Saudi Electricity Company الشركة السعودية للكھرباء SEC DISTRIBUTION MATERIALS SPECIFICATION53-SDMS-01DATE: 26-02-2013GTABLE OF CONTENTS1.0SCOPE2.0CROSS REFERENCES3.0APPLICABLE CODES AND STANDARDS4.0BASIC REQUIREMENTS AND GUIDELINES5.0DESIGN AND CONSTRUCTION 45.25GeneralPerformance Characteristics and RatingsConstructionTap ChangerTemperature Control DevicesOutdoor Control CabinetBuchholz RelayPressure Relief DeviceOutdoor Bushings (Oil/Air)RadiatorFansOil Preservation SystemBreatherDrain, Filter and Sampling ValvesInspection FacilitiesLifting, Moving and Jacking FacilitiesLadderGroundingExternal Terminal Markings and LocationTransformer OilBushing Current TransformersTerminationsSurge ArrestersOn line monitoringNameplatePage 2 of 66

Saudi Electricity CompanySEC DISTRIBUTION MATERIALS SPECIFICATION6.0DATE: 26-02-2013GPackingImpact .0 الشركة السعودية للكھرباء Type (Design) TestsRoutine TestsSpecial TestsDATA SCHEDULEPage 3 of 66

Saudi Electricity CompanySEC DISTRIBUTION MATERIALS SPECIFICATION1.0 الشركة السعودية للكھرباء 53-SDMS-01DATE: 26-02-2013GSCOPEThis SEC Distribution Materials Specification (SDMS) specifies the minimum technicalrequirements for design, engineering, manufacture, inspection, testing and performance ofoutdoor, three phase, mineral oil immersed Power Transformers, intended to be used in thesystem of the Saudi Electricity Company, Saudi Arabia.This SDMS does not cover Generator Transformers and associated auxiliary transformers.2.0CROSS REFERENCESThis Material Standard Specification shall always be read in conjunction with latest SECGeneral Specification No. 01-SDMS-01, titled "General Requirements for AllEquipment/Materials", which shall be considered as an integral part of this SDMS.This SDMS shall also be read in conjunction with SEC Purchase Order or ContractSchedules for project, as applicable.3.0APPLICABLE CODES AND STANDARDSThe latest revision/amendments of the following Codes and Standards shall be applicablefor the equipment/material covered in this SDMS.In case of conflict, thevendor/manufacturer may propose equipment/material conforming to one group of IndustryCodes and Standards quoted hereunder without jeopardizing the requirements of thisSDMS.3.1IEC 61869-1Instrument Transformers, Part 1: Current Transformers3.2IEC 61869-6Instrument Transformers, Requirements for Protective CurrentTransformers for Transient Performance3.3IEC 60076Power Transformers3.4IEC 60137Insulated Bushings for Alternating Voltages above 1000V3.5IEC 60214-1Tap Changers Part 1: Performance Requirements and TestMethods3.6IEC 60214-2Tap Changers Part 2 : Application Guide3.7IEC 60507Artificial Pollution Tests on High Voltage Insulators to be used onAC systemsPage 4 of 66

Saudi Electricity CompanySEC DISTRIBUTION MATERIALS SPECIFICATION الشركة السعودية للكھرباء 53-SDMS-01DATE: 26-02-2013G3.8IEC 60529Degrees of Protection Provided by Enclosures (IP Code)3.9IEC TR60616Terminal and Tapping Markings for Power Transformers3.10IEC 60076-7Loading Guide for Oil-Immersed Power Transformers3.11IEEE C57.12.00General Requirments for Liquid-Immeresed Distriution,Power and Regulating Transformers.3.12IEEE C57.12.10Requirements for Transformers, 230kV and below, 833/958through 8333/10417 kVA, Single Phase; and 750/862 through60 000/80 000/100 000 kVA, 3-Phase without Load TapChanging: and 3750/4687 through 60000/80000/100000 kVAwith Load Tap Changing – Safety Requirement3.13IEEE C57.12.70Terminal Markings and Connections for Distribution andPower Transformers3.14IEEE C57.12.90Test Code for Liquid Immersed Distribution, Power andRegulating Transformers and Guide for Short Circuit Testingof Distribution and Power Transformers3.15IEEE C57.109Guide for Liquid-Immersed Transformer Through-FaultCurrent Duration3.16IEEE C57.13Requirements for Instrument Transformers3.17NFPA 70National Electrical Code3.18IEEE C57.19.00General Requirements and Test Procedure for Outdoor PowerApparatus Bushings3.19IEEE C57.91IEEE Loading Guide for Loading sformers, Regulators and Reactors.3.21Cigre BrochureMechanical Condition Assesment of Transformer # 342(April 2008) Windings using Frequency Response AnalysisPage 5 of 66

Saudi Electricity CompanySEC DISTRIBUTION MATERIALS SPECIFICATION الشركة السعودية للكھرباء 53-SDMS-01DATE: 26-02-2013G3.22SASO/SSA 421 Testing Methods for Power Transformers3.23SASO/SSA 422 Power Transformers3.2454-TMSS-01Mineral Insulating Oil for Electrical Apparatus3.2550-TMSS-01Current Transformer (CT) up to 380kV3.2653-TMSS-03Online Gas Analyzer3.2731-TMSS-06Terminal Blocks4.0 BASIC REQUIREMENTS AND GUIDELINES4.1 Generala)All equipments shall be compact, simple for operation with highly securedperformance.b) Transformer shall be suitable to operate at ambient temperature varying from55 C to – 5 C, under dusty, dry climate out door conditions as given in 01SDMS-01.c)All equipments shall comply to the Specifications of SEC andrelevant IEC Standards.4.2 Bid ProposalThe Manufacturer shall provide the following along with his bid proposal, in additionto the requirements stipulated in the Purchase Order or Contract documents:(a)Scope of Equipment Supply.(b)Data Schedule for all SEC Materials Standard Specifications (SDMS, TMSSand SMSS) as given in this SDMS shall be duly filled-in.(c)Technical literature, brochures and list of users in the electric utility sector.(d)Complete type test reports/certificates of all major equipment of the PowerTransformers.Page 6 of 66

Saudi Electricity CompanySEC DISTRIBUTION MATERIALS SPECIFICATION(e) الشركة السعودية للكھرباء 53-SDMS-01DATE: 26-02-2013GA declaration from the Manufacturer that the bid proposal is in accordance withthe technical Specifications and associated SEC, material StandardSpecifications. Otherwise the Manufacturer must state clearly any exception ordeviation items from SEC Standards, these guideline Specifications anddrawing plans and the reasons for exceptions or deviations.(f)All documentation relating to this project shall be in English.4.3 Base Design PhaseThe base design phase is a period of 4-6 weeks of preliminary design following theissue of Purchase Order or award of Contract.Six (6) sets of the base design package shall be submitted to SEC for review andcomments at the base design review meeting which will be held by the SEC four (4)weeks after the receipt of the base design package.The base design document shall consist of :a.Detailed list of equipment to be supplied.b.Following design drawings, as a minimum, but not limited to:c. Drawing Control Sheet. One-Line Diagram (Main one-line diagram, AC and DC auxiliary one-linediagram, etc.) General arrangement of the transformer (giving details of variouscomponents)Literature (specifications, manuals, brochures, drawingsand completed DataSchedules) of the following materials, as a minimum, but not limited to:1)2)3)4)5)d.Power transformer with On Laod Tap Changer ( Maintenance Free On loadTap Changer)RelaysInstrumentsControl PanelsCTs/PTs.Following calculations and specifications, as a minimum, but not limited to:Page 7 of 66

Saudi Electricity Company الشركة السعودية للكھرباء SEC DISTRIBUTION MATERIALS SPECIFICATION53-SDMS-01DATE: 26-02-2013G1) Power Transformer rating with and without cooling.2) CT and PT Sizing, including auxiliary CTs.3) AC and DC auxiliary supply design with sizing of auxiliary transformer,batteries, chargers, etc.4) Grounding Conductor Sizing.e.Details of site commissioning tests to be carried out.4.4 Design Review DrawingsFollowing the base design phase, other detailed/manufacturer drawings shall besubmitted by the Manufacturer for approval by SEC. The list of detailed drawings tobe submitted for approval shall be mutually agreed to between the Manufacturer andSEC.4.5 Manufacturer Progress ReportingThe Manufacturer shall submit to the SEC, a monthly progress report on themanufacture of the Power Transformers.The progress report shall include among other items:a.Design.b.Procurement of Components.c.Testing and Commissioning.d.Overall Completion.The format shall be mutually agreed to between the Manufacturer and SEC.4.6 Test and InspectionAll equipment and materials shall be subject to inspection and tests as required inrelevant SEC Materials Standard Specification, QA/QC Procedures and applicableindustry standards or as may be decided by the SEC.All design (type) and production (routine) tests prescribed in this SDMS and relevantSEC Materials Standard Specifications shall be performed in accordance with theapplicable industry standards. In lieu of actual design (type) tests, the ManufacturerPage 8 of 66

Saudi Electricity CompanySEC DISTRIBUTION MATERIALS SPECIFICATION الشركة السعودية للكھرباء 53-SDMS-01DATE: 26-02-2013Gmay submit complete certificate reports or tests performed previously on identical unitsto the SEC for review and approval during the bidding stage.a. The Manufacturer shall submit for all major equipment a detailed testing andInspection program of respective manufacturers to the SEC for review, at least three(3) months before the commencement of manufacturing.b. The Manufacturer shall employ a reputable independent vendor inspection agencyto witness factory tests and inspect the equipment and materials that will bepurchased for the manufacture of this transformer. The Manufacturer shall submitpre-qualification documents for his proposed vendor inspection agency for approvalof SEC. The Manufacturer shall provide all technical specifications to theindependent vendor inspection agency. The entire test inspection report shallbe submitted for acceptance by the SEC.c. SEC will also send its employees or its inspectors to witness the factory tests andManufacturer will bear all the expenses involved.d. Four (4) initial sets of all factory tests reports shall be submitted by the Independentinspection agency to the SEC for review and approval. The equipment shall not beshipped ex-factory unless the test reports have been accepted, and shippingclearance is given by SEC.e. It shall be the vendor’s responsibility to obtain all the necessary Certificates ofConformity and/or other documentation required for import and/or registration ofthe unit.f. The unit shall undergo the vendor’s mandatory Pre-Delivery Inspection (PDI). Priorto the delivery, the PDI documents shall be forwarded to SEC for approval.4.7 Commissioning and Site TestsThe guidelines for Commissioning Tests and Checks as per SEC Standards andSpecifications witnessed by SEC personnel:The Manufacturer shall develop detailed commissioning and equipment site testsbased on the requirements of SEC Standard to be performed at a SEC station.During or after commissioning, training shall be given to operations staff covering theOperations and Maintenance of the complete unit.A list giving full details of the site tests, tools and equipment to be used shall bePage 9 of 66

Saudi Electricity CompanySEC DISTRIBUTION MATERIALS SPECIFICATION الشركة السعودية للكھرباء 53-SDMS-01DATE: 26-02-2013Gsubmitted by the Manufacturer for review and acceptance by SEC, six (6) months priorto the scheduled date of tests. Scheduled dates of all field/site tests shall be submitted toSEC two (2) months prior to arrange for the REPRESENTATIVES of SEC to witnessthe tests.The commissioning and equipment site testing shall be done in strict compliancewith the normal work schedule of SEC i.e. 8 hours per day, 5 days per week.4.8 Record BooksUpon completion of the manufacture, the Manufacturer shall submit eight (8) sets ofrecord books containing the following documents as a minimum:a) Approved design and manufacturer drawings.b) All calculation sheets.c) Brief technical specification of all components.d) Operation and maintenance manual consisting of: Manufacturer’s instructions manual applicable to each component or material. Manufacturer’s set-up procedures, including mechanical tolerances formaintenance or repair purposes.Complete set of Manufacturer’s drawings and catalogs with identified parts foreach device and other essential information for SEC cataloging and orderingreplenishment parts. Note: All documents in item (d) shall be originals.4.9 Spare PartsManufacturer shall provide recommended spare parts list required for O&M of powertransformers without including as part of bid.4.10 WarrantyA minimum warranty of twenty four (24) months shall be granted with effect from thefinal acceptance/commissioning date by SEC. The limits shall be those submitted withthe bid and accepted by SEC.Page 10 of 66

الشركة السعودية للكھرباء Saudi Electricity Company53-SDMS-01SEC DISTRIBUTION MATERIALS SPECIFICATION5.0DATE: 26-02-2013GDESIGN AND CONSTRUCTION REQUIREMENTS5.15.2General5.1.1The transformer shall be core type.5.1.2Vector group designation shall be per IEC60076.5.1.3The transformer shall be suitable for outdoor service.Performance Characteristics and Ratings5.2.1 Ratinga.Unless otherwise specified in project SOW/TS, standard powertransformer capacities (MVA) and vector groups for substations shall beone of the values as given in the below table:Substation NominalVoltage Rating, kV69/13.833/13.8or34.5/13.8b.5.2.2Transformer CapacityONAN/ONAF(MVA)20/25, 30/4010, 13/20,20/25, 25/30Vector GroupDyn1Dyn1, Dyn11YNyn0The transformer shall be capable of delivering its rated powercontinuously with rated voltage on the secondary winding under theambient temperature specified in 01-SDMS-01, including requirementsfor the higher altitude as applicable.Overloading Capabilitya)The power transformer shall be designed to meet the overloadingrequirements of the relevant IEC or IEEE Industry Standards adjusted toambient conditions specified in 01-SDMS-01.b)All transformer accessories (tap changer, bushings, CTs, etc.) shall berated to carry 120% of the transformer current with tap changer on theextreme minus tap.Page 11 of 66

الشركة السعودية للكھرباء Saudi Electricity CompanySEC DISTRIBUTION MATERIALS SPECIFICATION5.2.353-SDMS-01DATE: 26-02-2013GParallelingThe transformer shall meet the requirements for parallel operation.5.2.4LossesThe manufacturer shall state the guaranteed transformer losses as part of theproposal for natural cooling including tolerance per IEC or IEEE standards.The guaranteed total losses shall not exceed 0.5% (Max.) of ONAN rating.The factory measured total loss values shall not exceed guaranteed values.Otherwise penalty shall be imposed per Purchase Order or Contract Schedulesfor loss values up to 5% above guaranteed value including tolerance. If theactual losses exceed 5% above guaranteed value, SEC shall have the right toreject the transformer.5.2.5Operation at Higher than Rated Voltage/Frequencya.The transformer shall be designed for the following overfluxingrequirements on any tap while carrying the rated current for that tapwithout exceeding the temperature rise associated with temperature risetest:Continuous1 minute10 seconds110% of rated volts/Hz125% of rated volts/Hz140% of rated volts/Hzb. Over excitation curve for the transformer showing volts/Hz versus timeshall be submitted.5.2.6Short Circuit Withstanda.The transformer shall be designed and constructed to withstand onany tapping without damage, the thermal and mechanical effects ofshort-circuit in accordance with IEC 60076 or IEEE C57.12.90.b.Evidence regarding the thermal and dynamic withstand capabilityshall be demonstrated either by type test reports of short circuit fortransformer with same rating or by type test reports for short circuitof similar transfomer and calculations and other documents per IEC60076-5.Page 12 of 66

Saudi Electricity CompanySEC DISTRIBUTION MATERIALS SPECIFICATION5.2.7 الشركة السعودية للكھرباء 53-SDMS-01DATE: 26-02-2013GTertiary Winding (if applicable)Tertiary winding shall be delta or star connected as specified in dataschedule. Delta connected winding shall meet the following requirements:a. Tertiary winding rating shall be determined by the manufacturer withalculation based on dynamic short circuit withstand capability. The ratingshall be guaranteed by the manufacturer and prove the same withtemperature rise test if specified in data schedule. The delta- connectedwinding shall have at least a short time fault power rating equal to onethird of the power rating of the secondary winding.b. The tertiary winding shall be connected internally and all ends of thewindings shall be brought outside through three fully rated bushings forconnection to external circuit. The insulation level of the bushings shallmatch with that of the winding. Series current limiting reactor shall notbe used in the tertiary winding.c. The manufacturer shall investigate the transferred over voltagephenomenon from the HV winding to the tertiary winding and furnishcalculations for sizing of the tertiary surge arresters.As all construction factors influencing the magnitude of transferredvoltage are difficult to calculate, transferred voltage shall be proved withtests if stated in the data schedule.d. Grounding of tertiary winding shall be per clause 4.19.3.5.2.8Coolinga. The transformer shall be equipped with ONAN, ONAF etc., coolingsystem as specified in data schedule.b. Loss of 25% of forced air-cooling capacity shall not affect theContinuous Maximum Rating of the transformer. Heat run test shall beperformed without 25% redundant cooling.c. The start and stop impulses for fans shall be from winding temperatureindicator. Sufficient temperature difference between start and stop signalsshall be kept and frequent start/stop operation for small temperaturedifferences shall be avoided.Page 13 of 66

Saudi Electricity CompanySEC DISTRIBUTION MATERIALS SPECIFICATION الشركة السعودية للكھرباء 53-SDMS-01DATE: 26-02-2013Gd. Control shall be suitable for both manual and automatic operation foreach group of fans and changeover from automatic to manual controlshall be possible.e. Each fan motor shall be protected by a separate MCB (up to 32A) orMCCB (above 32A) provided with thermal over load and short circuitprotection. Thermal over-load protection shall be hand reset type.f. The failure of any individual fan or failure of a pump or fan motorMCCB/MCB in off position shall initiate an alarm.5.2.9Noise Level and Vibrationa. Unless otherwise specified in data schedule, noise level, when measuredin accordance with IEC 60076-10 or IEEE C57.12.90, shall not exceedthe limits specified in NEMA TR-1.Noise level shall be furnished for each stage of cooling. Positivetolerance on noise level is not acceptable.b. The design and clamping of the core and windings shall be such thatexcessive vibrations shall not be transmitted from the magnetic circuits tothe tank and accessories. The maximum limit of vibration shall be100µm.5.2.10Inrush CurrentInrush harmonic contents and the duration of inrush currents for worstenergization criteria shall be provided on current versus time curve for oddand even harmonics. All relevant factors such as source impedance,remanence, damping, switching instant, existence of already energizedparallel transformer shall be considered.5.3Construction5.3.1. Tanka. The tank shall be of conservator type construction.b. The tank shall be made of formed and electrically welded high strengthsteel-alloy plate. It shall be suitably braced to provide sufficient strengthfor support of internal parts and to prevent damage or distortion underPage 14 of 66

Saudi Electricity CompanySEC DISTRIBUTION MATERIALS SPECIFICATION الشركة السعودية للكھرباء 53-SDMS-01DATE: 26-02-2013Gservice condition

3.22 SASO/SSA 421 Testing Methods for Power Transformers 3.23 SASO/SSA 422 Power Transformers 3.24 54-TMSS-01 Mineral Insulating Oil for Electrical Apparatus 3.25 50-TMSS-01 Current Transformer (CT) up to 380kV 3.26 53-TMSS-03 Online Gas Analyzer 3.27 31-TMSS-06 Terminal

Related Documents:

Bruksanvisning för bilstereo . Bruksanvisning for bilstereo . Instrukcja obsługi samochodowego odtwarzacza stereo . Operating Instructions for Car Stereo . 610-104 . SV . Bruksanvisning i original

10 tips och tricks för att lyckas med ert sap-projekt 20 SAPSANYTT 2/2015 De flesta projektledare känner säkert till Cobb’s paradox. Martin Cobb verkade som CIO för sekretariatet för Treasury Board of Canada 1995 då han ställde frågan

service i Norge och Finland drivs inom ramen för ett enskilt företag (NRK. 1 och Yleisradio), fin ns det i Sverige tre: Ett för tv (Sveriges Television , SVT ), ett för radio (Sveriges Radio , SR ) och ett för utbildnings program (Sveriges Utbildningsradio, UR, vilket till följd av sin begränsade storlek inte återfinns bland de 25 största

Hotell För hotell anges de tre klasserna A/B, C och D. Det betyder att den "normala" standarden C är acceptabel men att motiven för en högre standard är starka. Ljudklass C motsvarar de tidigare normkraven för hotell, ljudklass A/B motsvarar kraven för moderna hotell med hög standard och ljudklass D kan användas vid

LÄS NOGGRANT FÖLJANDE VILLKOR FÖR APPLE DEVELOPER PROGRAM LICENCE . Apple Developer Program License Agreement Syfte Du vill använda Apple-mjukvara (enligt definitionen nedan) för att utveckla en eller flera Applikationer (enligt definitionen nedan) för Apple-märkta produkter. . Applikationer som utvecklas för iOS-produkter, Apple .

och krav. Maskinerna skriver ut upp till fyra tum breda etiketter med direkt termoteknik och termotransferteknik och är lämpliga för en lång rad användningsområden på vertikala marknader. TD-seriens professionella etikettskrivare för . skrivbordet. Brothers nya avancerade 4-tums etikettskrivare för skrivbordet är effektiva och enkla att

Den kanadensiska språkvetaren Jim Cummins har visat i sin forskning från år 1979 att det kan ta 1 till 3 år för att lära sig ett vardagsspråk och mellan 5 till 7 år för att behärska ett akademiskt språk.4 Han införde två begrepp för att beskriva elevernas språkliga kompetens: BI

**Godkänd av MAN för upp till 120 000 km och Mercedes Benz, Volvo och Renault för upp till 100 000 km i enlighet med deras specifikationer. Faktiskt oljebyte beror på motortyp, körförhållanden, servicehistorik, OBD och bränslekvalitet. Se alltid tillverkarens instruktionsbok. Art.Nr. 159CAC Art.Nr. 159CAA Art.Nr. 159CAB Art.Nr. 217B1B