Square DCatalogueI-LINE BusbarTrunking SystemApplications and Specifications

Delivering Powerto the PeopleI-LINE busbar trunking system was first introducedby Square D in 1961 in its production facility in Oxford,Ohio U.S.A. As one of the major brands of SchneiderElectric, Square D has acquired worldwide recognitionin a variety of busway applications.I-LINE busbar trunking system is designed withmaximum flexibility, ease of installation and electricalefficiency in the distribution of power of 600V andbelow, for both commercial and industrial application. Itis available in ratings from 250A to 4000A withaluminium conductors; and 250A to 5000A with copperconductors. Configuration offered are TP and TP&Nwith 100% capacity, neutral, and the unique 50%capacity integral earthing conductor.Square D facility in Oxford, Ohio U.S.A. is an ISO 9001registered busbar trunking manufacturing facility.To cope with rapid expansion of power network inthe Greater China and South East Asia, SchneiderElectric set up a joint venture in 1997 in GuangzhouEconomic & Technological Development District of PRChina, namely Schneider Busway (Guangzhou) Ltd., tomanufacture I-LINE busbar trunking system. Apart from ILINE, the Company is also marketing Telemecanique'sCanalis lighting busway to the regions.I-LINE busbar trunking system manufactured inGuangzhou achieves a high level of quality and productexcellence. It complies with international standards ofUL857, NEMA, CSA, ZBK, IEC439 and GB; and wasaccredited of ISO9002 and CCIB. The product alsopassed testing of ASTA and China Electrical EquipmentTesting Centre, Low Voltage Equipment Testing Centre.To ensure product is of the highest standard in themarket, specialists from Oxford facility visit Guangzhoufactory regularly to conduct training and audit. Inreturn, Guangzhou products are sent to U.S.A. forperiodical testing and inspection on a quarter basis.Square D’s success in launching I-LINE busbartrunking system, for sure, should be attributed to thetechnological expertise and quality assurance of theproduct itself. Yet merit should also go to the dedicatedsales and after-sales supports from Schneider Electric’slocal representative offices, only with which a total andmeticulous solution can be tailored to every uniqueapplication requirements. Empowered by the electricalengineers who master sound knowledge and practicalexperience, Schneider Electric can provide diversifiedproject management services to customers, from on-sitemeasurement, proposal on the best busducts routing, toinstallation assistance at site and “missing link units”arrangement. We trust this is the definite asset ofSchneider Electric that you customer can always counton.Want to know more about Schneider Electric orI-LINE busbar trunking system? Do contact our localrepresentative offices as printed on this publication.Schneider Busway (Guangzhou) Ltd. was certified toachieve ISO9002 quality management system.Schneider Busway (Guangzhou) Ltd. receives product certificationfrom ASTA and ISO system accreditation from DNV.ISO 9002: 1994Certificate No. 99-RGC-AQ-0086Square D I-LINE busbar trunking is designed and manufactured in afacility that is quality system registered by UL and BSI to ISO 9001.NATIONALACCREDITATIONOF CERTIFICATIONBODIESCertificate No.FM23076SQUARE D COMPANYREGISTERED TO ISO 9001CERTIFICATE NO. A2194

I-LINE Busbar Trunking SystemTable of ContentsCompany backgroundSection I : I-LINE and I-Line II Busbar Trunking SystemGeneral Description .I-LINE Busbar Trunking .I-LINE II Busbar Trunking .Product Features .Catalogue Numbering System .22368Section II : I-LINE and I-LINE II Busbar Trunking Application DataI-LINE Busbar Trunking – Physical Data .I-LINE Busbar Trunking – Electrical Data .I-LINE II Busbar Trunking – Physical Data .I-LINE II Busbar Trunking – Electrical Data .10161729Section III : I-LINE Plug-in UnitGeneral Description .I-LINE Plug-in Units with Square D MCCBand fuse switch .I-LINE Plug-in Unit with Merlin Gerin MCCB .Catalogue Numbering System .Application Data .3131313234AppendixApplication of I-LINE Busbar Trunking System . 42Suggested Specification of I-LINEBusbar Trunking System . 43Schneider Busway1

I-LINE Busbar Trunking SystemGeneral DescriptionWhat is I-LINE busbar trunking system?I-LINE busbar trunking system is a time proven design withinstallations all over the world. Available in two ranges withratings from 250 through 630 ampere and 800 through 5000ampere, this “sandwich type” plug-in and feeder busbartrunking accepts existing I-LINE plug-in (250A to 1600A) unit(subject to trunking amperage restrictions).The features of the design include the VISI-TITE bolt, platedaluminium or copper busbars and the integral earth conductor.I-LINE II busbar trunking has the additional standard featuresof internal barriers, the Joint-Pak assembly, and universal tiechannels.I-LINE Busbar Trunking (250A to 630A)Systems:TP and N (100% neutralcapacity) for AC systems;SP and TP for DCsystems.Earthing conductor:Rated at 50% of thenameplate rating of thebusbar trunking, the toppart of the conductor ismade of aluminium.Ratings:From 250 to 630 amperein aluminium or copperplated conductors. The 600volts maximum busbartrunking is fully rated formounting in eitherhorizontal or verticalpositions.VISI-TITE bolt:Double headed boltsare supplied on all jointconnections to assureproper torque on thejoint connector. Only astandard spanner isrequired to tighten thebolt until the outsidehead breaks off. A76mm Belleville washerwith a cupped surfacedispenses uniformpressure across the fulljoint surface area.2Plug-in openings:All I-LINE busbartrunking has a plug-inopening for plug-in unitevery 610mm on bothsides of the trunking.The openings arecovered by hingeddoors which cover theopenings when not inuse.Hangers:I-LINE busbar trunkingrequires support every 3metres when runhorizontally flatwise and 4.8metres vertically. It must besupported every 1.5 metresin the horizontal edgewiseposition.Enclosure:A three-piece formed steelhousing with plug-inopenings, supported bymoulded rigid insulators.Available in indoorenclosures only.Schneider Busway

I-LINE Busbar Trunking SystemGeneral DescriptionI-LINE II Plug-in Busbar Trunking (800A to 5000A)Systems:TP and N (100% neutralcapacity) for AC systems;SP and TP for DCsystems.Ratings:From 800 to 4000 amperewith aluminium and from800 to 5000 ampere withcopper conductors.Busbars are plated overtheir entire length. 600volts maximum busbartrunking is fully rated formounting in either verticalor horizontal positions.Schneider BuswayMoulded plug-inOpening insulator:Adds insulation andsupport at plug-incontact area.Joint-Pak connectorassembly:Includes commonphase connector onhigher amperageratings utilizing morethan one conductor perphase (plug-in busbartrunking only.)Earth jaw for plug-inunit:“Blow-on” designsimilar to phase jawconnection.This “blow-on” designprovides maximumstrength at contactareas during faultcurrent conditions.Fittings:Elbows, tees andflanged ends are easilyremoved and refittedwith the use of ourJoint-Pak assemblywithout disturbingadjacent lengths.Internal barriers:Internal barriers arestandard on I-LINE IIfeeder and plug-in busbartrunking. All interior spacesare barriered to protectagainst heated gases.Sandwich Construction:I-LINE II plug-in busbartrunking also includesfeatures depicted onpage 4 for I-LINE II feedertrunking.Available in indoor (IP-40/41) or indoor, drip resistant(IP-54/55) construction.3

I-LINE Busbar Trunking SystemGeneral DescriptionI-LINE II Indoor Feeder Busbar Trunking (800A to 5000A)Systems:TP and N (100% neutralcapacity) for AC systems;SP and TP for DCsystems.Ratings:From 800 to 4000 amperewith aluminium and from800 to 5000 ampere withcopper conductors.Busbars are plated overtheir entire length. 600volts maximum busbartrunking is fully rated formounting in either verticalor horizontal positions.4Earthing conductor:Provided as standardon I-LINE II system andconsists of two 1.6mmthick aluminiumbusbars. The earthingconductor is formed toserve as the top andbottom of the trunkinghousing.Joint-Pak connector:Removable for isolationand maintenance ofsystem. The VISI-TITEbolt is included.Common housing:For I-LINE II plug-inand feeder busbartrunking. Sameaccessories fit both.Steel side channels andaluminum housing.Electrodeposition:A paint process providescorrosion-resistant,long-lasting uniformappearance.Insulation:Indoor (IP-40/41/54/55/65) busbars areinsulated with two fulllength heat formedlayers of Class B130 C polyester film.We can also offerthree full length layersof insulation.Schneider Busway

I-LINE Busbar Trunking SystemGeneral DescriptionI-LINE II Outdoor Feeder Busbar Trunking (800A to 5000A)Joint Covers:Two piece joint coverswith quick-fasten nut forspeedy installation ofthe busbar trunking.EZ Joint-Pak:The same Joint-Pakused on indoor I-LINE IItrunking is continued inoutdoor feeder design.Flanged Collar:Simple installation ofthe joint covers is assistedby a smooth flangesurface with the joint ofButyl rubber sealant stripfactory installed.Schneider BuswayRemoval of thesealant’s protectivepaper covering andinstallation of the jointcovers with the quickfasten nut, sealing jointfrom contamination bywater.Completed Joint:The assembled jointwith all installationactivities complete.Indoor transition devicesare available whichdirectly connect anoutdoor (IP-66) device toan indoor (IP-40/41/54/55/65) device. (Suffix-IV orISV)Hangers are required on1.5 metre centres forvertical or horizontalmounting.5

I-LINE Busbar Trunking SystemProduct FeaturesSimple to install and maintainSquare D pioneered the single bolt joint in 1961 when itintroduced I-LINE busbar trunking. Continuing research andimprovements have led to our current design. I-LINE busbartrunking system features the following time-saving installationand maintenance features:Joint-PakJoint-Pak is standard onI-LINE II system. Itallows for quick removalof lengths from thebusbar trunking runs forload shifting ormaintenance. It also canbe removed andrelocated on theopposite end of thelength for last minutechanges.VISI-TITE boltVISI-TITE bolt is standard on allI-LINE busbar trunking. Thedouble head design, introducedby Square D in 1967 allows thecustomer to tighten the joint tothe proper torque using astandard spanner. The outerhead will break off when thecorrect torque is achieved. Whenthe head breaks off, a red plastic“VISI-TITE” disc drops off,indicating that the joint is properlytorqued. A second bolt headremains to allow for jointmaintenance or busbarrelocation. No need to purchasea replacement bolt. A cuppedBelleville washer provides equalpressure across the completejoint contact area to assureproper electrical contact.Universal fittingsUniversal fittings, which arestandard on I-LINE II system, allow feeders and plug-in ductsto be connected without special joint covers. All fittings arealso universal allowing simpler installation and maintenanceof your system.Broad range of productsI-LINE busbar trunking system comes in two basic ranges ofproducts:Totally enclosed housing – no de-rating necessaryI-LINE busbar trunking systems has a totally enclosed housingdesign which requires no de-rating, regardless of the mountingposition. No longer do you have to worry about preferredmounting positions or de-rating factors. With theI-LINE family of busbar trunking, the 100% current ratingsremain constant in any mounting position.Another advantage of our totallyenclosed housing versusventilated trunking is superiorprotection from accidentalcontact with busbars and fromaccumulation of dirt on exposedbusbars through the ventilatingscreens.I-LINE busbar trunking is available in an indoor version only.I-LINE II plug-in and feeder are available in indoor and indoordrip-resistant versions. There is also a version ofI-LINE II feeder busbar trunking suitable for outdoor use.Harmonics and electrical equipment neutralsHarmonics and the effects of nonlinear loads on electricalequipment neutral conductors are subjects of concern.Nonlinear load devices, such as variable speed drives,electronic ballast lighting, computers, printers, and faxmachines, generate harmonics, and their use is increasing.Harmonic effects are often exaggerated and singled out asthe cause for overloading electrical equipment neutrals.The research by Square D indicates that oversized neutralsare an unnecessary expense to most customers. In480Y/277 systems, neutral currents normally do not exceed100 percent of the neutral rating. In 208Y/120 systems, neutraloverloads occur only in rare, unusual cases. Therefore,oversized neutrals are an unnecessary expense to customers.Nonlinear loads, such as computers and electronic ballastlighting, create harmonics. In rare cases in 208Y/120 systems,distortion from harmonics may necessitate the use of oversizedneutral conductors in applications of 600 amperes and below.In 480Y/277 systems, oversized neutrals are not required.For more information on this subject, please order the SquareD document no. 0104ED9501, Neutral Currents in ThreePhase Wye Systems, by R. Arthur and R. A. Shanahan, P.E.or 0104PD9501, Harmonics and Electrical EquipmentNeutrals.Internal smoke/gas barriersContinuous air spaces inside I-LINE busbar trunking housingare closed off with special barriers to help prevent the spreadof smoke and gases in the event of a fire in the area of thebusbar trunking installation. This standard internal barrierallows busbar trunking to extend through walls or floors withoutcreating open space for a “chimney effect” fire path. I-LINE - From 250 to 630 ampere, aluminium or copperconductors. I-LINE II - From 800 to 4000 ampere with aluminiumconductors, and- From 800 to 5000 ampere with copperconductors.I-LINE is provided as a plug-in or feeder system, and ILINE II is available as a feeder, plug-in or riser plug-insystem.6Schneider Busway

I-LINE Busbar Trunking SystemProduct FeaturesHigh grade conducting and insulationmaterialI-LINE busbar trunking system uses either high grade tin platedaluminium or silver flashed copper for their conducting material.The conductors are plated over their entire surface for bettercorrosion protection. All busbars are insulated using Class B130 C vendor certified polyester film (Mylar) for long insulationlife. I-LINE busbar trunking insulation consists of two layers of7.5 mil heat formed polyester film surrounding each busbar. ILINE II busbar trunking uses the same two layers of polyesterfilm to insulate the busbars in indoor trunking.Short circuit strength and testingI-LINE busbar trunking design gives high short circuit strengthsuitable for today’s industrial and commercial electricalsystems. The system is certified at a 3 cycle rating byUnderwriters Laboratories and 1 sec/3sec certification byASTA.Integral earthing conductorI-LINE busbar trunking system is available with a 50% capacityintegral aluminium earthing conductor as an option. Theconductor is unique in that it is a part of the housing itself,which provides an effective path to earth for high level groundfaults.I-LINE II is furnished with the integral earthing bus as standard.The earthing bus is the bus housing itself and completelyencloses the bus sandwich. Like I-LINE, it is rated at 50%capacity.Square D believes an earthing conductor is extremelyimportant, to provide the maximum amount of protection for adistribution system in today’s ever expanding electricalsystems. With our design, we have given the maximum amountof protection in an economical package.Square D tests its products frequently at its own testinglaboratory in Cedar Rapids, Iowa, USA, to ensure the highstandards of quality and performance that I-LINE busbartrunking system has come to symbolize.Degree of ProtectionSquare D offers the I-LINE II busbar trunking system in a varietyof housing constructions to meet your application and needs.Choose from the following styles:LocationType of TrunkingIndoorFeeder and rIP-66Schneider BuswayDegree of Protection7

I-LINE Busbar Trunking SystemCatalogue Numbering SystemI-LINE Busbar TrunkingCatalogue numbers are composed of 2 basics parts – the PREFIX (as below) plus the SUFFIX of each individual busbar trunkingcomponent.The PREFIX contains necessary trunking information except individual component descriptive details which are defined by theSUFFIX. The catalogue number PREFIX will generally remain unchanged throughout a trunking system while the SUFFIX willvary with each individual length or fitting selected. A table of the standard SUFFIX designations can be found on page 28.A few devices, such as hangers and wall flanges, do not follow the exact pattern described above. For these exceptions, a morecomplete listing of device catalogue numbers is shown with the individual device drawing(s) beginning on page 25.Number of Poles5 TP N E2 I-LINE II busbar (800A - 5000A)no number designation I-LINE busbar* (250A - 630A)Special Features (Optional):F Outdoor feederJ 1sec/3sec high circuit breaking forindoor trunkingAmpere Rating:in hundreds of ampere(i.e. 20 2000 ampere)Type of Busbar Trunking:F Indoor feederP Plug-inO Outdoor feederR Riser plug-inEarth Bus:G 50% capacityintegral earth busBusbar Material:A AluminiumC CopperSUFFIXPREFIXof each individual busbartrunking componentFittings available:FE Flange endEL ElbowEJ Expansion fittingETB End cable tap boxCTB Centre cable tapboxDegree of protection**(for indoor only):– – IP4041 IP4154 IP5455 IP55***65 IP65*****I-LINE busbar (250A - 630A) is available for indoor feeder or plug-in system** Not applicable in I-LINE busway (250A - 630A)*** IP55 available for feeder system only**** IP65 available for feeder system only8Schneider Busway

I-LINE Busbar Trunking SystemCatalogue Numbering SystemPlug-in UnitA. Plug-in unit with BS88 fusible switchAmpere Rating Reference No:PQ 30A - 200APS 200A (vertical installation)PBQ 400A - 600APTQ 800A - 1600AG Fusible switch with earthbus and complies with ULstandardGE Fusible switch with earthbus and complies withBS standardType of System:4 TP&N&E3 TP&EMaximum Ampere Rating:03 30A, 06 60A,10 100A, 20 200A,40 400A, 60 600A,80 800A, 100 1000A,120 1200A, 160 1600AVoltage Level:6 600VNote: Fuse unit is not included in the plug-in unitB. Plug-in unit with Square D MCCBPlug-in Types:P Low current plug-in connectionPB High current plug-in connectionPT High current bolt-on connectionAmpere Rating Reference No:F Maximum 100AK Maximum 250AL Maximum 400AM Maximum 1000AP Maximum 1600AWith earth bus andneutralAmpere Rating:225 225AVoltage Level:6 380V - 600VNo. of Poles (MCCB):3 3-PoleRated Breaking Capacity:A StandardH HighC Extra high (available for 400A or below)I LimitedC. Plug-in unit with Merlin Gerin MCCBAmpere Rating Reference No:P 250A or belowPB 252A - 500ARated Breaking Capacity:N StandardH HighD EconomyNeutral Arrangement:N Neutral lugsS Side handleNV Neutral lugs and earthfault protectionT Switched neutralTV Switched neutral andearth fault protectionWith earth busAmpere Rating:200 200ASchneider Busway9

I-LINE Busbar TrunkingPhysical DataI-LINE busbar trunking (250A-630A)Straight LengthsSt

Schneider Busway (Guangzhou) Ltd. was certified to achieve ISO9002 quality management system. Schneider Busway (Guangzhou) Ltd. receives product certification from ASTA and ISO system accreditation from DNV. Square D I-LINE busbar trunking is designed and manufactured in a facility that is quality system registered by UL and BSI to ISO 9001.

Related Documents:

Texts of Wow Rosh Hashana II 5780 - Congregation Shearith Israel, Atlanta Georgia Wow ׳ג ׳א:׳א תישארב (א) ׃ץרֶָֽאָּהָּ תאֵֵ֥וְּ םִימִַׁ֖שַָּה תאֵֵ֥ םיקִִ֑לֹאֱ ארָָּ֣ Îָּ תישִִׁ֖ארֵ Îְּ(ב) חַורְָּ֣ו ם

ft feet 0.305 Meters m yd yards 0.914 Meters m mi miles 1.61 Kilometers km AREA in2 square inches 645.2 square millimeters mm2 ft2 square feet 0.093 square meters m2 yd2 2 square yard 0.836 square meters m ac acres 0.405 hectares ha mi2 square miles 2.59 square kilometers km2 VOLUME

5 What Are Lines And Stanzas? Line A line is pretty self-explanatory. Line A line of a poem is when it jumps Line To a new, well, line, Line Like this! Line Sometimes a line is a complete sentence. Line But it doesn’t Line Have to be! Line A stanza is kind of like a paragraph. Line Stanzas are made up of lines. Line This “stanza” has five lines.

square root of 144? 12 6 What is the value of (-11) squared? 121 7 What is the positive square root of 81? 9 8 What is the value of (-4) squared? 16 9 What is the positive square root of 225? 15 10 What is the positive square root of 121? 11 Day 8 Q Question Answer 1 What is the positive square root of 16? 4 2 What is the value of (-6) squared? 36

Section 6.3 Approximating Square Roots 247 EXAMPLE 2 Approximating Square Roots Estimate — 52 to the nearest integer. Use a number line and the square roots of the perfect squares nearest to the radicand. The nearest perfect square less than 52 is 49. The nearest perfect square greater than 52 is 64. Graph 52 . 49 7 64 8

Having de ned big-Oh and big-Omega y Having de ned big O and big Omega Page 13, line 12 Aug 20175 big-Theta y big Theta I Page 20, line 4 30 Mar 2017 line 3 y line 4 I Page 20, line 3 30 Mar 2017 line 11 y line 12 I Page 20, line 1 30 Mar 2017 line 6 y line 7 Page 40, line 17 12 Aug 2017 Using big

McAfee Live Safe - Produktuebersicht & Features Die 5 besten Tips Q & A . Title Line Subtitle Line Top of Content Box Line Top of Footer Line Left Margin Line Right Margin Line Top of Footer Line Top of Content Box Line Title Line Left Margin Line Right Margin Line . McAfee Confidential 3.

square statistic that would arise by chance follows quite closely a known mathemat ical distribution-the . chi-square distribution. The exact shape of the chi-square distribution depends on the degrees of free dom. For a chi-square