Surge Protector Per Phase Surge Current Capacities

2y ago
3 Views
3 Downloads
1.08 MB
16 Pages
Last View : 1m ago
Last Download : 3m ago
Upload by : Rosa Marty
Transcription

Surge Protective Devices (SPD)SPEEDFAXTM 2017Section contentsScan to connectonline to themost up-todate version ofthis Section ofSPEEDFAX.Siemens TPS3 family of hardwired Surge Protective Devices(formally known as Surge/Lightning Arrestors and/orTransient Voltage Surge Suppressors –TVSS)Family SPDs10-210-3SOLID ProtectionFirst Surge10-4 – 10-5TPS3 01 and TPS3 L1 (10 Mode)10-6TPS3 02 and TPS3 L2 (10 Mode)10-7TPS3 0310-8TPS3 03 DC10-9TPS3 05 and TPS3 L5 (10 Mode)10-10TPS3 06 and TPS3 L6 (10 Mode)10-11TPS3 0910-12TPS3 1110-13TPS3 12 and TPS3 L12 (10 mode)10-14TPS3 15 and TPS3 L15 (10 mode)10-15Frequently Asked Questions10-16Integrally Mounted SPDsResidential SPDsExternal or Wall Mounted SPDsSee pages 1-45 – 1-47FeaturesPer Phase Surge Current Capacityof 40, 50, 60, 100 or 140 kAn Complete Service Protection for- Power- Telephone- Coaxn Ground Reference Monitoring(GRM) diagnosticsnSiemens Industry, Inc. SPEEDFAX 2017 Product Catalog10-1SPDFeaturesPer Phase Surge Current Capacityranging from 50 kA to 1000 kAn Industry best VPRsn I 20 kA (most models)nn Across the board UL 96A compliance(most models)n Ground Reference Monitoring(GRM) diagnostics(excluding TPS3 03 & TPS3 09)n10Featuresn Per Phase Surge Current Capacityranging from 100 kA to 1000 kAn Industry best VPRsn I 20 kA (most models)nn Across the board UL 96A compliance(most models)n Ground Reference Monitoring(GRM) diagnostics

SPD - Surge Protective DevicesSiemens Surge Protection InnovationsIntroductionIn today’s electronic world, home andbusiness electrical systems just aren’tcomplete unless they incorporate surgeprotection. Stopping Surges BeforeThey Get Into these systems is bestaccomplished through the installationof appropriately sized hard-wired surgeprotective devices (SPDs) beginning atthe incoming service followed by installations at other key surge entry points.When Siemens first developed theTransient Protection System (TPS) familyof surge protectors, we knew early onthat hard-wired surge protectors neededfully coordinated safety controls. Thisled to the adoption of a number of SPDindustry safety control firsts includingthe patented Ceramgard and TranSafecircuitry, coordinated fusing and thermalcutouts, dielectric isolation, mechanicalre-enforcing taping, etc resulting in adesign that ensures the highest possibleelectrical system surge protection andreliability.Our next generation UL 1449 4th EditionTPS3 SPDs carry on this same legacy.Every TPS3 is infused with Siemensengineering safety and performance“know-how.” Siemens SPDs have thehighest degree of safety while deliveringthe industry’s best performance ratings– some of the lowest Voltage ProtectionRatings (VPRs), Type 1 or 2 and 20 kAI-nominal ratings (for most models)with surge current ratings from 50 to1000 kA.Electrical disturbances will always occur,but they don’t have to cause surge protectors to fail in an unsafe manner. Safersurge protection means uncompromisedelectrical system protection, safety,and reliability.The following pages provide additionaltechnical and ordering informationconcerning our TPS3 family of SurgeProtective Devices (SPDs).Surge Protector Per Phase Surge Current CapacitiesWall Mounted Standard ModePer PhaseSurgeCurrentTPS3 01TPS3 02TPS3 03TPS3 03 DCTPS3 05TPS3 06TPS3 L5TPS3 L6TPS3 09TPS3 11TPS3 12TPS3 15TPS3L 12TPS3L 1550 kA100 kA150 kA200 kA250 kA300 kA400 kA500 kA600 kA800 kA1000 kA10 Mode SPDsSPD10Per PhaseSurgeCurrentTSP3 L1TPS3 L2100 kA150 kA300 kA450 kA500 kA600 kA900 kA10-2Siemens Industry, Inc. SPEEDFAX 2017 Product Catalog

SPD - Surge Protective DevicesRecommending Surge ProtectionSOLID ProtectionEither at home or in the work place,nearly every electrical load is electronicinfused. With today’s power qualitybeing the same as it was 50 years ago,equipment is more susceptible to surgedamage and/or disruption generatedby normal electrical distributioninteractions. Places where lightningactivity is minimal are now experiencingmore electronic failures due to surgesgenerated by the day to day operationsof equipment like washers and dryers,copiers, chillers, etc.In response to this susceptibility, codeauthorities have mandated emergencypower distribution equipment nowmust be protected by a listed SPD.The reasoning is based upon anecdotalunderstating that surge protectedsystems are more reliable. Supported rTPS31110ServiceEntranceOutside loadslike ParkingLot LightingpoweredfromdistributionpanelsLower voltagedistributionpanelspoweringcomputersand otherelectronicsSurge Arrestor ReplacementLow-voltage surge and lightningarrestors became obsolete whenUL 1449 3rd edition went intoeffect in 2009.TPS3 03Type 1 SPDwith In 20 kAgovernment studies, the most efficientway to protect electrical systems fromsurges is through the installation ofhardwired SPDs at key points throughoutthe distribution system. These locationscan easily be remembered by memorizingthe locations of the acrostic found withinthe following phrase, “The best surgeprotected system is a SOLID one,” whereeach letter of the word SOLID stand forthe locations on the electrical systemwhere SPDs should be installed.They were replaced with Type1 SPDs having an I-nominal (In)rating equal to 20 kA. Most allSiemens TPS3s are rated asType 1, In 20 kA SPDs. However,the style and form factor of traditional surge arrestors is bestreplaced using our TPS3 03.IThe illustration to the right shows“SOLID” locations for a school’s electricalsystem. Under each ‘SOLID’ location is aSiemens TPS3 model number with surgecurrent capacities matching those to whatare typically specified by consultantsacross North America.DTPS31110orTPS30910TPS30350orCall TPS GroupIndividualcriticalequipmentlike serversData,telephone,and coaxialcablesDiscrete or True 10 Mode Style OVs Parallel MOVsFor mission critical or high profile applications,a growing number of end users prefer the assurance discrete or true 10-mode SPDs provide.When surges traverse the electrical systemvia phase to phase conductors, standard SPDsindirectly protect via the line to neutral or line toground modes of protection. Siemens integralor wall mounted “Discrete” or “True” 10-modeSPDs address L-L surges by incorporatingdirectly connected line to line surge protectionelements. This style of SPD provides the “Justin Case” assurance mission critical or high profile projects require.10SPDSiemens Industry, Inc. SPEEDFAX 2017 Product Catalog10-3

SPD - Surge Protective DevicesFirstSurgeFirstSurge Total Home Surge ProtectionTotal Home ProtectionSiemens believes today’s residentialsurge protectors come up short whenprotecting today’s modern home filledwith smart appliances and electronics.This is why we developed ourFirstSurge commercial class totalhome surge protectors. These electricalsystem surge protectors are sized forwhere you live. They will let you knowwhen there is something wrong orwhen they are worn out.Based upon thunderstorm frequency,geographic location, and home size,we developed a surge exposure mapcorrelating with FirstSurge currentcapacities known to provide years ofprotective service for each shaded area.Sized For Where You LiveSPD10ModelFirstSurge Power (FS060)FirstSurge Plus (FS100)FirstSurge Pro (FS140)10-4Siemens Industry, Inc. SPEEDFAX 2017 Product CatalogSurgeCapacity60,000 A100,000 A140,000 AKnow You’re Protected:3 Stage Commercial GradeNotificationWhen there is a problem, SiemensFirstSurge takes the guesswork out ofknowing when it is time to be replaced.What will you see and hear when thisoccurs?Audible Alarm:Green LED(s):Red Service Light:BeepsExtinguishFlashesGround Reference Monitoring (GRM)FirstSurge is GRM-equipped notifyingyou a rare safety hazard exists due to acompromised electrical system neutralto ground bond. What will you see andhear when this occurs?Audible Alarm: BeepsGreen LED(s): Remains LitRed Service Light: Flashes

SPD - Surge Protective DevicesFirstSurgeFeatures & BenefitsTechnical SpecificationsSurge Spike CapacityUL 1449 Listed, Type 2, Surge Protective Device (SPD)n Rated for 120/240 split phase panels up to 400An Surge Current Capacities:- 60,000 A- 100,000 A- 140,000 An 3 Stage Commercial Grade Notificationn Ground Reference Monitoring (GRM)n Installs onto any brand load centern Type 4 rated outdoor enclosuren 10 year product and connected equipment warranty*n*See warranty for detailsInstallation Instructions:FirstSurge is a Type 2 SPD. It is suitable for use downstream of the service disconnect.Pre-Plan your installation. You need to accomplish thefollowing: Meet all National and Local codes (NEC Article 285 andUL 1449 address SPDs). Confirm System voltage to SPD voltage (120V SPD will failinstantly on 240V, 277V, etc.). Mount SPD as close to panel or equipment as possible tokeep leads short. (long leads hurt performance). Ensure leads are as short and straight as possible,including neutral and ground. Use a breaker position thatis close to the SPD and the panel’s neutral and ground. Recommended breaker size is 20A. Make sure system is grounded per NEC and clear offaults before energizing SPD. (inadvertent system problemmay fail SPD). Never Hi-Pot test Any SPD. (will prematurely fail SPD).To Protected Loads Use closest breaker to SPD Locate SPD close to intended breakerC Keep Leads Short as Possible Avoid Sharp S060FS100FS140XMFMKIT1. Use voltmeter to check voltages and ensure correct SPD.See Data Sheet for specs and wire-outs.2. Determine Mounting location – weather resistantequipment may be required.3. If SPD has optional Flush Mount Kit, pre-plan itsinstallation. See Figure 3. (If flush mounting, be careful tonot drop SPD into wall).4. Remove power from panel/source. Confirm panel/source isdeenergized.5. Identify breaker location and SPD location. Position SPDsuch that LEDs are best visible. If Flush Mount Kit wasordered, follow Flush Mount instructions and then proceedat #6.6. Mount SPD – weather resistant applications requireadditional sealing, etc. (not included)-- Remove an appropriately sized knockout from panel.-- Connect conductors as appropriate – short and straightas possible.7. Label or mark conductors as appropriate (neutral: white,ground: green, energized: black).8. Make sure system is bonded per NEC and is clear ofhazards or faults before energizing (N-G bonding not perNEC will fail SPDs: #1 cause of SPD failures).9. Energize and confirm proper operation of green LEDindicators. If any connected phase LED does notilluminate, remove power, check all connections and testagain. If any connected phase LED still does not illuminate,contact Siemens Technical Support at: 1-888-333-3545.10.The SPD is equipped with an audible alarm which willsound in the event of an alarm condition. This indicates aproblem with the SPD which requires further evaluation.There is no test or silence switch. De-energizing the SPDwill silence the alarm.SPD Rotate FirstSurge such thatLED indicator is most visibleRated Voltage (MCOV)Response TimeEnclosureSelection InformationFirstSurge PowerFirstSurge PlusFirstSurge ProFirstSurge Flush Mount Kit101-888-333-3545usa.siemens.com/surgeNsALine VoltageUL 1449 3rd Ed VPRFirstSurge Power (FS060) 60,000 AFirstSurge Plus (FS100) 100,000 AFirstSurge Pro (FS140) 140,000 A120/240 Split Phase, 50/60 HzL-N:600 VL-G:600 VN-G:600 VL-L:900 V150V – L-N, L-G, and N-G; 300V – L-L 1 nanosecondNEMA 4X Indoor and Outdoor Rated Outdoor installation requiresappropriate weather sealing atnipple (gasket, sealing conduit, etc.)Siemens Industry, Inc. SPEEDFAX 2017 Product Catalog10-5

SPD - Surge Protective DevicesTPS3 Integral or Internally Mounted SPDsSelection TPS3 01 and TPS3 L1(True or Discrete 10-Mode)Siemens TPS3 01 and L1 surge protective devicesare designed for integration within our P1, P2,and P3 power distribution panel boards, as wellas TIASTAR motor control centers and buswaysystems. The TPS3 01 and L1 SPDs feature GroundIntegrity Monitoring (GIM) diagnosticsTPS3 01 and TPS3 L1 Key FeaturesUL 1449-4 Type 2 SPD and UL 1283 Listed– Optional UL 1449 4th Edition Listed Type 1n Type 1 / Type 2 SPDn 100 - 300 kA Per Phase Surge Currentn 20 kA I (Most models)nn 200 kA SCCR (Most models)n UL 96A Lightning Protection Master Labelingcompliant (@ 20 kA)n Large block, individually fused, thermallyprotected, 50kA MOVsn Every MOV is monitored, including N-Gn Mounts internal to:– P1, P2, and P3 panels– TIASTAR motor control centers –standard 6”bucket– STP series busplug on SX series buswayn Consult factory for field retrofit in P1 panelsn Modes of Protection: L-N, L-G, N-G, and L-Ln All UL required OCP & safety coordinationincluded– Type 1 SPDs intended for Line or Load side ofMain Disconnect– Type 2 SPDs intended for Load side ofMain Disconnectn Standard Monitoring: LED Indicators, SurgeCounter, Dry Contacts, Audible Alarm w/ silenceswitch & test buttonn Dimensions: 11.5” x 7.2” x 4.5”(292.1 mm x 182.9 mm x 114.3 mm)n Weight: 4.55 lb. (2.06 kg)n Designed, manufactured & tested consistent with:– ANSI / IEEE C62.41.1-2002, C62.41.2-2002,C62.45-2002, C62.62-1010, C62.72-2007 andCSA C22.2 No. 269.1 and 269.2– 1992/2000 NEMA LS-1– NEC Article 285– IEC 61643, CE n 10 Year Product WarrantyTPS3 01SPD10nAvailable Options:nDirect bus connected or can be wired to a circuitbreaker (include W option)Ordering InformationCatalog #TPS301Voltage CodeSurge Current (kA)OptionsA B C D E F G K L S 10 100 kA per phase15 150 kA per phase20 200 kA per phase25 250 kA per phase30 300 kA per phaseX Surge counter(Standard)120/240 V, 1Ø, 3W120/240 V, 3Ø, 4W120/208 V, 3Ø, 4W240 V, 3Ø, 3W277/480 V, 3Ø, 4W480 V, 3Ø, 3W600 V, 3Ø, 3W 380/220 V, 3Ø, 4W600/347 V, 3Ø, 4W400/230 V, 3Ø, 4WW Terminal lugB Busway applicationM MCC application2 Type 2 SPD(Default)Includes UL1283 EMI/RFI Filters0 Type 1 SPD(Consult Factory Priorto Ordering)Example: TPS3C0120X002 Type 2 SPD (Default) for a 208/120V panelboardwith a surge current capacity of 200 kA per phase and a surge counter.When an option is not selected, include a zero (0) in the field.Available Accessories: Ordered SeparatelyRMSIE Remote monitor Available in 100 kA & 150 kA onlyTPS3 L1Ordering InformationCatalog #TPS3L1Voltage CodeSurge Current (kA)OptionsA B C E K S 15 150 kA per phase30 300 kA per phaseX Surge counter(Standard)120/240 V, 1Ø, 3W120/240 V, 3Ø, 4W120/208 V, 3Ø, 4W277/480 V, 3Ø, 4W380/220 V, 3Ø, 4W400/230 V, 3Ø, 4WW Terminal lugB Busway applicationM MCC application2 Type 2 SPD(Default)Includes UL1283 EMI/RFI Filters0 Type 1 SPDExample: TPS3CL130X002 10 Mode Type 2 SPD (Default) for a 208/120V panelboard with a surge current capacity of 300 kA per phase and a surge counter.When an option is not selected, include a zero (0) in the field.Available Accessories: Ordered SeparatelyRMSIE Remote monitor10-6Siemens Industry, Inc. SPEEDFAX 2017 Product Catalog

SPD - Surge Protective DevicesTPS3 Integral or Internally Mounted SPDsSelection TPS3 02 and TPS3 L2(True or Discrete 10-Mode)Siemens TPS3 02 and L2 surge protective devicesare designed for integration within our Revised P1power distribution panel boards.The TPS3 01 andL1 SPDs feature Ground Integrity Monitoring (GIM)diagnostics.TPS3 02 and TPS3 L2 Key FeaturesUL 1449-4 Type 2 SPD and UL 1283 Listed– Optional UL 1449 4th Edition Recognized Type 1n Type 1 / Type 2 SPDn 100 - 300 kA Per Phase Surge Currentn Large block, individually fused, thermallyprotected, 50kA MOVsn 20 kA I (Most models)nn 200 kA SCCR (Most models)n UL 96A Lightning Protection Master Labelingcompliant (@ 20 kA)n Large block, individually fused, thermallyprotected, 50kA MOVsn Every MOV is monitored, including N-Gn Mounts internal to:– Revised P1 Lighting Panelboardsn Consult factory for field retrofit in P1 panelsn Modes of Protection: L-N, L-G, N-G, and L-Ln All UL required OCP & safety coordinationincluded– Type 1 SPDs intended for Line or Load side ofMain Disconnect– Type 2 SPDs intended for Load side ofMain Disconnectn Standard Monitoring: LED Indicators, SurgeCounter, Dry Contacts, Audible Alarm w/ silenceswitch & test buttonn Dimensions: 11.6” x 5.7” x 4.9”(294.6 mm x 144.8 mm x 124.5 mm)n Weight: 4.55 lb. (2.06 kg)n 10 Year Product WarrantynTPS3 02Ordering InformationCatalog #TPS3Voltage CodeSurge Current (kA)A B C D E F G K L S 10 100 kA per phase15 150 kA per phase20 200 kA per phase25 250 kA per phase30 300 kA per phase120/240 V, 1Ø, 3W120/240 V, 3Ø, 4W120/208 V, 3Ø, 4W240 V, 3Ø, 3W277/480 V, 3Ø, 4W480 V, 3Ø, 3W600 V, 3Ø, 3W 380/220 V, 3Ø, 4W600/347 V, 3Ø, 4W400/230 V, 3Ø, 4WDirect bus connectedCan be wired to a circuit breaker (consultfactory at time of order or see installation manualfor retrofit)OptionsX Surge counter (Standard)2 Type 2 SPD (Default)Includes UL 1283 EMI/RFI Filters0 Type 1 SPD(Consult Factory Prior to Ordering)Example: TPS3C0220X2 Type 2 SPD (Default) for a 208/120V panelboard with asurge current capacity of 200 kA per phase and a surge counter.When an option is not selected, include a zero (0) in the field.Available Accessories: Ordered SeparatelyRMSIE Remote monitor Available in 100kA & 150 kA onlyAvailable Options:n02TPS3 L2Ordering InformationCatalog #TPS315 150 kA per phase30 300 kA per phase120/240 V, 1Ø, 3W120/240 V, 3Ø, 4W120/208 V, 3Ø, 4W277/480 V, 3Ø, 4W380/220 V, 3Ø, 4W400/230 V, 3Ø, 4WOptionsX Surge counter (Standard)2 Type 2 SPD (Default)Includes UL 1283 EMI/RFI Filters0 Type 1 SPD(Consult Factory Prior to Ordering)Example: TPS3CL230X2 10 Mode Type 2 SPD (Default) for a 208/120 V panelboard with a surge current capacity of 300 kA per phase and a surge counter.When an option is not selected, include a zero (0) in the field.Available Accessories: Ordered SeparatelyRMSIE Remote monitorSiemens Industry, Inc. SPEEDFAX 2017 Product Catalog10-7SPDSurge Current (kA)A B C E K S 10Voltage CodeL2

SPD - Surge Protective DevicesTPS3 External or Wall Mounted SPDsSelection TPS3 03TPS3 03 is a UL 1449 4th Edition 50 kA Type 1 compact surgeprotective device that can be used as a replacement secondary surge or lighting arrestors. Having a Type 1 designationallows for flexible electrical system connection location (lineor load side) as well as UL 96A compliance (@ 20 kA In).TPS3 03 Key FeaturesnnnnnnnnnnnnnnUL 1449 4th Edition Listed Type 1Type 1 Rated SPD50 kA Per Phase Surge Current20 kA In (Most models)200 kA SCCR (Most modelsUL 96A Lightning Protection Master Labeling compliant(@ 20 kA))Every MOV is monitoredMounts external to electrical distribution equipment– Recommend for Line Side or Load Side ApplicationsStandard compact NEMA 4X polycarbonate enclosureModes of Protection: L-N or L-G and L-LStandard Monitoring: LED IndicatorDimensions: 3.25” x 3.25” x 3.3”(82.6 mm x 82.6 mm x 83.8 mm)Weight: 2 lb. (0.9 kg)2 Year Product WarrantyAvailable Options:nDry contacts & Audible Alarm (option “D”)Neutral to Ground Protection (option “N”)SPD10n10-8Siemens Industry, Inc. SPEEDFAX 2017 Product CatalogTPS3 01 DIN RAIL MountingTPS3 03Ordering InformationCatalog #Voltage CodeA 120/240 V, 1Ø, 3WB 120/240 V, 3Ø, 4WC 120/208 V, 3Ø, 4WD 240 V, 3Ø, 3WE 277/480 V, 3Ø, 4WF 480 V, 3Ø, 3WG 600 V, 3Ø, 3WK 380/220 V, 3Ø, 4WL 600/347 V, 3Ø, 4WTPS3Surge Current (kA)Options05 50 kA per phaseD Dry contact& audible alarmN Adds N-GProtectionExample: TPS3C0305D0 Type 1 SPD for a 208/120V applicationwith a surge current capacity of 50 kA per phase, in a standardNEMA 4X enclosure with dry contacts and audible alarm option.When an option is not selected, include a zero (0) in the field.Available Accessories: Ordered SeparatelyRMSIE Remote monitor03

SPD - Surge Protective DevicesTPS3 External or Wall Mounted SPDsSelection TPS3 03 DCTPS3 03 DC is available in 300VDC, 600VDC and 1000VDC versions, whichare designed to protect photovoltaic electrical systems. Typical PVinstallation would be on the DC solar panel side and also on the AC side ofthe inverter/converter. AC voltage TPS3 03’s are also available. SPDs arehighly recommended when lightning activity is present to protectsensitive electrical photovoltaic components.TPS3 03 DC is designed as a stand alone device in a NEMA 4Xpolycarbonate enclosure. Large block, thermally protected 50 kA MOVsare utilized. A green LED illuminates for diagnostic monitoring. TPS3 03DC comes standard with a Tri-Mount installation kit which allows it to beNipple, DIN-rail or Bracket mounted.DiagramTPS3 09Ordering InformationDimensionsCatalog #TPS30305Voltage CodeM 300 VDCP 1000 VDCR 600 VDCTri-Mount InstallationMounting Kit IncludedPerformance DataSiemens Part NumberTPS3M0305TPS3R0305Modes of ProtectionNominal Network VoltageUn300VDCTechnologyMaximum Continuous Operating Voltage DCMaximum Surge Current (8/20 μs)Nominal Discharge Current (8/20 μs)Voltage Protection Level (3kA 8/20μs)Installation mounting methodWiring (red , black - , green / yellow 0kA10kA 600V 1800V 2500VSafety Disconnectors-40oC 65oCtA 1nsDIN Rail, Nipple or BracketNEMA 4X PolycarbonatePre-wired w/3’( 1m) of 8AWG 6AWG Ground ConductorLow Consumption LED IndicatorSPDDiagnostic circuit1000VDC10Enclosure Material600VDCLarge Block, Thermally Protected 50kA MOVsOperating TemperatureResponse TimeTPS3P0305DC – DC- , DC – Ground, DC- – GroundThermal/Overcurrent Protection; Arc-Breaking Slide GateUL ListingUL 1449 Listed as Type 1 SPD as a DC SPD for PV and other types of DC applicationsWarranty5 YearsSiemens Industry, Inc. SPEEDFAX 2017 Product Catalog10-9

SPD - Surge Protective DevicesTPS3 Integral or Internally Mounted SPDsSelection TPS3 05 and TPS3 L5(True or Discrete 10-Mode)Siemens TPS3 05 and L5 surge protective devicesare designed for integration within our P4 and P5panelboards as well as distribution switchboards.The TPS3 01 and L1 SPDs feature Ground IntegrityMonitoring (GIM) diagnostics.TPS3 05 and TPS3 L5 Key FeaturesUL 1449-4 Type 2 SPD and UL 1283 Listed– Optional UL 1449 4th Edition Listed Type 1n Type 1 / Type 2 SPDn 100 - 300 kA Per Phase Surge Currentn 20 kA I (Most models)nn 200 kA SCCR (Most models)n UL 96A Lightning Protection Master Labelingcompliant (@ 20 kA)n Large block, individually fused, thermallyprotected, 50kA MOVsn Every MOV is monitored, including N-Gn Mounts internal to:– P4 & P5 panelboards and distributionswitchboardsn Modes of Protection: L-N, L-G, N-G, and L-Ln All UL required OCP & safety coordinationincluded– Type 1 SPDs intended for Line or Load side ofMain Disconnect– Type 2 SPDs intended for Load side ofMain Disconnectn Standard Monitoring: LED Indicators, SurgeCounter, Dry Contacts, Audible Alarm w/ silenceswitch & test buttonn Dimensions: 10” x 17” x 6”(254 mm x 431.8 mm x 152.4 mm)n Weight: 9.4 lb. (4.2 kg)n Designed, manufactured & tested consistent with:– ANSI / IEEE C62.41.1-2002, C62.41.2-2002,C62.45-2002, C62.62-1010, C62.72-2007 andCSA C22.2 No. 269.1 and 269.2– 1992/2000 NEMA LS-1– NEC Article 285– IEC 61643, CE n 10 Year Product WarrantynPanelboard Features:SPD10nCopper or aluminum busMB or MLOSwitchboard Features:nCopper or aluminum bus200% rated neutral bus for harmonic-richapplicationsCSA, UL 891, UL 67 and NEMA PB-2TPS3 05Ordering InformationCatalog #TPS3Voltage CodeSurge Current (kA)A B C D E F G K L S 10 100 kA per phase15 150 kA per phase20 200 kA per phase25 250 kA per phase30 300 kA per phase120/240 V, 1Ø, 3W120/240 V, 3Ø, 4W120/208 V, 3Ø, 4W240 V, 3Ø, 3W277/480 V, 3Ø, 4W480 V, 3Ø, 3W600 V, 3Ø, 3W 380/220 V, 3Ø, 4W600/347 V, 3Ø, 4W400/230 V, 3Ø, 4W05OptionsX Surge counter (Standard)2 Type 2 SPD (Default)Includes UL 1283 EMI/RFI Filters0 Type 1 SPD(Consult Factory Prior to Ordering)Example: TPS3C0530X2 Type 2 SPD (Default) for a 208/120V power panelwith a surge current capacity of 300 kA per phase and a surge counter.When an option is not selected, include a zero (0) in the field.Available Accessories: Ordered SeparatelyRMSIE Remote monitor Available in 100 kA & 150 kA onlyABMOVsCMOVsNMOVsMOVsMOVsMOVsMOVsMOVsMOVsMOVs Parallel MOVs“True” or “Discrete”10-Mode SPDTPS3 L5Ordering InformationCatalog #TPS3Voltage CodeSurge Current (kA)A B C E K S 15 150 kA per phase30 300 kA per phase120/240 V, 1Ø, 3W120/240 V, 3Ø, 4W120/208 V, 3Ø, 4W277/480 V, 3Ø, 4W380/220 V, 3Ø, 4W400/230 V, 3Ø, 4WL5OptionsX Surge counter (Standard)2 Type 2 SPD (Default)Includes UL 1283 EMI/RFI Filters0 Type 1 SPD(Consult Factory Prior to Ordering)Example: TPS3C0530X2 Type 2 SPD (Default) for a 208/120V power panelwith a surge current capacity of 300 kA per phase and a surge counter.When an option is not selected, include a zero (0) in the field.Available Accessories: Ordered SeparatelyRMSIE Remote monitor10-10Siemens Industry, Inc. SPEEDFAX 2017 Product CatalogGMOVs

SPD - Surge Protective DevicesTPS3 Integral or Internally Mounted SPDsSelection TPS3 06 and TPS3 L6(True or Discrete 10-Mode)Siemens TPS3 06 and L6 surge protective devicesare designed for integration within our SB1,SB2, SB3, Type RCS Switchboards, Low-voltageSwitchgear, Motor Control Centers, and BuswaySystems. The TPS3 01 and L1 SPDs feature GroundIntegrity Monitoring (GIM) diagnostics.TPS3 06TPS3 06 and TPS3 L6 Key FeaturesOrdering InformationCatalog #TPS306Voltage CodeSurge Current (kA)OptionsA B C D E F G K L S 10 100 kA per phase15 150 kA per phase20 200 kA per phase25 250 kA per phase30 300 kA per phase40 400 kA per phase50 500 kA per phaseX Surge counter(Standard)120/240 V, 1Ø, 3W120/240 V, 3Ø, 4W120/208 V, 3Ø, 4W240 V, 3Ø, 3W 277/480 V, 3Ø, 4W480 V, 3Ø, 3W 600 V, 3Ø, 3W 380/220 V, 3Ø, 4W600/347 V, 3Ø, 4W400/230 V, 3Ø, 4W2 Type 2 SPD(Default)Includes UL1283 EMI/RFI Filters0 Type 1 SPD(Consult FactoryPrior to Ordering)B Busway applicationM MCC applicationExample: TPS3C0120X002 Type 2 SPD (Default) for a 208/120V panelboardwith a surge current capacity of 200 kA per phase and a surge counter.When an option is not selected, include a zero (0) in the field.Available Accessories: Ordered SeparatelyRMSIE Remote monitor G voltage code only available in 200 & 250 kA Not available in 500 s Parallel MOVs“True” or “Discrete”10-Mode SPDTPS3 L6Ordering InformationCatalog #TPS3L6Surge Current (kA)OptionsA B C E K S 15 150 kA per phase30 300 kA per phase45 450 kA per phaseX Surge counter(Standard)120/240 V, 1Ø, 3W120/240 V, 3Ø, 4W120/208 V, 3Ø, 4W277/480 V, 3Ø, 4W380/220 V, 3Ø, 4W400/230 V, 3Ø, 4WB Busway applicationM MCC applicationExample: TPS3CL645X2 10 mode Type 2 SPD (Default) for a 208/120V switchboard with a surge current capacity of 450 kA per phase and a surge counter.2 Type 2 SPD(Default)Includes UL1283 EMI/RFI Filters0 Type 1 SPD(Consult FactoryPrior to Ordering)When an option is not selected, include a zero (0) in the field.Available Accessories: Ordered SeparatelyRMSIE Remote monitorSiemens Industry, Inc. SPEEDFAX 2017 Product Catalog10-11SPDVoltage Code10UL 1449-4 Type 2 SPD and UL 1283 Listed– Optional UL 1449 4th Edition Listed Type 1n Type 1 / Type 2 SPDn 100 - 500 kA Per Phase Surge Currentn 20 kA I (Most models)nn 200 kA SCCR (Most models)n UL 96A Lightning Protection Master Labelingcompliant (@ 20 kA)n Large block, individually fused, thermallyprotected, 50kA MOVsn Every MOV is monitored, including N-Gn Mounts internal to:– SB1, SB2, SB3 and Type RCS Switchboards– Type WL low-voltage switchgear– TIASTAR motor control centers standard 12” bucket– STP series busplug on SX series buswayn Modes of Protection: L-N, L-G, N-G, and L-Ln All UL required OCP & safety coordinationincluded– Type 1 SPDs intended for Line or Load side ofMain Disconnect– Type 2 SPDs intended for Load side ofMain Disconnectn Standard Monitoring: LED Indicators, SurgeCounter, Dry Contacts, Audible Alarm w/ silenceswitch & test button, Rotary disconnect switchn Dimensions: 10.7” x 11.5” x 4.5”(271.8 mm x 292.1 mm x 114.3 mm)n Weight: 6.8 lb. (3.0 kg)n Designed, manufactured & tested consistent with:– ANSI / IEEE C62.41.1-2002, C62.41.2-2002,C62.45-2002, C62.62-1010, C62.72-2007 andCSA C22.2 No. 269.1 and 269.2– 1992/2000 NEMA LS-1– NEC Article 285– IEC 61643, CEn Designed, manufactured & tested consistent with:– ANSI / IEEE C62.41.1-2002, C62.41.2-2002,C62.45-2002, C62.62-1010, C62.72-2007 & CSAC22.2 No. 269.1 and .2– 1992/2000 NEMA LS-1– NEC Article 285– IEC 61643, CEn 10 Year Product Warrantyn

SPD - Surge Protective DevicesTPS3 External or Wall Mounted SPDsSelection TPS3 09TPS3 09 is a UL 1449 4th Edition 100 kA Type 1 compactmulti-mode surge protective device that can be installed oneither the line or load side of the electrical service. Wheninstalled at the electrical service entrance, it can be used forUL 96A compliance (@ 20 kA In).TPS3 09 Key FeaturesnnnnnnnnnnnnnnnnUL 1449 4th Edition Listed Type 1Type 1 Rated SPD100 kA Per Phase Surge Current20 kA In (Most models)200 kA SCCR (Most models)UL 96A Lightning Protection Master Labeling compliant(@ 20 kA)Every MOV is monitored, including N-GMounts external to electrical distribution equipment– Weatherproof hub includedMounts internal to P1 panelboards & busway– P1 - Field retrofit or factory install– P2 and P3 - factory install onlyStandard compact NEMA 4X polycarbonate enclosureModes of Protection: L-N, L-G, N-G, and L-LStandard Monitoring: LED IndicatorsWire Size: Prewired with 3’ (91.4 cm) of #10 AWGDimensions: 8.3” x 3.6” x 3.0” (211 mm x 91 mm x 77 mm)Weight: 3 lb. (1.4 kg)10 Year Product WarrantyAvailable Options:nnSPD10nDry contacts & Audible Alarm (option “D”)Extended indicator light (option “E”)Internal mounting in P1, P2 Panels (option “I”), requiresTPS9IKITP1 or TPS9IKITP2 mounting bracket accessory.10-12Siemens Industry, Inc. SPEEDFAX 2017 Product CatalogTPS3 09Ordering InformationCatalog #Voltage CodeA 120/240 V, 1Ø,B

Siemens Industry, Inc. SPEEDFAX 2017 Product Catalog 10-5 10 SPD Features & Benefits n UL 1449 Listed, Type 2, Surge Protective Device (SPD) n Rated for 120/240 split phase panels up to 400A n UL 1449 3rd Ed VPRSurge Current Capacities: - 60,000 A - 100,000 A - 140,000 A n 3 Stage Commercial Grade Notification n Ground Reference Monitoring (GRM) n Installs onto any brand load center

Related Documents:

11. Roll-in pallet support 12. Double flanged pallet support 13. Drum/coil bed 14. Fork clearance bar 15. Skid channel 16. Wall tie 17. Drum cradle 18. Corner protector 19. Post protector Welded and bolted post protector Post protector 12 10 2 11 14 13 9 7 3 19 Welded Selective Pallet Rack End aisle protector Corner protector Welded and bolted .

steady fl ow from the header tank through the surge pipe. This fl ow creates a measurable head loss (due to friction) along the surge pipe from the header tank to the surge tower. To create the surge, students quickly shut the surge valve downstream of the surge pipe. VDAS displays and records the pressure surge in the surge tower. Students

Fixed Indexed Annuity All carriers shown may not be available. Please check your approved carrier list before proceeding. Please verify rate before submitting application. 12/28/2022 Corebridge(AIG) Corebridge(AIG) Power 5 Protector Power 7 Protector Power 7 Protector Plus Income Power 10 Protector Power 10 Protector Plus Income

0551 770 Surge protector, 100 120 V 0551 771 Surge protector, 230 V, EU 0551 772 Surge protector, 220 240 V, AU and CN AS-3112 0551 726, 9' 0551 728, 20' 220V 240V 0508 775 110V 120V 0

The coincidence of wind surge, spring high tide and external surge leads to extreme storm surge levels along the coast (figure 4). Figure 4: The components of a storm surge. Thus a storm surge is composed of the local tides, wind surge and a possible external surge. In the project storm surges from 1901 until 2008 at tidal gauge

Computers (PCs or MACs with My Endpoint Protector client installed) Devices (the devices, which are currently supported by My Endpoint Protector. e.g.: USB devices, digital photo cameras, etc.) The cloud/server side of My Endpoint Protector is the Administration and Reporting Tool. It is responsible for centrally managing devices,

3- Differential surge tank: an orifice tank having a riser is called differential tank. 4- One- way surge tank: in a one way surge tank the liquid flows from the tank into the pipeline only when the pressure in the pipeline drops below the liquid level in the surge tank. 5- Closed surge tank: if the top of the tank is closed and there is

Anatomy Fig 1. Upper limb venous anatomy [1] Vessel Selection Right arm preferable to left (as the catheter is more likely to advance into the correct vessel), vessel selection in order: 1. Basilic 2. Brachial 3. Cephalic Pre-procedure Patient information and consent Purpose of procedure, risks, benefits, alternatives. Line care: Consider using local patient information leaflet as available .