580J*08-16 LEGACY LINE SERIESSINGLE PACKAGE ROOFTOPGAS HEATING/ELECTRIC COOLING UNITSTWO-STAGE/TWO-CIRCUIT ANDTWO-STAGE/ONE-CIRCUIT COOLINGCAPACITY CONTROL— PERFORMANCE DATA— CERTIFIED DIMENSION PRINTS— CERTIFIED ROOF CURB DETAILSEdition Date: 11-19Printed in U.S.AManufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.Catalog No: SUB580J–8-16-03 Rev/AReplaces: SUB580J–8-16-02

JOB NAME:LOCATION:BUYER:BUYER PO #:UNIT NUMBER:MODEL NUMBER:BRYANT#:PERFORMANCE DATA CERTIFIED BY:DESCRIPTION580J units are single-packaged electric cooling, gas heating units that are pre-wired and pre-charged with Puron (R-410A)HFC refrigerant. The units are factory tested in both heating and cooling modes. These units meet the DOE-2018 (Departmentof Energy), ASHRAE (American Society of Heating, Refrigerating, and Air-Conditioning Engineers) 90.1-2016, andIECC-2015* (International Energy Conservation Code) minimum efficiency requirements. Models with two-stage cooling andtwo-circuit design (08-16 sizes) come standard with two-speed indoor fan motor for U.S. installations. Models with two-stagecooling and one-circuit design does not require two-speed fan motor to meet U.S. minimum efficiencies for DOE.FEATURESRefrigerant System (All) Accutrol† and/or TXV refrigerant metering system Liquid line filter drier Scroll compressors with internal line-break overloadprotection Copper tube, aluminum fin evaporator coils Top cover removable gauge line plugs for readingrefrigerant pressure with unit panels in place Round Tube/Plate Fin (RTPF) condenser coils on allmodel sizes or Novation all aluminum condenser coilsavailable on sizes 08-14 with two-stage/two-circuitGas Heat (All) IGC solid-state gas heat exchanger control for on-boarddiagnostics, anti-cycle protection, LED error code designation, burner control logic and energy saving indoorfan motor delay Gas efficiencies up to 82% Designed in accordance with ANSI Z21.47 (design andtest standard for gas furnaces) and ANSI Z233.1(National Fuel Gas code relating to appliance installation requirements) Induced draft combustion Redundant gas valve, with up to 2 stages of heating Flame roll-out safety protector Solid-state electronic direct spark ignition systemStandard Limited Parts Warranty 15-year limited on all gas heat exchanger parts Stainless Steel 10-year limited on all gas heat exchanger parts Aluminized 5-year limited on all compressor parts 5-year parts on Factory Installed Ultra Low LeakEconomizer 3-year limited on all Novation condenser coil parts 1-year limited on all Round Tube/Plate Fin (RTPF condenser coil parts 1-year limited on all partsStandard Base Unit (United States Models) Two-stage/two-circuit cooling capacity control on 08-16models Two-stage/one-circuit cooling capacity control on 08,09, and 12 models. Energy saving two-speed indoor fan motor on two-circuit (08-16). Required in U.S. installations. Not available or required to meet DOE on 580J*N models 08, 09,and 12 DOE-2018, ASHRAE 90.1-2016, and IECC-2015energy compliant Rated in accordance with AHRI Standard 340/360 Designed in accordance with Underwriters LaboratoriesStd 1995 Listed by ETL and ETL-Canada Non-corrosive composite sloping design; side or centerdrain condensate pan. Meets ASHRAE Standard 62 Standard cooling operating range from 40 F up to 115 F(4 C up to 46 C). Field installable accessory extends theminimum down to –20 F (–29 C) Field convertible from vertical to horizontal airflow forslab mounting Two-inch disposable return air filters Thru-the-bottom power and gas entry capability Single point gas and electric connections 24-volt control circuit protected with resettable circuitbreaker and 75-VA transformer Belt drive, constant torque, permanently lubricatedevaporator-fan motor Totally enclosed condenser motors with permanentlylubricated bearings Low-pressure and high-pressure switches Full perimeter base rail with built-in rigging adaptersand fork truck slots Central Terminal Board for component and unit wiringconnectionsStandard Base Unit (Non-United States Models) All features listed above IEERs:—up to 11.8 with standard motor—up to 12.8 with 2 speed/VFD indoor fan motor Two-stage/one-circuit cooling capacity control (sizes 08to 12)Cabinet (All) Access panels with easy grip handles and NO-STRIPscrew collars Pre-painted exterior panels and primer-coated interiorpanels tested to 500 hours salt spray protection Fully insulated cabinet Tool-less filter access door* IECC is a registered trademark of International Code Council Inc.† Accutrol is a trademark of Accutrol LLC.2

PERFORMANCE DATAUnit Operating Weight lbCurb Weight lbCOOLINGHEATING (GAS)Gross Total Capacity BtuhHeating Capacity:at Condenser Air Temperature FStage 1 BtuhGross Sensible Capacity BtuhStage 2 BtuhCompressor Power Input kWHeating Capacity Total BtuhIndoor Entering: db F / wb FStage 1 kWAirflow CFM External Static Pressure in. wgStage 2 kWIndoor Fan Motor Size HPHeating Capacity Total kWExhaust Fan Motor Size HPELECTRICAL DATAPower Supply to UnitVoltsPhase HzMaximum Circuit AmpsMaximum Overcurrent ProtectionSUBMITTAL DATAJob NameArchitectEngineerContractorUnit DesignationUse of the AHRI CertifiedTM Mark indicates amanufacturer’sparticipation in theprogram. For verificationof certification for individualproducts, go towww.ahridirectory.org.3

FACTORY-INSTALLED OPTIONS6.4.3.4.3, and meet 2016 Fault Detection andDiagnosis requirements in section 6.4.3.12.Economizers meet IECC 2012 sectionC402.4.5.2 and, IECC 2015 sectionsC403.2.4.3 and C403.3.3.5 for outside air, return air, and relief air damper leakage requirements and IECC 2015 section C403.2.4.7 forFault Detection and Diagnostic requirements.NOTE: IECC 2015 section C403.2.4.7.1 requires differential return air sensor, which mustbe ordered separately.Outside air, return air, and relief air (volume)dampers are AMCA rated — plus 5 year limitedparts warranty (EconoMi er 2 system).Economizer with ENTHALPY Sensing and Barometric ReliefULTRA LOW LEAK Air Dampers —Models with W7220 controller meet CaliforniaEnergy Commission Title 24-2016 perspectivesection 140.4 (damper leakage, etc.), and mandatory section 120.2.i for Fault Detection andDiagnostic controls. Economizers meetASHRAE 90.1-2016 damper leakage requirements as stated in section 6.5.1.1.4 and Table6.4.3.4.3, and meet 2016 Fault Detection andDiagnosis requirements in section 6.4.3.12. Foroutside air, return, and relief air damper leakagerequirements economizers meet IECC 2012section C402.4.5.2 and, IECC 2015 sectionsC403.2.4.3 and C403.3.3.5 and IECC 2015 section C403.2.4.7 for Fault Detection and Diagnostic requirements.NOTE: IECC 2015 section C403.2.4.7.1 requires differential return air sensor, which mustbe ordered separately.Outside air, return air, and relief air (volume)dampers are AMCA rated — plus 5 year limitedparts warranty (EconoMi er X system).Models with RTU Open meet California EnergyCommission Title 24-2016 perspective section140.4 (damper leakage, etc.) and mandatorysection 120.2.i for Fault Detection and Diagnostic requirements. Economizers meetASHRAE 90.1-2016 damper leakage requirements as stated in section 6.5.1.1.4 and Table6.4.3.4.3, and meet 2016 Fault Detection andDiagnosis requirements in section 6.4.3.12.Economizers meet IECC 2012 sectionC402.4.5.2 and, IECC 2015 sectionsC403.2.4.3 and C403.3.3.5 for outside air, return air, and relief air damper leakage requirements and IECC 2015 section C403.2.4.7 forFault Detection and Diagnostic requirements.NOTE: IECC 2015 section C403.2.4.7.1 requires differential return air sensor, which mustbe ordered separately.Outside air, return air, and relief air (volume)dampers are AMCA rated — plus 5 year limitedparts warranty (EconoMi er 2 system).Economizer with DRY BULB Sensing and Barometric ReliefLow Leak Air Dampers —Models with W7212 controller provide standardnon-diagnostic control (EconoMi er IV system).Models with W7220 controller meet CaliforniaTitle 24-2016 (Section 120.2) for FaultDetection and Diagnostic (FDD) requirements(EconoMi er X system).Models with RTU Open controller meet California Title 24-2016 (Section 120.2) FaultDetection and Diagnostic (FDD) requirements(EconoMi er 2 system).Economizer with ENTHALPY Sensing and Barometric ReliefLow Leak Air Dampers —Models with W7212 controller provide standardnon-diagnostic control (EconoMi er IV system).Models with W7220 controller meet CaliforniaTitle 24-2016 (Section 120.2) Fault Detection andDiagnostic (FDD) requirements (EconoMi er Xsystem).Models with RTU Open controller meet California Title 24-2016 (Section 120.2) FaultDetection and Diagnostic (FDD) requirements(EconoMi er 2 system).Economizer with DRY BULB Sensing and Barometric ReliefULTRA LOW LEAK Air Dampers —Models with W7220 controller meet CaliforniaEnergy Commission Title 24-2016 perspectivesection 140.4 (damper leakage, etc.), and mandatory section 120.2.i for Fault Detection andDiagnostic controls. Economizers meetASHRAE 90.1-2016 damper leakage requirements as stated in section 6.5.1.1.4 and Table6.4.3.4.3, and meet 2016 Fault Detection andDiagnosis requirements in section 6.4.3.12. Foroutside air, return, and relief air damper leakagerequirements economizers meet IECC 2012section C402.4.5.2 and, IECC 2015 sectionsC403.2.4.3 and C403.3.3.5 and IECC 2015 section C403.2.4.7 for Fault Detection and Diagnostic requirements.NOTE: IECC 2015 section C403.2.4.7.1 requires differential return air sensor, which mustbe ordered separately.Outside air, return air, and relief air (volume)dampers are AMCA rated — plus 5 year limitedparts warranty (EconoMi er X system).Models with RTU Open meet California EnergyCommission Title 24-2016 perspective section140.4 (damper leakage, etc.) and mandatorysection 120.2.i for Fault Detection and Diagnostic requirements. Economizers meetASHRAE 90.1-2016 damper leakage requirements as stated in section 6.5.1.1.4 and Table4

FACTORY-INSTALLED OPTIONS (CONT)Standard Base Unit (United States Models)RTU Open multi-protocol controller communicates toBACnet*, Modbus†, LonWorks**, and Johnson N2protocols.Through the base connectors for gas and electricconduit/pipingStainless steel gas heat exchanger (includes tubes,vestibule plate and collector box)Perfect Humidity adaptive dehumidification system(RTPF condenser coil units only)Two-position motorized outdoor air damperNon-fused disconnectPowered 115-volt convenience outletNon-powered 115-volt convenience outletHigh static evaporator fan motorReturn Air smoke detectorSupply Air smoke detectorCO2 sensorCondenser hail guard-louvered styleSpecial coating protection for evaporator andcondenser coilsHinged access doorsCondensate overflow switchStainless steel gas heat exchangerStandard Base Unit (Non-United States Models)2-speed indoor fan systemOptional WarrantiesComplete unit parts only, up to 5 yearsComplete unit parts and labor, up to 5 yearsMany other optional warranties are available. See theCommercial Start-Up and Optional ExtendedWarranty Price pages for further information.*†**5BACnet is a registered trademark of ASHRAE (AmericanSociety of Heating, Refrigerating and Air-ConditioningEngineers).Modbus is a registered trademark of Schneider Electric.LonWorks is a registered trademark of Echelon Corporation.

FIELD-INSTALLED ACCESSORIESModels with RTU Open meet California EnergyCommission Title 24-2016 perspective section140.4 (damper leakage, etc.) and mandatorysection 120.2.i for Fault Detection and Diagnostic requirements. Economizers meetASHRAE 90.1-2016 damper leakage requirements as stated in section 6.5.1.1.4 and Table6.4.3.4.3, and meet 2016 Fault Detection andDiagnosis requirements in section 6.4.3.12.Economizers meet IECC 2012 sectionC402.4.5.2 and, IECC 2015 sectionsC403.2.4.3 and C403.3.3.5 for outside air, return air, and relief air damper leakage requirements and IECC 2015 section C403.2.4.7 forFault Detection and Diagnostic requirements.NOTE: IECC 2015 section C403.2.4.7.1 requires differential return air sensor, which mustbe ordered separately.Outside air, return air, and relief air (volume)dampers are AMCA rated (EconoMi er 2system).Economizer with ENTHALPY Sensing and Barometric ReliefULTRA LOW LEAK Air Dampers —Models with W7220 controller meet CaliforniaEnergy Commission Title 24-2016 perspectivesection 140.4 (damper leakage, etc.), and mandatory section 120.2.i for Fault Detection andDiagnostic controls. Economizers meetASHRAE 90.1-2016 damper leakage requirements as stated in section 6.5.1.1.4 and Table6.4.3.4.3, and meet 2016 Fault Detection andDiagnosis requirements in section 6.4.3.12. Foroutside air, return, and relief air damper leakagerequirements economizers meet IECC 2012section C402.4.5.2 and, IECC 2015 sectionsC403.2.4.3 and C403.3.3.5 and IECC 2015 section C403.2.4.7 for Fault Detection and Diagnostic requirements.NOTE: IECC 2015 section C403.2.4.7.1 requires differential return air sensor, which mustbe ordered separately.Outside air, return air, and relief air (volume)dampers are AMCA rated (EconoMi er Xsystem).Models with RTU Open meet California EnergyCommission Title 24-2016 perspective section140.4 (damper leakage, etc.) and mandatorysection 120.2.i for Fault Detection and Diagnostic requirements. Economizers meetASHRAE 90.1-2016 damper leakage requirements as stated in section 6.5.1.1.4 and Table6.4.3.4.3, and meet 2016 Fault Detection andDiagnosis requirements in section 6.4.3.12.Economizers meet IECC 2012 sectionC402.4.5.2 and, IECC 2015 sectionsC403.2.4.3 and C403.3.3.5 for outside air, return air, and relief air damper leakage requirements and IECC 2015 section C403.2.4.7 forFault Detection and Diagnostic requirements.NOTE: IECC 2015 section C403.2.4.7.1 requires differential return air sensor, which mustbe ordered separately.Outside air, return air, and relief air (volume)dampers are AMCA rated (EconoMi er 2system).Economizer with DRY BULB Sensing and Barometric ReliefStandard Leak Air Dampers —Models with W7212 controller provide standardnon-diagnostic control (EconoMi er IV system).Models with W7220 controller meet CaliforniaTitle 24-2016 Section 120.2.i for FaultDetection and Diagnostic (FDD) requirements.(EconoMi er X system).Models with RTU Open controller meet California Title 24-2016 Section 120.2.i FaultDetection and Diagnostic (FDD) requirements.(EconoMi er 2 system).Economizer with ENTHALPY Sensing and Barometric ReliefStandard Leak Air Dampers —Models with W7212 controller provide standardnon-diagnostic control (EconoMi er IV system).Models with W7220 controller meet CaliforniaTitle 24-2016 Section 120.2.i Fault Detection andDiagnostic (FDD) requirements (EconoMi er Xsystem).Models with RTU Open controller meet California Title 24-2016 Section 120.2.i FaultDetection and Diagnostic (FDD) requirements(EconoMi er 2 system).Economizer with DRY BULB Sensing and Barometric ReliefULTRA LOW LEAK Air Dampers —Models with W7220 controller meet CaliforniaEnergy Commission Title 24-2016 perspectivesection 140.4 (damper leakage, etc.), and mandatory section 120.2.i for Fault Detection andDiagnostic controls. Economizers meetASHRAE 90.1-2016 damper leakage requirements as stated in section 6.5.1.1.4 and Table6.4.3.4.3, and meet 2016 Fault Detection andDiagnosis requirements in section 6.4.3.12. Foroutside air, return, and relief air damper leakagerequirements economizers meet IECC 2012section C402.4.5.2 and, IECC 2015 sectionsC403.2.4.3 and C403.3.3.5 and IECC 2015 section C403.2.4.7 for Fault Detection and Diagnostic requirements.NOTE: IECC 2015 section C403.2.4.7.1 requires differential return air sensor, which mustbe ordered separately.Outside air, return air, and relief air (volume)dampers are AMCA rated (EconoMi er Xsystem).6

FIELD-INSTALLED ACCESSORIES (CONT)Low ambient head pressure controller, down to0 F (–18 C)Low ambient head pressure controller, down to–20 F (–29 C)Time Guard II compressor anti-cycle protectionThermostats and SensorsSupply duct kit (size 16 units only)Disconnect switch bracket (size 16 units only)Condensate overflow switchNon-powered 115-volt (20 amp) convenience outletSide access hinged filter door kitHorn/strobe annunciatorEconomizer SensorsSingle Dry bulb controlDifferential Dry bulb controlSingle enthalpy controlDifferential enthalpy controlCO2 — wall mountedCO2 — duct mountedCO2 — unit mountedDisplay Kit for Variable Frequency Drive (VFD), 2speed indoor fan motor system. Allows additional setup and diagnostics of the unit VFD controller. Can beunit mounted or used with any other compatible VFDmodel as a reusable device.Prop power exhaustTwo-position motorized outdoor air damperManual outside air damper 25%Manual outside air damper 50%Roof Curb — 14 inch (356 mm) tallRoof Curb — 24 inch (610 mm) tallThru-the-bottom connections (electrical only)Thru-the-bottom connections (electrical and gas)Condenser hail guard (louvered style)Flue shieldFlue discharge deflectorLiquid propane (LP) conversion kitHigh altitude conversion kitPhase monitor (loss of phase/phase reversal)Winter start kit, down to 25 F (–4 C)7

8Fig. 1 — 580J*08-12 Dimensional DrawingCERTIFIED DIMENSION PRINT

9Fig. 2 — 580J*08-12 Corner WeightsCERTIFIED DIMENSION PRINT

10Fig. 3 — 580J*14 Dimensional DrawingCERTIFIED DIMENSION PRINT

11Fig. 4 — 580J*14 Corner WeightsCERTIFIED DIMENSION PRINT

12Fig. 5 — 580J*16 Dimensional DrawingCERTIFIED DIMENSION PRINT

13Fig. 6 — 580J*16 Corner WeightsCERTIFIED DIMENSION PRINT

14CRRFCURB004A014 9/16"[115.5]1 3/4"[44.5]1/4"[7.0]1 3/4"[44.5]15 13/16"[401.6]3"[76.2]4 3/16"[106.0]53 1/2"[1358.9]11.42"[290.0]SUPPLY AIR31 17/32"[800.9]SUPPLY AIROPENING32 016 3/64"[153.5]AROOF CURBACCESSORY #RETURN AIRRETURN AIROPENING14 3/4"[374.7]15 15/32[392.9]23 1/16"[585.8]81 3/4"[2076.3]40 3/16"[1020.8]1 3/4"[44.4]2 1/4"[57.2]REVCDATE4/22/13BYMMCROOFING MATERIAL(FIELD SUPPLIED)CANT STRIP(FIELD SUPPLIED)ROOFING FELT(FIELD SUPPLIED)COUNTER FLASHING(FIELD SUPPLIED)TYPICAL (4) SIDESCHK'D-APP'D-ECN NO.1067898-SURFACE FINISHWEIGHT:PURCHMFG/PURCHT-005, Y-002- --ANGMODEL (INTERNAL USE ONLY)CHECKERMANUFACTURING102912012/16/09 -DRAFTERMMC--3 DECAUTHORIZATION NUMBER-ENGINEERING-2 DECUNLESS OTHERWISE SPECIFIEDDIMENSIONS ARE IN INCHESTOLERANCES ON:PRODUCTION1 DEC--6' 6-1/4"[1987.5]1-3/4"TYP[44.5]SEE NOTE #21/2" [12.7] NPTACCESSORY CONVENIENCEOUTLET WIRING CONNECTOR-N/ACREV-DISTRIBUTIONSHEET 5 OF 5SCALE50HJ405012CURB ASY, ROOFDRAWING NUMBERNEXT DRAWINGDSIZETITLETHIS DOCUMENT AND THE INFORMATION CONTAINED THEREINIS PROPRIETARY TO CARRIER CORPORATION AND SHALL NOTBE USED OR DISCLOSED TO OTHERS, IN WHOLE OR IN PART,WITHOUT THE WRITTEN AUTHORIZATION OF CARRIER CORPORATION.2-3/8"[61]20-3/4"[513]INSIDE1/2" [12.7] NPTCONTROL WIRINGFITTINGRETURN AIR1 1/4" [31.7] NPTPOWER WIRINGFITTINGCERTIFIED DRAWINGENGINEERING REQUIREMENTS-MATERIALTHIRD ANGLEPROJECTIONDRAWING RELEASE LEVEL:SEE VIEW "B"4' 2"[1270.0]SUPPLY AIRGAS SERVICE PLATETHRU THE CURBDRILL HOLE2" [50.8] @ASSEMBLY (IFREQUIRED)(SEE NOTE #8)9-15/16" [252.4] WIDEINSULATED DECK PANEL"A"3/4" [19] NPTGAS FITTING12-1/2" [317.5] WIDEINSULATED DECK PANELSTHRU THE BOTTOMTHRU THE CURBGAS CONNECTION TYPEFig. 7 — 580J*08-14 Roof Curb DetailsREVISION RECORD1 3/4"[44.4]1.00"[25.4]SECTION THRU SIDE"A"1 3/4"[44.5]CRBTMPWR004A01CRBTMPWR002A01CONNECTOR PKG. ACC.NAIL (FIELD SUPPLIED)RIGID INSULATION(FIELD SUPPLIED)7/16"[11]UNIT6' 61/4" WAS 6' 7 1/6", 4'2' WAS 4' 2 13/16";18 GA WAS 16 GA.; 15 13/16" WAS 15 15/16"; NAILFIELD SUPPLIED WAS WITH CURBDUCT(FIELD SUPPLIED)GASKET(SUPPLIED WITH CURB)VIEW "B"CORNER DETAILNOTES:1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED.2. INSULATED PANELS: 25.4 [1"] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY.3. DIMENSIONS IN [ ] ARE IN MILLIMETERS.4. ROOFCURB: 18 GAGE STEEL.5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB).6. SERVICE CLEARANCE 4 FEET ON EACH SIDE.7.DIRECTION OF AIR FLOW.8. CONNECTOR PACKAGE CRBTMPWR002A01 IS FOR THRU-THE-CURB GAS TYPEPACKAGE CRBTMPWR004A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.CERTIFIED ROOF CURB DETAILS

15Fig. 8 — 580J*16 Roof Curb DetailsCERTIFIED ROOF CURB DETAILS

Copyright 2018 Bryant Heating & Cooling SystemsEdition Date: 11-19Printed in U.S.AManufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.Catalog No: SUB580J–8-16-03 Rev/APg 16Replaces: SUB580J–8-16-02

HFC refrigerant. The units are factory tested in both heating and cooling modes. These units meet the DOE-2018 (Department of Energy), ASHRAE (American Society of Heating, Refrigerating, and Air-Conditioning Engineers) 90.1-2016, and IECC-2015* (International Energy Conservation Code) minimum ef ficiency requirements. Models with two-stage .

Related Documents:

580J* 07A is a single-packaged electric cooling, gas heating unit that is pre-wired and pre-charged with Puron . Accutrol† refrigerant metering system Liquid line filter drier Scroll compressors with internal line-break overload protection Copper tube, aluminum fin coils with optional corro- .

2.16 Schematic of a legacy logo endorsement 2.17 Example of a legacy program logo endorsement 2.18 Example of a legacy agency logo endorsement 2.19 Legacy logo endorsement of a sub-program or initiative lock up 2.20 Schematic of a legacy logo endorsing a sub-program 2.21 Example of a legacy logo

network governance phases: legacy conceptualization, legacy planning and implementation, legacy transfer, and post-Games legacy governance, as well as a number of governance mechanisms (e.g., contracts, policies) that had an impact on the overall governance of the event's legacy. Finally, a critical analysis of the governance of

5 What Are Lines And Stanzas? Line A line is pretty self-explanatory. Line A line of a poem is when it jumps Line To a new, well, line, Line Like this! Line Sometimes a line is a complete sentence. Line But it doesn’t Line Have to be! Line A stanza is kind of like a paragraph. Line Stanzas are made up of lines. Line This “stanza” has five lines.

Legacy 2.5i Limited in Twilight Blue Metallic with optional equipment. Introducing the 2016 Subaru Legacy See ho far trust can take you. Confidence and trust are their own kind of freedom in the new 2016 Legacy, the longest-lasting midsize sedan in its class.1 Considering that 95% of all Subaru Legacy vehicles sold

Civil Liberties and the Legacy of Harry S. Truman The Truman Legacy Series, Volume 9 Based on the Ninth Truman Legacy Symposium The Civil Liberties Legacy of Harry S. Truman May 2011 . President Truman’s special message to Congress on Civil Rights, February 2, 1948 . . . 178

Dolomite Legacy Deluxe Rollator Padded backrest, padded seat and basket standard. The Dolomite Legacy is more than just a name, it is a Legacy. For over 10 years the Legacy has brought daily mobility back to hundreds of thousands throughout 80 countries worldwide. Founded on Dolomite’s patented flip-up seat technology, Legacy provides provenFile Size: 939KB

Por Alfredo López Austin * I. Necesidad conceptual Soy historiador; mi objeto de estudio es el pensamiento de las sociedades de tradición mesoamericana, con énfasis en las antiguas, anteriores al dominio colonial europeo. Como historiador no encuentro que mi trabajo se diferencie del propio del antropólogo; más bien, ignoro si existe alguna conveniencia en establecer un límite entre .