SOPHIA MULTI-ZONE - Ductless Mini Split Systems, Air .

3y ago
17 Views
2 Downloads
7.36 MB
24 Pages
Last View : 14d ago
Last Download : 3m ago
Upload by : Nixon Dill
Transcription

SOPHIAMULTI-ZONEINVERTERSPLIT AIR CONDITIONERWITH HEAT PUMPINSTALLATION MANUALOUTDOOR -230VOCH-48MSPH-230VOIMPORTANT NOTE: Read this manual carefully beforeinstalling or operating your new airconditioning unit. Make sure to savethis manual for future reference. This manual only describes the installation ofthe outdoor unit. When installing the indoor unit,refer to the installation manual of the indoor unit.

Table of ContentsInstallation Manual1 Accessories . 042 Safety Precautions . 053 Installation Overview . 064 Installation Diagram . 075 Specifications . 08Indoor Unit Installation.6 Outdoor Unit Installation . 09A. Outdoor Unit Installation Instructions . 09B. Drain Joint Installation . 11C. Notes on Drilling the Hole in the Wall . 11D. When Selecting a 24K Indoor Unit . 1107

7 Refrigerant Piping ConnectionL. 12N8 Wiring. 14A. Outdoor Unit Wiring . 14B. Wiring Figure . 169 Air Evacuation . 20MCMCA. Evacuation Instructions . 20B. Note on Adding Refrigerant . 2110 Test Run . 2211 Function of Automatic Wiring/Piping Correction . 23 Page 3

1AccessoriesThe air conditioning system comes with the following accessories. Use all of the installation parts andaccessories to install the air conditioner. Improper installation may result in water leakage, electricalshock, or fire, or cause the equipment to fail.NameInstallation plateShapeQuantity1Plastic expansion sheath5-8(depending on the models)Self-tapping screw AST3.9X255-8(depending on the models)Drain joint (some models)1Seal ring (some models)1ConnectingpipeassemblyLiquid sideGas sideØ 6.35Ø 9.52Ø 9.52Ø 12.7Ø 15.9Parts you must purchase(consult your technicianfor the proper size)User’s manual1Installation manual1Transfer connector (packed with the indoor unitor outdoor unit, depending on the model)(NOTE: Pipe sizes differ from appliance to appliance.To meet different pipe size requirements, sometimes atransfer connector must be installed on the outdoorunit.)Magnetic ring(After installation, hitch this on the connective cablebetween the indoor and outdoor units.)Cord protection rubber ring(If the cord clamp cannot fasten the cordbecause the cord is too small, wrap the cordprotection rubber ring (supplied with theaccessories) around the cord. Then fix it withthe cord clamp.)Optional part(one piece per indoor unit)Optional part(1-5 pieces per outdoor unit,depending on the model)Optional part(One piece per cable)1(on some models)Optional AccessoriesThere are two types of remote controls: wired and wireless.Select a remote control according to the customer's request and install it in an appropriate place.To select a suitable remote control, refer to catalogues and technical literature. Page 4

2Safety PrecautionsRead safety precautions before installationIncorrect installation due to ignoring instructions can cause serious damage or injury.The seriousness of potential damage or injuries is classified as either a WARNING or CAUTION.WARNINGFailure to observe a warning may result in death. The appliance must be installed inaccordance with national regulations.Failure to observe a caution may result in injury or equipment damage.CAUTIONWARNING Carefully read the safety precautions before installation. In certain functional environments, such as kitchens, server rooms, etc., the use of speciallydesigned air-conditioning units is highly recommended. Only trained and certified technicians should install, repair, and service this airconditioning unit. Improper installation may result in electrical shock, short circuit, leaks, fire, or other damage toequipment and personal property. Strictly follow the installation instructions set forth in this manual. Before you install the unit, consider strong winds, typhoons, and earthquakes that might affectyour unit and locate it accordingly. Failure to do so could cause damage to the unit. After installation, ensure there are no refrigerant leaks and that the unit is operating properly.Refrigerant is toxic and flammable and poses a serious health and safety risk.Note about Fluorinated Gasses1. This air conditioning unit contains fluorinated gasses. For specific information on the type of gasand the amount, please refer to the relevant label on the unit itself.2. Installation, service, maintenance, and repair of this unit must be performed by a certifiedtechnician.3. Product uninstallation and recycling must be performed by a certified technician.4. If the system has a leak-detection system installed, it must be checked for leaks at least every 12months.5. When the unit is checked for leaks, proper record-keeping of all checks is strongly recommended. Page 5

Unit InstallationOverview3Installation OverviewINSTALLATION ORDER1Install the outdoor unit(Page 9)234MCPerform a test run(Page 22) Page 6 NConnect the wires(Page 14)Connect the refrigerant pipes(Page 12)5LMCEvacuate the refrigerationsystem(Page 20)

Installation DiagramMorethan4.7 inMore(12 см)than4.7 inMore(12 см)More than 5.9 in (15 см)than4.7(12 с inм)More thanMore than 4.7in (12More than 23.6 in(60 см)4.7 in(12 см)см)Mor3.9 e thanin (10см)8.7n7haet002n(i)смhan см)re t0Mo in (3811.Mo23 re th.6in an(60см)rMoFig. 4.1Safety PrecautionsCAUTIONCAUTIONThis illustration is for explanation purposesonly. The actual shape of your aircondtioner may be slightly different. Copper lines must be insulatedindependently. To prevent unnecessary damage to the wall,use a stud finder to locate studs. A minimum pipe run of 9.8 ft (3 m) is requiredto minimize vibration and excessive noise. Two of the A, B, and C directions should befree from obstructions. Page 7 InstallationDiagram4Installation Diagram

5SpecificationsPower source voltageNumber of connectedunitsStop time1-5 unitsVoltage fluctuationwithin 10% of rated voltageVoltage drop during startwithin 15% of rated voltageInterval unbalancewithin 3% of rated voltage3 minutes or moreTable 5.21 drive 21 drive 3Unit: ft/m1 drive 4 1 drive 5Max. length for all rooms98.4/30147.6/45196.8/60246/75Max. length for one indoor unit65.6/2082/2598.4/3098.4/30OU higher than IU32.8/1032.8/1032.8/1032.8/10OU lower than Max. height different betweenindoor and outdoor unitMax. height difference between indoor unitsWhen installing multiple indoor units to a single outdoor unit, ensure that the length of the refrigerantpipe and the drop height between the indoor and outdoor units meet the following requirements:Outdoor unitIndoor unitMax. height differenceIndoor unit49ft (15m)49ft (15m)32.8ft (10m)Indoor unit Page 8 Outdoor UnitSpecificationsTable 5.1Indoor units that can be used incombinationCompressor stop/start frequency

6Outdoor Unit InstallationOutdoor Unit Installation InstructionsStep 1: Select installation location The area must be free of combustible gasesand chemicals.The pipe length between the outdoor andindoor units must not exceed the maximumallowable pipe length.If possible, DO NOT install the unit where itwill be exposed to direct sunlight.If possible, make sure the unit is located faraway from your neighbors’ property so thatthe noise from the unit will not disturb them.If the location is exposed to strong winds (forexample, near a seaside), place the unitagainst the wall to shelter it from thewind. If necessary, use an awning(see Fig. 6.1 & 6.2).Install the indoor and outdoor units, cables,and wires at least 1 meter from televisions orradios to prevent static or image distortion.Depending on the radio waves, a 39.3 in (1 meter)distance may not be enough to eliminate allinterference.Outdoor UnitInstallationWhen choosing a location to install the outdoorunit, consider the following: Place the outdoor unit as close to the indoor unit as possible. Ensure that there is enough room for installation and maintenance. The air inlet and outlet must not be obstructed or exposed to strong wind. Ensure the location of the unit will not be subject to snowdrifts, accumulation of leaves,or other seasonal debris. If possible, providean awning for the unit. Ensure the awningdoes not obstruct airflow. The installation area must be dry and wellventilated. There must be enough room to install the connecting pipes and cables and to accessthem for maintenance. Strong windStrong windStrong windFig. 6.1Fig. 6.2Step 2: Install outdoor unitFix the outdoor unit with anchor bolts (M10) 23.6”/60 cmCAUTIONFix with bolts Be sure to remove any obstacles thatmay block air circulation.Be sure to refer to LengthSpecifications to ensure there isenough room for installation andmaintenance.Fig. 6.3 Page 9

Split Type Outdoor Unit(Refer to Fig 6.4, 6.5, 6.6, 6.10, and Table 6.1)Table 6.1: Length Specifications of Split TypeOutdoor Unit (unit: inch/mm)Outdoor Unit DimensionsWxHxDHWOutdoor UnitInstallationFig. 6.4WHFig. 6.5ADBFig. 6.6 Page 10 Mounting DimensionsDistance ADistance B760 x 590 x 285 (29.9 x 23.2 x 11.2)20.85 (530)11.4 (290)810 x 558 x 310 (31.9 x 22 x 12.2)21.6 (549)12.8 (325)845 x 700 x 320 (33.27 x 27.5 x 12.6)22 (560)13.2 (335)900 x 860 x 315 (35.4 x 33.85 x 12.4)23.2 (590)13.1 (333)945 x 810 x 395 (37.2 x 31.9 x 15.55)25.2 (640)15.95 (405)990 x 965 x 345 (38.98 x 38 x 13.58)24.58 (624)14.4 (366)938 x 1369 x 392 (36.93 x 53.9 x 15.43) 24.96 (634)15.9 (404)900 x 1170 x 350 (35.4 x 46 x 13.8)23.2 (590)14.88 (378)800 x 554 x 333 (31.5 x 21.8 x 13.1)20.24 (514)13.39 (340)845 x 702 x 363 (33.27 x 27.6 x 14.3)21.26 (540)13.8 (350)946 x 810 x 420 (37.2 x 31.9 x 16.53)26.5 (673)15.87 (403)946 x 810 x 410 (37.2 x 31.9 x 16.14)26.5 (673)15.87 (403)952 x 1333 x 410 (37.5 x 52.5 x 16.14)24.96 (634)15.9 (404)952 x 1333 x 415 (37.5 x 52.5 x 16.14)24.96 (634)15.9 (404 )

23.6”/60 cm aboveNOTE: The minimum distance between theoutdoor unit and walls described in theinstallation guide does not apply to airtightrooms. Be sure to keep the unit unobstructedin at least two of the three directions(M, N, and P) (see Fig. 6.7).11.8”/30cm ockm0”/3cmfroballwaNOTE: When drilling the wall hole, makesure to avoid wires, plumbing, and othersensitive components.811n lefMt23.6”/60 c78inm onrightfrN3. Place the protective wall cuff in the hole.This will protect the edges of the hole and willhelp seal it when you finish the installationprocess.When Selecting a 24K Indoor UnitFig. 6.7Drain Joint InstallationBefore bolting the outdoor unit in place, installthe drain joint at the bottom of the unit.(See Fig. 6.8)1. Fit the rubber seal on the end of the drainjoint that will connect to the outdoor unit.2. Insert the drain joint into the hole in thebase pan of the unit.3. Rotate the drain joint 90 until it clicks inplace facing the front of the unit.4. Connect a drain hose extension (notincluded) to the drain joint to redirect waterfrom the unit during heating mode.NOTE: Make sure the water drains to a safelocation where it will not cause water damageor a slipping hazard.The 24K indoor unit can only be connected with anA system. If there are two 24K indoor units, theycan be connected with an A and B system(see Fig. 6.9).Table 6.2: Connective pipe size of an A and Bsystem (unit: inch)Indoor Unit /224K3/85/8Base pan hole ofoutdoor unitSealSealDrain jointFig. 6.9(A)(B)Fig. 6.8 Page 11 Outdoor UnitInstallationm0c0”/2PtonNotes on Drilling the Hole in the WallYou must drill a hole in the wall for therefrigerant piping and the signal cable that willconnect the indoor and outdoor units.1. Determine the location of the wall holebased on the location of the outdoor unit.2. Using a 2.5” (65 mm) core drill, drill a holein the wall.

7Refrigerant Piping ConnectionSafety PrecautionsWARNINGRefrigerant PipingConnection All field piping must be completed by alicensed technician and must comply withlocal and national regulations. When the air conditioner is installed in a smallroom, measures must be taken to prevent therefrigerant concentration in the room fromexceeding the safety limit in the event ofrefrigerant leakage. If the refrigerant leaksand its concentration exceeds its proper limit,hazards due to lack of oxygen may result. When installing the refrigeration system,ensure that air, dust, moisture, or foreignsubstances do not enter the refrigerant circuit.Contamination in the system may cause pooroperating capacity, high pressure in therefrigeration cycle, explosion, or injury. Ventilate the area immediately if there isrefrigerant leakage during the installation.Leaked refrigerant gas is both toxic andflammable. Ensure there is no refrigerantleakage after completing the installation work.CAUTIONDO NOT deform pipe while cutting. Be extracareful not to damage, dent, or deform the pipewhile cutting. This will drastically reduce theheating efficiency of the unit.1. Make sure the pipe is cut at a perfect90 angle. Refer to Fig. 7.1 for examples ofbad cuts.90 ObliqueStep 2: Remove burrsThe branching pipe must be installedhorizontally. An angle of more than 10 maycause malfunction. DO NOT install the connecting pipe until boththe indoor unit and the outdoor unit havebeen installed. Insulate the gas and liquid piping toprevent water leakage.Step1: Cut pipesFig. 7.1PipeReamerPoint down When preparing refrigerant pipes, take extracare to cut and flare them properly. This willensure efficient operation and minimize theneed for future maintenance.1. Measure the distance between the indoorand outdoor units.2. Using a pipe cutter, cut the pipe a littlelonger than the measured distance. Page 12 WarpedBurrs can affect the air-tight seal of the refrigerantpiping connection. They must be completelyremoved.1. Hold the pipe at a downward angle toprevent burrs from falling into the pipe.2. Using a reamer or deburring tool, removeall burrs from the cut section of the pipe.Refrigerant Piping Connection InstructionsCAUTIONRoughFig. 7.2Step 3: Flare pipe endsProper flaring is essential to achieve an airtight seal.1. After removing burrs from the cut pipe, sealthe ends with PVC tape to prevent foreignmaterials from entering the pipe.2. Sheath the pipe with insulating material.3. Place flare nuts on both ends of the pipe.Make sure they are facing in the rightdirection because you can’t put them onor change their direction after flaring(see Fig. 7.3).Flare nutCopper pipeFig. 7.3

4. Remove the PVC tape from the ends of theNOTE: Use both a spanner and a torque wrenchpipe when you're ready to perform the flaringwhen connecting or disconnecting pipes to/fromwork.the unit.5. Clamp the flare form on the end of the pipe. Theend of the pipe must extend beyond the flareform. Flare formPipeFig. 7.46. Place the flaring tool onto the form.7. Turn the handle of the flaring toolclockwise until the pipe is fully flared. Flarethe pipe in accordance with the dimensionsshown in table 7.1.Table 7.1: PIPING EXTENSION BEYOND FLAREFORMPipegaugeTighteningtorqueFlare dimension (A)(Unit: in/mm)Min.Max.14.2-17.2 N.m(144-176 kgf.cm)0.3/8.30.3/8.3Ø 9.532.7-39.9 N.m(333-407 kgf.cm)0.48/12.40.48/12.4Ø 12.749.5-60.3 N.m(504-616 kgf.cm)0.6/15.40.6/15.8Ø 15.961.8-75.4 N.m(630-770 kgf.cm)0.7/18.60.74/19Ø 19.197.2-118.6 N.m(990-1210 kgf.cm)0.9/22.90.91/23.3Ø 22109.5-133.7 N.m(1117-1364 kgf.cm)1.06/271.07/27.390 445 2AR0.4 0.8CAUTIONBe sure to wrap insulation around the piping.Direct contact with the bare piping may resultin burns or frostbite. Make sure the pipe is properly connected.Over tightening may damage the bell mouthand under tightening may lead to leakage. NOTE ON MINIMUM BEND RADIUSCarefully bend the tubing in the middleaccording to the diagram below. DO NOT bendthe tubing more than 90 or more than 3 times.Bend the pipe with your thumbFig. 7.58. Remove the flaring tool and flare form,then inspect the end of the pipe for cracksand even flaring.min. radius 10 cm (3.9”)Fig. 7.86. After connecting the copper pipes to theindoor unit, wrap the power cable, signalStep 4: Connect pipescable, and piping together with bindingConnect the copper pipes to the indoor unit first,tape.then connect them to the outdoor unit. First connectthe low-pressure pipe, then the high-pressure pipe. NOTE: When bundling these items together,do not intertwine or cross the signal1. When connecting the flare nuts, apply a thincable with any other wiring.coat of refrigeration oil to the flared ends ofthe pipes.7. Thread this pipeline through the wall and2. Align the center of the two pipes that you willconnect it to the outdoor unit.connect.8. Insulate all the piping, including the valvesof the outdoor unit.9. Open the stop valves of the outdoor unit tostart the flow of the refrigerant betweenthe indoor and outdoor units.Indoor unit tubingPipeFlare nutFig. 7.63. Tighten the flare nut as tightly as possibleCAUTIONby hand.After completing the installation work, make sure4. Using a spanner, grip the nut on the unitthere is no refrigerant leak. If there is, ventilatetubing.the area immediately and evacuate the system5. While firmly gripping the nut, use a torque(refer to the Air Evacuation section of thiswrench to tighten the flare nut according tomanual).the torque values in table 7.1. Page 13 Refrigerant PipingConnectionØ 6.4Flare shapeFig. 7.7

8WiringSafety PrecautionsWARNING Wiring Be sure to disconnect the power supplybefore working on the unit.All electrical wiring must be doneaccording to local and national regulations.Electrical wiring must be done by aqualified technician. Improper connectionsmay cause electrical malfunction, injury,and fire.An independent circuit and single outletmust be used for this unit. DO NOT pluganother appliance or charger into thesame outlet. If the electrical circuit capacityis not enough or there is a defect in theelectrical work, it can lead to shock, fire,and unit and property damage.Connect the power cable to the terminalsand fasten it with a clamp. An insecureconnection may cause a fire.Make sure that all wiring is done correctlyand the control board cover is properlyinstalled. Failure to do so can causeoverheating at the connection points, fire,and electrical shock.Ensure that the main supply connection ismade through a switch that disconnectsall poles, with a contact gap of a least0.118 in (3 mm).DO NOT modify the length of the powercord or use an extension cord.CAUTION Connect the outdoor wires beforeconnecting the indoor wires.Make sure to ground the unit. Thegrounding wire should be away from gaspipes, water pipes, lightning rods,telephone wires, or other grounding wires.Improper grounding may cause electricalshock.DO NOT connect the unit with the powersource until all wiring and piping iscompleted.Make sure that you do not cross yourelectrical wiring with your signal wiring, asthis can cause distortion and interference. Page 14 Follow these instructions to prevent distortionwhen the compressor starts: The unit must be connected to the mainoutlet. Normally, the power supply musthave a low output impedance of 32 ohms.No other equipment should be connectedto the same power circuit.The unit’s power information can be foundon the rating sticker on the product.Outdoor Unit WiringWARNINGBefore performing any electrical or wiring work

installing or operating your new air conditioning unit. Make sure to save this manual for future reference. This manual only describes the installation of the outdoor unit. When installing the indoor unit, refer to the installation manual of the indoor unit. MULTI-ZONE INVERTER SOPHIA SPLIT AIR CONDITIONER WITH HEAT PUMP OUTDOOR UNIT

Related Documents:

TIGO Orange Deutschland Telekom O2 . Ecuador Telefonica Zone 5 Zone 2 Elfenbeinküste Orange Zone 5 Zone 2 El Salvador Digicel Telefonica Zone 3 Zone 2 Zone EU Zone EU Zone EU Zone EU Zone 4 Zone 2 Zone 4 Zone 2 Zone 3 Zone 2 Zone 5 Zone 2 Zone 5 Zone 2 Zone 5 Zone 2 . Taiwan Star Tansa

MULTi-ZonE Ductless Heat Pump If a space is too large for one ductless system, Napoleon’s multi-zone ductless system will be the perfect fit. The multi-zone offers up to 4 indoor units that operate from one, powerful outdoor air condenser. The indoor units can be distributed

Elmhurst Plaza Tennis Courts . 2. ZONE 1. Eula Brunson Mini Park (88th St. Mini Park) 3 ZONE 1. Fremont Pool. 2 ZONE 1. Head start . 2 ZONE 1. Hellman Park . 2 ZONE 1. Holly Mini Park . 3 ZONE 1. Lion Creek Park. 2. ZONE 1. Melrose Library. 1. ZONE 1. MLK Library . 2 ZONE 1. MSC 7101 Edg

El Salvador Zone B Tigo El Salvador Zone B Claro El Salvador Zone B Digicel El Salvador Zone C Movistar Estonia Zone A Tele2 Estonia Zone A Elisa Estonia Zone A Telia Faroe Islands Zone A Hey Faroe Islands Zone B Faroese Telecom Fiji / Nauru Zone B Vodafone Fiji / Nauru Zone B Digicel Fin

Cold Climate Ductless Mini‐Split Heat Pumps To qualify for Efficiency Nova Scotia's Green Heat and Home Energy Assessment incentives, ductless mini‐split heat pump systems must be listed below. Definitions1 Heating Capacity (Btu/h): A Btu/h, or British thermal unit per hour, is a unit used to measure the heat output of a heating system. .File Size: 212KB

Unit Ventilators 500 to 2,000 cfm AHRI Certified. ETL Listed split systems. Ductless Systems, Light Commercial. Unit Ventilators Ductless Systems, Single Zone Ductless Systems, Multi-Zone ActivAIR 36IB Induction Beams 70 to 1,285

An EnviroAir Ductless System is . self-contained with two basic parts. An indoor Air Handler unit and . an outdoor Condenser unit with coolant lines and wires connecting both units. A small hole in an outside wall is all that's required to connect lines and wires between units. EnviroAir Ductless Single Zone . systems provide cooling or .

lic perceptions of the criminal courts by focusing on a few basic topics. We begin by discussing where the courts fit in the criminal justice system and how the public perceives the courts. Next, attention shifts to the three activities that set the stage for the rest of the book: Finding the courthouse Identifying the actors Following the steps of the process As we will see .