Data Center TrendsAnd DesignSteven ShapiroCritical Facilities Practice Lead

Data Center Trends & DesignAgenda IT Trends Cooling Design Trends Power Design Trends

IT Trends VirtualizationDensityDensity vs Reliability ProfileChip Cooling

Virtualization and Density For every 18’F rise in temperature hardwarereliability decreased by 50% Footprint reduction 30% per year Since 2000, power consumption for chips doubled 17% annual increase in load density in past 10 yearsIT Trends

Chip CoolingChip Manufacturers are Investigating: New Sink Architectures Water Cooled Sinks Large Cooling Fans (up to 70 cfm per server)IT Trends

Density vs. Reliability ProfileTIERIVENTERPRISEWEB HOSTINGCOLOIIIIIOLD MAINFRAMEI50Design CriteriaIT Trends100150W/SF200250300

Total Cost of OwnershipCostDesignConfigurationReliability g RisksResilience CostsHigher ReliabilityIT TrendsEfficiency

Best Practices – Data Center Planning/Design Don’t lose the forest forthe Tiers kW/cabinet is more insightful thanaverage W/sq ft Nail the program, budget and scheduleearly on Design in modularity and scalability Optimization through planning, designand commissioningIT Trends

Cooling Design TrendsFighting Density and IncreasingEnergy Efficiency In the Data Center For the Data Center System Selection Process Economization Alternatives

In The Data CenterFan Powered Cabinet ExampleCabinet FansHot Air PlenumRaisedFloorHot Airis discharged out ofthe top via ductworkCooling TrendsConditioned Airis drawn through thefront of the cabinet

In The Data CenterWater Cooled Cabinet ExampleCabinet FansDischarge AirCooling CoilSupply ReturnPipingHigh Pressureflex hose and quick-connectfittings to chilled water mainsCooling TrendsRaisedFloorFan Coilon rear doorcools serversConditioned Airis drawn through thefront of the cabinet

In The Data CenterHot Aisle Cold Aisle ConfigurationReturn AirColdAisleHotAisleConditioned Airis drawn through thefront of the cabinetCooling TrendsColdAisleHot Airis discharged out of theback of the cabinetConditioned Airis drawn through thefront of the cabinet

For The Data CenterSystem Alternatives Chiller/Cooling Tower Air Cooled Chiller Adiabatic Cooling/Swamp Cooler(Roof, Ground, CRAH) Outside Air Air to Air (Munthers, Schneider, HuntAire, Kyoto) Water Side Economizer (Heat Exchanger) DX Backup/Full-Partial DrycoolersCooling Trends

For The Data CenterSystem Selection ProcessCooling Trends

For The Data CenterSystem Selection ProcessCooling Trends

For The Data CenterSystem AlternativesDirect Air Economizer SystemOutside air doesenter the data centerCooling TrendsIndirect Air Economizer SystemOutside air does not enterthe data center

For The Data CenterSystem AlternativesDirect Evaporative Air Economizer“Swamp” cooler with outside airentering the data centerCooling TrendsIndirect Evaporative Air Economizer“Swamp” cooler without outsideair entering the data center

For The Data CenterSystem AlternativesKYOTO WHEELIndirect Air-side EconomizerCooling Trends

Power Design Trends Reliability / AvailabilityUPS TechnologyConcurrent MaintainabilityExample One Line

Reliability / Availability Load Density (The Major Issue) 99.9999% Availability (“Six Sigma”) 2(N 1), 2N, N 2 Redundancy Common N or (N 1) Systems Not Good Enough Full Concurrent Maintenance Fault Tolerant Configurations – Eliminate SPOF’sPower Design Trends

UPS Technology UPS with transformer or transformer free Efficiency Ground current issues UPS Modules with internal redundancy Internal redundancy but same single input/output UPS System Static Switch module level system level UPS Technology Double ConversionOfflineLine interactiveDelta ConversionRotaryetc.Power Design Trends

UPS Technology Eco Mode Good - Efficiency Bad – UPS Offline ITIC Curve/CBEMA Curve UPS Distribution Voltage 600, 575, 480V, 415V,120/208V 3 Phase 3 Wire,3 Phase 4 Wire DC systems andvoltage – 380VDCPower Design Trends

UPS TechnologyTypical UPS Configurations Single Module Systems Isolated Redundant Parallel Redundant Distributed Redundant Block RedundantPower Design Trends

Reliability / AvailabilityParallelRedundantPower Design Trends

Reliability / AvailabilityDistributedRedundantPower Design Trends

Reliability / AvailabilityBlock RedundantPower Design Trends

Cost, Availability and Design TopologyPushing the Limits of Complexity Bad Capital InvestmentPower Design Trends

Data Center Electrical InfrastructureTopologies – Reliability TableDescription of RBDMTBF(Hours)Inherent Availability(Ai)Probability ofFailure in 5 yearsN 1 UPS system - dual cord loads32,5090.9998162658.16%Distributed Redundant (2-3) UPS system - dual cordloads161,6460.999979947.43%2N UPS system - dual cord loads214,1820.999987236.56%2(N 1) UPS system - dual cord loads305,2510.99998686.49%Utility and N 1 UPS system, ASTSs - dual cordloads65,0560.999998218.02%Redundant Reserve (2-3) UPS System, ASTSs dual cord loads257,4590.999990582.58%Distributed Redundant (2-3) UPS system, ASTSs dual cord loads256,6740.999990462.72%2N UPS system, ASTSs - dual cord loads445,6910.999998451.12%2(N 1) UPS system, ASTSs - dual cord loads989,9600.999998390.88%Power Design Trends

Electrical Trends575V DistributionTraditional voltage distribution to the PDU primary is 480V,consider use of 575VBenefits: Reduces cable and bus sizes by 20% Allows systems to operate more efficiently Allows more capacity out of the equivalent 480Vinfrastructure Maintains the use of standard equipment sizes Can be utilized with UPS, motor and all other majorequipment within the building Overall reduces initial installation cost and long termmaintenance and operating costsPower Design Trends

Electrical Trends415V Distribution and Eliminate Transformers Transformers are traditionally used to step down the voltage to 208Vfor use at the server rack. Because the vast majority of modern servers are designed for theglobal market including the IEC low voltage standard 415/240V, theimplementation of a 415/240V UPS system with a 3 phase, four wiredistribution can be used. Distribution at 415/240V eliminates the transformation requirementsand aligns critical loads directly with the UPSBenefits: Still maintains the use of standard equipment, electrically and servers Reduces one level of transformation, increasing overall electricalefficiency by 2%. Reduces HVAC requirements by 6 tons/MW. Reduces the amount of equipment needed to support the load,reducing initial costs. Increases reliability and availability, and reduces maintenance costsPower Design Trends

Electrical Trends – Eco ModePower Design Trends

Concurrent MaintainabilityGoals “Change Tires, Transmission and Engine at60mph and Don’t Lose Speed.” No IT Downtime for Preventative andCorrective Maintenance ScalabilityPower Design Trends

Concurrent MaintainabilityThe Solution Dual/Diverse Utility Services Dual Active Distribution Paths N 2 Generator Plant “Self-Healing” Automation and Control Physical Separation/Compartmentalization 2N Static UPS or Similar Dual Electrical Cords to IT CabinetsPower Design Trends

Medium Voltage DistributionUtility Bypass/Gen Control MaintenanceRed-Normal ‘A’Green-Normal ‘B’Yellow-GeneratorPower Design Trends

UPS – Normal OperationRed-Normal ‘A’Green-Normal ‘B’Blue-UPS ‘A’Pink-UPS’B’Power Design Trends

UPS to RPP Normal OperationBlue-UPS ‘A’Pink-UPS’B’Power Design Trends

QUESTIONS?Steven Shapiro, /stevenshapiropeThank you and please feelfree to contact me

Data Center Trends And Design. Data Center Trends & Design Agenda IT Trends Cooling Design Trends Power Design Trends. IT Trends Virtualization . increasing overall electrical efficiency by 2%. Reduces HVAC requirements by 6 tons/MW. Reduces the amount of equipment needed to support the load,

Related Documents:

Trends in Care Delivery and Community Health State Public Health Leadership Webinar Deloitte Consulting LLP June 20, 2013. . Current state of Accountable Care Organizations (ACOs) and trends. Current state of Patient-Centered Medical Homes (PCMHs) and trends. Introduction.File Size: 2MBPage Count: 38Explore further2020 Healthcare Trends and How to Preparewww.healthcatalyst.comFive Health Care Trends For 2020 Health Affairswww.healthaffairs.orgTop 10 Emerging Trends in Health Care for 2021: The New .trustees.aha.orgRecommended to you b

The NIH Sustainable Data Center Design Guide can assist you with your data center design efforts by . and efficiency with data center infrastructure management . The NIH Sustainable Data Center Design Guide reflects the most current thinking in data center design strategies and provides viable solutions to sources of inefficiency such as .

SOFTWARE DEFINED DATA CENTER SERVICES VIRTUAL DATA CENTER VIRTUAL DATA CENTER VIRTUAL DATA CENTER VIRTUAL DATA CENTER VIRTUAL DATA CENTER Network Storage Server Security The Software-Defined Data center

long trends. Trends shaping the future of work Earlier Deloitte research identified seven disruptive trends that are shaping the future of work (see Figure 1). these trends can be grouped into two categories: socio-demographic trends and enabling technology trends. For example, the diversity of the workforce is increasing as we live longer and

In the 6 scatter plots, 2 reflect positive trends, 2 reflect negative trends, and 2 reflect no trends. In the 6 scatter plots, most of the scatter plots reflect the 3 different types of trends. In the 6 scatter plots, few of the scatter plots reflect the 3 different types of trends. The 3 different types of trends are not reflected in the

FinTech waves – Italian FinTech Ecosystem 2020 2 Research goals and methods 3 Executive summary 5 Update post COVID-19 8 1 Financial services trend 10 Global trends 11 Europe trends 13 Italian trends 16 2 The FinTech market 26 FinTech environment 27 Global trends 29 Europe trends 39 Italian trends 45 3 Italian FinTech ecosystem 53 4 The investor

2 ALASKA ECONOMIC TRENDS AUGUST 2014 August 2014 Volume 34 Number 8 ISSN 0160-3345 To contact Trends authors or request a free electronic or print subscription, e-mail trends@ alaska.gov or call (907) 465-4500. Trends is on the Web at labor.alaska.gov/trends. Alaska Economic Tr

Artificial intelligence is a new digital frontier that will have a profound impact on the world, transforming the way we live and work. WIPO Director General, Francis Gurry. Preface 7 Foreword 8 About the contributors 10 Acknowl- edgments 12 Executive summary 13 1 Introduction The past, present and future of AI: what research and innovation trends can reveal; the data used in this report and .