CONDENSING UNITAIR CONDITIONINGINSTALLATION & SERVICE REFERENCE 2005-2013, 2017-2018Goodman Manufacturing Company, L.P.5151 San Felipe, Suite 500, Houston, TX 77056www.goodmanmfg.com -or- www.amana-hac.comP/N: IO-258T Date: January 2018Important Safety InstructionsCodes & RegulationsThe following symbols and labels are used throughout thismanual to indicate immediate or potential safety hazards. It isthe owner’s and installer’s responsibility to read and complywith all safety information and instructions accompanying thesesymbols. Failure to heed safety information increases the riskof personal injury, property damage, and/or product damage.This product is designed and manufactured to comply withnational codes. Installation in accordance with such codesand/or prevailing local codes/regulations is the responsibilityof the installer. The manufacturer assumes no responsibilityfor equipment installed in violation of any codes or regulations. Rated performance is achieved after 72 hours ofoperation.Rated performance is delivered at the specified airflow. See outdoor unit specification sheet for split system models or product specification sheet for packaged and light commercial models. Specification sheets can be found atwww.goodmanmfg.com for Goodman brand products orwww.amana-hac.com for Amana brand products. Within either website, please select the residential or commercial products menu and then select the submenu for the type of product to be installed, such as air conditioners or heat pumps, toaccess a list of product pages that each contain links to thatmodel’s specification sheet.HIGH VOLTAGE!Disconnect ALL power before servicing.Multiple power sources may be present.Failure to do so may cause property damage,personal injury or death.ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ,ADJUST, SERVICE OR REPAIR (HEREINAFTER, “SERVICE”) THEEQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE THEEQUIPMENT. THE MANUFACTURER WILL NOT BE RESPONSIBLEFOR ANY INJURY OR PROPERTY DAMAGE ARISING FROMIMPROPER SERVICE OR SERVICE PROCEDURES. IF YOU SERVICETHIS UNIT, YOU ASSUME RESPONSIBILITY FOR ANY INJURY ORPROPERTY DAMAGE WHICH MAY RESULT. IN ADDITION , INJURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES TOSERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL, ONLYLICENSED PERSONNEL SHOULD SERVICE THE EQUIPMENT .IMPROPER INSTALLATION, ADJUSTMENT , SERVICING OR REPAIROF THE EQUIPMENT SPECIFIED IN THIS MANUAL, OR ATTEMPTINGTO INSTALL , ADJUST, SERVICE OR REPAIR THE EQUIPMENTSPECIFIED IN THIS MANUAL WITHOUT PROPER TRAINING MAYRESULT IN PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONALINJURY OR DEATH.Shipping InspectionAlways keep the unit upright; laying the unit on its side or topmay cause equipment damage. Shipping damage, and subsequent investigation is the responsibility of the carrier. Verifythe model number, specifications, electrical characteristics,and accessories are correct prior to installation. The distributor or manufacturer will not accept claims from dealers for transportation damage or installation of incorrectly shipped units.The United States Environmental Protection Agency (EPA)has issued various regulations regarding the introduction and disposal of refrigerants. Failure to follow theseregulations may harm the environment and can lead tothe imposition of substantial fines. Should you have anyquestions please contact the local office of the EPA.If replacing a condensing unit or air handler, the system mustbe manufacturer approved and Air Conditioning, Heating andRefrigeration Institute (AHRI) matched. NOTE: Installation ofunmatched systems is strongly discouraged.Outdoor units are approved for operation above 55 F in cooling mode. Operation below 55 F requires the use of an approved low ambient kit.Damage to the unit caused by operating the unit in a structurethat is not complete (either as part of new construction orrenovation) is not covered under the warranty.Installation ClearancesSpecial consideration must be given to location of the condensing unit(s) in regard to structures, obstructions, other units,and any/all other factors that may interfere with air circulation.Where possible, the top of the unit should be completely unobstructed; however, if vertical conditions require placement beneath an obstruction there should be a minimum of 60inches between the top of the unit and the obstruction(s).The specified dimensions meet requirements for air circulation only. Consult all appropriate regulatory codes prior todetermining final clearances.is a registered trademark of Maytag Corporation or its related companies and is usedunder license to Goodman Company, L.P., Houston, TX. All rights reserved.

Another important consideration in selecting a location for theunit(s) is the angle to obstructions. Either side adjacent thevalves can be placed toward the structure provided the sideaway from the structure maintains minimum service clearance.Corner installations are strongly discouraged.NOTRECOMMENDEDBBBARefrigerants are heavier than air. They can "push out"the oxygen in your lungs or in any enclosed space. Toavoid possible difficulty in breathing or death: Never purge refrigerant into an enclosed room orspace. By law, all refrigerants must be reclaimed. If an indoor leak is suspected, thoroughly ventilate thearea before beginning work. Liquid refrigerant can be very cold. To avoid possiblefrostbite or blindness, avoid contact and wear glovesand goggles. If liquid refrigerant does contact yourskin or eyes, seek medical help immediately. Always follow EPA regulations. Never burn refrigerant,as poisonous gas will be produced.OK!OK!AACAWhile these items will not cover every conceivable situation,they should serve as a useful guide.BAAOK!CAAAAAASafe Refrigerant HandlingOK!OK!OK!AACTo avoid possible explosion: Never apply flame or steam to a refrigerant cylinder.If you must heat a cylinder for faster charging,partially immerse it in warm water. Never fill a cylinder more than 80% full of liquid refrigerant. Never add anything other than R-22 to an R-22 cylinder or R-410A to an R-410A cylinder. The serviceequipment used must be listed or certified for thetype of refrigerant used. Store cylinders in a cool, dry place. Never use a cylinder as a platform or a roller.AACMinimum Airflow ClearanceModel TypeABCResidential10"10"18"Light Commercial12"12"18"AA20"24"This unit can be located at ground floor level or on flat roofs.At ground floor level, the unit must be on a solid, level foundation that will not shift or settle. To reduce the possibility ofsound transmission, the foundation slab should not be in contact with or be an integral part of the building foundation. Ensure the foundation is sufficient to support the unit. A concrete slab raised above ground level provides a suitable base.To avoid possible explosion, use only returnable (notdisposable) service cylinders when removing refrigerant from a system. Ensure the cylinder is free of damage which couldlead to a leak or explosion. Ensure the hydrostatic test date does not exceed5 years. Ensure the pressure rating meets or exceeds 400psig.When in doubt, do not use cylinder.Rooftop InstallationsIf it is necessary to install this unit on a roof structure, ensurethe roof structure can support the weight and that proper consideration is given to the weather-tight integrity of the roof. Sincethe unit can vibrate during operation, sound vibration transmission should be considered when installing the unit. Vibrationabsorbing pads or springs can be installed between the condensing unit legs or frame and the roof mounting assembly toreduce noise vibration.Refrigerant LinesCAUTIONThe compressor POE oil for R-410A units is extremelysusceptible to moisture absorption and could causecompressor failure. Do not leave system open to atmosphere any longer than necessary for installation.To avoid possible injury, explosion or death, practicesafe handling of refrigerants.Use only refrigerant grade (dehydrated and sealed) coppertubing to connect the condensing unit with the indoor evaporator. After cutting the tubing, install plugs to keep refrigeranttubing clean and dry prior to and during installation. Tubingshould always be cut square keeping ends round and freefrom burrs. Clean the tubing to prevent contamination.2

Insulation is necessary to prevent condensation from formingand dropping from the suction line. Armflex (or satisfactoryequivalent) with 3/8” min. wall thickness is recommended. Insevere conditions (hot, high humidity areas) 1/2” insulationmay be required. Insulation must be installed in a mannerwhich protects tubing from damage and contamination.Do NOT let refrigerant lines come in direct contact with plumbing, ductwork, floor joists, wall studs, floors, and walls. Whenrunning refrigerant lines through a foundation or wall, openingsshould allow for sound and vibration absorbing material to beplaced or installed between tubing and foundation. Any gapbetween foundation or wall and refrigerant lines should be filledwith a pliable silicon-based caulk, RTV or a vibration dampingmaterial. Avoid suspending refrigerant tubing from joists andstuds with rigid wire or straps that would come in contact withthe tubing. Use an insulated or suspension type hanger. Keepboth lines separate and always insulate the suction line.Where possible, drain as much residual compressor oil fromexisting systems, lines, and traps; pay close attention to lowareas where oil may collect. NOTE: If changing refrigeranttypes, ensure the indoor coil and metering device is compatible with the type of refrigerant being used; otherwise, the indoor coil must be replaced.These sizes are recommended for line lengths of 79 feet orless to obtain optimum performance. For alternate line sizingoptions or runs of more than 79 feet, refer to Remote CoolingService Manual or TP-107 Long Line Set Application R-410Aor contact your distributor for assistance.Burying Refrigerant LinesIf burying refrigerant lines can not be avoided, use the followingchecklist.1. Insulate liquid and suction lines separately.RECOMMENDED INTERCONNECTING TUBING (Ft)0-24Cond25-49Line Diameter (In. OD)50-79*UnitTonsSuctLiqSuctLiqSuctLiq1 1/222 1/233 3/43/47/81 1/81 1/81 1/83/83/83/83/83/83/83/83/43/47/81 1/81 1/81 1/81 1/83/83/83/83/83/83/83/82. Enclose all underground portions of the refrigerant linesin waterproof material (conduit or pipe) sealing the endswhere tubing enters/exits the enclosure.3. If the lines must pass under or through a concrete slab,ensure lines are adequately protected and sealed.Refrigerant Line ConnectionsIMPORTANTTo avoid overheating the service valve, TXV valve, or filterdrier while brazing, wrap the component with a wet rag, oruse a thermal heat trap compound. Be sure to follow themanufacturer’s instruction when using the heat trapcompound. Note: Remove Schrader valves from servicevalves before brazing tubes to the valves. Use a brazingalloy of 2% minimum silver content. Do not use flux.* Lines greater than 79 feet in length or vertical elevationchanges more than 50 feet refer to the Rem ote CoolingService Manual or contact your distributor for assistance.Torch heat required to braze tubes of various sizes isproportional to the size of the tube. Tubes of smaller sizerequire less heat to bring the tube to brazing temperaturebefore adding brazing alloy. Applying too much heat toany tube can melt the tube. Service personnel must usethe appropriate heat level for the size of the tube beingbrazed. Note: The use of a heat shield when brazing isrecommended to avoid burning the serial plate or the finishon the unit.1. The ends of the refrigerant lines must be cut square, deburred, cleaned, and be round and free from nicks or dents.Any other condition increases the chance of a refrigerantleak.3

2. “Sweep” the refrigerant line with nitrogen or inert gasduring brazing to prevent the formation of copper-oxideinside the refrigerant lines. The POE oils used in R410A applications will clean any copper-oxide presentfrom the inside of the refrigerant lines and spread itthroughout the system. This may cause a blockage orfailure of the metering device.System EvacuationCondensing unit liquid and suction valves are closed to contain the charge within the unit. The unit is shipped with thevalve stems closed and caps installed. Do not open valvesuntil the system is evacuated.WARNING3. After brazing, quench the joints with water or a wet clothto prevent overheating of the service valve.REFRIGERANT UNDER PRESSURE!Failure to follow proper procedures may causeproperty damage, personal injury or death.4. Ensure the filter drier paint finish is intact after brazing. Ifthe paint of the steel filter drier has been burned or chipped,repaint or treat with a rust preventative. This is especiallyimportant on suction line filter driers which are continually wet when the unit is operating.NOTE: Scroll compressors should never be used to evacuateor pump down a heat pump or air conditioning system.CAUTIONProlonged operation at suction pressures less than 20psig for more than 5 seconds will result in overheating ofthe scrolls and permanent damage to the scroll tips, drivebearings and internal seal.NOTE: Be careful not to kink or dent refrigerant lines. Kinkedor dented lines will cause poor performance or compressordamage.Do NOT make final refrigerant line connection until plugs areremoved from refrigerant tubing.1. Connect the vacuum pump with 250 micron capability tothe service valves.NOTE: Before brazing, verify indoor piston size by checkingthe piston kit chart packaged with indoor unit.2. Evacuate the system to 250 microns or less using suction and liquid service valves. Using both valves is necessary as some compressors create a mechanical sealseparating the sides of the system.Leak Testing (Nitrogen or Nitrogen-Traced)WARNING3. Close pump valve and hold vacuum for 10 minutes. Typically pressure will rise during this period.To avoid the risk of fire or explosion, never useoxygen, high pressure air or flammable gases for leaktesting of a refrigeration system. If the pressure rises to 1000 microns or less and remainssteady the system is considered leak-free; proceed tostartup.WARNING5000To avoid possible explosion, the line from thenitrogen cylinder must include a pressure regulatorand a pressure relief valve. The pressure relief valvemust be set to open at no more than 150 psig.VACUUM IN MICRONS4500Pressure test the system using dry nitrogen and soapy waterto locate leaks. If you wish to use a leak detector, charge thesystem to 10 psi using the appropriate refrigerant then usenitrogen to finish charging the system to working pressure thenapply the detector to suspect areas. If leaks are found, repairthem. After repair, repeat the pressure test. If no leaks exist,proceed to system NSIBLES OR SMALLLEAK PRESENT15001000NO LEAKSNO CONDENSIBLES50004123456MINUTES78910

If pressure rises above 1000 microns but holds steadybelow 2000 microns, moisture and/or noncondensiblesmay be present or the system may have a small leak.Return to step 2: If the same result is encountered checkfor leaks as previously indicated and repair as necessarythen repeat evacuation.Overcurrent Protection If pressure rises above 2000 microns, a leak is present.Check for leaks as previously indicated and repair as necessary then repeat evacuation.These devices have sufficient time delay to permit the motorcompressor to start and accelerate its load.The following overcurrent protection devices are approved foruse. Time delay fuses HACR type circuit breakersThree Phase Compressor RotationElectrical ConnectionsCAUTIONWARNINGUse care when handling scroll compressors. Dome temperatures could be hot.HIGH VOLTAGE!Disconnect ALL power before servicing.Multiple power sources may be present.Failure to do so may cause property damage,personal injury or death due to electric shock.Wiring must conform with NEC or CEC and alllocal codes. Undersized wires could causepoor equipment performance, equipment damageor fire.Three phase compressors are power phase dependent andcan rotate in either direction.Verify proper rotation for three phase compressors by ensuringthe suction pressure drops and discharge pressure rises whenthe compressor is energized. NOTE: When operated in reverse, a three phase scroll compressors is noisier and itscurrent draw substantially reduced compared to marked values.WARNINGTo avoid the risk of fire or equipment damage, usecopper conductors.To correct, disconnect power and switch any two leads at theunit contactor and re-observe.NOTICEHigh Voltage ConnectionsRoute power supply and ground wires through the high voltage port and terminate in accordance with the wiring diagramprovided inside the control panel cover.The condensing unit rating plate lists pertinent electrical datanecessary for proper electrical service and overcurrent protection. Wires should be sized to limit voltage drop to 2% (max.)from the main breaker or fuse panel to the condensing unit.Consult the NEC, CEC, and all local codes to determine thecorrect wire gauge and length.Low Voltage ConnectionsCondensing unit control wiring requires 24 Volt minimum, 25VAservice from the indoor transformer. Low voltage wiring fortwo-stage units depends on the thermostat used and the number of control wires between the indoor unit and the condensing unit. Route control wires through the low voltage port andterminate in accordance with the wiring diagram provided inside the control panel cover.Local codes often require a disconnect switch located near theunit; do not install the switch on the unit. Refer to the installation instructions supplied with the indoor furnace/air handler forspecific wiring connections and indoor unit configuration. Likewise, consult the instructions packaged with the thermostatTHERMOSTATSINGLE-STAGE HEATINGWITHSINGLE-STAGE COOLINGfor mounting and location information.Single-Stage Thermostatwith Two Low Voltage Wires to Remote5

System Start UpCAUTIONPOSSIBLE REFRIGERANT LEAKTo avoid a possible refrigerant leak, open the servicevalves until the top of the stem is 1/8” from the retainer.CAUTIONPOSSIBLE REFRIGERANT LEAKTo avoid a possible refrigerant leak, open the servicevalves until the top of the stem is 1/8” from the retainer.1. Break vacuum by fully opening liquid and suction basevalves.When opening valves with retainers, open each valve onlyuntil the top of the stem is 1/8” from the retainer. To avoid lossof refrigerant, DO NOT apply pressure to the retainer. Whenopening valves without a retainer remove service valve capand insert a hex wrench into the valve stem and back out thestem by turning the hex wrench counterclockwise. Open thevalve until it contacts the rolled lip of the valve body.2. Set thermostat to call for cooling. Check indoor and outdoor fan operation and allow system to stabilize for 10minutes for fixed orifices and 20 minutes for expansionvalves.Charge VerificationNOTE: These are not back-seating valves. It is not necessaryto force the stem tightly against the rolled lip.WARNINGREFRIGERANT UNDER PRESSURE!NOTE: Power must be supplied to the 18 SEER outdoorunits containing ECM motors before the power is appliedto the indoor unit. Sending a low voltage signal withouthigh voltage power present at the outdoor unit can causemalfunction of the control module on the ECM motor. Do not overcharge system with refrigerant. Do not operate unit in a vacuum or at negative pressure.Failure to follow proper procedures may causeproperty damage, personal injury or death.Adequate refrigerant charge for the matching HSVTC evaporator coil and 15 feet of lineset is supplied with the condensing unit. If using evaporator coils other than HSVTC coil, itmay be necessary to add or remove refrigerant to attain propercharge. If line set exceeds 15 feet in length, refrigerant shouldbe added at .6 ou

If replacing a condensing unit or air handler, the system must be manufacturer approved and Air Conditioning, Heating and Refrigeration Institute (AHRI) matched. NOTE: Installation of unmatched systems is strongly discouraged. Outdoor units are approved for operation above 55 F in cool-

Related Documents:

PF Prop Fan Condensing Unit A P 208/230V, 1 ph, 60 Hz C C Standard Condensing Unit X 277V, 1 ph, 60 Hz H Hot Gas Bypass S 220/240V, 1 ph, 50 Hz 18A 020A 1.5-ton Condensing Unit A 460V, 3 ph, 60 Hz 027A 2-ton Condensing Unit Y 208/230V, 3 ph, 60 Hz 037A 3-ton Condensing Unit

Condensing Unit, the minimum distance between the Control Panel and the wall is 3 feet. On Indoor Condensing Unit, Satellite Unit, Remote Condenser Unit and Water Cooled . Condensing Unit, the minimum distance between the Control Panel and another live panel is 4 feet

Condensing Unit EER - Standard vs. KeepRite SmartSpeed Standard Unit KeepRite SmartSpeed 15 %* * BIN ANALYSIS SHOWS AN AVERAGE OF 10% SAVINGS OVER THE RANGE OF THE YEAR Condensing Unit EER - Standard Unit vs. SmartSpeed Standard Unit SmartSpeed Condensing Unit with SmartSpeed Power Consumption Per Motor Chassis Size

Condensing Unit EER - Standard vs. KeepRite SmartSpeed Standard Unit KeepRite SmartSpeed 15 %* * BIN ANALYSIS SHOWS AN AVERAGE OF 10% SAVINGS OVER THE RANGE OF THE YEAR Condensing Unit EER - Standard Unit vs. SmartSpeed Standard Unit SmartSpeed Condensing Unit w

twc 18 18,000 btuh 1 1 phase condensing series louvered 10 seer ckl 18 18,000 btuh 1 1 phase condensing louvered 12 seer clj 18 18,000 btuh 1 1 phase condensing series t 13 seer crt 24 24,000 btuh condensing louvered 13 seer clt 24 24,000 btuh 1 1 phase condensing louvered 14 seer clq 24 24,000 btuh 1 1 phase

The condensing unit must be installed on a solid, level mounting pad that will not settle or shift. Isolate the pad from the building structure to avoid possible transmission of sound or vibration from the condensing unit into the conditioned space. The condensing unit foundation should

Condensing Unit Air Cooled Centrifugal Condensing Unit Water/Glycol Condensing Unit 3 Tons 60 Hz (50 Hz) B*036E (B*035E) PFH_42A (PFH_41A) MC_40A (MC_39A) MC_44W . Figure 20 Cabinet and floor planning dimensions—Split system 5 ton outdoor condensing u

Condensing Unit Replacement Checklist . Copeland Scroll outdoor condensing units for refrigeration applications 2011DS-4_XJ 4/11 . Nomenclature Welded Condensing Units Temperature Application Code High Temperature