actual load are estimated.From the rated output and measured output, transformer efficiency is calculated asfollows.Efficiency at full load Rated output 100 % Rated output Total losses at full load .Efficiency at actual load Output power at actual load 100 %Outputpoweratactualload Totallossesatactualload Considering the fact that distribution transformers are usually operated at around 50% ofthe rating, estimation of losses at 50% load can also be done by extrapolation methodand efficiency at 50% load can be calculated.8

44.1INSTRUMENTS AND METHODS OF MEASUREMENTSMeasurements/estimation of parametersThe measurements of the following parameters are required for transformer lossestimation.1.2.3.4.5.6.4.2Power inputCurrentVoltageFrequencyWinding ResistanceTemperature of windingPower inputA wattmeter or a suitable electronic 3-phase 4-wire energy meter calibrated for 0.1 p.fcan be used for measurement of power in no load test and short circuit test. It also givesa power reading or for improved resolution, energy reading over a period of measuredtime is possible. Modern digital energy meters have indications of voltage, current, powerand frequency; hence more convenient for site measurements.Electronic 3 phase 4 wire energy/power meters of 0-5A range and multiple voltageranges from 60 V to 500 V with a full-scale indication in the range of 0.1 pf and 0.5-classaccuracy is preferred.Separate single phase energy/power meters can be used but a single 3 phase 4- wireenergy meter is more convenient.CT’s of bar primary type 0.5-class accuracy with multiple ranges can be used. The CT'sshould be calibrated to indicate its ratio error and phase angle error at 10% to 100%current with the specific burden of ammeters and power meters used.During use, the phase angle error is directly taken from the calibration curve for specificcurrent readings. Ratio error can be taken as constant or the nominal ratio can be taken.4.2.1No load loss measurementsNo load losses can be measured from the L.V. side using an adjustable three phasevoltage source with neutral. It can be derived from mains or a D.G. set. The voltage andfrequency should be steady and at rated values and as near as possible to 50 Hz and itshould be measured. This test can give a basic value near rated conditions if allprecautions are taken.The L.V. side is energised at the rated tap at rated voltage and power is measured bythree watt meters or 3 phase, 4 wire single wattmeter/energy meter. Connections aremade as given in figure 4.1 for single phase transformers and figure 4.2 for 3 phasetransformers. Due to energisation on L.V. side, PT’s are avoided.9

Figure 4-1: No load test set up for single phase ntactorNTotal power W1 W2 W3Figure 4-2: No load test set up for 3 phase transformersThe following figure 4.3 shows connection diagram of a typical 3 phase 4 wire energymetering for measuring energy input to the transformer. All electrical parameters can bemonitored using this system.Figure 4-3: Connection diagram using 3-phase 4 wire energy meter10

The no load energy consumption, Enl can be measured in the 3 phase – 4 wire meterconnected as in figure-4.3. Time taken, t, between initial and final readings are noted.Average no load power is estimated from average energy consumption and time taken. Average energy consumption Time Enl 3600 Watts t Average no load power consumption, W nl ‘ Where Enl Energy consumption in at no load during ‘t’ seconds4.2.2Load loss TestThis test is done by energizing on the H.V. side at a suitable low voltage, while shorting theL.V. side (secondary). The applied voltage is adjusted to pass the needed current in theprimary/secondary. In order to simulate conditions nearest to full load, it is customary topass 100%, 50% or at least 25% of full load current.A simplified test using a single phase source for 3 phase transformers is explained below.The test configuration in given in figure 4.4.Figure 4-4: Load loss test using low voltage supplyTo avoid CT’s and PT’s, this method can be used at current levels of 2 to 5 A andmeasurement of load losses is done at this condition. This measured load loss is thenextrapolated to actual load currents to obtain l

IEC 60726: Dry type power Transformers 4. IEC 60076: Power transformers - general 5. IEC 61378: Converter transformers 1.2.3 Tests described in this code are as under: 1. Measurement of winding resistance 2. Measurement of no load losses 3. Measurement of load losses 4. Measurement of operating load and winding temperature

Related Documents:

applications including generator step-up (GSU) transformers, substation step-down transformers, auto transformers, HVDC converter transformers, rectifier transformers, arc furnace transformers, railway traction transformers, shunt reactors, phase shifting transformers and r

7.8 Distribution transformers 707 7.9 Scott and Le Blanc connected transformers 729 7.10 Rectifier transformers 736 7.11 AC arc furnace transformers 739 7.12 Traction transformers 745 7.13 Generator neutral earthing transformers 750 7.14 Transformers for electrostatic precipitators 756 7.15 Series reactors 758 8 Transformer enquiries and .

2.5 MVA and a voltage up to 36 kV are referred to as distribution transformers; all transformers of higher ratings are classified as power transformers. 0.05-2.5 2.5-3000 .10-20 36 36-1500 36 Rated power Max. operating voltage [MVA] [kV] Oil distribution transformers GEAFOL-cast-resin transformers Power transformers 5/13- 5 .

your classroom bee. If you would like to be well prepared for a school spelling bee, ask your teacher for the 450-word School Spelling Bee Study List, which includes the words listed here in addition to the words at the Two Bee and Three Bee levels of difficulty. 25. admit (verb) to accept as the truth. 26.

To the 4-H Leader: The honey bee project (Books 1 - 4) is intended to teach young people the basic biology and behavior of honey bees in addition to hands-on beekeeping management skills. The honey bee project books begin with basic honey bee and insect information (junior level) and advance to instruction on how to rear honey bee colonies and

- IEC 61558 – Dry Power Transformers 1.3. Construction This dry type transformer is normally produced according to standards mentioned above. Upon request transformers can be manufactured according to other standards (e.g. standards on ship transformers, isolation transformers for medical use and protection transformers.

cation and for the testing of the transformers. – IEC 61378-1 (ed. 2.0): 2011, converter transformers, Part 1, Transformers for industrial applications – IEC 60076 series for power transformers and IEC 60076-11 for dry-type transformers – IEEE Std, C57.18.10-1998, IEEE Standard Practices and Requirements for Semiconductor Power Rectifier

This paper aims to extend this range and introduces a novel engineering application of Origami: Folded Textured Sheets. Existing applications of Origami in engineering can broadly be catego-rized into three areas. Firstly, many deployable structures take inspiration from, or are directly derived from, Origami folding. Examples are diverse and range from wrapping solar sails [Guest and .