Building Management Systems (BMS) DESIGN GUIDELINES University Of .

1y ago
26 Views
3 Downloads
634.61 KB
60 Pages
Last View : Today
Last Download : 3m ago
Upload by : Louie Bolen
Transcription

UBC Technical GuidelinesUBC Vancouver and UBC OkanaganNovember 2021 RevisionSection 25 05 00Building Management System (BMS) Design GuidelinesPage 1 of 60Building Management Systems (BMS)DESIGN GUIDELINESUniversity of British ColumbiaRevised: November 2021

UBC Technical GuidelinesUBC Vancouver and UBC OkanaganNovember 2021 RevisionSection 25 05 00Building Management System (BMS) Design GuidelinesPage 2 of 60Contents12345OVERVIEW . 41.1.General . 41.2.Application of these BMS Design Guidelines . 41.3.List of Abbreviations . 51.4.Existing BMS Facilities . 71.5.Existing BMS Communication Network Facilities at UBC . 7BMS INSTALLATION GUIDELINES . 102.1.General BMS Installation Requirements . 102.2.BMS Electrical Installation Requirements. 122.3.BMS Communication Provisions . 162.4.BMS Pneumatic Control Installation Requirements . 162.5.BMS Installation Training Requirements . 162.6.BMS Documentation Requirements . 172.7.BMS Installation Commissioning and Testing . 18BMS DESIGN GUIDELINES . 203.1.General BMS Design Requirements . 203.2.BMS Subcontractor and System Qualifications . 213.3.BMS Network Architecture and Communications Requirements . 22BMS EQUIPMENT . 254.1.Management Level Network . 254.2.BMS Automation Level Network . 254.3.Communication Control Panels (CCP) . 254.4.Distributed Control Panels (DCP) . 264.5.Unitary Controllers (UC) . 284.6.Valves and Dampers . 294.7.Electrical Sub Meters . 374.8.BMS Field Devices and Instrumentation . 37BMS SOFTWARE, DATABASE AND PROGRAMMING REQUIREMENTS . 465.1.General . 465.2.System Requirements . 465.3.SOFTWARE . 48

UBC Technical GuidelinesUBC Vancouver and UBC OkanaganNovember 2021 Revision67Section 25 05 00Building Management System (BMS) Design GuidelinesPage 3 of 60CBMS SOFTWARE, DATABASE AND PROGRAMMING REQUIREMENTS . 506.1.Integration of Standalone Building BMS Into the Campus BMS . 506.2.CBMS Dynamic System Requirements . 506.3.CBMS Dynamic System Graphical Interface Requirements . 516.4.Alarm Management and Annunciation . 536.5.CBMS/BMS Alarm Handling Archiving Requirements . 546.6.Testing and Commissioning Requirements . 556.7.UBC BMS Point Naming Conventions Requirements . 556.8.UBC BMS Controller and Device Addressing and Naming Convention Requirements . 56GUIDELINES FOR APPLICATION OF BMS TO TYPICAL HVAC SYSTEMS . 577.1.BMS Sequences of Operation, Field Termination Schedules, and System Schematic Diagrams. 577.2.BMS Component and Building Equipment Failure Requirements . 577.3.BMS Automatic Sequenced Control of AHU Mixing Dampers and Valves . 587.4.General BMS Monitoring and Control Requirements . 587.5.Post Fire Alarm Equipment Restart . 587.6.Post Building Power Failure Equipment Restart . 597.7.Air Handling Unit Optimum Start and Stop Programs . 597.8.After-hours Equipment Operation . 597.9.Air Handling Unit Supply Air Temperature Reset Schedules . 597.10.Dynamic Mixed Air Calculations and Mixing Damper Minimum Outside Air Positioning . 607.11.Typical Sequence of Operation - Variable Volume Air Handling Unit . 607.12.Typical Sequence of Operation - VAV . 607.13.Chilled Water (CW) and Condenser Water (CSR) Systems . 607.14.Supply Hot Water System (SHW). 607.15.Domestic Hot Water System . 60

UBC Technical GuidelinesUBC Vancouver and UBC OkanaganNovember 2021 Revision1OVERVIEW1.1.GeneralA.1.2.Section 25 05 00Building Management System (BMS) Design GuidelinesPage 4 of 60The University of British Columbia is a large campus with numerous buildings of variousages. A significant number of these buildings are of a vintage that predates modernmicroprocessor based HVAC control systems and these older building control systems arecontinuously being upgraded. New buildings are also being constructed at the UBCCampus on an on-going basis.To assist in the operation and maintenance of campus buildings, UBC Building Operationsprovide centralized monitoring and control of UBC buildings from a central location viamicroprocessor based DDC controls. To facilitate the centralized BMS monitoring andcontrol standards have been applied to the selection of BMS equipment and for theapplication of BMS installations in buildings. The UBC BMS Design Guidelines serve toidentify typical standards for the application of BMS’s in UBC buildings. These DesignGuidelines have also been developed to assist UBC in ensuring that UBC buildings areprovided with high quality BMS installations that fully meet their requirements.Application of these BMS Design GuidelinesA.This document is intended to serve as a guideline for the Design of Building ManagementSystem (BMS) installations in buildings at the University of British Columbia (UBC). Theguideline serves to generally identify the existing UBC Campus BMS infrastructure andinstalled components and to record BMS design requirements specific to UBC installations.The UBC Design Guidelines may be used by BMS Designers for guidance in the design ofUBC BMS installations but shall not be reproduced, in whole, or part, for inclusion in BMSDesign Specifications, or Tender or Contract Documents. The UBC BMS Design Guidelinesare not Design Specifications and do not include sufficient detail to be used as such. BMSDesigners will be required to include additional detailed information in BMS DesignSpecifications to clearly identify all aspects of the BMS installation.B.BMS Designs shall be based on sound industry standard practices. BMS Designers shallprovide BMS Designs that have been specifically engineered for the application and shallexercise discretion in the application of these guidelines. All new building construction atUBC will utilize DDC BMS monitoring and control of building equipment and systems tosome degree. Existing buildings are also being upgraded with retrofits to mechanical andelectrical systems as well as to the building control and monitoring facilities. BMS DesignDocuments shall clearly identify the nature of the BMS installation work and shall includethe contractual documentation and requirements where applicable.C.All new BMS installations shall comprise equipment, data and data communications thatare fully compliant with ANSI/ASHRAE Standard 135-2001 “BACnet” and Division27Section 27 05 08 – 1.4.8.1.Legacy equipment manufactured by JCI and SBT that are not compliant withANSI/ASHRAE Standard 135-2001 shall NOT be used for NEW BMS installations.2.Equipment installed on extensions of a BMS using non-BACnet legacy equipment,manufactured by JCI and SBT, shall have the capability of directly communicating tothe legacy equipment in the proprietary communications protocol as well ascommunicating with BACnet devices. New equipment that does not have thecapability to communicate in both the proprietary protocol and BACnet is placedonto a legacy system; the device shall use the BACnet communications protocol.When equipment capable of communicating only with BACnet is placed onto an

UBC Technical GuidelinesUBC Vancouver and UBC OkanaganNovember 2021 RevisionSection 25 05 00Building Management System (BMS) Design GuidelinesPage 5 of 60existing legacy system, a communication gateway device shall be placed on to theproprietary network. The gateway shall bridge the two disparate communicationprotocols and act as a translator that allows bilateral communication between theBACnet compliant devices and devices communicating using proprietarycommunication protocols.1.3.List of AbbreviationsA.The following are a list of abbreviations used throughout these design guidelines andare also abbreviations used by the University of British Columbia relating to BuildingManagement Systems.ANSI ASC ASHRAE -American National Standards InstituteApplication Specific ControllerAmerican Society of Heating, Refrigerating and AirConditioning EngineersASTM AWG B-AWS -American Society for Testing MaterialsAmerican Wire GaugeBACnet Advanced Operator Workstation: The B-AWS is the advancedoperator's window into a BACnet system. It is primarily used to monitorthe performance of a system and to modify parameters that affect theoperation of a system. It may also be used for configuration activitiesthat are beyond the scope of this standard.B-OWS -BACnet Operator Workstation: The B-OWS is used for monitoringand basic control of a system, but differs from a B-AWS in that it doesnot support configuration activities, nor does it provide advancedtroubleshooting capabilities.B-OD -BACnet Operator Display: The B-OD is a basic operator interface withlimited capabilities relative to a B-OWS. It is not intended to performdirect digital control. The B-OD profile could be used for wall-mountedLCD devices, displays affixed to BACnet devices; handheld terminalsor other very simple user interfaces.B-BC -BACnet Building Controller: A B-BC is a general-purpose, fieldprogrammable device capable of carrying out a variety of buildingautomation and control tasks.B-AAC -BACnet Advanced Application Controller: A B-AAC is a control devicewith limited resources relative to a B-BC. It may be intended for specificapplications and supports some degree of programmability.B-ASC -BACnet Application Specific Controller: A B-ASC is a controller withlimited resources relative to a B-AAC. It is intended for use in aspecific application and supports limited programmability.B-SA -BACnet Smart Actuator: A B-SA is a simple control device withlimited resources; it is intended for specific applications.B-SS -BACnet Smart Sensor: A B-SS is a simple sensing device with verylimited resources.BMS BACnet -Building Management and Control SystemBuilding Automation and Controls Network - ANSI/ASHRAEStandard 135-2012

UBC Technical GuidelinesUBC Vancouver and UBC OkanaganNovember 2021 RevisionSection 25 05 00Building Management System (BMS) Design GuidelinesPage 6 of 60BTL -BACnet Testing Laboratory: A recognized, independent third partylaboratory certified to test product for compliance to BACnet standards.BTL Mark -A seal affixed to product certifying that it has been tested by arecognized BACnet Testing Laboratory and found to conform toBACnet standards.CBMS CCF CCP CPU DAUCampus Building Management SystemBMS Central Computer FacilityCommunications Control PanelCentral Processing UnitData Archival Unit. A device that sits on the Automation NetworkLevel and automatically collects data to be sent up to the central dataarchive server that resides on the Management Level network and islocated in the MACC.DCP DDC DELTAESCDistributed Control PanelDirect Digital ControlDelta Controls Inc.ESC Automation Inc. is the installing contractor and localrepresentative for DELTA Controls.FAS FTS H/O/A HDASHVAC IEEE I/OJCILAN LCD LED LON LonTalk -Fire Detection, Alarm and Communication SystemField Termination ScheduleHand/Off/Auto Motor Control Switch/CircuitHistorical Data Archiving ServerHeating, Ventilating and Air ConditioningInstitute of Electrical and Electronics EngineersInput/OutputJohnson Controls, Inc.Local Area NetworkLiquid Crystal DisplayLight Emitting DiodeLocal Operating NetworkThe open control networking protocol developed byEchelon CorporationLONWORKSMACCNDS NEC NEMA OIW PCPICSEchelon’s family of hardware and software productsBMS Master Alarm and Control CentreNetwork Data ServerNational Electrical CodeNational Electrical Manufacturers AssociationOperator Interface WorkstationPersonal ComputerProtocol implementation conformance statement: All devicesconforming to the BACnet protocol shall have a documentedstatement (PICS) that identifies all of the portions of BACnet that areimplemented in the device.POT PIMRAM RFIPortable Operator WorkstationProcess Interface ModuleRandom Access MemoryRadio Frequency Interference

UBC Technical GuidelinesUBC Vancouver and UBC OkanaganNovember 2021 Revision1.4.RHROW RTD SBT -Relative HumidityRemote Operator WorkstationResistance Temperature DeviceSiemens Building Technologies Ltd.SVGA UBC UCcULUPS VDU -Super Video Graphics AdapterUniversity of British ColumbiaUnitary ControllerUnderwriters Laboratory CanadaUninterruptible Power Supply UnitVideo Display UnitExisting BMS FacilitiesA.There are three separate and autonomous BMS’s installed and operating on the UBCCampus, both with individual central alarm monitoring and control facilities, interconnectingnetwork communications facilities and BMS monitoring and control facilities installed withincampus buildings. BMS installations within individual buildings are configured as stand- aloneBMS installations capable of real-time monitoring and control. Each of the stand-alonebuilding BMS installations communicates with central computer equipment at the MACC andACC in the University Services Building. The existing BMS facilities are as manufactured byDelta Controls Ltd. (DELTA), Johnson Controls (JCI), and as manufactured by SiemensBuilding Technologies, Ltd. (SBT). The three different BMS’s utilize separate communicationnetwork facilities.B.The following is a list of existing Delta Controls Ltd. BMS facilities and equipment at UBC:1.2.3.4.C.D.Delta EnteliWEB software running on a Virtual Server.The EnteliWEB server is running on a virtual server segment, provided and maintainedby UBC-BIS group.Delta DCP’s and ASC’s installed in distributed standalone building BMSinstallations.Copper tree brand Copper Cubes for long-term storage, as required per building.The following is a list of existing Siemens Building Technologies, Ltd. BMS facilities andequipment at UBC:1.2.3.1.5.Section 25 05 00Building Management System (BMS) Design GuidelinesPage 7 of 60Insight server running revision 3.14 client.Desigo server running v5.1The Insight server and Desigo server is running on a virtual server segment provideby and maintained by the UBC-BIS group.The following is a list of JCI BMS Facilities and equipment at UBC.1.Metasys Application Data Extended Server (ADX) (10 user) server runningMEA version 10.1/UI version 4.12.The ADX server is running on a virtual server segment, provided byand maintained by UBC-BIS group.3.Metasys Network Engines installed in distributed standalone buildingBMS installations.Existing BMS Communication Network Facilities at UBCA.All controls additions or modifications involved in a building renovation and/or addition shall

UBC Technical GuidelinesUBC Vancouver and UBC OkanaganNovember 2021 RevisionSection 25 05 00Building Management System (BMS) Design GuidelinesPage 8 of 60be an extension of the existing BMS located in the building being renovated. An exception tothis clause may be made if a vendor, other than the vendor of the existing BMS, makes anacceptable bid to replace the entire existing BMS system as well as satisfying therequirements of the building renovation or addition specifications.1.UBC retains the right to define what an acceptable bid is,2.UBC retains the right to define the extent of work required to be completed beforean existing BMS can be deemed to be replaced,3.The vendor seeking to replace an existing BMS shall submit a comprehensiveengineering proposal to UBC Energy, Planning & Innovation department detailing theproposed replacement BMS. The UBC Energy, Planning & Innovation department mustapprove of the replacement BMS system design and scope before the system can beapproved as an acceptable replacement.B.The Delta Controls BMS, JCI Metasys BMS, and the SBT Apogee BMS at UBC utilizeseparate network communication facilities. Existing BMS Network Communications facilitiesare generally as follows:1.Delta Controls BMS Data Communication within Buildinga.Automation Level communication LAN (native BACnet) for data communicationbetween CCP’s/DCP’s (and local OWS’s where applicable) within buildinginstallations utilizes either BACnet/Ethernet or MS/TP communications. TheBMS Automation Level communication networks within buildings are dedicatedBMS network segments and are not shared with other building datacommunications.b.Each building shall be a separate site and a separate subnet in the Delta system.2.Delta Controls Campus BMS Data Communicationsa.Management Level communication LAN (native BACnet) utilizes UBC campusenterprise Ethernet/ IP Network for communication between remote buildingBMS installations and the central monitoring and control equipment. Thededicated standalone BMS network is interconnected to the UBC CampusEnterprise Network at a location within the building.3.JCI BMS Facilities BMS Data Communication within Buildinga.b.c.4.Automation Level communication LAN (labelled the “Building Network” or N2Bus)for data communication between DCP’s (and local OWS’s whereapplicable) within building installations utilizes a proprietary dedicatedcommunications network on the older JCI installations. The networkcommunications is accomplished using a 3-wire, 18 gauge, RS-485 platform.The newer JCI installations utilize BACnet data communications over a MSTPnetwork that operates across a 3-wire, 22 gauge RS- 485 platform. The BMSprimary communication networks within buildings are dedicated BMS networksegments and are not shared with other building data communications.The same network topology indicated above is used for, dedicated Field Levelcommunications network (labelled the “Floor Network”) for communicationbetween ASC’s and between ASC’s and DCP’s. The older installations utilize aproprietary communication on the N2 bus and the newer installations utilizeBACnet across the MSTP bus.N2 network is only permitted by exception, approved by the UBC-BMS group.JCI Campus BMS Data Communicationsa.There are a number of JCI building installations that utilize TCP/IP Ethernetdata communications over the UBC campus enterprise Ethernet Network forcommunication between the remote building BMS installations and thecentral monitoring and control equipment. The dedicated standalone BMS

UBC Technical GuidelinesUBC Vancouver and UBC OkanaganNovember 2021 RevisionSection 25 05 00Building Management System (BMS) Design GuidelinesPage 9 of 60network is interconnected to the UBC Campus Enterprise Network at alocation within the building.5.SBT Apogee BMS Data Communications within Buildinga.b.c.6.Automation Level communication LAN (labelled the “Building Network” or P2 Bus)for data communication between DCP’s (and local OWS’s where applicable)within buildings utilizes a proprietary dedicated communications network. TheBMS primary communication networks within buildings are dedicated BMSnetwork segments and are not shared with other building data communications.Proprietary, dedicated Field Level communications network (labelled the “FloorNetwork”) for communication between ASC’s and between ASC’s and DCP’s.Non BACnet networks are only permitted by exception, approved by the UBCBMS group.SBT Apogee BMS Campus Data Communicationsa.Management Level communications LAN (Building Network/P2 Bus) for datacommunications between campus buildings is via a proprietary communicationsnetwork. The Management Level communications network utilizes coppertelephone grade cable between the remote buildings and the UBC telephonecentral exchange in the Henry Angus Building. Signal conditioning and networkinterface equipment is required to transmit the data communications via thetelephone grade lines. There are four SBT Apogee primary communicationnetwork segments at the UBC campus. All of the network segments areconnected to the SBT Apogee Server. Individual building BMS’s areinterconnected to one of the network segments based on a number of criteriaincluding the building geographical location.b.There are a number of newer SBT Apogee building installations that utilize TCP/IPEthernet data communications over the UBC campus enterprise EthernetNetwork for communication between the remote building BMS installations andthe central monitoring and control equipment. The dedicated standalone BMSnetwork is interconnected to the UBC Campus Enterprise Network at a locationwithin the building.

UBC Technical GuidelinesUBC Vancouver and UBC OkanaganNovember 2021 RevisionSection 25 05 00Building Management System (BMS) Design GuidelinesPage 10 of 602BMS INSTALLATION GUIDELINES2.1.General BMS Installation RequirementsA.This section of the UBC Design Guidelines identifies minimum requirements for BMSfield installations. BMS designs shall include these requirements and BMS designersshall ensure that design specifications include these requirements.B.All DDC connected devices shall be provided in SI units from the factory. Localconversions are not acceptable. This applied to all devices connected to the BMSsystem as well. No imperial units are acceptable.C.BMS installations shall be fully native BACnet, and be based on sound industry standardpractices that are in compliance with all applicable codes, statutes and ordinances.D.All building controls shall be by the base building contractor (existing buildings) or one ofthe three approved controls vendors (new construction, or if the competing controlscontractor wants to replace all of the existing building controls with their system).E.Integrations that provide control that is not completely controlled by the base buildingcontrols contractor is not acceptable1.F.The following items are not acceptable:a.Air handling unit package controlsb.VAV box packaged controlsc.Damper packaged controlsd.Fan coil packaged controlse.HRV packaged controlsAcceptable third party controls1.2.3.Devices that server as a safety device that would have special requirements thatcannot normally be executed by a controls contractor.Devices that meet these requirements:a.Variable speed drives.b.Kitchen ecology unitsc.Chiller controllers for modular chillersd.Boiler controllers for modular boilersThese devices still have the requirement to integrate via BACnet.G.Exceptions are acceptable. But must be approved by UBC - BMS.H.All BACnet equipment and software supplied for the projects shall be supported bymanufacturer supplied PICS (Protocol Implementation Conformance Statement)certifying that the device complies with the specified BACnet requirements.1.All products have a BTL Mark certifying that the product was independentlytested by a third party testing facility and complied with BACnet conformancerequirements.I.Design Specifications for BMS Installations shall provide detailed specifications forthe all components of the BMS including equipment, field devices, wire/cable,conduit, pneumatic tubing, mounts, terminations, etc.J.The BMS Designer shall fully coordinate BMS design requirements with the other project

UBC Technical GuidelinesUBC Vancouver and UBC OkanaganNovember 2021 RevisionSection 25 05 00Building Management System (BMS) Design GuidelinesPage 11 of 60design team parties (where applicable). The BMS Designer shall coordinate field panelmounting locations, intended DCP/ASC locations, power supply requirements,communications outlet requirements, etc.K.All new BMS Installations shall be integrated into the CBMS through either the SBT,JCI or Delta.L.The following are general installation guidelines for BMS installations:1.2.3.4.5.6.7.8.All equipment and materials furnished shall be new.All equipment and materials shall be cUL and/or UL listed and/or CSA approvedwhere applicable. Equipment and components shall be labelled accordingly.Wherever possible all similar components (e.g. temperature sensors, differentialpressure transducers, current transformer/relay combinations, signal transmitters,etc.) in a BMS installation shall be by the same manufacturer.Components shall be provided which are suitable for the intended application.Components shall be capable of maintained operation in the applicableenvironmental conditions and operation in contact with the controlled/monitoredmedium.With the exception of field mounted instrumentation and devices, all BMScomponents shall be installed in field panels. Panels and enclosures shall meet, atminimum, the following requirements:a.Painted steel panels with hinged locking door. All panels shall be keyedto the controls vendors’ standard key, or provided with non-keyed twistlocks.b.Ventilated to prevent excessive heat build-up, where required.c.Cable within enclosures shall be installed in cable ducts with snap oncovers.d.Internal components shall be installed to allow easy access fordiagnostics, maintenance, removal or replacement.e.Panel or enclosure shall be suitable rated for the environment for which itis to be installed.f.Exterior enclosures shall be, at minimum, NEMA 1 for indoor applicationsand NEMA 3R for outdoor applications.Panels and enclosures shall only be located within mechanical rooms or atapproved locations. Panel locations shall be coordinated during design by theBMS Consultant and shall be identified on project design drawings. For newconstruction projects the BMS panel locations shall be identified in the projectmechanical design drawings, and coordinated on site. For retrofit applications theBMS panel locations shall be identified on building floor plan drawings and in thegraphics package to be included in the project BMS Specifications/ContractDocuments.All components of the BMS shall be Identification tagged. Identification tags shall beresistant to mechanical damage and securely fastened to the device. Identificationtags shall be provided for, at minimum, the following;a.Sensors.b.Transmitters.c.BMS controlled valve and damper actuators.d.End-Devices (other).e.Field panels.All BMS wire and cable and pneumatic control tubing shall be identification tagged.Wire/cable shall be identification tagged at every termination location. Wire/cable andtubing termi

The UBC Design Guidelines may be used by BMS Designers for guidance in the design of UBC BMS installations but shall not be reproduced, in whole, or part, for inclusion in BMS Design Specifications, or Tender or Contract Documents. The UBC BMS Design Guidelines are not Design Specifications and do not include sufficient detail to be used as s uch.

Related Documents:

S. MPC. BMS 1&2 BMS 3&4 BMS 5 Pno. I ff was cheat ed-by you since I don't know when, 16 S. MPC. BMS 1&2 BMS 3&4 BMS 5 Pno. so I made up my mind it must come to an end,File Size: 423KBPage Count: 34

BMS, a control stage and the system load [3]. Fig. 1. Full system would be located the BMS When any cell voltage reaches the maximum load, the BMS should be disconnected from the charger (Fig. 2). The BMS must also balance the cells to maximize their capacity. The system can make the balancing by disabling the load of the

The individual cell-balancing units are controlled by the central Master RT-BMS Control Unit. New in version 4.0: we offer two basic models: 1) RT-BMS main unit with one data line for managing up to 64 cells. 2) RT-BMS main unit with three data lines for managing up to 192 cells. Real Time Battery Management System (RT-BMS) operating block diagram

conjunction with the BMS when the Orion BMS or Orion Jr. BMS are used with parallel strings. Electrical engineering is required to use the Orion BMS or. Orion Jr. BMS with parallel strings, and this work must be performed by an electrical engineer who is trained in working with and understands the risks of paralleled lithium ion batteries.

Oct 05 2015 BMS 3.1 Issue 1.5 Eric Kauz GDSN Dec ECL See summary of changes section Jun 01 2016 BMS 3.1 Issue 1.6 Eric Kauz 3.1.2 See summary of changes section. Jan 03 2020 BMS 3.1 Issue 1.7 Radhika Chauhan Release 3.1.12 See Summary of Changes Section Jan 28 2020 BMS 3.1 Issue 1.8 Radhika Chauhan Release 3.1.13 See Summary of

General description, BMS hs and BMS hp 8 3 BMS Fig. 6 Filtration Automatic control devices To protect the pumps against dry running, fit the system with flow and pressure control devices. A pressure switch on the inlet side is sized in accordance with the estimated inlet pressure. At a pressure lower than 1 bar (14.5 psi), an alarm is given

provide centralized monitoring and control of UBC buildings from a central location via microprocessor based DDC controls. To facilitate the centralized BMS monitoring and control standards have been applied to the selection of BMS equipment and for the application of BMS installat

Jadi osteologi adalah cabang dari anatomi yang memelajari tentang tulang. Dalam memelajari tulang sering pula dijumpai istilah “skeleteon”, yang berasal dari bahasa latin yang berarti kerangka. Tulang atau kerangka bagi manusia mempunyai fungsi yang amat besar, antara lain: a. Melindungi organ vital b. Penghasil darah tertentu c. Menyimpan dan mangganti kalsium dan fosfat d. Alat gerak .