Acuvim-LCopyright 2013 V2.01This manual may not be altered or reproduced in whole or in part by any meanswithout the expressed written consent of Accuenergy.The information contained in this document is believed to be accurate at the time ofpublication, however, Accuenergy assumes no responsibility for any errors which mayappear here and reserves the right to make changes without notice. Please ask thelocal representative for latest product specifications before ordering.[ Document #1030E2201Revision Date: Apr, 2013 ]I

Acuvim-LPlease read this manual carefully before installation, operation and maintenance ofAcuvim-L power meter.The following symbols in this manual and on Acuvim-L series meters are used toprovide warning of danger or risk during the installation and operation of the meters.Electric Shock Symbol: Carries information about procedures which must befollowed to reduce the risk of electric shock and danger to personal health.Safety Alert Symbol: Carries information about circumstances which if notconsidered may result in injury or death.This mark indicates that this product is UL listed.Installation and maintenance of the Acuvim-L power meter should only be performedby qualified, competent professionals who have received training and should haveexperience with high voltage and current device.Accuenergy shall not be responsible or liable for any damages caused by impropermeter installation and/or operation.II

Acuvim-LContentChapter 1 -----------------------------11.1 Functionality -------------21.2 Areas of application -----------21.3 Meter --------------------3Chapter 2 -------------------------------72.1 Appearance and -----92.2 Installation -----------------122.3 Wiring -----------------------------15Chapter 3 Meter Operation and Parameter Setting-------------------------------313.1 Display Panel and --323.2 Metering Data -------343.3 Statistics ------------------423.4 System Parameter Setting ---473.5 DO Parameter Setting and Expansion module Setting----------------543.6 Ethernet Network Module Settings----------------------------------------- 613.7 DI Status Display --------------653.8 TOU Energy and Maximum Demand Display-------------------------663.9 Measurement Methods and Parameter Definitations------------------69Chapter 4 ------------------------------------854.1 Modbus protocol ---------864.2 Modbus ----------------------874.3 Communication -----894.4 Ethernet Module --------94III

Acuvim-L4.5 Data address ---------------134Appendix A Technical data and ----------178Appendix B Ordering ----------------------182Appendix C Revision --------------------------184IV

Acuvim-LStarting!Congratulations!You have purchased an advanced, versatile and multifunction power meter. Thismeter can work as a remote terminal unit (RTU) that contributes to your system’sstability and reliability by providing real-time power quality monitoring and analysis.When you open the package, you will find the following items:1. Acuvim-L power meter2. Terminal Blocks3. [INSERT] Installation Clips4. Product Disk (Manual, Warranty, Software)5. Additional documentation(Quick Setup Guide, Calibration Certificate)13 (2 for basic model)412To avoid complications, please read this manual carefully before installation andoperation of the Acuvim-L series meter.Chapter 1 Chapter 1 Introduction.Chapter 2 Installation and Wiring.Chapter 3 Meter Display and Parameter Settings.Chapter 4 Communication Protocols and Modbus Map.Appendix Technical Data, Specifications and Ordering Information.V

VIAcuvim-L

Chapter 1 Introduction1.1 Functionality1.2 Areas of Application1.3 Meter Overview

Acuvim-L1.1 FunctionalityMultifunction, high accuracyAcuvim-L series multifunction power meter is designed with the latestmicroprocessor and digital signal process technology. It can measure voltage,current, active power, reactive power, apparent power, power factor for threephases, individual harmonics up to the 2nd or 31th order, THD, real and reactiveenergy, current and demand and max/min values for real time readings.The optional Digital Output and RS485 communication can be used for sendingenergy pulse output and event alarming signals. The RS485 port also can be usedfor remote meter controlling and data collection. Acuvim-L series meter deliversexceptional metering functionality and provides a cost effective solution forcustomers.Compact and Easy to InstallAcuvim-L series meter can be installed into a standard ANSI C39.1 (4" round) oran IEC 92mm DIN (square) slot. With the 51mm depth , the meter can be installedin a small cabin. Installation clips are used for easy installation and removal.Easy to useAll metering data and setting parameters can be accessed by using the frontpanel keys or via the communication port. Setting parameters are stored in theEEPROM so that content will be maintained even when the meter is powered off.Multiple Wiring ModesThe Acuvim-L series meter can be used in high voltage, low voltage, three phasethree wires, three phase four wires and single phase systems by using differentwiring mode settings.1.2 Application Area2

Power Distribution Automation    Electric Switch Gear and Control PanelsIndustrial Automation       Building AutomationEnergy Management Systems    Marine ApplicationsRenewable Energy1.3 Meter OverviewThe Acuvim-L series have six standalone models: Acuvim-AL(basic model),Acuvim-BL(basic model 2DO), Acuvim-CL(basic model RS485), AcuvimDL(basic model RS485 Extend IO), Acuvim-EL(TOU RS485 Extend IO) andAcuvim-KL(Simplified Acuvim-CL). Please see table 1-1 for their functionalitiesand details.Table 1-1 Functions of Acuvim-L seriesFunctionVoltageCurrentPowerReal TimeMeasuringReactive PowerApparentPowerPower FactorLoad NatureFrequencyParametersU1, U2, U3,U12, U23, U31I1, I2, I3,In,(AcuvimKL non-neutral currentmeasurement)P1, P2, P3, PsumALBLCLDLEL KL Q1, Q2, Q3, QsumS1, S2, S3, Ssum PF1, PF2, PF3, PFL/C/RF 3Acuvim-LAcuvim-L series meter is the ideal choice for replacing traditional, analogelectric meters. It uses true RMS measuring methods so that nonlinear load canbe monitored. Except providing means of monitoring and measuring powerdistribution automation system, it can also be used as a remote terminal unit(RTU) for monitoring and controlling a SCADA system. Users can access allmeasurement parameters via the optional RS485 communication port withModbusTM protocol. Main application areas Electric Switch Gear and ControlPanels include:

Acuvim-LFunctionEnergyReactive EnergyEnergyApparentEnergyCurrentDemandDemandPower DemandParametersEp imp, Ep expEq imp, Eq expEsDmd I1, Dmd I2,Dmd I3Dmd Psum, DmdQsum,Dmd SsumTOU, 4 Tariffs,Energy/max12 Seasons, 14demandSchedulesTOUDaylightSaving ePower Quality Voltage THDCurrent THDIndividualHarmonics4AL BL CL DL EL KL Daylightsaving timeautomaticallyadjustUp to decadeholidays settings U unbl I unbl THD V1, THD V2,THD V3THD I1, THD I2,THD I32nd to 31th(Voltageand Current)

Statistics Umax, Umin Imax, Imin Hour Load RunningHourHour Max PowerDemandMax/MinVoltageMax/MinCurrentRunning HourHOURI/ODmd I1 max,Dmd I2 max,Dmd I3 maxDmd Psum max,Dmd Qsum max,Dmd Ssum maxAcuvim-LMax CurrentDemandEnergy PulseOutput/AlarmOutputExpansion I/Omodule2 DO(Standard)4DI, 2DO/2ROModbus -RTUProtocol(Standard)RS-485EthernetModbus -TCP,(ExtendedHTTP, SMTP, SNMP,communicationSNTPmodule)COMMUNICATIONModbus -RTUSecond e)Note: Possessed functions PROFIBUS-DP(V0) Protocol,according toEN50170 standards Optional function Blank NA5

6Acuvim-L

Chapter 2 Installation2.1 Appearance and Dimensions2.2 Installation Methods2.3 Wiring6

Acuvim-LConsiderations When Installing Meters Installation of the meter must be performed by qualified personnel only, whofollow standard safety precautions through the installation procedures. Thosepersonnel should have appropriate training and experience with high voltagedevices. Appropriate safety gloves, safety glasses and protective clothing arerecommended. During normal operation, dangerous voltage may flow through many parts ofthe meter, including: terminals, any connected CTs (Current Transformers) and PTs(Potential Transformers), all I/O (Inputs and Outputs) modules and their circuits. Allprimary and secondary circuits can, at times, produce lethal voltages and currents.Avoid contact with any current-carrying surfaces. The meter and its I/O output channels are NOT designed as primary protectiondevices and shall NOT be used for primary circuit protection or in an energy-limitingcapacity. The meter and its I/O output channels can only be used as secondaryprotection. AVOID using the meter under situations where failure of the meter maycause injury or death. AVOID using the meter for any application where risk of firemay occur. All meter terminals should be inaccessible after installation. Do NOT perform Dielectric (HIPOT) test to any inputs, outputs or communicationterminals. High voltage testing may damage electronic components of the meter. Applying more than the maximum voltage the meter and/or its modules canwithstand will permanently damage the meter and/or its modules. Please refer tothe specifications for all devices before applying voltages.8

2.1 Appearance and DimensionsUnits: mm(inches)A-LMultifunction Power Meter96.00 (3.800) HPEGasket V/A96.00 (3.800)GasketFront View of the Display Meter andRemote Display Unit7.60 (0.300)35.90(1.413)50.70 (1.996)Side View of theDisplay Meter91.00 (3.583)91.00 (3.583)91.00 (3.583) 38.00 (1.496) 35.90(1.413)10.00(0.394)Side View of the RemoteDisplay Unit35.90(1.413)50.70 (1.996)14.00(0.551)Side View of the DINrail Meter9Acuvim-LThe installation method is introduced in the chapter. Please read this chaptercarefully before beginning installation .

Acuvim-L Rear View Rear View of the RemoteDisplay UnitInstallation ClipFig.2-1 Appearance and dimensionsPart Name LCD DisplayDescriptionLarge bright white backlight LCD display.Visible portion (for display and control) after Front Casingmounting onto a panel.Four keys are used to select display and set. KeyThe Acuvim-L series meter enclosures is madeof high strength anti-combustible engineering Enclosureplastic.Used for Installation 35mm rail of the DIN rail DIN railMeter. Voltage Input Terminals Used for voltage input. Current Input Terminals Used for current input. Power Supply Terminals Used for aux. power supply input. Communication Terminals Communication output.Used for link the remote display unit and the DIN Interfacerail meter.Installation ClipUsed for fixing the meter to the panel.Insert the gasket in between the meter and theGasketcutout to cover up gaps from the round hole.10

Acuvim-LIO module appearance and mechanical dimensions19 .5 mmFig.2-2 structure configuration of IO modulesPROFIBUS module and Ethernet module appearance and mechanical dimensions55.6090.0022.00Fig.2-3 structure configuration of PROFIBUS modules11

EnvironmentNoteTemperature and humidityof the environmentmust accord with therequirement of acuvim-L,Otherwise it may causethe meter damaged.Please check the environmental temperaturea n d h u m i d i t y a c c o r d i n g t o A c u v i m - L’srequirement to ensure the power meter canwork well.1. TemperatureOperation: -25 C to 70 C Storage: -40 C to 85 C2. Humidity5% to 95% No condensation3. LocationAcuvim-L power meter should be installed in a dry and dust free environment.Avoid exposing meter to excessive heat, radiation and high electrical noisesource.Installation stepsAcuvim-L series meter can be installed into a standard ANSI C39.1 (4” round) oran IEC 92mm DIN (square) form. 1. Cut a square or round hole on the panel ofthe switch gear. The cutting size shows as Fig.2-4.Unit: mm (inches)101.6 0.5-0.092 0.5-0.0(4.000)Cutting92 0.5-0.0ALUM0206Acuvim-L2.2 Installation Methods(3.622)PanelPanelFig.2-4 Panel cutting12

ALUM0207PanelPanelFig.2-5 Put the meter into the squareALUM02083. Install the clips to the meter from backside and push the clips tightly so thatthe meter is fixed on the panel.PanelFig.2-6 Use clips to fix the meter13Acuvim-L2. Remove the clips from the meter and put Acuvim-L into the square hole fromthe front side.

Acuvim-LModule Installation(1) The extend module could be installed from the bottom of the meter .(2) The extend module is fixed on the meter by the screw.(3) Please install the PROFIBUS module first if both IO and PROFIBUS module areselected.(4)Please install the Ethernet module first if both IO and Ethernet module areselected.Fig.2-7 IO installation diagramNote: Acuvim-DL and Acuvim-EL Power meter can connect at most one IOmodule, one PROFIBUS module and one Ethernet module at the same time.14

Acuvim-L2.3 Wiring2.3.1 Terminal StripsThere are three or four terminal strips at the back of the Acuvim-L series meterdepending on different models. The terminal strip diagrams are shown inbelow. The three phase voltage and current are represented by using 1, 2, and 3respectively. These numbers have the same meaning as A, B, and C or R, S, and Tused in other literature.Current input terminal stripsALUM0209!I111I122I213I224I315I326Voltage input terminal stripsALUM02107V18V29V310VNPower supply terminal stripsALUM0211131211N/- L/ Power Supply15

Acuvim-LCommunication terminal stripsDigital output terminal stripsALUM0213ALUM021216 15 1416 15 14S B AComm PortDOC DO2 DO1Digital OutputFig.2-8 Terminal diagram of Acuvim-LNote: Acuvim-AL does not have digital output and commnication terminal stripsAcuvim-BL has digital output terminal stripAcuvim-CL/DL/EL/KL have communication terminal stripDigital InputDICDI4DI3DI2Digital OutputDI1 DO22 DO21 DO12 DO11Comm PortABSFig.2-9 Expansion module terminal descriptionSafety Earth ConnectionDangerOnly qualified personnelshould perform thewiring connection. Makesure the power supply isdisconnected. Failure tofollow these instructionsmay result in severe injuryor death.16Before setting up the meter’s wiring, pleasemake sure that the switch gear has an earthground terminal. Connect both the meter andthe switch gear ground terminals together. Thefollowing ground terminal symbol is used in thisuser’s manual.Fig.2-10 Safety Earth Symbol

Acuvim-L2.3.2 Power RequirementAuxiliary powerNoteThere are two Auxiliary Power Supply options for theAcuvim-L series meter:Make sure the powersupply voltage iswithin the requiredauxiliary power supplyrange.1. Standard: 100 415Vac (50/60Hz) or 100 300Vdc2. Low Voltage DC Option: 20-60VdcChoose the option according to the application.The meter’s typical power consumption is very lowand can be supplied by an independent source or by the measured load line. Aregulator or an uninterrupted power supply (UPS) should be used under highpower fluctuation conditions. Terminals for the auxiliary power supply are 11, 12 ,13 (L, N, ).The typical wiring connection is shown as Fig.2-11.1A FUSEPower SupplyGround11L12NAcuvim-L13Fig.2-11 wiring connection of power supplyALUM0214The wire of power supply should be AWG22-16 or 0.6-1.3mm2. A fuse (typical1A/250Vac) should be used in the auxiliary power supply loop. No.13 terminalmust be connected to the ground terminal of switchgear. An isolatedtransformer or EMC filter should be used in the auxiliary power supply loop ifthere is a power quality problem in the power supply.17

Acuvim-L1A FUSEPower SupplyGroundLL11LNN12NGG13EMC FilterAcuvim-LALUM0215Fig.2-12 wiring connection of auxiliary power supply with EMC filtersVoltage inputMaximum input voltage for the Acuvim-L series meter shall not exceed400LN/690LL VAC rms for three phase or 400LN VAC rms for single phase.Potential Transformer (PT) must be used for high voltage systems. Typicalsecondary output for PTs shall be less than or equal to 400V. Please make sure toselect an approprate PT to maintain the measurement accuracy of the meter.NoteThe secondary of PTcan not be shorted;otherwise it maycause severe damagesto the instrument.A fuse (typical 1A) should be used in the voltageinput loop. The wire for voltage input could beAWG16-12 or 1.3-2.0mm2.Note: In no circumstance should the secondary ofthe PT be shorted. The secondary the PT should begrounded at one end.Please refer to the wiring diagram section for furtherdetails.Current inputCurrent Transformers (CTs) are required in most engineering applications.Typical current rating for the secondary side of the CT shall be 5A (standard)or 1A (optional, please refer to the ordering information appendix for further18

The wire size of current input could be AWG15-16 or 1.5-2.5mm2.Note: The secondary side of the CT should not be open circuit in anycircumstance when the power is on. There should not be any fuse or switch inthe CT loop. One end of the CT loop should be connected to the ground.Vn connectionVn is the reference point of the Acuvim-L voltage input. Low wire resistancehelps improve the measurement accuracy. Different system wiring modesrequire different Vn connection method. Please refer to the wiring diagramsection for more details.Three phase wiring diagramAcuvim-L can satisfy almost all kinds of three phase wiring diagram. Please readthis section carefully before choosing the wiring diagram suitable for your powersystem.Voltage and current input wiring mode can be set separately in the meterparameter setting process. The voltage wiring mode can be set as 3-phase 4-lineWye(3LN), 3-phase 3-line direct connection mode(3LL), 3-phase 3-line open delta(2LL), single-phase two-line(1LN) and single-phase three-line(1LL). The currentinput wiring mode can be set as 3CT, 2CT and 1CT. Any voltage wiring setup canbe matched with any one of the current wiring setup.19Acuvim-Ldetails). CTs must be used if the system rated current is over 5A. The accuracy ofthe CT should be better than 0.5% with rating over 3VA is recommended in order topreserve the meter’s accuracy. The wire between CTs and the meter shall be as shortas possible. The length of the wire may increase the error of the measurement.

Acuvim-L2.3.3 Voltage Input Wiring3-Phase 4-Line Wye mode (3LN)The 3-Phase 4-Line Wye mode is popularly used in low voltage electricdistribution power system. For voltage lower than 400LN/690LL Vac, power linecan be connected directly to the meter’s voltage input port as shown in Fig.213a. In the high voltage input system, 3PT Wye mode is often used as in Fig.213b. The meter should be set to 3LN for both voltage levels.LINEABCN1A FUSE7V18V29V310VNAcuvim-LALUM0221LOADFig.2-13a 3LN direct connectionLINEABCN1A FUSE7V18V29V310VNAcuvim-LALUM0222LOADFig.2-13b 3LN connection with 3PTs20

In a 3-Phase 3-Line system, power line A, B and C

Acuvim-L power meter should be installed in a dry and dust free environment. Avoid exposing meter to excessive heat, radiation and high electrical noise source. Installation steps Acuvim-L series meter can be installed into a standard ANSI C39.1 (4” round) or an IEC 92mm DIN (sq

Related Documents:

Developed by Accuenergy Corporation, Acuview software is designed for the Acuvim-X, Acuvim-L, Acuvim II, Acuvim and AcuDC 200 series power meters. Acuview software provides user-friendly real-time monitoring and data logging features for energy saving and power quali

The Acuvim II series are high-end multifunction power and energy meters manufactured by Accuenergy. They are the ideal choice for the monitoring and controlling of power distribution systems. The Acuvim II series may be used as data gathering devices for intelligent power

Acuvim-L series meter is the ideal choice for replacing traditional, analog Acuvim-L electric meters. It uses true RMS measuring methods so that nonlinear load can be monitored. Except providing means of monitoring and measuring power

The Acuvim II series are high-end multifunction power and energy meters manufactured by Accuenergy. They are the ideal choice for the monitoring and controlling of power distribution systems. The Acuvim II series may be used as data gathering devices for intelligent power

The aAcuvim-L series are multif unction power meters manuf actured by Accuenergy. It is the ideal choice for monitoring and controlling of power distribution system. Some of the features and electric power parameters available on the Acu

Acuvim II Series Intelligent Power Meter (Web Accessible) y Revenue Grade with Data Logging y Waveform Capture . are high-end multifunction power and energy meters manufactured by Accuenergy. They are the ideal choice for the monitoring and controlling of power distribution sy

The Acuvim II series are high-end multifunction power and energy meters manufactured by Accuenergy. They are the ideal choice for the monitoring and controlling of power distribution systems. The Acuvim II series may be used as data gathering devices for intelligent power

Accounting information from several branches can be merged, making decision-making easy and fast. End of Chapter Questions 1 Anti-virus software, complicated passwords. 2 Email, cloud. 3 You can save your work, easy to send to other people, calculations and templates are already there for you to use. 4 Hacking, failure in technology – power cut, some software is expensive. Exam Practice 1B .