E110 FIREYE FLAME-MONITOR - Westmill Industries

2y ago
5 Views
3 Downloads
772.88 KB
48 Pages
Last View : 2m ago
Last Download : 3m ago
Upload by : Gia Hauser
Transcription

E-1101NOVEMBER 2000E110 FIREYEFLAME-MONITOR BURNER MANAGEMENT CONTROLFOR USE WITH THEMICROPROCESSOR-BASEDEP AND EPD STYLEPROGRAMMER MODULES UL E110 with ED510 Display ModuleLISTEDAPPROVEDYear 2000 Compliant in accordance with BSI document DISC PD200-I:1998DESCRIPTIONThe Fireye E110 FLAME-MONITOR System is a microprocessor based burner managementcontrol system designed to provide the proper burner sequencing, ignition and flame monitoring protection on automatically ignited oil, gas, and combination fuel burners. In conjunction with limit andoperating controls, it programs the burner/blower motor, ignition and fuel valves to provide forproper and safe burner operation. The control also provides current operating status and lockoutinformation in the event of a safety shutdown. The manner in which this information is displayed isdependent on the type of programmer (EP or EPD) and display module (ED510 or ED500).* Referto Flame-Monitor PROGRAMMER SELECTION later in this document for the various combinations of programmer and display modules.The E110 consists of the EB700 chassis, dust cover, and shortened mounting screw (P/N 48-1836).The display module (ED510 or ED500), if required, must be ordered separately. Interchangeableprogrammer and flame amplifier modules allow for complete versatility in selection of control function, timing, and flame scanning means. Functions such as pre-purge, recycling interlocks, high fireproving interlock, and trial for ignition timing of the pilot and main flame are determined by the programmer module. The E110 Flame-Monitor can be used with ultra-violet, autocheck infrared, photocell, flame rod, or self-check ultraviolet flame scanners by choosing the proper amplifier module.The eighteen (18) terminal wiring base allows for many functional circuits including motors, valves,and ignition transformers as well as multiple interlocks such as high purge, low purge, fuel valve andrunning interlock circuits. The E110 uses the same wiring base as the Fireye E100 Flame-Monitorcontrol, D Series and C Series Controls and is directly interchangeable with most models withoutrewiring.Additional functions of the Flame-Monitor system include: *A non-volatile memory which allows the control to remember its history and present positioneven when power is interrupted.A constant flame signal read-out via display module or 0-10 VDC output (EPD programmersonly).Read-out of main fuel operational hours and complete cycles via display module.Modbus communications via RS485 multi-drop link.The ED500 display was the predecessor of the ED510 display and uses an older design. It does not have the latest featuresof the ED510 display module.1

Dipswitches located on the EP programmer to allow selectable purge time.A run/check switch which allows the operator to stop the program sequence in any of three different positions (Purge, PTFI, or Auto).Remote Display Capability.CAUTION: While programmers are mechanically interchangeable in that they mate with acommon wiring base, you should select the correct model for your application. Inappropriateapplication of a control could result in an unsafe condition hazardous to life and property.Selection of a control for a particular application should be made by a competent professional, such as a boiler/burner service technician licensed by a state or other governmentagency.FLAME-MONITOR SPECIFICATIONSSupply Voltage: 120 VAC ( 10%, -15%) 50/60 HzPower Consumption: 25 VAShipping Weight: (E110 Approx.) 5 lbs. (2.3kg)Operating Temperature Limits:With ED500 Display: - 40 F Minimum, 125 F Maximum- 40 C Minimum, 52 C MaximumWith ED510 Display: 32 F minimum, 125 F Maximum0 C Minimum, 52 C MaximumHumidity: 85% R.H. Maximum (Non-condensing)AMBIENT TEMPERATURE LIMITSMAXIMUM2MINIMUMCONTROL140 F60 C- 40 F- 40 CScanner UV1A, UV2,UV8A, 45UV3200 F93 C- 40 F- 40 C45UV5-1007, 45UV51009200 F93 C- 40 F- 40 CPhotocell 45CM1165 F74 C- 40 F- 40 CFlame Rod(Tip 2460 F)1500 F816 C- 40 F- 40 C48PT2125 F52 C- 40 F- 40 C

LOAD RATINGSTERMINALTYPICAL LOADA. Maximum Rating @120V-50/60HzB.Alternate Rating @120-50/60Hz5, 6 Individually orCombinedPilot Valve(s) and Ignition Transformer(s)50VA Pilot Duty (Solenoid Valves)plus 500VA (Transformer)125VA Pilot Duty Solenoid Valves plus250VA (Transformer)7Main Fuel Valve(s)250VA Pilot Duty (Solenoid Valve)1250 VA Opening 500 VA Holding(Motorized Valve) plus 65 VA Pilot Duty(Solenoid Valve)MBurner/Blower Motor9.8 F.L.A. * 58.8 L.R.A.240 VA Pilot Duty (Motor Starter Coil)10-11-12-XModulatorAAlarm125 Pilot Duty50 VA Pilot DutyTerminal ratings may be selected from either column A or B: (select the rating from the column for each terminal which best applies tothe connected load on that terminal).* F.L.A. full load amps L.R.A. locked rotor ampsMaximum Simultaneous Connected Load: 2000 VAELECTRICAL RATINGSVA ratings (not specified as pilot duty) permit the connection of transformers and similar deviceswhose inrush current is approximately the same as their running current.VA Pilot Duty ratings permit the connection of relays, solenoid valves, lamps, etc. whose total operating load does not exceed the published rating and whose total inrush current does not exceed 10times the rating.Running and locked rotor ratings are intended for motors. VA and VA Pilot Duty loads may beadded to a motor load provided the total load does not exceed the published rating.WARNING: This equipment is a Class B digital apparatus which complies with the RadioInterference Regulations, CRC c.1374.CAUTION: Published load ratings assume that no contact be required to handle inrush current more often than once in 15 seconds. The use of control switches, solenoid, relays, etc.which chatter will lead to premature failure. It is important to run through a test operation(with fuel shut off) following the tripping of a circuit breaker, a blown fuse, or any knowninstance of chattering of any external current consuming devices.APPROVALSUnderwriters Laboratories Inc.: Listed Guide MCCZ File MP1537Canadian Standards Association: File #LR7989Acceptable by: Industrial Risk Insurers (I.R.I.)Factory Mutual ApprovedYear 2000 Compliant in accordance with BSI document DISC PD2000-I:1998WARNING: This equipment generates and can radiate radio frequency energy, and if notinstalled and used in accordance with the instruction manual may cause interference to radiocommunications. It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment.Operation of this equipment in a residential area is likely to cause interference in which casethe user, at his own expense, will be required to take whatever measures which may berequired to correct the interference.3

FLAME AMPLIFIER SELECTIONFIREYE P/NDESCRIPTIONUSE WITH SCANNEREUV1Standard UV AmplifierUV1A, UV8A 45UV3, UV2E1R1Autocheck Infrared Amplifier48PT2E1R2Autocheck Infrared Amplifier (For special applications high sensitivity—consult factory)48PT2E1R3Autocheck Infrared Amplifier. (Without oil fog rejectionspray circuitry.)48PT2ERT1Rectification Amplifier45CM1, 69ND1EUVS4Self-Check UV Amplifier45UV5-1007/1008/1009SCANNER SELECTIONFIREYE P/NDESCRIPTIONUSE 8PT2-9007Infrared 1/2" straight mount 96" cableInfrared 1/2" 90 angle mount 96" cableInfrared 1/2" straight mount 48" cableInfrared 1/2" 90 angle mount 48" cableE1R1, E1R2,or E1R3SC-103UV1A3UV1A6UV8AUV245UV3-1050UV 1/2" straight 36" flex conduitUV 1/2" straight 72" flex conduitUV 1/2" 90 head 72" unshielded leadsUV 3/8" straight 36" flex conduitUV 3/4" cast aluminum housing 8' ND1-1000K669ND1-1000K8Photocell Scanner with filterPhotocell Scanner without filterFlame rod 12", 1/2" N.P.T. mountFlame rod 18", 1/2" N.P.T. mountFlame rod 24", 1/2" N.P.T. check UV 1" British thread mounts, 230VSelf-check UV 1" British thread mounts, 120VSelf-check UV 1" N.P.T. threads, 120VEUVS4SC-101FIREYE FLAME-MONITOR Selection Guide1.2.Non-Recycle OperationSELECT CHASSISE110 FLAME-MONITORSELECT PROGRAMMEREP Programmers provide selectable operation (e.g. extended purge time)EPD programmers have integral LED indicator displayRecycle EPD160EP260EPD26010 and 15 sec. TFIEP380EPD38030 sec. purgeEP161EPD161EP261EPD261Extended MTFIEP381EPD38115 sec. purgeEP165EP166EPD165EP265EPD265Pilot stabilizationPilot stabilizationEP382EPD3821 sec. purgeEP170EPD170EP270EPD270Early spark terminationEP390EP39090 sec. purgeNOTE: The EP programmers listed above are available in both Spanish and French languages.Consult factory or your local Fireye distributor for ordering information.4

3.4.SELECT DISPLAY Required for EP Programmers, Optional for EPD programmersED510 2 line x 16 character LCD display.SELECT AMPLIFIERRequires appropriate flame scanner.DescriptionUse with scannerEUV1Standard ultra-violet amplifierUV1A, UV2, UV8A, 45UV3EUVS4Self-check ultra-violet amplifier45UV5-1007, 1008, 1009E1R1Autocheck infra-red amplifier48PT2E1R2Autocheck infrared amplifier (with high sensitivity circuitry)48PT2E1R3Autocheck infrared amplifier (without oil fog rejection circuitry)48PT2ERT1Flame rectification amplifier69ND1, 45CM15.6.SELECT WIRING BASE60-1386-2Surface mount60-1466-2Panel mountSELECT ACCESSORIESFIREYE P/NDESCRIPTIONBULLETINED510Display Module (2 line x 16 characters LCD Display)ED5101129-145-1, -2, -3Remote Display Mounting Kit (for ED510) with 4’, 8’ or 2’ cable respectivelyE-8002ED500Display Module (8 character LED Display)E-8101ED400Remote display mounting kit (for ED500)E-8001ED550Remote display cables (for ED500)E-8001E300Expansion ModuleE-3001E350-3, -6Expansion Module cables in 3’ and 6’ lengthsE-3001ED150-3, -6, -15, -25Remote Reset cables in 3’, 6’, 15’ and 25’ lengthsE-8001ED600Multi-port Cable AdapterE-8001ED610Multi-port Adapter (for ED510 and RS485 communications)E-8002E500-3Communication Interface (up to 6 Flame-Monitor controls)E-5001E700Software Program to Monitor E500 Operation. IBM CompatibleE-700160-2333Noise Line FilterE-1021EC485RS232 to RS485 converter for direct connectEC-4851ED512-2, -4, -8Communications interface cables in 2’, 4’ and 8’ lengthsE-8002ED580-2, -4, -8Remote display cables in 2’, 4’ and 8’ lengthsE-80025

FLAME-MONITOR Ordering InformationE110 Flame-Monitor (One required)ED510 Display ModuleE110 consists of:EB700 ChassisEC600 Dust CoverMounting Screw (48-1836)Required with EP ProgrammersOptional with EPD ProgrammersEP programmers must have an Eng. code of 28 orlater (e.g. 9414-28). EPD Programmers must havean Eng. code of 02 or later.Amplifier ModuleE1R1E1R2E1R3EUV1EUVS4ERT1Wiring Base(One Required)(One Required)60-1386-2Surface Mount(shown)60-1466-2Cabinet MountProgrammer Module (One Required)EP P261EP265EP370EP380EP381EP382EP3906orEPD 61EPD265EPD270EPD380EPD381EPD382EPD390

FLAME 2-9000CAUTION: The UV1, UV2, UV8A and 45UV3 ultra-violet flame scanners and associatedamplifier modules are non-self checking UV systems and should be applied only to burnersthat cycle often (e.g.: a minimum of once per 12 hours) in order for the safety checking circuitto be exercised. If component checking is required during burner operation for constantlyfired burners, utilize the self-checking ultra-violet flame scanners (45UV5) with associatedamplifier module (EUVS4), or the infrared flame scanner (48PT2) with associated AutoCheck amplifier (E1R1, E1R2, E1R3).FLAME-MONITOR PROGRAMMER SELECTIONAll programmers for the Flame-Monitor Series are designated with the prefix "EP" or “EPD.” Thefunctional operation, flame failure response time, purge timings, firing rate motor circuit, trial forignition timings, recycling function and display messages are determined by the programmer.A chart of the most common programmers is found below. Refer to the appropriate product bulletinfor a detailed description of the operation of each programmer.Take note of the programming sequence chart for each programming module for the proper explanation of prepurge timings.WARNING: THE INAPPROPRIATE SELECTION OR APPLICATION OF A PROGRAMMER MODULE COULD RESULT IN AN UNSAFE CONDITION HAZARDOUS TO LIFEAND PROPERTY. The various programmer modules (EP(D)160, EP(D)260 and EP(D)380)are interchangeable because they plug into a common chassis. Changing the dipswitchesmodifies the operation of each programmer module. Care should be taken to insure theproper dipswitch settings. Refer to the appropriate programmer bulletin for dipswitch settings. Selection of the programmer module and setting the dipswitches for a particular application should be made by a competent professional, such as a Boiler/Burner technicianlicensed by a state or government agency, engineering personnel of the burner, boiler or furnace manufacturer (OEM) or in the performance of duties based on the information from theOEM.7

nHigh FirePurgeInterlock(D/8 Ckt)ProvenLow FireStartInterlock(M/D Ckt)YesIntermittent Ignition/PilotInterruptedIgnition/PilotEarly SparkTerminationPilotTrail-for-IgnitionTerm 5Term 6MainTrail-for-IgnitionTerm 5RunningInterlock(3/P CKT)Firing RateMotorCircuitTerm 62EPD/EP 1EP16130 1SupervisedYesEPD165,EP165 70EP17030 1SupervisedYesEPD260EP26030 1NoEPD261EP26130 1EPD265EP26530 1EPD270EP27030 sNoYesYes10YesYes3YesYes 4YesYes3YesYes 410—510YesYes3YesYes 4YesYes3YesYes 4Non Recycle 5NoneRecycle 5NoneRecycle 5NoneRecycle 103Intermittent10NoYes—10NoNon Recycle3010No61010NoYes1510NoNon Recycle1010No61010NoYes—10YesNon Recycle3010YesYes1010YesNon Recycle153IntermittentAll programmers have a maximum 4 second Flame Failure Response Time (FFRT) with the exception of the EP165, EP(D)166 and EP265 (2 sec. FFRT).All EPD Programmers and EP Programmers have selectable 3-P Proven Open to Start feature via dipswitch.1These programmers add a 30 second waiting period to the prepurge while the firing rate motor is driven to the low fire position.2Purge timings can be extended via dipswitches.3EP380, EP381, EP382, and EP390 have selectable intermittent or interrupted (15 sec. MTFI) operation of terminal 6 via dipswitch.4These programmers can use terminal “X” for spark termination. This requires jumpering terminals 5 and 10 on the wiring base. PTFI timing is 5 seconds on terminal “X.”5EP380, EP381, EP382, and EP390 have selectable Recycle or Non-Recycle Operation via dipswitch.6During MTFI terminal 6 is energized for 5 seconds (pilot stabilization) before energizing terminal 7 for 10 seconds for EP165 and EP265 and 15 seconds for EP(D)166 only.7EP165 will lockout on power interruption.8The EPD167 waits indefinitely for the low fire start switch (M-D) to close.PROGRAMMER AND DISPLAY MODULE COMPATIBILITYAll programmers for the Flame-Monitor Series are designated with the prefix “EP” or “EPD.” Twodisplay modules are functional with the E110 Flame-Monitor control (ED510 and ED500).TheED510 is a 2 line by 16 character LCD with keypad to provide both current and historical information pertaining to the operation of the control. Refer to Bulletin ED-5101 for a complete descriptionof the features and capabilities of the ED510 display module. The ED500 is an eight character LEDdisplay and was the predecessor to the ED510. The ED500 does not have the latest features of theED510 display module. EP style programmers with an Engineering code of 28 or later (e.g. 9414-28)are compatible with both the ED510 and ED500 display module. EP style programmers with anEngineering code before 28 are only compatible with the ED500 display. The EPD style programmers (with an Engineering code 02 or later) are compatible with the ED510 display module as well.Note: The EPD style programmers do not require a display module to function.8

For a complete system, choose one of each of the following:- Chassis- Programmer Module- Amplifier Module- Flame Detector- Wiring BaseWARNING: Installer must be trained and qualified. Follow the burner manufacturers instructions, if supplied. Otherwise, proceed as follows:INSTALLATION OF CONTROLWiring BaseMount the wiring base on the burner or on a panel. The location should be free from excessive vibration and within the specifies ambient temperature rating. The base may be mounted in any angularposition.All wiring should comply with applicable electrical codes, regulations and local ordinances. Usemoisture resistant wire suitable for at least 90 degrees C. Good electrical wiring practice should befollowed to ensure an adequate ground system. Refer to Fireye Service Note 100 separately andGeneral Grounding Rules, later in this document, for recommended grounding methodsA good ground system should be provided to minimize the effects of AC quality problems. A properly designed ground system meeting all the safety requirements will ensure that any AC voltagequality problems, such as spikes, surges and impulses have a low impedance path to ground. A lowimpedance path to ground is required to ensure that large currents involved with any surge voltageswill follow the desired path in preferences to alternative paths, where extensive damage may occur toequipment.Refer to suggested Wiring Diagram on page 30.WARNING: Controls require safety limits utilizing isolated mechanical contacts. Electroniclimit switches may cause erratic operation and should be avoided.BEFORE INSTALLING THE CONTROLCAUTION: Ensure that electric power is turned off. Refer to SN-100 for recommendedgrounding techniques.If either a ground or a short circuit is detected, it must be eliminated before the control is pluggedinto the wiring base and power turned on.Test the electrical field wiring for short circuits and grounds. The recommended method requires theuse of an ohmmeter set on its lowest resistance scale.Note: When using ultra-violet or infrared scanning, be sure to remove any jumpers on the wiringbase which ground the S2 terminal.1.2.Touch the meter probes together and calibrate accurately to ensure a reliable test.Disconnect the neutral wire (L2) from the control system at the power source. Clip one metertest lead to the grounded green terminal on the lower right side of the wiring base and with theother probe touch each other terminal. At no time should the meters show continuity or read 0ohms.9

3.Reconnect the neutral wire (L2) at the power source. Remove the test probe from the groundedterminal and reconnect it to Terminal L2 in the wiring base. With the other probe, touch eachother terminal. It is normal to obtain a resistance reading on the meter at some terminals duringthis test as there are resistive loads (coils, transformers, lamps, etc.) connected whose normalDC resistance may be less than 5 ohms. However, at no time should the test meter read zeroohms.CAUTION: Restore power for the following test.4.With Flame-Monitor removed, measure voltage from L2 to all other terminals. Reading shouldbe zero on all terminals except Ll.INSTALLING THE CONTROLCAUTION: Electric power must be turned off during installation.1.Check the electrical tabs on the bottom of the chassis—if they are bent out of position, reposition them with your fingers so that they are in line as shown here.2.Select the appropriate programmer and amplifier modules for your application. Remove the dustcover from the chassis. Insert the amplifier module into the slot marked Flame Amplifier Moduleand gently push the module into position. Insert the programmer module into the slot markedProgrammer Module and gently push the module into position. Attach the display to the program module and plug ED580-1 into RJ45 connections.Slide the slots at the bottom of the assembled control over the tabs on the wiring base. Push thecontrol into position. Insert a screwdriver through the hole in the top of the control and tightenthe retaining screw.Electric power may now be turned on.3.4.OPERATIONThe programmer module determines the functional operation of the E110 control (e.g. purge timing,trial for ignition timings, recycle or non-recycle operation, etc.). For purposes of illustration, we willbe looking at the EP160/EPD160 Programmer functions and messages associated with the ED510display module in this bulletin. Because the messages change depending upon which EP styleprogrammer is being used, it is necessary to check the bulletin covering the specific programmer for exact details. Refer to the suggestions shown in this bulletin before proceeding to power theFireye E110 Flame-Monitor system. Items such as scanner installation, short circuit tests and safetyinformation should be reviewed.10

TYPE EP(D)160DIPSWITCH SETTINGSNON-RECYCLE RUNNING INTERLOCKS (3/P) PURGE TIME - 30 SEC.*FLAME FAILURE RESPONSE TIME 4 SEC.123456INACTIVE Down Down Down DownPROGRAMMING SEQUENCELFSCLOSED(MD)HFSL1/13 CLOSEDON(D8)FIRINGPERIODL1/13OFFMTERMINALSPURGE30 SEC5POST PURGE15 SECMIN30 SECPTFI10 SECMTFI10 SECRefer to appropriate programmerbulletin for a complete descriptionof the dipswitch functions.6MTFI15 SEC7(MODULATOR MOTOR CIRCUIT)HIGH (10-X)LOW (10-12)AUTO (10-11)LOW (10-12)CAUTION: On initial power-up and on restarts following a power failure, the control willperform self-test diagnostics for 15 seconds.Start-Up (Normal Cycle)Note: For direct spark ignited oil burners, substitute the words Main-Oil Valve for Pilot Valve.1.2.3.4.5.Constant 120 VAC should be available to the Ll-L2 terminals only on the wiring base.The operating control circuits (Ll-13) will close, signaling the burner to start its firing sequence.If the fuel valve end switch (13-3) is closed, the burner/blower motor (terminal M) circuit isenergized. The running interlock (limit) circuit (3-P) will close (e.g.\ all limits, interlocks, etc.are proven).The firing rate motor (Modulator Motor) is driven toward the high purge open damper position(10-X circuit made).When the firing rate motor reaches its open damper position, the Hi Purge switch closes (D-8)and the prepurge interval of 30* seconds is initiated. The ED510 will display:PURGE0:05HIGH FIRE PURGEIf the D-8 circuit does not close, the program will hold in this position for ten minutes waiting for itto close. If it does not, the control will lockout.6.7.*When the prepurge is completed, the firing rate motor is driven toward the low purge damperposition (10-12 ckt. made). The ED510 will display:PURGE0:35LOW FIRE PURGEFollowing the minimum 30 second delay (to permit the firing rate motor to get to the low fireposition), the control will wait for the low fire switch (M-D) to close. When it closes, the trial forignition sequence will start. If after ten minutes, the M-D circuit is not closed, the control willlockout. The EPD167 will wait indefinitely for the M-D circuit to close.Prepurge timing is selectable via dipswitches.11

8.The trial for ignition period begins with Terminal 5 and 6 being energized simultaneously. Thisis known as PTFI (Pilot Trial for Ignition). The ED510 will display:PTFI0:02IGNITION TIMINGThis period is ten seconds in duration. If no flame is detected after ten seconds, the control will deenergize Terminals 5 and 6 and lockout. When flame is detected during this 10 second period, theED510 will displayPTFI20FLAME SIGNALFLAME SIGNAL0-91020-809.NOT ACCEPTABLEMINIMUM ACCEPTABLENORMALWith flame proven at the end of PTFI, the main flame trial for ignition (MTFI) period begins.Terminal 7 is energized. The ED510 will display:MTFI35FLAME SIGNALTerminal 5 is de-energized 10 seconds later and Terminal 6 is de-energized after another 5 seconds.10. The firing rate motor is now sent to the auto position (10-11 ckt made) and is under the command of the proportional controller. The ED510 will display:AUTO40FLAME SIGNALNOTE: Trial-for-Ignition timings depend on the programmer selected. The timing charts on pages 11and 4 point out the differences in the EP(D)160, EP161, EP165, and EP(D)170.Normal Shutdown1.When the operating control circuit (L1-13) opens, the main fuel valve is de-energized. The firingrate motor is driven to the low purge position (10-12 ckt mode).2. Following a 15 second post purge, the burner/blower motor is de-energized.3. The burner is now off and the ED510 will displaySTANDBYL1-13 OPENBurner history can be displayed by using ED510 keypad. See bulletin E-5101.BACKLIT DISPLAYThe ED510 display has a two (2) line by sixteen (16) character backlit LCD display. The backlitfunction is energized when power is applied to the FLAME MONITOR.Contrast Control: The contrast for the LCD display is factory set. If the contrast must be adjustedfor any reason (e.g.: remote mounting), a potentiometer is provided on the back of the ED510 displayboard. Refer to bulletin ED-5101 for detailed information.LOCKOUTSWhen a safety shutdown occurs, the control will display a message indicating LOCKOUT and thereason for the lockout. The alarm circuit (Terminal “A”) will be energized. The non-volatile memorywill remember the status of the control even if a power failure occurs. By momentarily depressing12

the reset button on the display, the control can be reset. The button must be held down for one secondand then released. Very little force is required to do this. Do not press hard.Safety Shutdown1.If the running interlock circuit does not close, the control will lockout and the blower motor willbe de-energized. If the interlock circuit opens during a start-up or firing period, all fuel valveswill be de-energized and the control will lockout.2. If the proven high fire circuit (D-8) has not closed after a ten (10) minute “Hold” period at thestart of prepurge, the control will lockout.3. If the low fire start circuit (M-D) has not closed after a ten (10) minute “Hold” period at the endof prepurge, the control will lockout.4. If dipswitch 6 is in the “Up” position (3-P prove open to start-enabled), and the 3-P circuit isclosed at the start of the operating cycle, the control will hold for one (1) minute waiting for the3-P circuit to open. If, after one (1) minute, the 3-P circuit does not open, the control will lockout.5. If pilot flame is not detected during the 10 second trial for ignition period, the pilot valve andignition transformer will be de-energized and the control will lockout on safety.6. If main flame is not detected at the end of the main flame trial for ignition period, all fuel valveswill be de-energized and the control will lockout on safety.7. If the main flame fails during a firing cycle, all fuel valves will be de-energized within 4 secondsmaximum, after loss of flame signal and the control will lockout on safety.8. The EP165and EP(D)166 programmers will lockout on a power interruption.9. If flame is detected when the operating control (L1-13) is open, the control will wait sixty (60)seconds and then lockout if flame is still present. If the operating control closes and flame isdetected during purge, the blower motor (term M) remains energized and the purge sequence isput on hold. If the flame signal goes away within sixty (60) seconds, the control will proceedwith a normal start-up. If flame signal is still present after sixty (60) seconds, the control willlockout.NOTE: Manual Reset is required following any safety shutdown.NOTE: Depressing and releasing the reset button during a cycle will cause the control to shut theburner down and recycle.DESCRIPTION OF FUNCTIONS OF OPERATING CONTROLS1.2.Operating Controls: Generally pressure or temperature activated, the operating control closes,causing the burner start-up sequence to begin. When the operating control opens, the burnershuts off. The operating control is connected in the L1-13 circuit on the wiring base.Limit Switches: These are generally pressure, water level or temperature activateda. Recycle —when it is desired to stop the burner when the limit switch opens and restart itwhen the limit switch reclosed, they are connected between Terminals L1 and 13.b. Non-Recycle —when it is necessary to stop the burner when the limit switch opens andprevent it from starting until both the limit switch recloses and the manual reset is activated,they are connected between terminals 3 and P.*3.*Fuel Valve End Switch Interlock: This is generally an integral switch mounted on the mainfuel valve and activated by the valve stem. It is connected between Terminal 3 & 13. The fuelvalve end switch interlock prevents a burner start-up if the valve stem is not in the “valveclosed” position.Refer to programmer selection on page 8 to determine which programmers offer non-recycle operation of the running interlock circuit (ckt. 3-P).13

4.5.6.14Purge Interlock: Generally a firing rate motor linkage position switch or a differential air-pressure switch, that proves a maximum purge air flow rate. It is connected between Terminals D and8. The purge interlock proves that the purge air flow rate is at maximum during the purge.Running Interlocks: These generally are air flow switches, high and low fuel pressure switches,oil temperature switches, atomizing media pressure switches, and excess smoke density controls.These interlocks prove proper conditions for normal operation of the burner. They are wired inseries and connected between Terminals 3 and P.Low Fire Start Interlock: Generally a firing rate motor linkage position switch or a damperposition switch,

The Fireye E110 FLAME-MONITOR System is a microprocessor based burner management control system designed to provide the proper burner sequencing, ignition and flame monitoring pro-tection on automatically ignited oil, gas, an

Related Documents:

ment controls. The application of these scanners to other than Fireye equipment should be reviewed for approval by Fireye. APPLICATION REFERENCE UV1A, UV2, UV8A, 45UV2, 45UV3 and UV90 can be used only with the following FIREYE flame safeguard controls. FIREYE FLAME-MONITOR MB-2

Boiler Feed Water Heat Exchanger Dearator Feed Water (Tube-Side) DGA Steam Condensate (Shell-Side) Steam Condensate Tanks D-102 A/B To Dearators D-103 A/B/C E110 -A 10 - B E110 -C E110 -D E110 -E E110 - F DGA Steam Condensate (Shell-Side) Condensate Stripper Reboiler Type: Shell & Tube

The Fireye 65UV5 flame scanner is a microprocessor-based flame scanner utilizing an ultraviolet tube-type sensor and an electro-mechanical self-checking shutter mechanism. The Fireye 65UV5 flame scanner incorporates an internal flame relay with a fixed ON/OFF threshold thereby eliminat-ing the need for an external flame amplifier.File Size: 722KB

Persons not familiar with Fireye products should contact the nearest Fireye representative or other qualified service group. The UV1AL, UV5, and UV90L, as well as all other Fireye scanners, are designed to be used exclusively with the appropriate Fireye

of the information in this manual, do not continue. Contact your Fireye sales office or Fireye. WARNING: - All installation, service and troubleshooting of Fireye products must be per-formed by a qualified technician! The Fireye rotary actuator is a keypad programmable, direct coupled, modulating motor for use in burner and valve control systems.

Fireye Discrete Flame Scanners 125.00 273 Fireye Integrated Flame Scanners with Internal Flame Relay 1917.00 272 Honeywell R78 Series Flame Signal Amplifiers 269.26 266 Honeywell Flame Detectors 126.75 268 Honeywell IRIS Industrial Flame Detectors 1560.65 276 Kromschroder UVS10D2

Fireye flame safeguard control. There is no polarity associated with the wire colors. Either wire (red or black) can be wired to either terminal (S1 or S2). . This test assures that the flame detector will not detect a pilot flame too small to reliably light off the main flame. The test should be made on every new installation, and following .File Size: 634KB

the youth volunteers who participate in the annual Diocesan Pilgrimage to Lourdes. I have been very impressed with their energy, good humour and spirit of service towards those on the pilgrimage who have serious health issues. The young, gathered from around the diocese show a great sense of caring and goodwill to those entrusted to their care over the days of the pilgrimage. Young people have .