Installation CAUC-IOM-8 Operation Maintenance Library Service Literatur

1y ago
11 Views
2 Downloads
1.12 MB
36 Pages
Last View : 13d ago
Last Download : 3m ago
Upload by : Mya Leung
Transcription

TMInstallationOperationMaintenanceLibraryProduct SectionProductModelLiterature TypeCAUC-IOM-8Service LiteratureRefrigerationAir Cooled uenceDateFile No.Supersedes8October 2008SV-UN-S/S-CAUC-IOM-8 10/08December 2001Remote Air Cooled CondensersModels"J" and Later Design SequenceCAUC-C80CAUC-D10CAUC-D12 2008 Trane All rights reservedhttp://www.trane.comNote: The installation of this equipment mustcomply with all National, State, and LocalCodes.Since the manufacturer has a policy of continuous productimprovement, it reserves the right to change specifications anddesign without notice.

About The ManualLiterature Change HistoryOverview of ManualCAUC-IOM-8 (December 2001)First issue of manual; provides Installation, Operation, andMaintenance instructions for “J” and later design sequenceon CAUC 80 through 120 Ton air cooled condensing units.Note: One copy of this document ships inside thecontrol panel of each unit and is customerproperty. It must be retained by the unit'smaintenance personnel.This booklet describes proper installation, operation, andmaintenance procedures for air cooled systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/orcomponent damage will be minimized.It is important that periodic maintenance be performed tohelp assure trouble free operation. A maintenance scheduleis provided at the end of this manual. Should equipmentfailure occur, contact a qualified service organization withqualified, experienced HVAC technicians to properly diagnose and repair this equipment.Note: The procedures discussed in this manualshould only be performed by qualified, experiencedHVAC technicians. Do Not release refrigerant to theatmosphere! If adding or removing refrigerant isrequired, the service technician must comply withall federal, state, and local laws.2

Table of ContentsDischarge (Hot Gas) Lines . 15Discharge Line Components . 16Making Refrigerant Connections . 16Brazing Procedures . 16Leak Testing Procedure . 17Field Installed Power Wiring . 17Main Unit Power Wiring . 17Field Installed Control Wiring . 20Section OneAbout The ManualLiterature Change History . 2Overview of Manual . 2Section TwoGeneral InformationModel Number Description . 4Unit Nameplate . 4Hazard Identification . 4Unit Description . 4Unit Component Layout and "Shipwith" Locations . 5Section ThreeInstallationUnit Inspection . 6Unit Clearances . 6Unit Dimensions & Weight Information . 6Foundation . 6Rigging . 11Unit Isolation . 12Spring Isolators . 12Leveling the Unit . 13General Unit Requirements . 14Refrigerant Piping . 14Main Electrical Power Requirements . 14Field Installed Control Wiring . 14Refrigerant Piping . 15Liquid Lines . 15Liquid Line Components . 15Section FourSystem Pre-Start ProceduresSystem Evacuation Procedures . 21Voltage Imbalance . 23Electrical Phasing . 23Section FiveSystem Start-UpSequence of Operation . 24Verifying Proper Fan Rotation . 25All Fans are Rotating Backwards; . 25Some Fan Rotating Backwards . 25Low Ambient Damper Adjustment . 26System Charging . 26Section SixService and MaintenanceMonthly Maintenance . 32Coil Cleaning . 33Index . 343

General InformationModel Number DescriptionWhen ordering replacement parts or requesting service, besure to refer to the specific model number, serial number,and DL number (if applicable) stamped on the unit nameplate.All Trane products are identified by a multiple-charactermodel number that precisely identifies a particular type ofunit. An explanation of the alphanumeric identification codeis provided below. Its use will enable the owner/operator, installing contractors, and service engineers to define the operation, specific components, and other options for any specific unit.Sample Model No.: CAUC - D12 4 - 2 B 1 0 H, etc.Digit No.: 1 2 3 4 5,6,7 8 9 10 11 12 13,14Digit 1C CondenserDigit 2 - CondenserA Air CooledDigit 8 - Power Supply4 460/60/3 XL5 575/60/3 XLE 200/60/3 XLF 230/60/3 XLDigit 11 - Ambient Control0 Standard1 0FDigit 3 - Air FlowU Up FlowDigit 9 - Condenser Circuit2 DualDigit 4 - Development SequenceC ThirdDigit 10 - Design SequenceJ Disconnect RedesignDigit 12 - Agency Approval0 None2 CSA3 UL / CSADigit 13, 14 - Miscellaneous OptionsH Copper Fins1 Spring IsolatorsDigits 5, 6, 7 - Nominal CapacityC80 80 TonsD10 100 TonsD12 120 TonsUnit NameplateUnit DescriptionOne Mylar unit nameplate is located on the outside upperright corner of the control panel door. It includes the unitmodel number, serial number, electrical characteristics,weight, refrigerant charge, as well as other pertinent unitdata. A small metal nameplate with the Model Number, Serial Number, and Unit Weight is located just above the Mylarnameplate, and a third nameplate is located on the inside ofthe control panel door.All air cooled condensing units are designed for outdoor installations with vertical air discharge. These units may beinstalled on a flat roof or placed on a concrete slab atground level.When ordering replacement parts or requesting service, besure to refer to the specific model number, serial number,and DL number (if applicable) stamped on the unit nameplate.The condenser coils are aluminum fin, bonded to coppertubing. Copper-fin coils are optional. Louvered condensergrilles for coil protection are standard.Before shipment, each unit is leak-tested, evacuated, a Nitrogen holding charge is added, and the controls are testedfor proper operation.Direct-drive, vertical discharge condenser fans are providedwith built-in current and overload protection.Hazard IdentificationFor “Shipwith” items, refer to the Unit Component “Layout”and “Shipwith” Locations illustration.Warnings are provided throughthismanualtoindicatetoinstalling contractors, operaouttors, and service personnel of potentially hazardous situations which, if not avoided, COULD result in death or serious injury.If low ambient operation is required, low ambient dampersare available as a field or factory installed option.The unit control panel contains all required fan cycling controls, compressor interlocks, and a 115 volt control powertransformer. Field wiring, electrical schematics and panelconnection diagrams are located inside the control panelaccess door.Cautions are provided throughoutthis manual to indicate to installing contractors, operators,and service personnel of potentially hazardous situationswhich, if not avoided, MAY result in minor or moderate injury.4

General Information (Continued)Unit Component "Layout" and "Shipwith" Locations(120 Ton Unit Illustrated)5

InstallationUnit InspectionUnit ClearancesAs soon as the unit arrives at the job siteFigure 3-1 illustrates the minimum operating and serviceclearances for either a single, multiple, or pit application.These clearances are the minimum distances necessary toassure adequate serviceability, cataloged unit capacity, andpeak operating efficiency.[ ] Verify that the nameplate data matches the data on thesales order and bill of lading (including electrical data).[ ] Verify that the power supply complies with the unit nameplate specifications.Providing less than the recommended clearances may result in condenser coil starvation or recirculation of hot condenser air.[ ] Visually inspect the exterior of the unit, including the roof,for signs of shipping damage.Locate the unit as close to the applicable system supportequipment as possible, to minimize refrigerant pipinglengths.[ ] Check for material shortages. Refer to the ComponentLayout and Shipwith Location illustration.If the job site inspection of the unit reveals damage or material shortages, file a claim with the carrier immediately.Specify the type and extent of the damage on the "bill oflading" before signing.Unit Dimensions & Weight Information[ ] Visually inspect the internal components for shippingdamage as soon as possible after delivery and before itis stored. Do not walk on the sheet metal base pans.A Center-of-Gravity illustration and the dimensional data isshown in Figure 3-3.Overall unit dimensional data for each unit is illustrated inFigure 3-2.Table 3-1 lists the typical unit operating and point loadingweights.FoundationN O S T E P S U R FA C E !If the unit is installed at ground level, elevate it above thesnow line. Provide concrete footings at each support location or a slab foundation for support. Refer to Table 3-1 forthe unit operating and point loading weights when constructing the footing foundation.FOR ACCESS TO COMPONENTS, THE BASE SHEETMETAL SURFACE MUST BE REINFORCED.Bridging between the unit's main supports may consist of multiple 2 by 12 boards or sheet metal grating.Anchor the unit to the footings or slab using hold down boltsor isolators. Isolators should be installed to minimize thetransmission of vibrations into the building. Refer to the“Unit Isolation” section for spring isolator installation instructions.Failure to comply can cause severe personal injuryor death from falling.[ ] If concealed damage is discovered, notify the carrier'sterminal of damage immediately by phone and by mail.Concealed damage must be reported within 15 days.For rooftop applications, ensure the roof is strong enough tosupport the unit. Refer to Table 3-1 for the unit operatingweights.Request an immediate joint inspection of the damage bythe carrier and the consignee. Do not remove damagedmaterial from the receiving location. Take photos of thedamage, if possible. The owner must provide reasonableevidence that the damage did not occur after delivery.Anchor the unit to the roof with hold-down bolts or isolators.Follow the instructions under “Unit Isolation” for proper isolator placement and installation.[ ] Notify the appropriate Trane office before installing or repairing a damaged unit.Check with a roofing contractor for proper waterproofingprocedures.6

Installation (Continued)Figure 3-1Typical Installation Clearances for Single, Multiple and Pit Applications7

Figure 3-2CAUC-C80 Unit Dimensional Data & Recommended Clearances8

Figure 3-2 (Continued)CAUC-D10 Unit Dimensional Data & Recommended Clearances9

Figure 3-2 (Continued)CAUC-D12 Unit Dimensional Data & Recommended Clearances10

Installation (Continued)Table 3-1Typical Unit Weights & Point Loading DataOperatingUnit Weight on Isolator @ Mounting LocationUnitWeightLocation 12345678SizeALCUAL CU AL CU AL CU AL CU AL CU AL CU AL CU AL CUC80 4036 4637 514 586 478 549 522 597 485 560 524 600 487 562 532 611 494 572D10 4675 5472 603 698 571 666 600 700 569 668 600 700 569 668 597 702 566 670D12 4911 6109 631 774 600 742 630 779 598 747 629 780 598 748 628 786 597 753Notes: Mounting locations correlate with those shown in point loading illustration.Figure 3-3Rigging and Center-of-Gravity DataUnitSizeC80D10D12ShippingWeight(Max. Lbs)454253715971Location of Center ofGravity FTING AND MOVING INSTRUCTIONS!DO NOT USE CABLES (CHAINS OR SLINGS) EXCEPT ASSHOWN. OTHER LIFTING ARRANGEMENTS MAY CAUSEEQUIPMENT DAMAGE OR SERIOUS PERSONAL INJURY.EACH OF THE CABLES (CHAINS OR SLINGS) USED TO LIFTUNIT MUST BE CAPABLE OF SUPPORTING THE ENTIREWEIGHT OF THE UNIT.LIFTING CHAINS (CABLES OR SLINGS) MAY NOT BE THESAME LENGTH. ADJUST AS NECESSARY FOR EVENLEVEL LIFT.USE SPREADER BARS AS SHOWN IN DIAGRAM. REFERTO INSTALLATION MANUAL OR NAMEPLATE FOR UNITWEIGHT. REFER TO INSTALLATION INSTRUCTIONSLOCATED INSIDE CONTROL PANEL FOR FURTHERRIGGING INFORMATION.11

Installation (Continued)RiggingSpring IsolatorsInstall the spring isolators at each unit mounting (load)point, using the following procedure:A Rigging illustration and Center-of-Gravity dimensionaldata table is shown in Figure 3-3. Refer to the typical unitoperating weights table before proceeding.1. Elevate the unit (one side at a time) to allow access tothe base rail mounting holes.1. Rig the condensing unit as shown in Figure 3-3. Attachadequate strength lifting slings to all four lifting bracketsin the unit base rail. Do not use cables, chains, or slingsexcept as shown.Note: Use solid type blocks, i.e. 4" X 4" woodblocks or similar material to prevent collapsing.Keep hands and other body limbs clear of elevatedbase rail while installing isolators to preventpersonal injury.2. Install spreader bars, as shown in Figure 3-3, to protectthe unit and to facilitate a uniform lift. The minimum distance between the lifting hook and the top of the unitshould be 7 feet.2. Align the mounting holes in the base rail of the unit withthe positioning pin in the top of the appropriate isolator.Refer to Figure 3-4 for the appropriate isolator for eachload point.3. Test-lift the unit to ensure it is properly rigged and balanced, make any necessary rigging adjustments.3. Position the isolator to allow access to the mountingholes in the base of the isolator.4. Lift the unit and position it into place.Unit Isolation4. Lower the unit onto the isolator. The positioning pin onthe isolator must engage into the hole of the base rail.The clearance between the upper and lower isolatorhousings should be approximately 1/4 to 1/2 inch. Referto Figure 3-4. A clearance greater than 1/2 inch indicatesthat shims are required to level the unit. Refer to the“Leveling the Unit” section.To minimize unit sound and vibration transmission, one ofthe following installation methods should be used:1. Install the unit directly on an isolated (detached) concretepad or on isolated concrete footings located at each unitload point.5. Make minor clearance adjustments by turning the isolator leveling bolt (Figure 3-4) clockwise to increase theclearance and counterclockwise to decrease the clearance. If proper isolator clearance cannot be obtained byturning the leveling bolt, level the isolators themselves.A 1/4 inch variance in elevation is acceptable.2. Install the optional spring isolators at each mounting location. Refer to the following “Spring Isolator” section.Figure 3-4Typical Spring Isolator Selection & LocationFinSpring Isolator Part Number @ Mounting LocationUnit Size Mat'l. Location Note:1. Mounting locations correlate with those shown in point loading illustration.2. The spring is marked with the full spring ID part # (ie CP-1D-900)If the isolator is color coded, there is a painted mark on each spring as follows;CP-1D-1200 grayCP-1D-1360 whiteCP-1D-900 dark green3. Refer to the "Spring Isolator" section, step 4, for proper 00CP-1D-900CP-1D-1200CP-1D-900CP-1D-1200

Installation (Continued)Leveling the Unit6. Secure the isolator to the mounting surface using thebase holes in the isolator.Before tightening the mounting bolts, level the unit carefully.Use the unit base rail as a reference. Level the unit to within1/4 inch over its entire length. Use shims if adjustable isolators (neoprene) are not used.7. After the unit is level, tighten the isolator base mountingbolts to secure them to the mounting surface.If adjustable isolators (spring) are used, ensure that theproper isolator housing clearance is maintained while leveling the unit. Isolators are identified by color and/or an isolator part number. Shims under the isolators may be requiredif the unit can not be leveled using the isolator leveling bolt.13

Installation (Continued)General Unit Requirements[ ] Install proper filter driers in each liquid line.The checklist listed below is a summary of the steps required to successfully install a commercial air cooled condenser. This checklist is intended to acquaint the installingpersonnel with what is required in the installation process. Itdoes not replace the detailed instruction called out in theapplicable sections of this manual.[ ] Leak test the system. Refer to the “Refrigerant Piping”section for recommended procedures.Main Electrical Power Requirements[ ] Verify the power supply meets the required power requirements of the system.[ ] Verify that the power supply complies with the unit nameplate specifications.[ ] Install power wiring in accordance with all applicablecodes.[ ] Check the unit for shipping damage and material shortage; file a freight claim and notify Trane office.[ ] Install and connect properly sized power supply wiring,with over current protection, to the main power terminalblock (1TB1) in the unit control panel.[ ] Verify that the installation location of the unit will providethe required clearance for proper operation.[ ] Install proper grounding wires to an earth ground.[ ] Install appropriate isolators, if required.Field Installed Control WiringRefrigerant Piping[ ] Verify that the Control transformer (1T1) is wired for theproper operating voltage.[ ] Install properly sized liquid line(s) between the liquid lineconnections on the unit and the evaporator. (i.e., DXevaporator or an EVP Chiller Barrel). Refer to the “Refrigerant Piping” section for recommended liquid linecomponents and guidelines.[ ] Install the interlock circuitry wiring between the unit andthe appropriate compressor unit to permit condenser fanoperation when the compressor starter auxiliary contactscloses. Refer to the Field Connection Diagram thatshipped with the unit for interlocking information.[ ] Install properly sized discharge (hot gas) line(s) betweenthe discharge line connections on the unit and the compressor unit. Refer to the “Refrigerant Piping” section forrecommended discharge line components and guidelines.[ ] Verify the appropriate jumpers have been installed on theunit to allow proper condenser fan operation (If applicable). Refer to the control wiring diagram that shippedwith the unit for jumper details.[ ] Install shutoff valves in the liquid line(s) to isolate the filter drier(s) for service.14

Installation (Continued)Refrigerant PipingLiquid Line ComponentsRefrigerant piping must be properly sized and applied.These two factors have a very significant effect on both system performance and reliability.Filter driers and valves (expansion valves, charging valves,etc.) should be provided in the liquid lines just before theevaporator. Minimize the use of valves, reducers and tubebends as much as possible to avoid excessive pressuredrop before the expansion valve.Note: Use Type "L" refrigerant grade copper tubingonly.Liquid Line Filter DrierInstall the filter driers (provided by the installer) in the liquidlines as close as possible to the expansion valves. Locatethem upstream of the moisture indicator and solenoidvalves (Solenoid valves may not be applicable).Refrigerant Piping should be sized and laid out according tothe job plans and specifications. This should be done whenthe system components are selected. The primary objectivewhen sizing refrigerant piping for this unit is to make refrigerant line sizes as small as possible while avoiding excessive refrigerant pressure drops.Liquid Line Moisture IndicatorsTo aid in troubleshooting, charging and servicing the system, install moisture indicators in the liquid lines near theevaporator, down stream of the liquid line drier between thesolenoid valve (if applicable) and the expansion valve.Sizing refrigerant lines as small as possible minimizes therequired refrigerant charge and maximizes compressor life.Trane recommends that the Refrigerant Line Sizing program in the "Trane C.D.S. Application Toolbox" be used tosize the refrigerant lines. This program supersedes the linesizing tables in both the Trane Reciprocating Refrigerationpublication and the Trane Air Conditioning Manual. If you donot have access to this program, contact your local TraneCommercial Sales office for assistance.Liquid Line Solenoid ValvesLiquid line solenoid valves are not recommended on unitswhen they are connected to DX coils. Liquid line solenoidvalves are recommended for refrigerant migration controlwhen they are connected to an EVP chiller and should beconnected as described in the “Electrical Wiring” section.Liquid LinesNote: Do not use any solenoid valve as apumpdown device. Equipment damage will occur.Basic sizing parameters with the system operating at fullload for liquid lines are:Thermostatic Expansion Valve (TEV)Trane recommends a balance-ported externally equalizedvalve in order to maintain satisfactory superheat controldown to lower valve loading conditions and to compensatefor pressure drops between the expansion valve and superheat control point (evaporator refrigerant outlet). The powerhead should be a “VGA” charge with Sporlan valves or a“W” charge with Alco valves. These charges provide smoothcontrol at air conditioning conditions and are less susceptible to power head “charge migration” than the conventional gas charged types.Maximum Liquid velocity . 600 fpmMaximum allowable pressure drop . 7 psig (1 F)As the pressure drop in the liquid line increases, the potential for liquid flashing, due to reduced refrigerant pressurecorresponding to a reduced liquid temperature (subcooling),increases. Under these conditions, liquid lines exposed tohigh surrounding ambient temperatures must be insulated.Discharge (Hot Gas) LinesNote: Adding refrigerant to a system withimproperly sized refrigerant lines will onlydecrease system performance and reliability andaccentuate poor operating condition.Discharge lines should be pitched downward 1/2 inch foreach 10 feet of horizontal run in the direction of hot gas flowand away from the compressor. Insulate any portion of thedischarge piping that is exposed to outdoor ambient temperature.Isolate all refrigerant lines from the building. This preventstransferring line vibration to the structure. Do not secure thelines rigidly to the building at any point since this will defeatthe isolation system of the unit.Discharge line sizing is based on the minimum velocity required to provide good oil movement through the system.Refer to the appropriate unit illustration in Figure 3-2 for refrigerant line size connections and locations. Connect theliquid line piping to the stubs provided at the liquid line shutoff valves.Basic discharge line parameters are:Maximum allowable pressure drop . 6 psigMaximum velocity . 3500 fpmNote: The installer must cut an appropriately-sizedopening in the unit sheet metal for the refrigerantpiping entrance into the unit.Minimum velocities at Minimum Load:Horizontal Lines . 500 fpmVertical Lines . Refer to the Table 3-215

Installation (Continued)A double riser system may be necessary to meet the discharge line velocity requirements.present, relieve the pressure before attempting to unsweatthe “seal” caps. If refrigerant connections are not capped,but are “spun-end” tubes, use a tubing cutter to remove theend from the pipe.When either a single or double discharge riser is used, theline should drop well below the discharge outlet of the compressor before starting the vertical rise to prevent the possibility of refrigerant draining back to the compressor duringthe "Off" cycle.Note: To prevent damage to the system, do not drilla hole in the seal caps or saw the ends off pipestubs. This may introduce copper chips into thesystem piping.Table 3-2Minimum Vertical Line VelocitiesLineMinimumDia.Velocity 5/8"8253-1/8"9153-5/8"975Brazing ProceduresProper brazing techniques are essential when installing refrigerant piping. The following factors should be kept inmind when forming sweat connections.1. When copper is heated in the presence of air, Copper oxide forms. To prevent copper oxide from forming insidethe tubing during brazing, sweep an inert gas, such asdry nitrogen, through the tubing. Nitrogen displaces air inthe tubing and prevents oxidation of the interior surfaces.A nitrogen flow of one to three cubic feet per minute issufficient to displace the air. Use a pressure regulatingvalve or flow meter to control the flow.Discharge (Hot Gas) Line ComponentsField supplied hot gas mufflers, pipe anchors, single ordouble risers, oil traps, etc. as applicable, should be provideto prevent excessive line vibration and assure proper oil return to the compressor for proper system operation.USE NITROGEN ONLY TO PURGE THE SYSTEMWHILE SWEATING CONNECTIONS.A field supplied discharge “shutoff” valve in each hot gasline near the condenser is recommended to facilitate refrigerant storage in the condenser during service procedures.Failure to follow proper procedures can result in personal injury or death due to a possible formation ofan explosive mixture of R-22 and air and/or inhalation of phosgene gas.A “constant drain” oil trap is illustrated below and can beused as an alternative to a double riser application. Theconstant drain oil trap assures adequate oil return to thesuction line even at part load conditions. Refer to “Reciprocating Direct Expansion Piping Systems” (AM-REF 1/82) forsuggested piping arrangement details.2. Ensure that the tubing surfaces to be brazed are clean,and that the ends of the tubes have been carefullyreamed to remove any burrs.3. Make sure the inner and outer tubes of the joint are symmetrical and have a close clearance, providing an easyslip fit. If the joint is too loose, the tensile strength of theconnection will be significantly reduced. The overlap distance should be equal to the diameter of the inner tube.Hot Gas1/4" SolenoidValve4. Wrap the body of each refrigerant line component with awet cloth to keep it cool during brazing. Move any tubeentrance grommets away for the brazing area.Oil TrapOil ReturnLineNote: Use 40 to 45% silver brazing alloy (BAg-7 orBAg-28) on dissimilar metals. Use BCup-6 brazingalloy on copper to copper joints.5 feet of 1/8"Copper TubingFilterDrip Leg5. If flux is used, apply it sparingly to the joint. Excessiveflux can enter the system which will contaminate the refrigerant system.Final Refrigerant Pipe Connections6. Apply heat evenly over the length and circumference ofthe joint to draw the brazing material into the joint bycapillary action. Remove the brazing rod and flame fromthe joint as soon as a complete fillet is formed to avoidpossible restriction in the line.To access the refrigerant pipe connections, remove the louvered side grills. Refer to Figure 3-2.These condensing units are shipped with a Nitrogen holding charge. Install pressure gauges to the appropriate access valve(s) and take a reading. If no pressure is present,refer to the “Leak Testing Procedure” section. If pressure is7. Visually inspect the connection after brazing to locateany pin holes or crevices in the joint. The use of a mirrormay be required, depending on the joint location.16

Installation (Continued)Leak Testing ProcedureField Installed Power WiringWhen Leak-testing a refrigerant system, observe all safetyprecautions.An overall dimensional layout for the field installed wiringentrance into the unit is illustrated in Figure 3-2. To insurethat the unit’s supply power wiring is properly sized and installed, follow the guidelines outlined below.Note: Never use oxygen, acetylene or compressedair for leak testing. Always install a pressureregulator, shutoff valves and gauges to controlpressure during leak testing.Note: All field installed wiring must conform to NECguidelines as well as State and Local codes.Trane condensing units are shipped with a Nitrogen holding charge. If there is no p

maintenance personnel. This booklet describes proper installation, operation, and maintenance procedures for air cooled systems. By care-fully reviewing the information within this manual and follow-ing the instructions, the risk of improper operation and/or component damage will be minimized. It is important that periodic maintenance be .

Related Documents:

First issue of manual; provides Installation, Operation, and Maintenance instructions for "J" and later design sequence on CAUC 20 through 60 Ton air cooled condensing units. Overview of Manual Note: One copy of this document ships inside the control panel of each unit and is customer property. It must be retained by the unit's maintenance .

The IOM 12-point Global Strategy2 defines the overall focus of IOM’s work. The IOM Regional Strategies are based on the IOM mandate enshrined in the IOM Constitution and derived from the IOM’s Global Strategy. This document presents a forward-looking Regional Strateg

MS-IOM1711-0 4-Point IOM with 4 BI, FC Bus and SA Bus Support X X MS-IOM2711-0 6-Point IOM with 2 UI, 2 UO, 2 BO, FC Bus, and SA Bus Support. Relays are rated for 120/240 VAC. X MS-IOM2711-2 6-Point IOM with 2 UI, 2 UO, 2 BO, FC Bus, and SA Bus Support. Relays are rated for 240 VAC. X MS-IOM2721-0

INTERNAL AUDIT REPORT IOM Sana'a YE201701 16 - 23 MAY 2017 Issued by the Office of the Inspector General . Page 2 of 13 Report on the Audit of IOM Sana'a Executive Summary Audit File No. YE201701 The IOM Office of the Inspector General (OIG) conducted an internal audit of the IOM Sana'a, Yemen

Installation and Operation Manual Installation, Operation, and Service Information IOM 7509401 (ENG) Revision 6 English Master Language. . ainet ase allon ail ack Tyical ide iew ront iew Tyical ide iew ront iew allon Drum ack Tyical ide iew ront iew. Cabinet Model 90 Cabinet Models 54-4 ront iew. Tyical ide iew. D DWER

Following the service manual procedure, remove the IOM from the engine. a b c 50466 . If the rubber end sheet has moved above the cooling stack tubes, contact Mercury Technical Service at 920‑929‑5884 for further instruction. If the IOM is replaced, record the IOM serial number in the warranty claim text.

The IOM Regional Office for Southern Africa, based in Pretoria, covers 15 countries in the Southern African region.4 IOM operates through 5865 staff members located in 24 offices across the region. The Regional Office provides technical backstopping and programme support to IOM country offices in the Southern African region.

Kindergarten Writing Curriculum Pacing Guide Content Area: Writing-Language Arts Grade Level: Kindergarten Building a Talking Community: Oral Language September Unit 1: Launch Writing October-November Unit 2: Writers are Readers December-January Unit 3: How-To Books February-March Unit 4: Persuasive Writing April-June