SAFETY DATA SHEET:NOVEC 1230 pressurized with NitrogenPageRevision n.DatePrevious1 di 13207/01/202004/04/2018SDS reference--SECTION 1: Identification of the substance/mixture and of the company/undertaking1.1. Product identifierProduct nameTrade nameCAS-No.REACH Registration No.3M NOVEC 1230 Fire Protection Fluid (FK 5-1-12) pressurized withNitrogen3M NOVEC 1230 Fire Protection Fluidnot relevant (mixture)not relevant (mixture)1.2. Relevant identified uses of the substance or mixture and uses advised againstIdentified usesFire extinguishing agent1.3 Details of the supplier of the safety data sheetSupplierE-mail1.4. Emergency telephone numberEmergency telephone numberMedicAir Industry srlVia T. Tasso, 29 - 20010 Pogliano Milanese (Mi)Tel 39.02.93282361industry.info@medicair.it 39 02 932821SECTION 2: Hazards identification2.1 Classification of the substance or mixtureClassification according to Regulation (EC) No 1272/2008 (CLP) as amended.Hazard classGases under pressureHazardous to the aquatic environment – chronic hazardHazard class and categoryPress. Gas CAquatic Chronic 3Hazard StatementH280H412For full text of abbreviations: see SECTION 16Additional informationThis mixture does not contain any substances that are assessed to be a PBTor a vPvB.EIGA-0783: Contains fluorinated greenhouse gases covered by the Kyotoprotocol.EIGA-As: Asphyxiant in high concentrations.2.2 Label ElementsLabelling according to Regulation (EC) No 1272/2008 (CLP)Signal WordsWarningPictogramsGHS04Hazard Statement(s)Precautionary StatementH280: Contains gas under pressure; may explode if heated.H412: Harmful to aquatic life with long lasting effects.P273 Avoid release to the environment.P410 P403 Protect from sunlight. Store in a well-ventilated place.2.3 Other hazardsGastec-Vesta srl Via Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932821 Fax 39.02.93282342nfo@gastecvesta.com www.gastecvesta.comMedicAir Industry S.r.l. - Via T. Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932281 Fax 39.02.93282342industry.info@medicair.it - www.medicairindustry.comIn caso di emergenza: 39 02.932821 (ore ufficio)In caso di emergenza: 39 02.932821 (ore ufficio)

SAFETY DATA SHEET:NOVEC 1230 pressurized with NitrogenResults of PBT and vPvB assessmentPageRevision n.DatePrevious2 di 13207/01/202004/04/2018SDS reference--Asphyxiant in high concentrations.This mixture does not contain any substances that are assessed to be a PBTor a vPvB.SECTION 3: Composition/information on ingredients3.1 Substancesnot relevant (mixture)3.2 MixturesDescription of the mixtureHazardous ingredients acc. to CLPName of ethyl)-3pentanoneIdentifierCAS No756-13-8Wt%80-99Classification acc. to GHSAquatic Chronic 3 / H412 20Press. Gas C / H280PictogramsEC No436-710-6Index No606-108-00-XNitrogenCAS No7727-37-9EC No231-783-9SECTION 4: First Aid Measures4.1 Description of first aid measuresGeneralInhalationEye contactSkin ContactIngestionNotes for the doctorIn all cases of doubt, or when symptoms persist, seek medical adviceProvide fresh air. If breathing is irregular or stopped, immediately seekmedical assistance and start first aid actions. Mouth to mouth resuscitationshould be avoided. Use alternative methods, preferably with oxygen orcompressed air driven apparatus.Rinse cautiously with water for several minutes. Remove contact lenses, ifpresent and easy to do. Continue rinsing.Wash with plenty of soap and water.Rinse mouth. Do not induce vomiting. Get medical advice/attention if youfeel unwell.none4.2 Most important symptoms and effects, both acute and delayedThese information are not available.4.3 Indication of any immediate medical attention and special treatment neededHazardsTreatmentNoneNoneGastec-Vesta srl Via Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932821 Fax 39.02.93282342nfo@gastecvesta.com www.gastecvesta.comMedicAir Industry S.r.l. - Via T. Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932281 Fax 39.02.93282342industry.info@medicair.it - www.medicairindustry.comIn caso di emergenza: 39 02.932821 (ore ufficio)In caso di emergenza: 39 02.932821 (ore ufficio)

SAFETY DATA SHEET:NOVEC 1230 pressurized with NitrogenPageRevision n.DatePrevious3 di 13207/01/202004/04/2018SDS reference--SECTION 5: Firefighting Measures5.1 Extinguishing mediaSuitable extinguishing mediaUnsuitable extinguishing mediaco-ordinate firefighting measures to the fire surroundingsNone5.2 Special hazards arising from the substance or mixtureHazardous Combustion ProductsHazardous decomposition products: Section 10. Contact with the product cancause burns and/or frostbite. Contains gas under pressure; may explode ifheatedhydrogen fluoride (HF)5.3 Advice for firefightersSpecial firefighting proceduresSpecial protective equipmentfor firefighters:In case of fire and/or explosion do not breathe fumes. Co-ordinatefirefighting measures to the fire surroundings. Do not allow firefighting waterto enter drains or water courses. Collect contaminated firefighting waterseparately. Fight fire with normal precautions from a reasonable distance.self-contained breathing apparatus (EN 133)SECTION 6: Accidental Release Measures6.1 Personal precautions, protective equipment and emergency proceduresFor non-emergency personnelRemove persons to safety.Ventilate affected area.Wearing of suitable protective equipment (including personal protectiveequipment referred to under Section 8 of the safety data sheet) to preventany contamination of skin, eyes and personal clothing.For emergency respondersWear breathing apparatus if exposed to vapors/dust/spray/gases.6.2 Environmental PrecautionsKeep away from drains, surface and ground water.Retain contaminated washing water and dispose it.6.3 Methods and material for containment and cleaning upVentilate affected area.6.4 Reference to other sectionsHazardous combustion products: see section 5. Personal protectiveequipment: see section 8. Incompatible materials: see section 10.Disposal considerations: see section 13.SECTION 7: Handling and Storage7.1 Precautions for safe handlingGastec-Vesta srl Via Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932821 Fax 39.02.93282342nfo@gastecvesta.com www.gastecvesta.comMedicAir Industry S.r.l. - Via T. Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932281 Fax 39.02.93282342industry.info@medicair.it - www.medicairindustry.comIn caso di emergenza: 39 02.932821 (ore ufficio)In caso di emergenza: 39 02.932821 (ore ufficio)

SAFETY DATA SHEET:NOVEC 1230 pressurized with NitrogenPageRevision n.DatePrevious4 di 13207/01/202004/04/2018SDS reference--Measures to prevent fire as well as aerosol and dust generationUse local and general ventilation.Prevent from heating up above 50 C/122 F. Pressurized container: mayburst if heated.Specific notes/detailsNoneMeasures to protect the environmentAvoid release to the environment.Advice on general occupational hygieneDo not to eat, drink and smoke in work areas.7.2 Conditions for safe storage, including any incompatibilitiesFlammability hazardsProtect from sunlightIncompatible substances or mixturesIncompatible materials: see section 10.Protect against external exposure, such asHeatConsideration of other adviceKeep away from food, drink and animal feeding stuffsVentilation requirementsProvision of sufficient ventilation.Packaging compatibilitiesOnly packaging which are approved (e.g. acc. to ADR) may be used.7.3 Specific end use(s):No information available.SECTION 8: Exposure Controls/Personal Protection8.1 Control ParametersNo data available.Relevant DNELs of components of the mixtureName uoro-4-(trifluoromethyl)-3pentanoneCAS NoEndpointThresholdlevel1,286,130mg/m³Protection goal,route of exposurehuman, inhalatory756-13-8DNEL756-13-8756-13-8worker (industry)DNEL780 mg/m³human, inhalatoryworker (industry)chronicsystemic effectsDNEL1,000,000mg/m³human, inhalatoryworker (industry)chroniclocal effectsGastec-Vesta srl Via Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932821 Fax 39.02.93282342nfo@gastecvesta.com www.gastecvesta.comMedicAir Industry S.r.l. - Via T. Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932281 Fax 39.02.93282342industry.info@medicair.it - www.medicairindustry.comUsed inExposuretimeacutesystemic effectsIn caso di emergenza: 39 02.932821 (ore ufficio)In caso di emergenza: 39 02.932821 (ore ufficio)

NOVEC 1230 pressurized with NitrogenSAFETY DATA yl)-3pentanone756-13-8DNEL147 mg/kghuman, dermalPageRevision n.DatePrevious5 di 13207/01/202004/04/2018SDS reference--worker (industry)chronicsystemic effectsRelevant PNECs of components of the mixtureName of substanceCAS NoEndpointPNECThresholdlevel0.008 mg/lProtection goal,route of exposureFresh waterExposuretimeacutesystemic anone756-13-8756-13-8PNEC0.001 mg/lMarine waterchronicsystemic effects756-13-8PNEC1 mg/lsewage treatmentplant (STP)chroniclocal effects756-13-8PNEC0.006 mg/kgfreshwater sedimentchronicsystemic effects756-13-8PNEC0.001 mg/kgmarine sedimentchroniclocal effects756-13-8PNEC0.006 mg/kgsoilchronicsystemic effects8.2 Exposure controlsAppropriate engineering controlsGeneral ventilation.Individual protection measures, such as personal protective equipmentEye/face protectionUse protective eyewear to guard against splash of liquids.Hand ProtectionMaterialdata are not availableMaterial hicnessdata are not availableBreakthrough times of the glove materialdata are not availableRespiratory Protection[In case of inadequate ventilation] wear respiratory protection.Self-containedbreathing apparatus (EN 133).Environmental exposure controlsUse appropriate container to avoid environmental contamination.Keep away from drains, surface and ground water.Gastec-Vesta srl Via Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932821 Fax 39.02.93282342nfo@gastecvesta.com www.gastecvesta.comMedicAir Industry S.r.l. - Via T. Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932281 Fax 39.02.93282342industry.info@medicair.it - www.medicairindustry.comIn caso di emergenza: 39 02.932821 (ore ufficio)In caso di emergenza: 39 02.932821 (ore ufficio)

SAFETY DATA SHEET:NOVEC 1230 pressurized with NitrogenPageRevision n.DatePrevious6 di 13207/01/202004/04/2018SDS reference--SECTION 9: Physical And Chemical Properties9.1 Information on basic physical and chemical propertiesAppearancePhysical stateFormColourOdourOdour ThresholdpHMelting Point/Freezing pointFlash PointEvaporation RateFlammability (solid, gas)Lower explosion limit (LEL)Upper explosion limit (UEL)DensityVapour pressureVapour densityRelative densitySolubility (ies)Solubility in WaterPartition coefficient (n-octanol/water)Autoignition TemperatureDecomposition TemperatureViscosityKinematic viscosityDynamic viscosityExplosive propertiesOxidising PropertiesLiquidPressurizedColorlessOdorlessthese information are not available.not rellevant.49 CNot applicablethese information are not availablenon-flammablethese information are not available.these information are not available.1.6 g/cm³ at 20 Cthese information are not available.these information are not available.these information are not available.insolublethese information are not available.these information are not available.these information are not available.not relevantthese information are not available.these information are not available.Not explosiveshall not be classified as oxidisingSECTION 10: Stability and Reactivity10.1 ReactivityIf heated:Gas under pressure.danger of explosion, gas under pressure, danger of bursting container10.2 Chemical StabilitySee below "Conditions to avoid".10.3 Possibility of Hazardous ReactionsNo known hazardous reactions10.4 Conditions to AvoidContains gas under pressure; may explode if heated.10.5 Incompatible Materialsbases, amine.Gastec-Vesta srl Via Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932821 Fax 39.02.93282342nfo@gastecvesta.com www.gastecvesta.comMedicAir Industry S.r.l. - Via T. Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932281 Fax 39.02.93282342industry.info@medicair.it - www.medicairindustry.comIn caso di emergenza: 39 02.932821 (ore ufficio)In caso di emergenza: 39 02.932821 (ore ufficio)

SAFETY DATA SHEET:NOVEC 1230 pressurized with NitrogenPageRevision n.DatePrevious7 di 13207/01/202004/04/2018SDS reference--10.6 Hazardous Decomposition ProductsCarbon monoxide (CO).Carbon dioxide (CO2).Hydrogen fluoride (HF).SECTION 11: Toxicological Information11.1 Information on toxicological effectsTest data are not available for the complete mixture.Classification procedureThe method for classification of the mixture is based on ingredients of themixture (additivity formula).Classification according to GHS (1272/2008/EC, CLP)Acute toxicityShall not be classified as acutely toxic.Acute toxicity of components of the mixtureName of ifluoromethyl)-3pentanoneSkin Corrosion/IrritationSerious Eye Damage/Eye IrritationRespiratory or Skin SensitisationProductGerm Cell Mutagenicity ProductCarcinogenicity ProductReproductive toxicity ProductSpecific Target Organ Toxicity Single Exposure ProductSpecific Target Organ Toxicity Repeated Exposure ProductAspiration Hazard ProductCAS No756-13-8Exposure routeOralEndpointLD50Value 2,000 mg/kgSpeciesrat756-13-8DermalLD50 2,000 mg/kgratShall not be classified as corrosive/irritant to skin.Shall not be classified as seriously damaging to the eye or eye irritant.Shall not be classified as a respiratory or skin sensitiser.Shall not be classified as germ cell mutagenic.Shall not be classified as carcinogenic.Shall not be classified as a reproductive toxicant.Shall not be classified as a specific target organ toxicant (single exposure).Shall not be classified as a specific target organ toxicant (repeated exposure).Shall not be classified as presenting an aspiration hazard.SECTION 12: Ecological Information12.1 ToxicityAcute toxicity (acute)Test data are not available for the complete mixture.Aquatic toxicity (acute) of components of the mixtureAquatic toxicity (acute) of components of the mixtureGastec-Vesta srl Via Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932821 Fax 39.02.93282342nfo@gastecvesta.com www.gastecvesta.comMedicAir Industry S.r.l. - Via T. Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932281 Fax 39.02.93282342industry.info@medicair.it - www.medicairindustry.comIn caso di emergenza: 39 02.932821 (ore ufficio)In caso di emergenza: 39 02.932821 (ore ufficio)

SAFETY DATA SHEET:NOVEC 1230 pressurized with NitrogenName of ifluoromethyl)-3pentanonePageRevision n.DatePrevious8 di 13207/01/202004/04/2018SDS reference--CAS No756-13-8EndpointLC50Value 1,070mg/lSpeciesfathead minnow(Pimephales promelas)Exposure time96 hours756-13-8EC50 1,080mg/ldaphnia magna48 hoursAcute toxicity (chronic)Harmful to aquatic life with long lasting effects.Test data are not available for the complete mixture12.2 Persistence and Degradability ProductDegradability of components of the mixtureDegradability of components of the mixtureName of ethyl)-3pentanoneCAS No756-13-8Processcarbon dioxide generationBiodegradationDegradation rate1.8 - 3.4 %Time28 dThe relevant substances of the mixture are readily biodegradablePersistenceData are not available.12.3 Bioaccumulative Potential ProductData are not available.Bioaccumulative potential of components of the mixtureDegradability of components of the mixtureName of ethyl)-3pentanoneCAS No756-13-8BCF4.8Log KOW3.0812.4 Mobility in Soil ProductData are not available.12.5 Results of PBT and vPvB assessment ProductThis mixture does not contain any substances that are assessed to be a PBTor a vPvB.Gastec-Vesta srl Via Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932821 Fax 39.02.93282342nfo@gastecvesta.com www.gastecvesta.comMedicAir Industry S.r.l. - Via T. Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932281 Fax 39.02.93282342industry.info@medicair.it - www.medicairindustry.comIn caso di emergenza: 39 02.932821 (ore ufficio)In caso di emergenza: 39 02.932821 (ore ufficio)

SAFETY DATA SHEET:NOVEC 1230 pressurized with NitrogenPageRevision n.DatePrevious9 di 13207/01/202004/04/2018SDS reference--12.6 Other Adverse EffectsGlobal warming potential 1Endocrine disrupting potentialRemarksNone of the ingredients are listed.Water hazard class - WHC (Wassergefährdungsklasse): 1 (Slightly hazardousto water)SECTION 13: Disposal Considerations13.1 Waste treatment methodsGeneral informationThis material and its container must be disposed of as hazardous waste.Dispose of contents/container to an authorized waste treatment facility.Sewage disposal-relevant informationDo not empty into drainsWaste treatment of containers/packaging It is a dangerous waste; only packaging which are approved (e.g. acc. to ADR)may be used.Handle contaminated packages in the same way as the substance itself.RemarksPlease consider the relevant national or regional provisions.SECTION 14: Transport Information98-0212-3203-2International RegulationsADR14.1 UN Number14.2 UN Proper Shipping Name14.3 Transport Hazard Class (es)ClassLabel(s)Hazard No. (ADR)Tunnel restriction codeEmergency Action Code14.4 Packing Group14.5 Environmental hazards14.6 Special precautions for userRID14.1 UN NumberNot dangerous for transport purposes according to the criteria and inaccordance with current legislation.Novec 1230, is not regulated by the ADR.If pressurized with Nitrogen gas it is regulated by the ADR and theclassification is as follows:NUMBER: UN 3164 - CLASS 2.2 AObjects under pneumatic pressure (Novec 1230 extinguishing - FK5-1-12)Charged with compressed nitrogenNOVEC 1230 pressurized with nitrogen22.220(E)2Tnot applicable-Novec 1230, is not regulated by the ADR.If pressurized with Nitrogen gas it is regulated by the ADR and theclassification is as follows:NUMBER: UN 3164 - CLASS 2.2 AObjects under pneumatic pressure (Novec 1230 extinguishing - FK5-1-12)Charged with compressed nitrogenGastec-Vesta srl Via Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932821 Fax 39.02.93282342nfo@gastecvesta.com www.gastecvesta.comMedicAir Industry S.r.l. - Via T. Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932281 Fax 39.02.93282342industry.info@medicair.it - www.medicairindustry.comIn caso di emergenza: 39 02.932821 (ore ufficio)In caso di emergenza: 39 02.932821 (ore ufficio)

SAFETY DATA SHEET:NOVEC 1230 pressurized with Nitrogen14.2 UN Proper Shipping Name14.3 Transport Hazard Class (es)ClassLabel(s)Hazard No. (ADR)Tunnel restriction codeEmergency Action Code14.4 Packing Group14.5 Environmental hazards14.6 Special precautions for userIMDG14.1 UN Number14.2 UN Proper Shipping Name14.3 Transport Hazard Class (es)ClassLabel(s)Hazard No. (ADR)Tunnel restriction codeEmergency Action Code14.4 Packing Group14.5 Environmental hazards14.6 Special precautions for userPageRevision n.DatePrevious10 di 13207/01/202004/04/2018SDS reference--NOVEC 1230 pressurized with nitrogen22.220(E)2Tnot applicable-Novec 1230, is not regulated by the ADR.If pressurized with Nitrogen gas it is regulated by the ADR and theclassification is as follows:NUMBER: UN 3164 - CLASS 2.2 AObjects under pneumatic pressure (Novec 1230 extinguishing - FK5-1-12)Charged with compressed nitrogenNOVEC 1230 pressurized with nitrogen22.220(E)2Tnot applicable-IATA14.1 UN NumberNovec 1230, is not regulated by the ADR.If pressurized with Nitrogen gas it is regulated by the ADR and theclassification is as follows:NUMBER: UN 3164 - CLASS 2.2 AObjects under pneumatic pressure (Novec 1230 extinguishing - FK5-1-12)Charged with compressed nitrogen14.2 UN Proper Shipping Name14.3 Transport Hazard Class (es)ClassLabel(s)Hazard No. (ADR)Tunnel restriction codeEmergency Action CodeNOVEC 1230 pressurized with nitrogen22.220(E)2TGastec-Vesta srl Via Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932821 Fax 39.02.93282342nfo@gastecvesta.com www.gastecvesta.comMedicAir Industry S.r.l. - Via T. Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932281 Fax 39.02.93282342industry.info@medicair.it - www.medicairindustry.comIn caso di emergenza: 39 02.932821 (ore ufficio)In caso di emergenza: 39 02.932821 (ore ufficio)

SAFETY DATA SHEET:NOVEC 1230 pressurized with Nitrogen14.4 Packing Group14.5 Environmental hazards14.6 Special precautions for userPageRevision n.DatePrevious11 di 13207/01/202004/04/2018SDS reference--not applicable-14.7 Transport in bulk according to Annex II of MARPOL73/78 and the IBC Codenot applicableAdditional identificationAvoid transport on vehicles where the load space is not separated fromthe driver's compartment. Ensure vehicle driver is aware of the potentialhazards of the load and knows what to do in the event of an accident oran emergency. Before transporting product containers ensure that theyare firmly secured. Ensure that the container valve is closed and notleaking. Container valve guards or caps should be in place. Ensureadequate air ventilation.SECTION 15: Regulatory information15.1 Safety, health and environmental regulations/legislation specific for the substance or mixtureRelevant provisions of the European Union (EU)Restrictions according to REACH, Annex XVIInone of the ingredients are listed.List of substances subject to authorisation (REACH, Annex XIV)none of the ingredients are listedDirective 2011/65/EU on the restriction of the use of certain hazardous substances in electrical and electronic equipment(RoHS) - Annex IInone of the ingredients are listedRegulation 166/2006/EC concerning the establishment of a European Pollutant Release and Transfer Register (PRTR)none of the ingredients are listedDirective 2000/60/EC establishing a framework for Community action in the field of water policy (WFD)none of the ingredients are listedExplosives precursors which are subject to restrictionsnone of the ingredients are listedSECTION 16: Other InformationAbbreviations and acronymsAbbr.ADNADRAquaticChronicDescriptions of used abbreviationsAccord européen relatif au transport international des marchandises dangereuses par voies de navigation intérieures(European Agreement concerning the International Carriage of Dangerous Goods by InlandWaterways)Accord européen relatif au transport international des marchandises dangereuses par route (EuropeanAgreement concerning the International Carriage of Dangerous Goods by Road)hazardous to the aquatic environment - chronic hazardGastec-Vesta srl Via Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932821 Fax 39.02.93282342nfo@gastecvesta.com www.gastecvesta.comMedicAir Industry S.r.l. - Via T. Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932281 Fax 39.02.93282342industry.info@medicair.it - www.medicairindustry.comIn caso di emergenza: 39 02.932821 (ore ufficio)In caso di emergenza: 39 02.932821 (ore ufficio)

SAFETY DATA SHEET:NOVEC 1230 pressurized with NitrogenPageRevision n.DatePrevious12 di 13207/01/202004/04/2018SDS reference--BCFCASCLPDGRDNELEC NoEmSGHSBioConcentration FactorChemical Abstracts Service (service that maintains the most comprehensive list of chemical substances)Regulation (EC) No 1272/2008 on classification, labelling and packaging of substances and mixturesDangerDerived No-Effect LevelThe EC Inventory (EINECS, ELINCS and the NLP-list) is the source for the seven-digit EC number, an identifierEmergency Schedule"Globally Harmonized System of Classification and Labelling of Chemicals" developed by the United NationsIATAIATA/DGRICAOIMDGindex NoInternational Air Transport AssociationDangerous Goods Regulations (DGR) for the air transport (IATA)International Civil Aviation OrganizationInternational Maritime Dangerous Goods Codethe Index number is the identification code given to the substance in Part 3 of Annex VI to Regulation(EC) No 1272/2008log KOWMARPOLPBTPNECPress. GasREACHRIDn-octanol/waterInternational Convention for the Prevention of Pollution from Ships (abbr. of "Marine Pollutant)Persistent, Bioaccumulative and ToxicPredicted No-Effect Concentrationgas under pressureRegistration, Evaluation, Authorisation and Restriction of ChemicalsRèglement concernant le transport International ferroviaire des marchandises Dangereuses (Regulationsconcerning the International carriage of Dangerous goods by Rail)very Persistent and very BioaccumulativevPvBKey literature references and sources for dataRegulation (EC) No 1272/2008 on classification, labelling and packaging ofsubstances and mixtures.Regulation (EC) No. 1907/2006 (REACH), amended by 2015/830/EU.Transport of dangerous goods by road, rail and inland waterway(ADR/RID/ADN).International Maritime Dangerous Goods Code (IMDG).Dangerous Goods Regulations (DGR) for the air transport (IATA).Classification procedurePhysical and chemical properties.Health hazards.Environmental hazards.The method for classification of the mixture is based on ingredients of themixture (additivity formula).List of relevant phrases (code and full text as stated in chapter 2 and 3)CodeH280Textcontains gas under pressure; may explode if heatedGastec-Vesta srl Via Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932821 Fax 39.02.93282342nfo@gastecvesta.com www.gastecvesta.comMedicAir Industry S.r.l. - Via T. Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932281 Fax 39.02.93282342industry.info@medicair.it - www.medicairindustry.comIn caso di emergenza: 39 02.932821 (ore ufficio)In caso di emergenza: 39 02.932821 (ore ufficio)

SAFETY DATA SHEET:H412DisclaimerNOVEC 1230 pressurized with NitrogenPageRevision n.DatePrevious13 di 13207/01/202004/04/2018SDS reference--harmful to aquatic life with long lasting effectsThis information is based upon the present state of our knowledge.This SDS has been compiled and is solely intended for this product.End of documentGastec-Vesta srl Via Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932821 Fax 39.02.93282342nfo@gastecvesta.com www.gastecvesta.comMedicAir Industry S.r.l. - Via T. Tasso, 29 - 20010 Pogliano Milanese (MI)Tel. 39.02.932281 Fax 39.02.93282342industry.info@medicair.it - www.medicairindustry.comIn caso di emergenza: 39 02.932821 (ore ufficio)In caso di emergenza: 39 02.932821 (ore ufficio)

756-13-8 PNEC 1 mg/l sewage treatment plant (STP) chronic local effects 1,1,1,2,2,4,5,5,5- nonafluoro-4-(tri fluoromethyl)-3- pentanone 756-13-8 PNEC 0.006 mg/kg freshwater sediment chronic systemic effects 1,1,1,2,2,4,5,5,5- nonafluoro-4-(tri fluoromethyl)-3- pentanone 756-13

Related Documents:

The Janus Fire Systems Mv Series Clean Agent Fire Suppression System utilizes 3M Novec 1230 Fire Protection Fluid as the extinguishing medium. Novec 1230 fluid is a clear, colorless and low odor liquid perfectly suited to protect high value assets in areas that may be normally occupied,

2-methylpentan-3-one known as SEVO 1230 Fire Protection Fluid (also known as FK-5-1-12, 3M NOVEC 1230 Fire Protection Fluid, C 6-F-ketone) produced by 3M . 2.2 DESCRIPTION NOVEC 1230 Acute Exposure LC50 (4 is a colorless fluid. It is stored a

3M Novec 1230 Fire Protection Fluid is an advanced, "next generation" clean agent halon and CO 2 replacement, suitable for use in a wide range of offshore and land-based oil and gas operations to protect occupied spaces and critical equipment. Based on a patented chemistry from 3M, Novec 1230 fluid offers a number of important

The 3M Novec fluids, designed as alternatives to PFCs and having sharply lower GWP, include a range of HFE liquids with GWP 60-300 and FK liquids, Novec 649 and 774, with GWP 1. . class: the FK Novec 774 and the HFE Novec 7200. Even the PFC class contains liquids that are somewhat superior to C6F14, e.g.3M FC -84 (C7F16) which has a bit lower .

3M Novec 1230 Fire Protec on Fluid 3M Novec 1230 Fire Protec on Fluid is based on sustainable technology, designed to balance industry concerns for human safety, performance, and the environment. This unique agent is an advanced replacement for halon and fi rst genera on halo

Refer also to 3M Novec 1230 Fire Protection Fluid Storage and Handling document 60-5002-0131-8. The filling station or pump designated for use with

The Janus Fire Systems Lv 500 Series Clean Agent Fire Suppression System utilizes 3M Novec 1230 Fire Protection Fluid as the extinguishing medium. Novec 1230 fluid is a clear, color-less and low odor liquid perfectly suited to protect high value assets in areas that may be normally

The Janus Fire Systems Lv Series Clean Agent Fire Suppression System utilizes 3M Novec 1230 Fire Protection Fluid as the extinguishing medium. Novec 1230 fluid is a clear, colorless and . low odor liquid perfectly suited to protect high value assets in areas that may be normally occupied,