THE OFFICIAL JOURNAL OF AIRAH AUGUST 2017 · VOLUME 16.7 Ecolibrium

1y ago
2 Views
1 Downloads
1.26 MB
6 Pages
Last View : 1m ago
Last Download : 3m ago
Upload by : Raelyn Goode
Transcription

EcolibriumTHE OFFICIAL JOURNAL OF AIRAHAUGUST 2017 · VOLUME 16.7RRP 14.95PRINT POST APPROVALNUMBER PP352532/00001All naturalABSTL I SHED 19 4770ouiatngrnbralCe leo f AIR AHEA new style for supermarkets?yearsfi cia s the o falj

FORUMP EER - R E V I E W ED T ECH N I C A L PA P ER SAn engineer’s guide tointernational fan test standardsAndrew Rossi, B.Eng. (Mech & Aero)ABSTRACTThis paper aims to update the knowledge of the mechanical design engineer and mechanical contractorwith regards to the current internationally standardised testing methods for fan performance and acoustics.In particular:1. ISO 5801: Industrial fans – Performance testing using standardized airways;2. ISO 13347: Industrial fans – Determination of fan sound power levels under standardized laboratory conditions;3. ISO 5136: Acoustics – Determination of sound power radiated into a duct by fans and other air-moving devices – In-duct method.Having knowledge and contextual awareness of these test standards may allow the mechanical design engineerand mechanical contractor to avoid potentially costly post-installation problems caused by underperforming or noisy fans.When selecting or approving a fan for use in any engineeringproject the most scrutinised details are achieving the designairflow, and meeting the acoustic requirements for the project.A fan’s performance curve, which graphs fan characteristics atvarying airflow, allows the designer to ascertain the fan’s abilityto achieve the design airflow at a particular system resistancepressure (McQuiston, Parker and Spitler, 2005). A fan’s soundspectrum, which shows the sound power level of the fan atdiscrete frequencies, allows the designer to ascertain the fan’sability to meet the calculated acoustic requirements of theproject (Sharland, 2005). These properties should be measuredand documented by the use of internationally recognised testingstandards.2. PERFORMANCE TESTINGTypical performance curves for fans plot the pressure,efficiency, or power against the airflow. This may be combinedwith the system pressure curve in order to match a system witha fan that can achieve the required performance (McQuiston,Parker and Spitler, 2005).The internationally standardised test methods that shouldbe used to produce fan performance curves are covered byISO 5801: “Industrial fans — Performance testing usingstandardized airways”. ISO 5801 describes the methodsto measure airflows and pressures developed by fans instandardised testing environments to result in four mutuallyexclusive performance characteristics, corresponding to fourinstallation categories:A – free inlet, free outlet;B – free inlet, ducted outlet;C – ducted inlet, free outlet;D – ducted inlet, ducted outlet (ISO, 2007).42ECO L I BR I U M AUGUS T 2017Performance curve450400350Static pressure Pa1. INTRODUCTIONPerformance ume flow m2/s1.01.2Figure 1: Centrifugal fan curve with overlayedexample system curve (Fantech, 2017).The minimum requirements of the various instrumentsthat are able to be used to measure pressure, temperature,rotational speed, power input and output, sizes, air properties,and flow rate are all included within ISO 5801 for completeness.A number of test installations are described within the standard,and are able to be selected for usage, giving flexibility of bothinstrumentation and installation to those testers who haveconstructed test installations to superseded test standards.There is, however, a list of preferred test arrangements due tothe goal of reducing the number of test arrangements in futurerevisions of the standard (ISO, 2007).Providing the testing is performed correctly, ISO 5801 resultsrequire a 95% confidence level, and produce results concerning

FORUM3. ACOUSTIC TESTINGWhile the performance of a fan can be verified to withindesign limits on site using in-situ measurement techniques(ISO, 2001), it is difficult to use similar techniques to verifythe manufacturer’s acoustic data. This is due to the manyinstallation factors, which may affect the end result, and maybe difficult to account for (Sharland, 2005).Figure 2: Example Category D Test Installation (ISO, 2007).the power, pressure, airflow, efficiency, and the fan’s workingrange (ISO, 2007). The system curve may then be overlayed todetermine the suitability of a particular fan’s performance levelηr , ηsrPaPf , Psffor a particular system design.1,400η 48 r/sq vsg1 1.2 kg/m3Pf1,200Psf1,00010800ηrPa400200660ISO 13347 is made up of four parts covering a general overview,the reverberant room method, enveloping surface method, andsound intensity methods (ISO, 2004a).4403.1.1 Reverberant Room Method21234206 q vsg15Key1working rangePafan shaft power, in kilowattsPffan pressure, in pascalsPsffan static pressure, in pascalsq vsg1 fan inlet volume rate, in cubic metres per secondηrfan efficiency, as a percentageηsrfan static efficiency, as a percentage3.1 ISO 13347:8010It has been recognised in the fan performance testing standard,ISO 5801, that the installation category has an effect on the fan’sperformance and needs to be taken into account in order to produceaccurate results (ISO, 2007). This relation between installationtype and fan performance is also recognised within the currentinternational noise- testing standards. The difference betweensound powers radiated from the fan inlet or outlet into eitherfree space or into a duct is taken into account by having a separatetesting standard, ISO 5136, for in-duct noise levels. Testing of thenoise levels radiated into free space should be determined by useof methods as described in ISO 13347 (ISO, 2003 and ISO, 2004a).8ηsr600The expected final result of the system’s acoustic levelscan be calculated by techniques that have been developedin the fields of room acoustics and building acoustics(Norsonic, 2017), as well as duct acoustics (Sharland, 2005).All of these calculations depend on the acoustic data of the soundsource, which is obtained from the equipment manufacturer.Figure 3: Example set of complete, constant-speed,fan characteristic curves (ISO, 2007).The reverberant room method as described in ISO 13347part 2 is based on the North American AMCA 300 standardand the international general acoustics standard ISO 3743.The testing environment must be qualified in accordancewith the testing standard in order to satisfy the reverberationrequirements. Providing a qualified test environment is available,this method has the shortest testing period (Guédel, 2003).The requirement of a specialised test environment makes thistest method practicable only for manufacturers that are preparedto invest in long-term premises to house such an environment.The reverberant room method itself compares the soundpressure levels of a fan running within a qualified reverberanttest room with the combined sound pressure levels of boththe fan running and a known reference sound source.Knowing the sound power levels of the reference sound sourceallows the determination of the fan sound power level throughalgebraic substitution as per equation (1) (ISO, 2004b).Sound DataSpectrum (Hz)631252055001K2K4K8KdBWdB(A)@3mInlet (dB)67656663585452497244Sound levels are quoted as in-duct values. dB(A) values are average spherical free-field for comparative use only.Figure 4: Example ISO 5136 tested sound spectrum – Type C/D installation (Fantech, 2017).AUGUS T 2017 ECO L I BR I U M43

FORUMThe sound power level in each frequency band shall be calculatedfrom:Lw   Lpc (Lwr – Lpq ) dB (1)Where:Lwis the fan sound power level(dB)Lpcis the fan sound pressure level(dB)Lwris the reference sound source sound power level(dB)Lpqis the reference sound source sound pressure level(dB).Figure 6: Example enveloping surface method installation (ISO, 2004c).3.1.3 Sound intensity methodFigure 5: Example reverberant room installations (ISO, 2004b).3.1.2 Enveloping surface methodThe enveloping surface method as described in ISO 13347part 3 is based on the international general acoustics standardISO 3744. In contrast to the reverberant room method, thismethod does not require any specific acoustic environment,and instead relies on an environmental correction factor.The lack of a specific test environment or specialisedmeasurement equipment makes this the easiest test methodto implement (Guédel, 2003). For a fan manufacturer wantingto produce standardised test results without a high upfrontinvestment this method is the most practicable.The sound intensity method is based on the ability tomeasure the sound intensity distribution on a definedmeasurement surface which completely encloses the sourcesof interest. The sound intensity distribution of the fan is thencompared to the sound intensity distribution of a knownreference sound source for calibration and convertedto a sound power level using equation (3) (ISO, 2004d).The enveloping surface method directly measures the radiatedsound pressure level from a fan, and applies an environmentalcorrection factor in order to determine the fan’s sound powerlevel using equation (2). The correction factor is determined byuse of a known reference sound source and methods containedwithin ISO 3744, and should be less than 2 dB. This standarddoes not rely upon a specific test chamber and only requiresthe background noise level to be at least 10 dB lower thanthe measured sound pressure level of the fan (ISO, 2004c).The sound power level in each frequency band shall be calculatedfrom:Lw   Lif Rw 10log ( SS ) dB 0Lwis the fan sound power level(dB)Lifis the surface average sound intensity level(dB)adjustment(dB)Sis the total measurement surface area(m2)pcLw   Lp 10log ( SS ) – K1 – K2 – 10log ( 400) S0 1m2(2)(3)Rw is the sound power level reference sound sourceThe sound power level in each frequency band shall be calculatedfrom:03.1.4 LimitationsWhere:Lwis the fan sound power level(dB)Lpis the fan surface sound pressure level(dB)Sis the total measurement surface area(m2)S0 1m2K1 & K2 are correction factors for background noiseand testing environment(dB)44The sound intensity method as described in ISO 13347part 4 is based on the international general acoustics standardISO 9614 as well as the North American AMCA 320 standard.As with the enveloping surfaces method there is no specificacoustic environment required for the sound intensity method.Rather than reading sound pressure levels with a microphone,this method uses a sound intensity probe, which is calibratedfrom readings of a reference sound source. (Guédel, 2003).The need for specialist equipment as well as more thoroughlytrained test operators makes this test method less practicablefor commercial fan manufacturers.pis the density of thecis the speed of sound in the air(m s)ECO L I BR I U M air(kg m3AUGUS T 2017)The distinction between sound power levels radiated intofree space or into duct is made clear in section 7.1 of the generaloverview, which states that the sound power level on a sideof a fan that is unducted should be determined using a methodas detailed in ISO 13347, and for the sound power level on a sideof a fan that is ducted should be determined using an in-ductmethod as detailed in ISO 5136 (ISO, 2004a).While the ISO 13347 test standard outlines the conditionsunder which the data is most suitable, and refers the testerto the in-duct test method of ISO 5136 when the soundpower is radiating into ductwork, it also makes allowances

FORUMfor manufacturers who may not have access to the equipmentnecessary for in-duct testing. In these cases, duct end correctionfactors are supplied within the standard for addition tothe critical lower frequencies. It is the responsibility of themanufacturer to clearly state the use of these correction factors.The standard notes that these correction factors are theoreticalonly (ISO, 2004a) and while this correction is necessary toprovide a closer alternative to the invariably higher in-ducttesting results, comparison tests have produced results in whichthe duct end corrections have not been sufficient (Cory, 2010).This suggests that when ambiguity of installation type arises,the in-duct method may be used as a noise level that will beas high as or higher than the actual application.3.2 ISO 5136:The ISO 5136 test standard describes the procedure ofmeasuring the sound pressure levels in the inlet or outlet ductsof a fan as well as a method to convert these sound pressurelevels to sound power levels radiated by the fan into these ducts.The test set-up includes the fan to be tested, ducting on theopposing side to that of the test, the test duct with an anechoictermination on the side to be tested, and the measurementinstrumentation. The measurements are to be taken while alsomeasuring fan performance by use of the procedures specifiedin ISO 5801. The standard applies to any sound source in whicha fan is connected to a duct on at least one side, including fans,air-handling units, duct-collection units, air conditioning units,and furnaces (ISO, 2003). This test method, while required toproduce the most accurate results for in duct noise levels, mayrequire a large and costly test set-up and considerable investmentfor new manufacturers and testers.Figure 7: Installation category D test arrangement for simultaneousmeasurement of performance and noise (ISO, 2003).The standard takes into account the difference in acousticproperties of different types of duct, and so the test duct hasbeen clearly defined to remove ambiguity of results or the needto make corrections using a reference sound source. The test ductis circular in cross-section, with an anechoic termination in orderto represent actual application conditions, which when coupledwith the concurrent measurement of fan performance, resultsin data that is suitable for acoustical calculations (ISO, 2003).The test duct for use in the testing is defined to be between0.15m and 2m in diameter to suit the size of the test fan, but thestandard also includes an informative allowance for duct sizesoutside of that range, from 0.048m to 7.1m. The airflow shieldingused on the microphone is also limited by the maximum flowvelocity produced by the fan, with a maximum velocity of 40m/sable to be measured using a sampling tube. The measured soundpressure levels taken while the fan is operating as required are tobe at least 6dB above the background noise levels, and are to betaken in at least three positions for spatial-averaging as well asover time periods for time-averaging (ISO, 2003).Once the measurements have been taken, the sound power ofeach frequency band radiated into the duct can be found using theplane-wave formula, equation (4), which relates the two throughthe duct size and general acoustic properties of air (ISO, 2003).The sound power level in each frequency band shall be calculatedfrom:(Lw   Lp 10logSS0– 10logpc(pc)0) (4)Where:Lwis the fan sound power level(dB)Lpi s the spatially and time averaged fan soundpressure level(dB)Sis the cross-sectional area of the duct(m2)S0 1m2pis the density of the air(kg m3 )cis the speed of sound in the air(m s)(pc)0 400 N s/m33.3 Comparison:Consistency of an acoustic test method within a manufacturer’srange allows a high level of comparability between fans.Due to the differences in test environment and test equipmentthis comparability is likely to decrease between manufacturers,but within the same order of uncertainty. When comparingacoustic data of fans tested to different test methodology it’simportant to consider the uncertainty levels of both the testmethods themselves as well as the context in which the resultsare relevant. While the uncertainty levels of the varying testmethods may be reduced by careful construction of the testenvironment, the standard deviation uncertainty for the mostpracticable test methods in octave frequency bands is givenbelow, as per ISO 13347-1:Contextually the uncertainty levels between ISO 13347 andISO 5136 are not directly comparable due to the application oftheoretical duct end corrections to the ISO 13347 results, whichcarry the uncertainty of theoretical results compared to realworld installations. This suggests that while duct end correctionsmay be applied for an informative in-duct level, a reliable resultcan only be obtained by use of the in-duct testing method.4. CONCLUSIONThis process of international test standardisation allowsdesigners to scrutinise the performance and acoustic data offans with context and in a comparative way between ranges andmanufacturers. The ISO 5801 test standard gives installationspecific data concerning the fan’s power, pressure, airflow,efficiency, and the fan’s working range. When referring to fanacoustic data it is important to note the installation type suchthat sound power levels of fans radiating into free space shouldbe tested to a method within ISO 13347, and sound power levelsof fans radiating into ductwork should be tested to theISO 5136 in-duct method. The in-duct acoustic data may alsobe used when the installation type is unknown to represent thehighest level. While in-duct test methodology is more accuratefor ducted fan installations it may not be practicable for allAUGUS T 2017 ECO L I BR I U M45

FORUMmanufacturers, in which case ISO 13347 makes allowance.Acoustic data collected by use of a free-field test methodshould not prohibit usage on ducted installations, but insteadbe considered to have a higher level of variance under thoseconditions in contrast to acoustic data collected by use of an induct method. Comparing the context of testing and installationmay be crucial in the avoidance of post-installation problemscaused by underperforming or noisy fans. ISO (2003). International Standard: ISO 5136 – 2003 Acoustics– Determination of sound power radiated into a duct by fansand other air-moving devices – In-duct method.ISO (2004a). International Standard: ISO 13347, part 1 – 2004Industrial fans –Determination of fan sound power levels understandardized laboratory conditions, Part 1 – General overview.ISO (2004b). International Standard: ISO 13347, part 2 – 2004Industrial fans – Determination of fan sound power levels understandardized laboratory conditions, Part 2 – Reverberant roommethod.5. NOMENCLATUREISO (2004c). International Standard: ISO 13347, part 3 – 2004Industrial fans – Determination of fan sound power levels understandardized laboratory conditions, Part 3 – Enveloping surfacemethods.Anechoic Sound deadeningor free from reverberation.dB Decibel – A logarithmic ratio of levels,in this context a ratio of either pressuresor sound intensities .ReverberantA tendency to reflect sound.Sound intensity The energy of sound wavesper unit area W m2 .Sound power level The rate at which acoustic energyis emitted from the sound source.Sound pressure level The local pressure differencecaused by a soundwave.ISO (2004d). International Standard: ISO 13347, part 4 – 2004Industrial fans – Determination of fan sound power levels understandardized laboratory conditions, Part 4 – Sound intensitymethod.ISO (2007). International Standard: ISO 5801 – 2007: Industrialfans – Performance testing using standardized airways.Norsonic, (2017), Building Acoustics, [online] Available g acoustics/[Accessed 8 Mar. 2017].Cory, W. (2010). Fans and Ventilation: A Practical Guide,Amsterdam, The Netherlands: Elsevier B. V., pp.228–2296. REFERENCESGuédel, A. (2003). ISO 13347: The new standard for measuringnoise by reverberant room, enveloping surface and intensitymethods. Acoustique & techniques, (33), pp.40–42.McQuiston, F. and Parker, J. and Spitler, J. (2005). Heating,Ventilating, and Air Conditioning Analysis and Design. 6th ed.New Jersey, United States: Wiley, pp.394-407.Sharland, I. (2005). Fläkt Woods Practical Guide toNoise Control. 9th ed. Colchester, England: Fläkt WoodsLimited,pp.37-108.ABOUT THE AUTHORAndrew Rossi holds a Bachelor of Mechanical andAerospace Engineering from the University of Adelaide.Fantech Pty Ltd. (2017) Fantech Selection Program.Melbourne, Australia: Fantech Pty Ltd.He currently works in the South Australian Branchof Fantech, and can be contacted at arossi@fantech.com.auISO (2001). International Standard: ISO 5802 – 2001 Industrialfans – Performance testing in situ.Standard Deviation, dBOctave BandFrequencies,HzIn-Duct– ISO 5136Reverberant FieldWith AnechoicTerminations– ISO 13347-2Reverberant FieldWithout AnechoicTerminations– ISO 13347-2EnvelopingSurfaces Method– ISO 2231.540002231.580003.5332.5Uncertainty in determination of the frequency-band sound power levels (ISO, 2004a)46ECO L I BR I U M AUGUS T 2017

1. ISO 5801: Industrial fans - Performance testing using standardized airways; 2. ISO 13347: Industrial fans - Determination of fan sound power levels under standardized laboratory conditions; 3. ISO 5136: Acoustics - Determination of sound power radiated into a duct by fans and other air-moving devices - In-duct method.

Related Documents:

May 02, 2018 · D. Program Evaluation ͟The organization has provided a description of the framework for how each program will be evaluated. The framework should include all the elements below: ͟The evaluation methods are cost-effective for the organization ͟Quantitative and qualitative data is being collected (at Basics tier, data collection must have begun)

Silat is a combative art of self-defense and survival rooted from Matay archipelago. It was traced at thé early of Langkasuka Kingdom (2nd century CE) till thé reign of Melaka (Malaysia) Sultanate era (13th century). Silat has now evolved to become part of social culture and tradition with thé appearance of a fine physical and spiritual .

Chris Orr, Brett Staines; Matthew Wright n Greg Buckley – Fire NSW/AFAC n Peter Conroy – City of Sydney n Dan Dainard, M.AIRAH n Brett Fairweather, M.AIRAH n James Fricker, F.AIRAH n Simon Hill, L.AIRAH n David Kearsley – CFA n Doug Lamac n P

On an exceptional basis, Member States may request UNESCO to provide thé candidates with access to thé platform so they can complète thé form by themselves. Thèse requests must be addressed to esd rize unesco. or by 15 A ril 2021 UNESCO will provide thé nomineewith accessto thé platform via their émail address.

̶The leading indicator of employee engagement is based on the quality of the relationship between employee and supervisor Empower your managers! ̶Help them understand the impact on the organization ̶Share important changes, plan options, tasks, and deadlines ̶Provide key messages and talking points ̶Prepare them to answer employee questions

Dr. Sunita Bharatwal** Dr. Pawan Garga*** Abstract Customer satisfaction is derived from thè functionalities and values, a product or Service can provide. The current study aims to segregate thè dimensions of ordine Service quality and gather insights on its impact on web shopping. The trends of purchases have

Chính Văn.- Còn đức Thế tôn thì tuệ giác cực kỳ trong sạch 8: hiện hành bất nhị 9, đạt đến vô tướng 10, đứng vào chỗ đứng của các đức Thế tôn 11, thể hiện tính bình đẳng của các Ngài, đến chỗ không còn chướng ngại 12, giáo pháp không thể khuynh đảo, tâm thức không bị cản trở, cái được

Le genou de Lucy. Odile Jacob. 1999. Coppens Y. Pré-textes. L’homme préhistorique en morceaux. Eds Odile Jacob. 2011. Costentin J., Delaveau P. Café, thé, chocolat, les bons effets sur le cerveau et pour le corps. Editions Odile Jacob. 2010. Crawford M., Marsh D. The driving force : food in human evolution and the future.