Variable Frequency Drives (VFD’s)

3y ago
36 Views
2 Downloads
1.82 MB
61 Pages
Last View : 8d ago
Last Download : 3m ago
Upload by : Casen Newsome
Transcription

Understanding & ManagingVariable Frequency DrivesPresented by: Greg Stark, P.E.September 10, 2014Sponsored by:Variable Frequency Drives (VFD’s) Popular speed control devicesused in industrial, commercialand residential applications.– Huge energy savings potentialoperating centrifugal fans,pumps and compressors Vary frequency of electricalsupply to an induction motor tovary the motor speed.– Vary the speed/flow of theoperation/application.1

VFD Applications Industrial– Fans, Pumps, Compressors– Conveying Systems Commercial– HVAC Compressors– Pumps and Air Handlers Residential– Variable Speed HVAC equipment– Energy Efficient Washing MachinesHow Have We Varied Speed Historically? Change Speed––––Belts & pulleysChains & sprocketsGear drivesMulti-speed motors Vary Speed––––––Variable pitch belts & pulleysEddy current clutchHydrostatic drivesWound rotor motorDC DrivesAC Variable Frequency Drives2

How Have We Varied Flow Historically?Typical Airflow Requirements60005000CFM Size motor/systemfor maximum flow Use throttlingdevices on fans,pumps &compressors toreduce flow h– Valves– Vanes & DampersConsiderations? Initial Cost– VFD vs other device Maintenance Cost– VFD vs other device Maintenance Issues(Downtime, etc) Effectiveness– How well does it do what Ireally want/need it to do? Others?3

Induction Motor Constant Speed? Synchronous Speed– Speed the motor’s magnetic field rotates.– Theoretical speed with no torque or friction.– A well built motor may approach synchronousspeed when it has no load.– Factors Electrical Frequency (cycles/second) # of poles in motorSpeed (120 * Frequency)/(# of poles) Rated Speed– Speed the motor runs at when fully loaded andsupplied rated nameplate voltage.VFD Principles of Operation Motor speed can be varied by changing the frequency, # ofpoles, or both. Example:– 4 pole motor @ 60 hertz 1800 rpm– 4 pole motor @ 50 hertz 1500 rpm– 4 pole motor @ 40 hertz 1200 rpm4

Drive Function Input:– 60 hertz AC & rated voltage Converter– Rectifies to DC & changesfrequency to desired value Inverter– Converts DC back to AC Regulator– Adjusts voltage level to desiredvalue as a % of speed/frequencyvalue.– Volts/Hertz Ratio (480/60 8) AC Output:– Desired frequency and voltagefor speed requirement.Torque vs Speed What happens to torque whenspeed is decreased?– Torque increases If torque increases, currentincreases and producesadditional heat in the windings.5

However!!!! For many types of loads, asspeed drops, torquerequirements also drop. What happens when speedAND torque decrease?– Reduced Horsepower Reduces our energy costs!Increase Speed? What about increasing speed above themotor’s synchronous speed usingfrequency higher than 60 hertz?– 4 pole motor @ 60 hertz 1800 rpm– 4 pole motor @ 70 hertz 2100 rpm Most motors were not balanced tooperate above synchronous speed. The load may not have been balancedabove this speed either.6

Common Applications Constant Torque Loads– conveyor belts, augers,reciprocating pumps &compressors, extruders,gear pumps. Variable Torque Loads– centrifugal fans, pumps,and compressors Constant HorsepowerLoads– winding machinesTorque-Speed Curve Amount of Torqueproduced by motorsvaries with Speed. Torque Speed Curves– Starting Torque– Pull Up Torque– Breakdown Torque7

Torque-Speed Issues Some single phasemotors have startingand running windings The starting windingscan not be energizedcontinuously If a VFD is used andspeed is reduced toomuch the startingwindings burn out.Constant Torque Loads Require the same amount oftorque at low speeds as highspeeds.– For a given weight on the belt, thetorque to turn the belt is alwaysthe same regardless of speed. Horsepower increases ordecreases as a direct function ofspeed. Examples:– Conveyor belts, reciprocatingpumps & compressors8

Constant Torque Loads Horsepower increases ordecreases as a direct functionof speed.– A 50% drop in speed produces a50% reduction in power required toturn the load. Energy savings using a VFD tocontrol the speed of aconstant torque load is adirect function of speedreduction.Variable Torque Loads Require much lower torque &horsepower at low speeds than athigh speeds. Power required varies as the cubeof the speed. Examples:– Centrifugal fans, pumps &compressors, mixers and agitators.9

Variable Torque Loads Horsepower increases ordecreases as cubic function ofspeed.– A 50% drop in speed producesalmost an 88% reduction in powerrequired to turn the load. Energy savings using a VFD tocontrol the speed of avariable torque load can bevery large due to howcentrifugal loads operate.Constant Horsepower Loads Constant horsepower loadsinclude equipment such asgrinders, winders, and lathes.– Since the power requiredremains the same regardless oftorque or speed requirements ofthe operation, there are no directenergy savings from installingVFD's with constant horsepowerloads.10

Constant Horsepower Loads Traditionally considered DCDrive applications Some movement to use ofnewer AC Flux Vector Drives The only justification forinstallation of an VFD wouldbe based on improvement inthe process control of theoperation.Advantage: Energy Savings Traditionally used to justifyinstallation. Centrifugal Fans, Pumps,Compressors– As the speed of thedevice is slowed, thetorque and powerrequired to run theoperations is significantlyreduced.11

Throttling Flow May Not Save Energy Traditional methods ofreducing flow by throttling(dampers, vanes, valves) don’tconsistently provide energysavings. Depending on where thesystem is on the pump curve,reducing flow has the result ofincreasing pressure on theback side of the pump andchanging the pump efficiency.Energy Savings With VFDs Using a VFD can result insignificant energy savings whenthrottling flow for centrifugal fans,pumps and compressors. The reduction in flow and pressurein the system from controllingflow with fan/pump speed willresult in a decrease in powerrequired to turn the deviceresulting in energy savings at thereduced flow rate.12

VFD’s Increase Power Factor Power Factor Penalties can bea part of commercial andindustrial electric bills VFD’s have two types of powerfactor– Total Power Factor– Displacement Power Factor Utilities measure displacementpower factor so a VFD canimprove power factor of asystem without addingcapacitorsAdvantage: Reduced Voltage Starting An VFD acts like a reducedvoltage starter to limit the inrush current when the motorstarts. VFD’s can generally limit inrush current to a maximum of150% of a motors FLA/RLA ifdesired.– What is the downside of limitingstarting amps?13

Why Reduced Voltage (Soft) Starting Reduce motor in-rushcurrent and the associatedvoltage drop when startingthe motor for power qualitybenefits.– Can cause nuisance tripping ofsensitive electronicequipment. Reduce mechanical shock toproducts and drive systemsduring startup.Advantaged: Improved Process Control Can be linked intoprocess control systemsto provide feedback toDCS and PLC’s. More consistent controlof manufacturingoperation.– Better dissolvedoxygen control?14

Advantage: Lower System Maintenance Eliminate need for maintenanceitems in some system. Extend operating life ofequipment that is occasionallyoverloaded and the system isnot optimized. Reduces motor cycling andassociated driveline shock insome systems.Can Eliminate Some MaintenanceRequirements May eliminate theneed for complexbelt, gearboxes,valve and dampersystems and theassociatedmaintenancerequirements.15

Maintenance: ReducedShort Cycling Frequently starting andstopping motors cansignificantly reduce theiroperating life. A VFD can reduce inputflow rate so that pumpsdo not have to befrequently started andstopped.VFD Maintenance Drives are similar to a powersupply & computer– Keep it Clean– Keep it Dry– Keep connections Tight NEMA 1 or NEMA 12 are themost common enclosures– NEMA 1 dust and moistureissues occasionally are an issue16

Advantage: Bypass Capability If there is a problem with the drive, it can be bypassedeasily and the motor operated without the drive.(Although without speed control)Advantage: Multi-Motor Control Some VFD’s cancontrol multiplemotors from the samedrive. Reduces sizerequirements and theinitial cost.17

Advantage: Phase Conversion VFD’s can be used to operate 3-phasemotors from single phase powersupplies. Motor starting currents of 150%producing full torque starts up to 125Hp Issues:– Cost of VFD vs Phase Converter– Drive is 95% efficient– Need for Reduced Voltage Start?– Eliminates need for “Pump Panel”– Multi-motor control (center pivot)– * Harmonic output is usuallyhigher when used single phaseDisadvantage: Initial Cost Initial cost of an VFD isgreater than the cost ofother types of variablespeed controlequipment. Energy savings isgenerally low forapplications whereaverage speedrequirements are nearthe motors ratedspeed.18

VFD on a Constant Speed Pump? Are there energy savings fromusing a VFD on a constantspeed/flow pump?– Flow is never throttled so flow andenergy use will never be lowered.– There might be other advantageslike maintenance, soft start, etc. How about a pumping systemwhere multiple pumps feedmultiple systems and valves areused to match the number ofpumps with the amount of flowneeded for the number of systemsoperating?Disadvantage: Complexity VFD’s like other solidstate devices requirespecializedtroubleshootingknowledge. Manufacturer’s aremaking progress withsimplicity & selfdiagnostic programs.19

Disadvantage: Motor Heating VFD’s used to run constanttorque loads (conveyorbelts) at slow speeds havepotential for overheating.– At low speed, the fan onthe motor produces lesscooling air. Constant torquerequirements withreduced cooling air resultsin motor heating.VFD Slow Speed/Heating Options Increase cooling air flow– Add Pony Motor/Fan ( ) Use better motor insulation– General Purpose Motor with ahigher than standard insulationclass (Class F, H, N, etc) ( )– Invertor Ready Motor ( )– Invertor Duty Motor ( )20

Disadvantage: Power Quality VFD’s can produce significantinput & output waveformdistortion including harmonicdistortion, noise and linenotching. Input Side– Can cause multiple problemsimpacting sensitive electronicdevices, transformers,capacitors, neutral conductorsand neighboring services. Output Side– Causes multiple issues formotors and circuit conductors.Drives As Power Quality Problem Sources1. Induce harmonic distortion onthe incoming supply lines.1.2.3.4.Interfere with other electronics at thesame service or neighboring servicesOverload neutrals and transformersStrange breaker tripsCapacitor failures2. Produce harmonic distortionon the output circuit to themotor/load.1.2.3.Excessive motor heatingExcessive bearing vibration/wearVoltage overshoot on motors &cables.21

Harmonic DistortionHarmonic Distortion( )Voltage3rd Harmonic(-)– 2nd is 2 X 60 120– 3rd is 3 X 60 180– 4th is 4 X 60 240 Odd harmonics are usuallythe problematicfrequencies.TimeResultant Waveform250200150100Voltage Harmonic distortion is“noise” created by theoperation of electronicdevices with “internal AC toDC power supplies” It causes the system toresonate at differentfrequencies of the 60 cs Can Be Quantified VFD’s produce specific harmonicfrequencies with highmagnitudes.– This “fingerprint” can helpdetermine where harmonics arecoming from Standard Electronic Harmonics– Odd harmonics stairstep down– 3rd, 5th, 7th, 11th, 13th, 15th, etc. VFD harmonics– Function of drive “pulse number”– Produce “pairs” of odd harmonics– 5th& 7th, 11th & 13th, etc.22

Total Harmonic Distortion (THD) Common way of quantifying “how muchharmonic distortion” is present.– The amount of distortion from each harmonicfrequency in a waveform can be measured as apercentage of the fundamental frequency.– The individual harmonic % is squared, summedand the square root taken to determine the totalharmonic distortion (THD) content.– Example: 7% voltage THD 7% of the total voltage is non 60 hertz frequencies This is commonly done for both voltage andcurrent.Line Side-Harmonic Distortion Interfereswith Operation of Electronics Line side harmonic current fromdrives can distort the distributionvoltage within your facility and atother customer locations. Distorted current interacts with thesystem impedance to distort thevoltage somewhere else. If the harmonics are large enough,they can impact the operation ofelectronics equipment and VFD’s atneighboring customer locations.23

Harmonic Current Distortion Data Interference Problems AC currents generateelectromagnetic fields The higher thecurrent frequency,the higher theelectromagnetic fieldfrequency These fields caninterrupt data flowcausing; data errors,lost data, and slowerdata transmissionratesLine Side-Unusual Breaker Tripping Customers often report having bad breakersthat trip below rated levels.– If measuring the current trip point without a TrueRMS device, the current value may not be measuredaccurately. Non-True RMS meters don’t really measure the RMS voltage,they calculate it based on assuming a pure sine waveform. Non-True RMS ammeters commonly measure low whenattempting to measure a highly distorted current. Most true RMS meters usually indicate on theircover that they are true RMS meters. Otherswill say in their specifications that they are atrue RMS sensing meter.– A quick check with the vendor or manufacturer canverify any questions.24

Line Side-Overloaded Transformers Current harmonics produce abnormalheating in transformer windings.– Heating reduces the life of the transformer K-Factor Transformers– Transformer with a higher grade ofinsulation to better withstand theadditional heating from the harmonics.– Should be used where significant harmonicdistortion is present. K-Factor can be calculated frommonitoring the harmonic content ofthe system.– Select a higher K-Factor Transformer thanthe calculated K-Factor of your system.Line Side-Harmonics & Capacitors Capacitors near the input side of drives(in the plant or close to the service)should be carefully analyzed (tuned) toavoid problems. Harmonic resonance– Causes heating and reduced life incapacitors.– Capacitors tuned to one of thecharacteristic frequencies (5th, 7th,etc) will have dielectric failure orrupture the capacitor.25

Load Side-Motor Heating Reverse sequence harmonics (5, 11,17, 23, etc) are opposite polaritycurrents that produce opposingmagnetic fields in the windings– Try to run induction motors in theopposite direction and create heating– Enough distortion in these frequenciescauses excessive motor heating.– The more harmonic distortion in thesefrequencies, the higher the excessheating. In addition, what happens to airflowwhen you run a motor at low speed?– The fan runs slower and airflow issignificantly reduced.Load Side – Bearing Fluting Excess bearing vibration andwear problems with VFD’scan come from:– Resonant Frequencies– Common Mode Noise fromTriplen Harmonics (3,9,15,etc) Results in premature bearingfailure.26

Load Side - Voltage Overshoot Also called dV/dT or “slew rate” VFD’s use power electronics thatswitch at very high rates resulting in avoltage “pulse” with a high rate ofrise in a short amount of time.– When put in front of an induction motor,the pulses in combination with the cableand motor impedance generaterepetitive voltage overshoots at themotor terminals. Voltage overshoot affects theinsulation life of the conductor andmotor.– Common problem where long conductorsare used between the drive and themotor.Types of AC Drives Variable Voltage Input (VVI)– Oldest drive technology Current Source Input (CSI) Pulse Width Modulated (PWM)– Newest drive technology– Variable VoltageVariable Frequency Drives– Flux Vector Drives Standard Flux Vector (Closed Loop) Sensorless Drives (Open Loop)27

Variable Voltage Input (VVI) 1st AC Drive to gainacceptance. Called “Six-Step Drive” Advantages– Good speed range– Multiple motor control– Simple control Disadvantages–––––Power factorPoor ride throughSignificant output harmonicsLow speed coggingIsolation TransformerCurrent Source Input (CSI) Voltage closer to outputexpected by motor. Sold as motor/drivepackage. Advantages– High efficiency– Regeneration Disadvantages–––––Power factorLow speed coggingPoor ride throughIsolation transformerLarge physical size28

Pulse Width Modulated (PWM) Newest technology &lowest price. Best current waveformto the motor. Advantages––––High efficiencyWide speed rangeHigh power factorNo cogging Disadvantages– Complexity of equipment– Significant audible noisePWM Drive Control Types PWM drives are sometimesreferred to by their controltype– Variable Voltage VariableFrequency (VVVF) Drive Constant Volts/Hertz ratio– Flux Vector Can vary volts & hertzseparately Closed Loop– Original Flux Vector Drives Open Loop– Sensorless Vector Drives29

Variable Voltage Variable Frequency(VVVF) The standard type of control in earlymodern PWM drives.– Varies output in a constant Volts/Hertzratio to control speed. Works well for loads where the change inspeed doesn’t have to be instantaneous.– Mostly steady state conditions– Fans and pumps Lower cost than a Flux Vector DriveFlux Vector Drive (Closed Loop) Uses a more sophisticated drivecontroller to modify both the magnitudeand flux direction of the output to themotor.– Faster, more precise speed response andcontrol Can be important for very sensitivetypes of applications and certain typesof constant torque loads.– Traditionally done with DC Drives andspecialty motors. Lower cost than a DC Drive but highercost than a standard VVVF drive.– Requires use of closed loop controls tomonitor and regulate the driven loadprecisely.30

Sensorless (Open Loop) Vector Drive Attempts to provide performance of aClosed Loop Flux Vector system withoutusing as many sensors and feedback devices.– Closed Loop system uses shaft encoder on motorto measure exact position– Sensorless uses an algorithm programmed in thedrive. Most advantages of a Closed Loop FluxVector setup without additional cost andcomplexity of sensors.– Accuracy of the algorithm for motor voltage andfrequency control compared to the actual needsof the system?– How do you handle variations not in the model?What About DC Drives? DC drives still have their place inthe industry.– Allow more precise speed control However, they tend to be;– Expensive Sophisticated drives More complex DC motor– DC motors historically requiredsignificant maintenance31

ECM Motors? Newer technologycombining a DC Drive anda DC motor in oneenclosure Higher efficiency thanmany single phase motors. Lower cost than AC VFDand AC motor Lower maintenance coststhan traditional DC motorsAC VFD Drive Pulse Ratings Number of current pulses per cycledepends on rectifier configuration. 3 Phase VFD’s use multiples of 6– (6, 12, 18, 24, etc.) The problematic odd harmonicfrequencies can be calculated based ondrive pulse number and compared to themeasured harmonic frequencies. Higher the pulse #:– Lower harmonics– More complex & costly the drive32

VFD Harmonics VFD’s produce specific harmonicfrequencies with high magnitudes.– This “fingerprint” can help determinewhere harmonics are coming from. The drive pulse number can be foundfrom the manufacturer or drivespecification sheet.– The higher the drive pulse number, thehigher the problematic harmonicfrequencies become.– Because the lower order harmonicfrequencies are generally the mostproblematic, a higher drive pulse numbereliminates the most common problemfrequencies.Pulse Ratings & Harmonics Characteristic harmonic current is: h n x p 1– Where h is the harmonic, n is an integer, and p drive pulses 6 Pulse Driveh 1x6 1 5&7h 2

Variable Frequency Drives Presented by: Greg Stark, P.E. September 10, 2014 Sponsored by: Variable Frequency Drives (VFD’s) Popular speed control devices used in industrial, commercial and residential applications. –Huge energy savings potential operating centrifugal fans, pumps and compressors Vary frequency of electrical

Related Documents:

1 All VFD-V drives are Constant and Variable Torque rated. 2 All VFD-V drives are Nema 1 rated enclosures. 3 All VFD-V drives are UL, cUL and CE marked. 4 An EMI filter is required to conform to the CE EMI directive 5 Please refer to the Accessory list for optional items used with the drives above. 6 All VFD-V drives are capable of 0 - 3000Hz in.

Variable Frequency Drive Troubleshooting Tutorial Figure 2: Variable Frequency Drive Welcome to the VFD Troubleshooting Tutorial. This guide will help you step through the processes of troubleshooting a VFD. Please note, every VFD will be different; different housings, components, locations, terminals, specifications, etc so your VFD may not

1. Using Variable Frequency Drives (VFD) to save energy and reduce emissions in newbuilds and existing ships Energy efficiency plays the most important role in CO 2 emission reductions, accounting for up to 53% of total CO 2 emission reductions. In pump and fan applications onboard vessels, using Variable Frequency Drives (VFD) can cut

Feed a VFD feed or combination VFD feed to animals by no later than the expiration date on the VFD. Provide a copy of the VFD order to the distributor if the issuing veterinarian sends the distributor's copy of the VFD through you, the client. Maintain a copy of the VFD order for a minimum of 2 years

C. Energy Saving With VFD in Fan Fig. 7: Ideal energy consumption with VFD Fig. 8: VFD fan control The fixed speed motor load application such as the forced obtained by variable speed drive by using fan affinity laws. By using a Variable Frequency Drive (VFD) to slow down a fan or pump motor speed from 100% to 50% can save as 80% of energy.

The VFD system must be designed and fabricated by a UL-listed panel shop for UL508C VFD systems. New VFD-driven motors must be designed for VFD applications and be equipped with shaft grounding rings and insulated bearing carriers, depending on the application and horsepower. A minimum level of VFD

VFD Training 2010. Training Agenda 1. Why use a VFD / Proper control of systems for efficiency 2. Using all VFD efficiency features 3. VFD theory of operation 4. Basic power structure . VFD temperature, trip ID, trip reset (remote), load "health" (plugged pump, stuck valve, etc), man-auto control, KWH and much more!