Report Number: 1757-16008-002 Project Number: Contact - Schier Products

1y ago
4 Views
1 Downloads
602.21 KB
10 Pages
Last View : 1m ago
Last Download : 3m ago
Upload by : Callan Shouse
Transcription

Report Number:1757-16008-002Report Issued:March 3th, 2016Client:Schier Products9500 Woodend Rd.Edwardsville, KS 66111Project Number: 26020Contact: Charlie IsmertSource of Samples: Samples were manufactured at the client’s facility in Edwardsville, KS andwitnessed tested by Dale E. Holloway of IAPMO R&T Lab. Samples aremanufactured in good condition.Date of Testing:March 1st, 2016Sample Description: Grease Interceptor.Model: GB-2 (50 gpm)Refer to the manufacturer’s drawings and installation instructions for moredetailed measurements and information.Scope of Testing:The above grease interceptor was witnessed tested to meet therequirements of ASME A112.14.3-2000 (Reaffirmed 2004) “GreaseInterceptors” and CSA B481.1-12 “Testing and rating of greaseinterceptors using lard”.Conclusion:The “GB-2 (50 gpm)” Grease Interceptor DID COMPLY with therequirements of ASME A112.14.3-2000 (Reaffirmed 2004) for “GreaseInterceptors” and CSA B481.1-12 “Testing and rating of greaseinterceptors using lard”.By the signature below, I certify that all the testing and preparation for this report was performedunder direct supervision of IAPMO R&T Lab, unless otherwise stated.Witness tested and reported by,Dale E. Holloway, Regional Technical ManagerIAPMO R&T LabAll testing and sample preparation for this report was performed under the continuous, direct supervision of IAPMO R&T Lab, unless otherwise stated. The observations, test results andconclusions in this report apply only to the specific samples tested and are not indicative of the quality or performance of similar or identical products. Only the Client shown above isauthorized to copy or distribute the report, and then only in its entirety. Any use of the IAPMO R&T Lab name for the sale or advertisement of the tested material, product or service mustfirst be approved in writing by IAPMO R&T Lab.Page 1 of 10

Primary Standards: ASME A112.14.3-2000 (Reaffirmed 2004)22.12.22.32.433.13.23.33.43.5General RequirementsDesignRatingInlet and Outlet ConnectionsFlow Controls and/or VentsTestingConstruction of Test EquipmentInstallation of Testing EquipmentPreliminary Test ProcedureSkimming ProcedureRating Test Procedure44.14.24.3Labeling, Installation, and Maint.LabelingInstallation InstructionsMaintenance InstructionsTest Results: All test and evaluations were conducted per the written procedures in the specificstandards.CSA B481.1-125Test Method (Testing is covered under ASME A112.14.3 below)Test Results: All test and evaluations were conducted per the written procedures in the specificstandards.ASME A112.14.3-2000 (Reaffirmed 2004) (also covers CSA B481.1-12)2 General Requirements:2.1 Design:COMPLIESThe grease interceptor complies with all the applicable requirements of ASME B1.20.1 andASTM A888.2.2 Rating:COMPLIESThe unit tested was a “Type C” - Units without an external flow control, directly connected.The manufacturer’s installation instruction’s identifies installation parameters consistentwith the test parameters.2.3 Inlet and Outlet Connections:Inlet and Outlet connections -COMPLIESHubless coupling is compliant with ASTM A8882.4 Flow Controls and/or Vents:COMPLIES2.4.1Vents or air intakes were used. There was no flow control2.4.2When a flow control and/or vent is used during testing for rating a grease interceptor, therating of the unit did not exceed the maximum flow through the flow control.The manufacturer’s literature reflected that the rating was achieved with the ventattached, and that the vent was installed with the unit.Report No. 1757-16008-002Page 2 of 10

3Testing3.1 Construction of Test Equipment:3.1.1Test Sink:COMPLIESLength - 8 ft. (8 ft)Width 2 ft. (2 ft)Depth - 12.5” (12.5 inches)Corrosion Resistant Material - stainless steel (yes)Number of compartments Compartment length Structurally reinforced Supported on legs Rim height with legs Legs structurally supported -24yesyes3’yes(2)(4 ft)(yes)(yes)(3 ft)(yes)3.1.1.1 Sink Waste Connections:COMPLIESEach sink compartment was fitted with a 1-½” standard sink waste connection withflange, crossbars, slip joint tailpiece, and locknut.The waste connections were located on opposite sides of the center partition in thecorner formed by the side of the sink and the center partition.3.1.1.2 Water Level Gauges:COMPLIESEach compartment was equipped with a gauge connection and a water level gauge withgauge glass.Each gauge connection was fitted into the bottom of a sink compartment and in closeproximity to the waste outlet.Each gauge was mounted on the outside of the sink, adjacent to its respective gaugeconnection, and extended diagonally upward from the bottom center to the top outsidecorners.The gauges were calibrated to read directly the number of inches of water in the sinkcompartments above the sink waste flange.3.1.1.3 Movable Sink Partitions:COMPLIESEach compartment of the sink was fitted with a movable partition, making it possible toregulate the size of the compartment to any desired capacity.Report No. 1757-16008-002Page 3 of 10

3.1.2Skimming Tank:COMPLIESThe skimming tank was rectangular in shape; open at the top and equipped with astationary baffle located approximately 3 feet from the end of the tank receiving thedischarge from the interceptor.The baffle extended the width of the tank and to within 4 inches of the bottom of thetank.Tank Length Tank Width Tank Depth -8’28”32”Tank was made of corrosion resistant material Tank was structurally reinforced -yesyes(yes)(yes)Waste outlet diameter 4”(4 inches)The waste outlet was connected to the bottom of the tank at one end and trapped toretain approximately 26 inches of water in the tank.The tank provided a 4 inch bottom drain valve to permit draining and cleaning.3.2Installation of Testing Equipment:3.2.1Direct Connection Test Types A, B, and C:Findings- The “GB-2 (50 gpm)” was a Type C unit.3.2.1.1 Waste Piping:COMPLIESThe combined horizontal waste, vertical waste riser, interceptor inlet, and dischargepiping shall; be 2 inches for test flows of 50 gpm or less and 3 inches for test flows over50 gpm.Findings - Test flow was 50gpm. Pipe size was 2inches.3.2.1.2 Sink and Interceptor Locations: COMPLIESThe sink was located with the sink rim 13 feet above the outside bottom of the greaseinterceptor being tested.3.2.1.3 Skimming Tank Location:COMPLIESThe skimming tank was located low enough, with respect to the interceptor, for thedischarge piping from the interceptor to clear the tank rim by not less than 3 inches.Report No. 1757-16008-002Page 4 of 10

3.2.1.4 Installation of Waste Piping: COMPLIES(a) Sink Connections- The sink outlet waste connection from each sink compartmentwas 1-½ inches in size and each connection was fitted with a quick-opening gatevalve.(b) Combined Horizontal Waste Piping- The combined horizontal waste piping intowhich the sink outlets connect were installed with the center line 11 inches belowthe bottom of the sink and properly hung and braced from the sink reinforcementand supports.The waste pipe was fitted to the inlet of a flow control and vent.(c) Flow Control and/or Vent Device (Optional)- The flow control and device wasadequate in size for the interceptor to be tested and was equipped with the propersize orifice and/or other details to provide the proposed flow rate of the subjectinterceptor. The waste piping on either side of the flow control and vent was fittedwith unions to permit removal of the device.(d) Vertical Waste Riser- The vertical waste riser was connected to the outlet of the flowcontrol and vent device and extended downward to connect to the greaseinterceptor inlet by means of an elbow and a short horizontal nipple.(e) Interceptor Discharge- The discharge pipe from the interceptor outlet to theskimming tank had a minimum pitch of 1/8 inch per foot and was provided with a 2inch vent properly located to prevent siphoning of the interceptor.(f) Interceptor Connections- When inlet and outlet openings of the interceptor exceed 2inches or 3 inches for test flows exceeding 50 gpm, reducing couplings were usedto permit connections of the 2 inch or 3 inch.3.2.2Indirect Connection Test Type D: NOT APPLICABLE3.3Preliminary Test Procedure:3.3.1Media Analysis:COMPLIESpH of water 6.4(6.0 to 8.0)Specific Gravity of Lard 0.875 at 150 F(0.875 0.005 at 150 F)3.3.2Establishing Sink Compartment Capacity: COMPLIESCapacity of compartment 160gallons (1.2 x flow rate of interceptor)Capacity of compartment 260gallons (1.2 x flow rate of interceptor)3.3.3Establishing Vol. of Incremental Discharge: (based on 10” water above sink outlet):COMPLIESCompartment 1 Discharge 50gallons (equal to flow rate of interceptor)Compartment 2 Discharge 50gallons (equal to flow rate of interceptor)3.3.4Computation of Flow Rate: FOLLOWEDThe flow rate from the sink was computed by timing the rate of drainage of the first 9½” of water from the sink compartment, measured from the 10” mark to the datum line½” above the sink outlet flange.Report No. 1757-16008-002Page 5 of 10

3.3.4.1Check Flow Rate Tests:COMPLIESTest number123Compartment111Time (sec)656567gpm43.843.842.5Avg: 43.4Based on Time-12322262605946.047.548.3Avg: s11350.4Compartment 111250.9Compartment 111250.9Compartment 123Avg: us11051.8Compartment 210952.3Compartment 210952.3Compartment 2Avg: 52.1For all of the above flow rates, the time for total discharge did not exceed 126seconds.3.3.4.2Calibrated Drainage Flow Rates: COMPLIESProposed flow rate of Interceptor being tested 50gpm.The average of the above calibrated flow rates for simultaneous discharge was equaland didn’t exceed by not more than 5% the proposed flow rated of the interceptorbeing tested.Findings 51.4 gpm average (52.50 gpm max.)3.4Skimming Procedure:FOLLOWEDThe skimming procedure was initiated 5 minutes after the increment to be skimmedhas discharged into the tank. The baffles were used alternately until the amounts ofgrease collected in the procedure are less than 1% by visual observation. Uponcompletion of the skimming procedure, water shall be drained from the bottom of thepail by means of a spigot. The remainder of the water was collected as describe in theprocedure until only a few drops are observed. The lard is then weighed to the nearest½ gram.Report No. 1757-16008-002Page 6 of 10

3.5Rating Test Procedure :See Table 1 of test report for Rating Testing.3.5.1Test Media:FOLLOWEDCertification tests were conducted with fresh, unused lard and water as defined andboth within a temperature range from 150 F to 160 F.3.5.2Ratio of Lard to Water:FOLLOWEDThe test lard was introduced into one compartment, during each incrementaldischarge, in the ratio of 1 lb. of lard for each 5 gallons of water in that compartment.Consequently, the proportion of lard to the total amount of water discharged from bothsink compartments during each increment was 1 lb. for each 10 gallons respectively.The required amount of test lard, within the above temperature range, was weighedout and poured into the test compartment of the sink.Findings- 10 lbs per increment used.3.5.3Test Increments:3.5.3.1Each test increment consisted of the simultaneous discharge of water from both sinkcompartments and the lard from the test compartment.3.5.3.2During the first test increment, the lard was poured into compartment 1 whilecompartment 2 discharged clear water. During the second test increment the lard waspoured into compartment 2 while the water in compartment 1 remained clear.3.5.4Flow Rates:FOLLOWEDThe drainage period for each increment was gauged and timed on the basis of the flowfrom the compartment containing the clear water. The flow rate from the sink wascomputed and recorded for each increment. (See Table 1 of test report).3.5.5Efficiency Determinations:FOLLOWEDThe grease was removed from the skimming tank and the efficiency of the interceptorwas computed at intervals of five increments or less until the average efficiencyreached 93% or less and/or the incremental efficiency reached 85% or less (See Table1 of test report).3.5.6Duration of the Test:FOLLOWEDThe testing was continued until the average efficiency reached 85% or less and/or theincremental efficiency reached 75% or less.3.5.7Determination of Grease Retention Capacity:FOLLOWEDMaximum grease retention capacity was established at the increment preceding twosuccessive increments in which either the average efficiency is less than 90% or theincremental efficiency is less than 80 %.Report No. 1757-16008-002FOLLOWEDPage 7 of 10

3.5.8Performance Requirements for Rating:COMPLIESThe interceptor did conform with or exceeded the following requirements at thebreakdown point:(a) Had an average efficiency of 90% or more.Findings –91.2 %(b) Had an incremental efficiency of 80% or more.Findings –82.0 %(c)Had retained not less than 2 lbs of grease for each 1 gpm average flow rate asdetermined during the testing.Findings –127.65 lbs.3.5.9Rated Capacities:COMPLIESStandard rating flow rate and grease retention capacities for grease interceptors weretested in accordance with the above test procedure and did conform with therequirement of ASME A112.14.3-2000.FindingsFlow Rate50 gpmGrease Retention Capacity Rating 100 lbs.4Labeling, Installation, and Maintenance4.1Labeling:COMPLIESProducts were labeled with the following information:(a) Manufacturer’s name Schier Products(yes)(b) Model number yes(yes)(c) Rated flow(s) yes(yes)(d) “Inlet” and “Outlet” yes(yes)(e) ASME A112.14.3 yes(yes)(f) Product type by rating yes(yes)(g) Efficiency at the rated capacity yes(yes)4.2Installation Instructions:COMPLIESThe grease interceptor was provided with complete installation instructions, includingbut not limited to the following:(a) Flow control and/or vent requirements NA(yes)(b) Separate trapping requirements yes(yes)(c) Elevation and accessibility requirements yes(yes)(d) Safety and health-related instructions yes(yes)(e) Cleanout locations yes(yes)(f) Instructions that show the clearances required for maintenance, cleaning, andhazard prevention yes (yes)(g) Cautions against installation in any manner except as tested and rated - yes(yes)Report No. 1757-16008-002Page 8 of 10

4.3Maintenance Instructions:COMPLIESUnits were provided with complete maintenance instructions including but not limited tothe following:(a) Maintenance Instructions yes(yes)(b) Safety and health provisions yes(yes)Each grease interceptor was provided with service instructions which included atrouble-shooting guide as well as instructions for performing necessary servicing or forobtaining servicing.Report No. 1757-16008-002Page 9 of 10

TABLE 1 – Test Results per ASME A112.14.3-2000 (Reaffirmed 2004)“ GB-2 (50 gpm) ” Grease InterceptorTest .085.350.451.450.451.850.42821Performance Requirement RatingReport No. 1757-16008-002ACCUMULATEDFlowRate(GPM)Page 10 of 10

Interceptors" and CSA B481.1-12 "Testing and rating of grease interceptors using lard". . Conclusion: The "GB-2 (50 gpm)" Grease Interceptor DID COMPLY with the requirements of ASME A112.14.3-2000 (Reaffirmed 2004) for "Grease Interceptors" and CSA B481.1-12 "Testing and rating of grease interceptors using lard".

Related Documents:

CS0-002-demo Author: common Subject: CS0-002-demo Keywords: Latest CompTIA exams,latest CS0-002 dumps,CS0-002 pdf,CS0-002 vce,CS0-002 dumps,CS0-002 exam questions,CS0-002 new questions,CS0-002 actual tests,CS0-002 practice tests,CS0-002 real exam questions Created Date: 2/12/2021 9:31:02 PM

Latest CompTIA exams,latest CS0-002 dumps,CS0-002 pdf,CS0-002 vce,CS0-002 dumps,CS0-002 exam questions,CS0-002 new questions,CS0-002 actual tests,CS0-002 practice tests,CS0-002 real exam questions Created Date

Latest CompTIA exams,latest CS0-002 dumps,CS0-002 pdf,CS0-002 vce,CS0-002 dumps,CS0-002 exam questions,CS0-002 new questions,CS0-002 actual tests,CS0-002 practice tests,CS0-002 real exam questions Created Date

25 Weather station defect Output 1,002 C R T 26 Block Input 1,002 C S 27 Wind sensor 1 defect Output 1.002 C R T 28 Wind sensor 2 defect Output 1.002 C R T 29 Wind sensor 3 defect Output 1.002 C R T 30 Wind sensor 4 defect Output 1.002 C R T 31 Wind direction defect Output 1.002 C R T 32 R

002.097 VM20/300 FITTNG 3.85 002.098 VM38/06 PLUNGER 16.17 002.099 VM30/103 GASKET 5.45 002.100 999-631-011 GAS 5.45 002.101 999-631-010 GAS 5.45 002.102 VM36/20 GASKET 5.45 Legal in California only for racing vehicles which may never be used upon a highway.

CASE - IH With Scania Engine M24x2.0 EZ-6 H-002 L-002 CASE - IH With IVECO Engine, P85, 6.7L M22x1.5 EZ-7B H-002 L-002 CASE - IH STX Tractors with Cummins QSX M27x2.0 EZ-211 H-002 L-002

02 1 Waterslager/Kleur 02.005.001 2 002 02.005 02 1 Timbrado's/Kleur 02.006.001 2 002 02.006 02 1 Harzers/Postuur 02.007.001 2 002 02.007 02 1 Waterslagers/Postuur 02.008.002 2 002 02.008 02 1 Timbrado's/Postuur 02.009

hydrate (C–S–H), ettringite, and Ca(OH) 2 through a hydration reaction in which hydration heat is produced within the concrete because of an exothermic reaction. Since the thermal cracking of concrete reduces its internal force, watertightness, and durability, an appropriate measure is required to control the heat of hydration. The factors that influence the hydration heat of concrete .