CASE STUDY – CLEAN ROOM DESIGN

2y ago
73 Views
3 Downloads
3.51 MB
30 Pages
Last View : 13d ago
Last Download : 3m ago
Upload by : Kelvin Chao
Transcription

CASE STUDY – CLEANROOM DESIGNMicroelectronics Manufacturing FacilityRocky Mountain ASHRAE 25th Annual Technical ConferenceApril 28, 2017

Agenda Terminology Clean Room Design BasicsISO ClassificationsFiltration and air-change ratesFilter basics Case StudyFacility descriptionProject design criteriaHVAC system descriptionsEnergy efficiency considerations Conclusion / Q & A

Relevant Terminology1. ACH/ACR: Air changes per hour / air change rate2. Air Lock: A transitional room between two other rooms of differentcleanliness.3. Challenge: An airborne dispersion of particles used to test filter integrity andefficiency.4. Cleanroom: A room in which the concentration of airborne particles iscontrolled, and which is constructed and used in a manner to minimize theintroduction, generation, and retention of particles inside the room and inwhich other relevant parameters, e.g. temperature, humidity and pressureare controlled as necessary (ISO 14644‐1 definition).5. DOP: Dioctyl phthalate, and aerosol used for filter challenge.6. FS‐209: Federal Standard recommends ACH rate for various classifications.7. HEPA: High‐efficiency particular air filter.8. ISO 14644‐1: International Organization for Standardization standard thatdefines airborne particulate cleanliness classifications9. Unidirectional (Laminar) flow: Air flowing at a constant and uniform velocityand direction.10. ULPA: Ultra‐low penetration air filter11. Particle concentration: The number of particles per unit of air.

Airborne ParticulatesPerspective: 98% of all particles found in indoor air are smaller than 1 micron in size.

Filter MERV RatingsULPA Filters MERV19‐20MERV 13 is standard for aClass A office designHEPA filters MERV17‐18

Filter MediaOlder generations ofHEPA filters usedaluminum pleatseparatorsGlass fiber papertechnologyToday’s micro‐pleatmedia technologyallows for lowerpressure drop andreduced filter mediadepth

Airborne Particulate CleanlinessClassificationsISO 14644‐1ISO ClassFEDERAL STANDARD 209EEnglishMetricISO 31M1.5ISO 410M2.5ISO 5100M3.5ISO 61,000M4.5ISO 710,000M5.5ISO 8100,000M6.5ISO 9N/AN/AISO 1Increasing CleanlinessISO 2Standard 209E classifications are out‐of‐date.This standard was officially retired in 2001.

Airborne Particulate CleanlinessNumber of Particles per Cubic Meter by Micrometer SizeCLASS0.1 micron 0.2 micron 0.3 micron 0.5 micron1 micron5 0,0008,320,000293,000Perspective: A strand of human hair is about 40‐100 microns in diameter.

Air Change Rates / Ceiling HEPACoverageUni‐directional air flowin cleanroom applies toISO 6 and above300 ACH 45 CFM/SF ina cleanroom with a 9’ceiling% of cleanroomceiling area occupiedby filter modules

Case Study Introductory NotesProject specifics – location, company, etc. areconfidential.Photos used in this presentation are generic,unless otherwise noted.The Case Study project was delivered to theOwner as a design‐assist, with contractorinvolvement early in the design process.

Design Criteria – Clean RoomISO Class 6 Environment: 36,000 SF open‐bay type cleanroom Positive room pressure controlled to 0.05” WC Room conditions at 69 F and 40% RH Minimum of 120 air‐changes per hour 33% ceiling HEPA coverage Unidirectional vertical airflow 12’ ceiling heightRoom features: Smooth, cleanable interior surfaces Gasketed grid ceiling with luminaires, HEPA modules, and systemscomponents (sprinkler heads, smoke detectors, etc.), smoke exhaust grilles Perforated floor serves as return air path Wafer manufacturing tools with specialized solvent and acid exhaust systems

HVAC Design – Clean RoomMake‐up Air AHUs: 100% outside air delivery to plenum Temperature and humidity control ofmake‐up air (6) units, each sized for 30,000 CFM Make‐up air flow is 5 CFM/SF, or 25 ACH.Recirculating AHUs: (40) units, each sized for 24,000 CFM Recirculated air flow is 26.7 CFM/SF, or133 ACH. Powder‐coated finishExhaust Systems: Acid Exhaust (2.8 CFM/SF), with scrubbers and N 1 redundancy Solvent Exhaust (0.8 CFM/SF), N 1 redundancy. Smoke Exhaust (2.7 CFM/SF)

Building Cross-sectionMake‐up AHU’sRecirculating AHU’sISO Class 6CleanroomPerforated floorslab for RA pathThis multi‐level configuration is often applied tomore stringent ISO cleanroom classifications.Ducted HEPAterminals

Manufacturing Level Ceiling PlanHEPA filter modulearrangement in a 2’X 4’ clean‐roomsealed ceiling gridOverall CeilingHEPA coverage is33%

Filter TerminalsSA connection –AHU supply fanprovidesrequired staticFilter mediaKnife‐edge sealwith gel gasketBalancing damper,accessible from themanufacturing level

Interstitial Level PlanActual project photoSupply air plenums areconnected to provide a level ofredundancy betweenrecirculation units.Supply air plenums withmultiple take‐off fittingsto HEPA ceiling modules

Fan Attic Level PlanMake‐up air units,with outside airhoods aboveThe entire fanattic level servesas a mixed airplenum.Exhaust mainsRecirculated air units, withdownward discharge tosupply plenums at theInterstitial level.

Fan Attic LevelAHU supportstructureSupply air plenum(flex ducts to HEPAsnot shown).Recirculated air units,supported from structuralframework.Smoke exhaust

Clean Room Make-up Air UnitsOutside airfrom roof hoodUnits are scheduledfor 8.0” TSP, andonly 0.75” ESP.Pre‐ andintermediatefiltration8‐row, 10 FPI dehumidificationcoil sized for 400 FPM facevelocity and 1.13” DP8‐row, 8 FPI cooling coil sizedfor 400 FPM face velocity and0.83” DPDirect‐drive fanarray (4 fans) (535CFM/BHP), N 1Outside air make‐up AHUdesign with completetemperature and humiditycontrol.Air is HEPA filtered tomaximize the service lifeof terminal HEPAs

Fan Array TechnologyMany advantages over single‐fan systems: Equipment redundancyLess vibrationLower noiseLess space requiredTighter duty selectionDirect drive fans – no beltloss

Psychrometrics – Make-up Air UnitsMake‐up Air AHUcooling coil:EA 85 F db/70 F wbLA 52 F db/52 F wbMake‐up Air AHUdehumidification coil:EA 53 F db/53 F wbLA 42 F db/42 F wbOutside air conditions atMaximum wb temp andcoincident db tempMake‐up Air AHUReheat Coil:EA 41 F dbLA 72 F dbRoom conditions:69 F db/40% RH

Clean Room Recirculation UnitsSimple, low‐pressurerecirculating AHUdesign with very lowunit pressure dropUnits are scheduledfor 3.0” TSP, whichincludes terminalHEPA DP.3‐row, 8 FPI coolingcoil sized for 400 FPMmaximum facevelocity and 0.17” DPDirect‐drive fan withcustom wheel width(1500 CFM/BHP)

Psychrometrics – Recirculation UnitsRecirculating AHUcooling coil:EA 72 F db/59 F wbLA 64 F db/57 F wbRoom conditions:69 F db/40% RHNote:The recirculating AHU Coolingprocess is 100% sensiblecooling. Condensate does notcollect on the cooling coil

Energy Efficiency ConsiderationsCleanrooms can easily be 50X more energy‐intensive than typical office space, and thatis heavily impacted by the fan energyrequired to deliver the prescribed air‐changerate at the required filtration level. Theroom cooling load is often a small fraction ofthe energy demand. Things to prioritize:1. Efficient fan selection – direct‐drive, withcustom wheel selection2. High‐efficiency fan motors3. Low system pressure drop – size ductworkfor low velocity and minimize length ofduct runs4. Low component pressure drop – keep airvelocity (and pressure drop) across coilsand filters as low as practicalFan EnergyCooling EnergyPowerLighting

Other Energy Efficiency ConsiderationsOther design considerations:1. AHU cooling coils are sized for a low face velocity(400 FPM) and air temperature drop (less than 8 F),which allows coil selections to have 3 rows/8 FPI,and minimized pressure drop (0.17” WC) as a result.2. Because cooling coil temperature drop is minimized,chilled water supply temperature can be increased(57 F) during mild and cold weather, which furtherincreases the efficiency of the chilled water plant.3. Pre‐filters: Intended to maximize the life‐span ofthe HEPA terminal filters. 400 FPM face velocity.4. Supply fan speeds are modulated through VFDs as afunction of filter loading.5. Limiting the cleanroom ceiling height to 12’ helpsminimize the CFM required to maintain ACH rates.Chilled water coil

Specialty Exhaust SystemsNote the structureabove is the perforatedfloor /return air pathAcid and solventexhaust systems: Epoxy‐lined stainless‐steelexhaust ductwork withwelded seams andflanged connections.Acid exhaust stream isrouted through ascrubber system prior tobeing discharged at highvelocity vertical plumedischarge at roof level.Actual project photo – Sub-Fab Level

Recommended References: ASHRAE Applications Volume,Chapter 18: Clean Spaces ISO Cleanroom Standards Manufacturer web‐sites:Cam‐fil (filters)Flanders (filters)Price Design Guide (air devices)

Questions?

Thank you!

Contact InformationBarry J. Stamp, PE, LEED APDirector of Engineering ServicesU.S. Engineering om

ISO 14644‐1 FEDERAL STANDARD 209E ISO Class English Metric ISO 1 ISO 2 ISO 31 M1.5 ISO 410 M2.5 ISO 5 100 M3.5 ISO 6 1,000 M4.5 ISO 7 10,000 M5.5 ISO 8 100,000 M6.5 ISO 9N/A N/A Standard 209E classifications are out‐of‐date. This standard was officially retired in 2001. Increasing Cleanliness

Related Documents:

Clean Room FL/ Clean Room VL & VL 869 0.55 Medical Standard 33200 2' x 2' x 5/8" SQ 0.90 Clean Room FL/ Clean Room VL & VL 871 0.55 Please Call 1-855-330-6878 Clean Room OPTIMA 3114 0.95 No Equal Clean Room OPTIMA 3115 0.95 No Equal Rockfon Cross Reference to Armstrong

series b, 580c. case farm tractor manuals - tractor repair, service and case 530 ck backhoe & loader only case 530 ck, case 530 forklift attachment only, const king case 531 ag case 535 ag case 540 case 540 ag case 540, 540c ag case 540c ag case 541 case 541 ag case 541c ag case 545 ag case 570 case 570 ag case 570 agas, case

Fargo, ND 58102 . 1stFloor Layout 2ndFloor Layout 3rdFloor Layout Room 360 Room 370 Room 358 Room 368 AgCountry Auditorium (Room 140) Eide Bailly Boardroom Room 118 Room 120 Room 126 . Note: Room 20 is on the basement floor of Richard H. Barry Hall. Room 262 Room 262 . 7 Page

PATIENT ROOM CLEANING CHECKLIST: TERMINAL CLEAN PATIENT ROOM BATHROOM CLEANING PROCEDURES Clean the mirror using a blue Microfiber glass cloth Clean the sink area, including the counter, faucet and handles, and sink basin with a clean yellow Microfiber cloth Clean other surfaces of the bathroom

Worlds of Legend: Son of the Empire – Adventurer’s Handbook _ Imperia - Level 2 . Key Located at Opens (A) GOLD Room 3 S door, outside room 5. (B) IRON Room 5 W door, Start room. (C) IRON Room 10 W door, outside room 11. (D) BRONZE Room 11 E door, outside room 12. (E) CRYSTAL Room 12 W door, outside room 13.

Case Studies Case Study 1: Leadership Council on Cultural Diversity 19 Case Study 2: Department of the Prime Minister and Cabinet 20 Case Study 3: Law firms 21 Case Study 4: Deloitte Case Study 5: Department of Foreign Affairs and Trade 23 Case Study 6: Commonwealth Bank of Australia 25 Case Study 7: The University of Sydney 26 Case Study 8 .

Thursday, October 4, 2018 Materials Selection 2 Mechanical Properties Case Studies Case Study 1: The Lightest STIFF Beam Case Study 2: The Lightest STIFF Tie-Rod Case Study 3: The Lightest STIFF Panel Case Study 4: Materials for Oars Case Study 5: Materials for CHEAP and Slender Oars Case Study 6: The Lightest STRONG Tie-Rod Case Study 7: The Lightest STRONG Beam

3 Contents List of acronyms 4 Executive Summary 6 1 Introduction 16 2 Methodology 18 3 Case Studies 25 Case Study A 26 Case Study B 32 Case Study C 39 Case Study D 47 Case Study E 53 Case Study F 59 Case Study G 66 Case Study H 73 4 Findings 81 Appendix A - Literature findings 101 Appendix B - CBA framework 127 Appendix C - Stakeholder interview questionnaire 133