19SЕRIESRelay actuators &Status indicating modulesPanels forelectricaldistribution

FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.

19 SERIESRelay actuators & Status indicating modules19SERIES19.21.0.024.0000Auto/Off/On output module 10 A Auto/Off/On output module intended topermit the automatic control of pumps,blowers or motor groups. Or, in the case ofinstallation, maintenance or failure, to permitthe load equipment to be turned “Off“ orturned “On“ Ideal interface for PLC and electronic systems Only 11.2 mm wide 3 function selector switch:- Auto: works as a monostable relay(following A3 input)- Off: relay permanently OFF- On: relay permanently ON 24 V AC/DC supply and module input 35 mm rail (EN 60715) mountingApplication examples: control of pumps, blowers or motor groups primarily suited to Industrial control systemsB 1 CO output contact 11.2 mm wide Feedback onSwitch position:Wiring diagramRequestResponseLED SignalsB1-B2 feedback to the controller signaling Auto-operationA3-A2 “Auto“ signal from ControllerController, PLCType 19.21For outline drawing see page 9Contact specificationContact configuration1 CO (SPDT)Rated current/Maximum peak current Rated voltage/Maximum switching voltage AV AC10/15250/400Rated load AC1 VA2500Rated load AC15 (230 V AC) VA500Single phase motor rating (230 V AC) kWBreaking capacity DC1 (24/110/220 V) Minimum switching load AmW (V/mA)Standard contact material0.4410/0.3/0.12300 (5/5)AgSnO2Feedback contact specification (terminals B1-B2)Contact configurationMaximum current Rated voltage 1 NO (SPST-NO)mA300V AC/DC24V AC (50/60 Hz)24Supply & Input specificationNominal voltage (UN) V DCRated power X-2017, www.findernet.comOperating range VA (50 Hz)/W240.6/0.4AC(0.8 1.1)UNDC(0.8 1.1)UN C–20 50Technical dataAmbient temperature range Protection categoryIP 20Approvals (according to type)3

19SERIES19 SERIESRelay actuators & Status indicating modules19.50.0.024.0000Analogue override module - Auto/Hand(0 10)V Analogue output module intended to provide, Analogue output (0 10)V,plus 1 feedback output contact 17.5 mm wide LED tionSwitch position:Wiring diagramRequestController, PLCResponseLED Signals53-54 feedback to the controller signaling Auto-operationYin-A2 variable (0 10)V DC from the controllerHand (0 10)V DC value set by the potentiometerType 19.50For outline drawing see page 9(0 10)V Signal specification (terminal Y-in)Input control signal V DCGreen LED 25%0 10 (Imax 20 mA - short-circuit protected) 2.5 VGreen LED 50% 5VGreen LED 75% 7.5 VFeedback output specification (terminals 53-54)Output configurationMaximum / Minimum current Rated voltage 1 NO (SPST-NO)mA100/10V AC/DC24Nominal voltage (UN)V AC (50/60 Hz)24Rated power AC/DC VA (50 Hz)/WSupply & Input specificationV DCOperating range240.9/0.7AC(0.8 1.1)UNDC(0.8 1.1)UN C–20 50Technical dataAmbient temperature range Protection categoryApprovals (according to type)4IP 20X-2017, www.findernet.comBby the selection switch on the front panel, a(0 10)V output, automatically or by hand. With the selector switch in position “A“(Automatic) the (0 10)V signal is derivedfrom the controller.In position “H” (Hand) the controller signal isignored and the (0 10)V signal is deriveddirectly from the potentiometer setting on thefacia of the module The level of the (0 10)V output signal isdisplayed by 3 green LEDs, set at 25%, 50%and 75%. 24 V AC/DC supply 35 mm rail (EN 60715) mountingApplication examples: permits the direct control of proportionalvalves under exceptional circumstances orwhere the automatic controller has failed

19 SERIESRelay actuators & Status indicating modules19SERIES19.91.9.0xx.4000Power relay module 16 A Suitable for Lamps load AgSnO2 contacts for heavy duty, high inrushcurrent loads DC supply (12 or 24 V) LED indicator Reinforced insulation between supply andcontactsB Cadmium Free contacts 35 mm rail (EN 60715) mounting 1 Pole changeover contact 17.5 mmWiring diagramFor outline drawing see page 9Contact specificationContact configuration1 CO (SPDT)Rated current/Maximum peak current Rated voltage/Maximum switching voltage AV AC16/30 (120 A - 5 ms)250/440Rated load AC1 VA4000Rated load AC15 (230 V AC) VA750incandescent/halogen W2000Nominal lamp rating (230 V): fluorescent tubes with electronic ballast Wfluorescent tubes with electromechanical ballast W750CFL W400230 V LED W400halogen or LED with electronic ballast Whalogen or LED with electromechanical ballast WMinimum switching load 1000mWStandard contact material400800300 (5 V/ 5 mA)AgSnO2Coil specificationNominal voltage (UN) V DCRated power DC WOperating range12 - 240.5(0.8 1.1)UNX-2017, www.findernet.comTechnical dataMechanical life AC/DC cycles10 · 106Electrical life at rated load AC1 cycles80 · 103Operate/release time Ambient temperature range Protection categoryms12/8 C–20 50IP 20Approvals (according to type)5

19SERIES19 SERIESRelay actuators & Status indicating modulesSwitching actuator with KNX technology - 16 A19.6K.9.030.4300Compact and powerful switching actuatorwith 6 relay outputs 6 output contacts rated 16 A 250 V AC,individually configurable NO or NCoutput (AND, OR, XOR, THRESHOLD, WINDOW) Scenario Management Output control area for manual control Supply voltage via KNX bus 35 mm rail (EN 60715) mounting Bistable relay ENEC approved(Maximum peak current up to 120 A) Suitable for lamp loads19.6KScrew terminalFor outline drawing see page 9Contact specificationContact configuration (via ETS) V ACNO - NCRated current/Maximum peak current A16/120 (5 ms)Rated voltage/Maximum switching voltage V250/400Rated load AC1 VA4000Rated load AC15 (230 V AC) VA750Single phase motor rating (230 V AC) kW0.5Nominal lamp rating (230 V): incandescent/halogen Wfluorescent lamp with electronic ballast Wfluorescent lamp with electromecanical ballast W20001000750CFL W400LED 230 V W400halogen or LV LED with electronic ballast Whalogen or LV LED with electromechanical ballast WStandard contact material400800AgSnO2Supply specificationSupply voltage V DC30Rated current mA12Technical dataMechanical life cycles10 · 106Electrical life at rated load AC1 cycles100 · 103 C–5 45Ambient temperature range Protection categoryApprovals (according to type)6IP 20X-2017, www.findernet.comB LED status indicator for each output Time functions (ON, OFF, Blink, Staircase) Independent logic and analog functions for each

19 SERIESRelay actuators & Status indicating modules19SERIESOrdering informationExample: 19 series Auto/Off/On override module, 1 CO (SPDT) 10 A contact, 24 V AC/DC supply.1 9 . 21 . 0 . 0 2 4 . 00Series00Contact circuit0 Standard3 NO (19.6K)Type21 Auto/Off/On output module, 11.2 mm50 Analogue override module (0 10)V91 Power relay module6K KNX actuator, 6 poles 16 ABContact material0 Standard for 19.21, 19.504 Standard for 19.91, 19.6KSupply version0 AC (50/60 Hz)/DC9 DCSupply voltage012 12 V024 24 V030 KNX BusCodes / Module width19.21.0.024.0000/11.2 mm19.50.0.024.0000/17.5 mm19.91.9.012.4000/17.5 mm19.91.9.024.4000/17.5 mm19.6K.9.030.4300/70 mmTechnical dataInsulationDielectric strength (V AC)19.2119.5019.91between supply and contacts3000—4000between open contacts1000—1000between supply and feedback output20001500—Reference standard19.21/91EMC specificationsType of testElectrostatic dischargecontact discharge19.50EN 61000-4-2air discharge4 kVEN 61000-4-28 kVRadiated electromagnetic field (80 1000 MHz)EN 61000-4-330 V/mFast transients (burst) (5-50 ns, 5 kHz)EN 61000-4-4Voltage pulses (1.2/50 µs)common modeEN 61000-4-52 kV1 kVon supply terminalsdifferential modeEN 61000-4-51 kV0.5 kVTerminalsScrew torqueNmMax. wire sizemm2AWGmm19.21/6K19.50/910.50.8solid cablestranded cablesolid cablestranded cable1 x 6 / 2 x 2.51 x 4 / 2 x 1.51x6/2x41 x 4 / 2 x 2.51 x 10 / 2 x 141 x 12 / 2 x 161 x 10 / 2 x 121 x 12 / 2 x 1479X-2017, www.findernet.comWire strip length4 kV7

19SERIES19 SERIESRelay actuators & Status indicating modulesWiring diagrams - Application examplesType 19.21BController, PLCType 19.21End processType 19.50Input analogsignalOutput analogsignalController, PLCType 19.50End processIn selector position A (Automatic) the (0 10)V controller variable is transferred via Yin - A2 and Yout to the end process.In selector position H (Hand) the (0 10)V value set by the regulator is transferred via Yout to the end process.X-2017, www.findernet.comType 19.6K8

19 SERIESRelay actuators & Status indicating modules19SERIESOutline drawingsType 19.21Screw terminalType 19.50Screw terminalBType 19.6KScrew terminalX-2017, www.findernet.comType 19.91Screw terminal9

19SERIES19 SERIESRelay actuators & Status indicating modulesAccessories060.48Identification tag, for 19.50 types, plastic, 1 tag, 17 x 25.5 mm019.01Adaptor for panel mounting, for 19.21/50/91 types, plastic, 17.5 mm wide020.01060.48019.01020.01X-2017, www.findernet.comBSheet of marker tags (CEMBRE Thermal transfer printers) for 19.21/50/91/6K types(48 tags), 6 x 12 mm10

19 SERIESRelay actuators & Status indicating modules19SERIESApplication notesIntervention ModulesThe demand for security apparatus, heating, air conditioning orefficient energy use in offices, hotels, and private homes or inindustrial space is growing constantly, leading to the installation ofincreasingly complex electronic systems. But what happens if thesesystems malfunction and a qualified service technician will only beavailable in a few hours, or even days?BWith the use of carefully installed intervention modules, a trainedcaretaker or security guard can be in a position to recognizeinterruptions in service, and by manual intervention perform thenecessary override actions to maintain system operation until a repaircan be effected.Digital Override control moduleAuto-Off-On output module (Type 19.21)Many processes or systems are automatically controlled by anelectronic control system or by a Programmable Logic Controller.In the event of an electronic system malfunction it is important,in order to avoid damage or downtime, to plan for the possibilityof controlling the process manually. An Auto-Off-On Module canprovide this, located between the output of the electronic system(Controller) and the process to be controlled (End Process) - bypassingthe malfunctioning control unit in a planned way. For malfunctioningelectronic systems, the process to be controlled can be manuallyswitched On or Off, as needed, using the switch on the front of theunit. Under healthy functioning of the electronic system, the switch isleft in the Auto position. In this configuration the process is controlledby the normal functioning of the electronic system and its output. Itmay be important to know (remotely) if the process is being controlledmanually or automatically, in which case the feedback contact on theAuto–Off–On module 19.21 can provide this.X-2017, www.findernet.comAnalogue Override control moduleAnalogue output module (0 10)V (Type 19.50)This module can be installed where there is need to give a manuallyadjustable analog signal (0 10)V priority over an analog signalfrom a electronic control unit or PLC, or to override and replace amalfunctioning signal.The Analogue override module provides, by the selection switch on thefront panel, a (0 10)V output signal either generated automaticallyor by hand. With the selector switch in position “A“ (Automatic)the (0 10)V signal at Yout-A2 is derived from the controller signalapplied to terminals Yin-A2. In position “H” (Hand) the controllersignal is ignored and the (0 10)V signal is derived directly from thepotentiometer setting on the module front panel.Operation in switch position H is indicated by a blinking yellow LED,and by the opening of contact 51-52 – which could be used to reportthe override condition to the central control room.The level of the (0 10)V output signal is displayed by 3 green LEDs,set at 25%, 50% and 75%Please see general technical information11

B Power relay module 16 A Suitable for Lamps load AgSnO 2 contacts for heavy duty, high inrush current loads DC supply (12 or 24 V) LED indicator Reinforced insulation between supply and contacts Cadmium Free contacts 35 mm rail (EN 60715) mounting Wiring diagram 19.91.9.0xx.4000 1 Pole ch

Related Documents:

Nissan Micra - OWM 4734 Nissan Micra - OWM 4734 CPU E6 H33750 1 Battery 2 Ignition switch 3 Fusible link holder 4 Fuse box 5 Fuse and relay box a) accessory relay b) blower motor relay 6 Intelligent power distribution module a) starter relay b) cooling fan hi relay c) cooling fan lo relay d) fuel pump relay e) ignition relay f) ECM relay

38 - Check voltage output to fuel pump @ relay set 39 - Check voltage input to relay set from ignition switch 40 - Check voltage input to fuel pump relay of relay set 41 - Check input voltage to control relay of relay set 42 - Check input voltage to control relay of relay set (continued)

work in SC. Bill Payne Environmental Services Section Washington Savannah River Company LLC Building 735-B Aiken, SC 29808 803-952-7989 South Carolina Drought Respon

with the material in this study guide. This guide can be referenced at www.srs.gov and on InSite (InSite is the SRS intranet). This study guide does not contain classified information or Unclassified Controlled Information (UCI). A. SRS Vision Statement SRS is recognized as a long-term national asset in the areas of environmental stewardship,

Circuit symbols - A description of symbols to BS2917 and ISO1219 The design, operation and application of pneumatic actuators and valves - including: compact actuators ISO actuators VDMA actuators rod-less actuators cushioning actuators manual valves mechanical valves pilot valves electrically operated valves

Power MOSFET Relay Specifications (G6D Relay) The following specifications apply to G6D Relays mounted in a G70D Relay Terminal and not the G6D Relay itself. Coil Ratings (per G6D Relay) Note: 1. The must-operate voltage is 75% or less of the rated voltage if the relay is mounted upside down. 2. Rated current and coil resistance were measured .

Results are provided for actual relay testing. Part I: Distance Relay Tests (Texas A&M University) Distance relay testing can evaluate relay performance, calibrate relay settings, and identify system conditions that could cause unexpected relay operation. Developing a relay testing methodology requires consideration of how to model the power .

Graphic Symbols N Up 17R Stair direction symbol Indication arrows drawn with straight lines (not curved); must touch object Note Note Note North point to be placed on each floor plan, generally in lower right hand corner of drawings 111/ 2 T The symbols shown are those that seem to be the most common and acceptable, judged by the frequency of use by the architectural offices surveyed. This .