M0310 MODBUS To HART Module User Manual

1y ago
8 Views
2 Downloads
1.58 MB
37 Pages
Last View : 1m ago
Last Download : 3m ago
Upload by : Camryn Boren
Transcription

M0310 MODBUS to HART ModuleUser ManualMicrocyber Corporation

Caution1. Please don‟t take off/install components at random.2. Please check if the power meets the power request in the User Manual.VersionV2.0Disclaimer of LiabilityWe have reviewed the contents of this publication to ensure consistency with thehardware and software described. Since variance cannot be precluded entirely, wecannot guarantee full consistency. However, the information in this publication is reviewedregularly and any necessary corrections are included in subsequent editions.Microcyber Corporation 2016The technical data may change at any time.

Table of Contents1.Overview1.1Conversion Logic . 11.2Analog Current Output . 21.3Configure Interface . 31.4Hardware User Interface. 41.5Software User Interface . 61.6Dimensions . 72.Quick Configuration92.1Configuration Tool Introduction . 92.2To Configure Modbus Inteface . 152.3To Configure Device Variables . 162.4To Configure Dynamic Variables . 172.5Running Inspection . 183.Other Configuration203.1To Configure Device Status . 203.2To Configure PV Range . 223.3To Configure Scaling Factor . 243.4Debug Operation of Calibration Area . 243.5Data Save and Restore . 253.6Batch Download . 253.7To Modify Manufacturer ID and Device Type . 264.5.1Technical Specification284.1Basic Parameters. 284.2Electrial Interface . 28Troubleshooting30Annex 1 Model Selection31I

Figure DirectoryFigure 1.1 Data Mapping Logic Diagram . 1Figure 1.2 Wiring Diagram to Configure HART Module . 3Figure 1.3 Hardware User Interface Diagram . 4Figure 1.4 Front Dimensions of HART Module. 8Figure 1.5 Front Back Height Dimensions of HART Module . 8Figure 2.1 Configuration Software Icon and Intial Interface .10Figure 2.2 Poll Online HART Module .11Figure 2.3 TAB of HART Module .11Figure 2.4 TAB of Gateway Configuration .12Figure 2.5 Function Menu Tree .14Figure 2.6 Modbus Communication Parameters .15Figure 2.7 Device Variable Configuration .16Figure 2.8 Assignments from Device Variable to Dynamic Variable .18Figure 2.9 Device Scan .19Figure 3.1 HART Device Status .20Figure 3.2 Device Status .21Figure 3.3 HART Extended Device Status .22Figure 3.4 PV Range Operation .22Figure 3.5 PV Range Operation Examples .23Figure 3.6 Debug Calibration Function .24Figure 3.7 Data Save and Restore .25Figure 3.8 Batch Download .26Figure 3.9 Manufacturer Information Configuration .26II

Table DirectoryTable 1.1 Two Groups Fixed Output Current of HART Module. 3Table 1.2 Pin Definition List of HART Module Socket . 5Table 1.3 HART Module Working Status Indication List. 6Table 1.4 Command List Supported by HART Bus Interface . 6Table 1.5 Feature List of Modbus Communication Interface . 7Table 1.6 Command List Supported by Modbus Communication Interface . 7Table 2.1 Modbus Communication Parameters .15Table 2.2 Device Variable Configuration .16Table 4.1 Basic Parameters .28Table 4.2 Electrical Interface .28Table 5.1 Troubleshooting .30III

http://www.microcyber.cn1. OverviewMicrocyber Corporation (hereinafter referred to as “Microcyber”) hascustomized many built-in protocol converting modules for the majority of fielddevice manufacturers, supporting to connect MODBUS RTU protocol(hereinafter referred to as “MODBUS” protocol) slave device into a variety offieldbus system. The function of M0310 built-in MODBUS to HART module(hereinafter referred to as "HART module") is to convert MODBUS slavedevice into HART slave device.1.1Conversion LogicHART module can convert MODBUS flow / level instrument to HART flow /level instrument.HART Module (M0310) is a built-in converting module, converting MODBUSinput device into HART current output device. HART module is built intoMODBUS input device (measure instruments, like flow, level etc.), and thenMODBUS application layer protocol is run by TTL level signal. HART moduleas MODBUS master and HART slave, converts data registers (such as inputregister, holding register) of MODBUS device into all the dynamic variables ofHART commands. For example, holding register of one flow meter withaddress 30000 (range 1-65536) contains instantaneous flow value. Then wemay configure the holding register to device variable 0 (range 0-5) of HARTmodule. And nominate device 0 as Primary variable (or Secondary, Teritary,Quatenary variable). Converting logic is shown in the figure below.Data register 3Data register 4Data register 5Data register 6MODBUS slaveMapping from data register todevice variableData register 2Device variable 0Device variable 1Device variable 2Device variable 3Device variable 4Mapping from device variable todynamic variableData register 1PV4-20mAAnalogchannelSVTVQVHART dynamicvariableMODBUS to HART ModuleDevice variable 5Figure 1.1 Data Mapping Logic Diagram1

http://www.microcyber.cnHART Module as a universal product will face with different interface featuresof various MODBUS devices (slave address, baud rate, parity, etc.), datastorage mode (data register address, data type, sequence of bytes, etc.) andend users‟ requirements to HART dynamic variable allocation (data registermapping to device variable, device variable mapping to dynamic variable). Allabove may be configured again by device manufacturer.Microcyber can provide PC configuration software for above configuration.Also provide HART module DD files, which is for HART master station (PC,communicator) which owns DD file analytical ability. HART module isconfigured through HART communication from HART master station, toconfirm interface features between HART module and MODBUS device, datastorage mode and mapping from device variable to HART dynamic variable.After above configuration, HART master devie can access dynamic variable ofHART module with HART commands, and realize the data‟s digitaltransmission from MODBUS data register (such as instaneous flow values ofmemory flowmeter) to HART master.1.2Analog Current OutputIn HART module, the measuring value of Primary variable (PV) is transmittedby 4-20mA analog current output value. For example, flowmeter‟s instaneousflow is named as HART primary variable. When instanenous flow valueachieves half of measuring range. HART module outputs 12.000mA.Running HART module continuously compares primary variable value withupper and lower limit of its range. If primary variable value reaches to its upperlimit, HART module outputs analog current 20.000 mA. If primary variablevalue down to zero, HART module outputs analog current 4.000 mA.If primary variable value exceeds its upper and lower limit, HART moduleoutputs a fixed current, indicating primary variable exceeds range, and thecurrent value is called saturated output current. If primary variable value ismore than upper limit, HART module outputs fixed 20.800mA; if less than2

http://www.microcyber.cnlower limit, HART module outputs fixed 3.800mA.HART module has another group of fixed current used for fault alarm, whichcan be selectd by a DIP switch on HART module for high or low current alarm.If selecting high current alarm, when fault found, HART module outputs 21.750mA. If selecting low current alarm, when fault found, HART module outputs3.750 mA.Table 1.1 Two Groups Fixed Output Current of HART ModuleTransfinite Direction of Primary Variable (not optional)Saturated Output Current ValueExceed lower limit3.800mAExceed upper limit20.800mAFault alarm mode (Alternative)Alarm output current valueLow current alarm3.750mAHigh current alarm21.750mAWhen HART module polling address isn‟t set as „0‟, no matter how much isprimary variable value, HART module analog channel outputs fixed 4.000mA.Only polling address is set as „0‟, HART module outputs 4-20mA analogcurrent corresponding to primary variable.1.3Configure InterfaceHART module is between HART bus and MODBUS device. It connects themain control board (hereinafter referred to as the "user board”) of the fielddevice through the socket on the back. It connects HART bus outside, andconnects field device inside, see Figure 1.2 below.Figure 1.2 Wiring Diagram to Configure HART Module3

http://www.microcyber.cnFor example, taking PC as master device, connect field device (four wiresystem) via HART bus. HART bus, which is composed of DC power supply(POWER1: 9-36VDC) and series-resistance (250Ω), is connected into HARTModule; And field device is powered by another two wires. PC connects HARTmodem via USB (or RS-232) interface, and the other side of HART modem(Microcyber‟s) is nonpolar crocodile clips clipped on both sides of matchedresistance. Use Microcyber‟s configuration software to configure HARTModule. After configuration, HART module and field device become a whole,and can be connected into other HART network as HART device.When configuration is required to complete by the communicator having DDanalysis capability, just substitute PC and HART modem in Figure 1.2 abovewith the communicator.1.4Hardware User InterfaceHART module uses 2.54mm spacing IDC16, 2x8 socket (JP3) to connect userboard. Pin number definition is in Figure 1.3. Pin function explanation is inTable 1.2. If HART bus runs through user board, it may be lead in HARTmodule via two pins in the socket.Figure 1.3 Hardware User Interface Diagram4

http://www.microcyber.cnTable 1.2 Pin Definition List of HART Module C Isolated Power2IGNDFor VCC3I/RSTReset, low active4IGNDFor VCC5OTxD6O-Reserved7O-Reserved8IRxDThe receive of MCU UART9O-Reserved10OLED11I/OHART bus 12I/OHART-HART bus he send of MCUHART UARTFor LED-, HARTcommunication indicatingShown in Figure 1.3, HART module has another reserved bus interface. It isused to connect HART bus directly when HART bus not running on userboard.HART module and user board master controller are connected by isolated TTLlevel. Both sides of isolation respectively are two MCU UART interfaces. Toachieve user board circuit isolated with HART bus, 5 VDC isolation powersupply shall be provided by user board. HART module power supply is fromHART bus. Because HART module doesn‟t supply power to user board, theHART module can only support 3-wire, 4-wire HART device.As shown in Figure 1.3, HART module has two DIP switch, “AL” is fault alarmcurrent selection DIP switch, “WP” is write protect DIP switch. When AL isturned to OFF, high current alarm selected; When AL is turned to ON, lowcurrent alarm selected.When write protect DIP switch is turned to OFF side, write enabled state is set,means not write protect, HART master can configure HART module; Whenwrite protect DIP switch is turned to ON, write protect state is set, unable toconfigure HART module.HART module is provided with two LED indicating lights, used to indicate the5

http://www.microcyber.cncurrent working status.Table 1.3 HART Module Working Status Indication ListInitial Power-upContinuousWork1.5LED1LED2Status DescriptionLight onLight onModule initialization, not enter working statusNormallyNormallyononTwinkle——Indicate there‟s HART communication at present——TwinkleIndicate there‟s Modbus communication at presentLight offLight offIndicate there‟s no any communication or fault statusAfter module initialization, no any HART and Modbus communicationSoftware User InterfaceMODBUS link and application layer standard is used between HART moduleand user board. HART module is master station, user board is slave station.HART fieldbus interface of HART module executes HART 7.0 protocol, andsupports BURST mode operation. Common and general commands areshown in Table 1.4.Table 1.4 Command List Supported by HART Bus InterfaceCommonGeneralCommand NameCommand No.Command NameCommand No.0Read Unique Identifier33Read Device Variables1Read Primary Variable34Write Primary Variable Damping Value35Write Primary Variable Range Values36Set Primary Variable Upper Range Value23Read Loop Current and Percent ofRangeRead Dynamic Variables and LoopCurrent6Write Polling Address37Set Primary Variable Lower Range Value7Read Loop Configuration40Enter/Exit Fixed Current Mode8Read Dynamic Variable Classifications41Perform Self Test9Read Device Variables with Status42Perform Device Reset43Set Primary Variable Zero11Read Unique Identifier Associated withTag12Read Message44Write Primary Variable Units13Read Tag, Descriptor, Date45Trim Loop Current Zero (4.000mA)46Trim Loop Current Gain (20.000mA)Write Primary Variable Transfer 15Read Device Information4716Read Final Assembly Number4917Write Message50Read Dynamic Variable Assignments18Write Tag, Descriptor, Date51Write Dynamic Variable Assignments19Write Final Assembly Number53Write Device Variable Units20Read Long Tag59Write Number of Response Preambles6Write Primary Variable Transducer SerialNumber

http://www.microcyber.cnRead Unique Identifier Associated with21Long Tag105Read Burst Mode Configuration22Write Long Tag107Write Burst Device Variables38Reset Configuration Changed Flag108Write Burst Mode Command Number48Read Additional Device Status109Burst Mode ControlFactory default polling address (short address) of HART module is „0‟.Serial transmission mode supported by HART module is Modbus RTU mode.Serial communication interface feature supported is shown in Table 1.5.Table 1.5 Feature List of Modbus Communication InterfaceSlave addressDefault parameterOptional range11-247Baut rate96001200,2400,4800,9600, 9200,35700,38400,57600Data bits87, 8 (this version only supports ModbusRTU, so 8-bit is valid)Stop bits11, 2EVENODD,EVEN,NONELower-High OrderLow-High Order,High-Low OrderParityCRC verificationMODBUS communication interface of HART module supports the followingMODBUS commands.Table 1.6 Command List Supported by Modbus Communication InterfaceCommand No.1.6Command NameNo.Command Name1Read coil status4Read input register value2Read discrete input status5Write coil3Read holding register value16Write multi register valuesDimensionsHART module PCB depth is 1.6mm, rectangular. Front (shown in Figure 1-4),the highest component is 5mm from board surface; Back, the highest is 9mmfrom board surface. Others all are surface mount components, lower than4mm. Length, width, fixed hole‟s location, etc. of HART module are shown infigure below.7

2.52.62.665.02.5Figure 1.4 Front Dimensions of HART ModuleUnit: mm单位:mm5.01.69.0Figure 1.5 Front Back Height Dimensions of HART ModuleIDC16(2x8) standard socket of 2.54mm spacing is used on backside, to pluginto user board; HART module has another 3 fixed holes of Dia.3.0mm, usedto fix HART module onto user board.8

http://www.microcyber.cn2. Quick Configuration2.1Configuration Tool IntroductionAs previously mentioned, Microcyber can provide PC configuration softwarefor HART module configuration. Or provide HART module DD files for HARTmaster station (PC, communicator) which owns DD file analytical ability. Heretake PC configuration software as an example, hardware connection is shownin Figure1-2, connection description is shown in Section 1.4.About usage and status description of HART modem, refer to “HART ModemDatasheet” of Microcyber.About installation and general operation of PC configuration software, refer to“HART PC Configuration Tool” of Microcyber.Here only introduce HART module configuration and simple general operation.After wiring according to Figure1-2, and electrifying field device with HARTmodule, double-click shortcut iconHARTconfigurationsoftwareon PC which has been icrocyber\HartMPT\HartMPT.exe"), enter initial interface of HART PCconfiguration software, see figure below:9

http://www.microcyber.cnFigure 2.1 Configuration Software Icon and Intial Interface„COM3‟ in Figure 2.1 is Windows system‟ virtual serial port used for USBinterface HART modem. If driver of HART Modem (virtual serial port chip) iscorrectly installed, green light will be on when HART modem is inserted intoPC; otherwise, check wiring and driver‟s installation result. After module iselectrified, check status of HART module‟s LED1 and LED2, if both arenormally on, that means HART module is on standby.In webview of intial interface, right-click serial port node (COM3), select „singlenode‟ „node 0‟. Configuration software sends „universal command 0‟ toquery if HART device with short address „0‟ is online.10

http://www.microcyber.cnFigure 2.2 Poll Online HART ModuleFactory default short address of HART module is „0‟, without error for wiringand power supply, HART configuration software will list query result, shown inFigure 2.2. The device with short address „0‟ in Figure 2.2 (Hereinafter called 0device) is online, click 0 device, after continuous communication betweenconfiguration software and HART module, change of TAB webview is shown inthe following figure.Figure 2.3 TAB of HART Module11

http://www.microcyber.cnHART module, compared with other type of HART device, its TAB 'ModBus toHart Setting‟ and ManufactureInfoConf are unique, and other 4TABs shown inthe figure above are shared by all HART devices. Here only emphasizes 'Modbus to HART Setting‟ of HART module, as shown below:Figure 2.4 TAB of Gateway ConfigurationTo configure HART module, firstly modify ' ModBus to Hart Setting \ DetailedSetup \ Normal Operation‟ option groupt to 'Configuration Mode‟. Under thismode, the user can operate other functions of „Detailed Setup‟; underconfiguration mode, HART module won‟t send Modbus data to user board ininitiative and cycle mode.To configure HART module, there are three steps:1. Configure Modbus interface; 2. Configure device variable; 3. Configuredynamic variable.1. Configure Modbus interface, that is to use 'ModBus to Hart Setting \ Detailed12

http://www.microcyber.cnSetup \ Modbus Variables‟, configure Modbus interface based on differentModbus device interface features.2. Configure device variable, that‟s to use 'ModBus to Hart Setting \ DetailedSetup \ Device Variable‟, configure device variable based on different Modbusdevice data storage mode, i.e.data register is mapped to device variable.3. Configure dynamic variable, that‟s to use 'ModBus to Hart Setting \ DetailedSetup \ Device Variable Assignments‟, configure dynamic variable based onrequirements to HART dynamic variables from different end users, i.e.devicevariable is mapped to dynamic variable.As mentioned earlier, configuration function of the software can also berealized by HART master station (such as PC, communicator) with DD fileanalysis capability. The functions decribed by HART module DD files arebasically same with HartMPT configuration software. The figure below isfunction menu tree of DD files, and the user can quickly find the parameters toconfigure in 475 communicator, etc. by the function menu tree.13

http://www.microcyber.cnStatus2-1Test Device2-1-11 Status2 Test self3 Device TestProcess Variables12341PVPV % rngePV LoopCurrentPv Range12345678Device 0Status group 0Status group 1Status group 2Status group 3Status group 4Status group 5Ext dev statusOperate mode 14-2-13 USL4 LSL5 Min span6 URV7 LRVRe-range2-4-11 Range ValuesDevice 12 Apply Values4-2-2Anolog output2-4-2Diag/Service1 Test Device22 CalibrationCalibrationBasic Setup312345672-4TagLong TagPv UnitPV xfer fncntPV DampRange valuesDevice information1 Re-range2 Anolog output3 Sensor trim4 Coils trim5 Registers trim6 Recall factory trim2-4-32-4-4Coils trimRegisters trimDevice 31 Registers trim2-4-61 Manufacturer2 Model3 Dev id4 Cfg chng count5 Tag6 Long Tag7 Date8 Write project9 Descriptor10 Message11 Final asmbly num12 Revision #’s1 Classe2 Unit3 USL4 LSL5 Min span6 URV7 LRV1 Coils trim3-7On lineDevice 24-2-3Sensor trim2-4-51 Classe2 Unit3 USL4 LSL5 Min span6 URV7 LRVPV Loop currentPV Alrm typPV Channel flagsPV Xfer fnctnLoop current modeLoop testD/A trim1 Zero trimDevice information1 Process Variables2 Diag/Service3 Basic Setup4 Detailed Setup5 Review12345671 Classe2 Unit4-2-4Recall factory trim1 Classe2 Unit3 USL4 LSL5 Min span6 URV7 LRV1 Restore to default factory2 Save as factory3 Restore to factoryDevice 44-2-53-7-12Revision #’s1 Classe2 Unit3 USL4 LSL5 Min span6 URV7 LRV1 Universal rev2 Fld dev rev3 Software revDevice 54-2-63 USL4 LSL5 Min span6 URV7 LRVDevice Variable AssignmentsDetailed Setup41 Device Variable Assignments2 Sensors3 MODBUS4 Signal condition5 Output condition6 Device information7 Configuration Mode4-15MODBUS VariablesSensorsReview1 Model2 Manufaturer3 Write project4 Device id5 Cfg chng count6 Max dev vars7 Tag8 Long tag9 Descriptor10 Message11 Date12 Final asmbly num13 Universal rev14 Fld dev rev15 Software rev16 Poll addr17 Loop current mode18 Num req preams19 Num resp preams1 PV is2 SV is3 TV is4 QV is4-3-14-212345674-34-3-24-3-3MODBUS VariablesDevice statusPV RangeDevice variable 0Device variable 1Device variable 2Device variable 3Device variable 4Device variable 54-51234PV LRVPV URVPV % rngePV Damp4-5-1Output condition1 Analog outputDevice information1 Manufacturer2 Model3 Dev id4 Cfg chng count5 Tag6 Long Tag7 Date8 Write project9 Descriptor10 Message11 Final asmbly num12 Revision #’sPV Range1 PV Range Source2 PV Range OptionDevice variable 04-3-4Analog output1 PV Loop current2 PV alrm typ3 PV Channel flags4 PV Xfer fnctn5 Loop current mode6 Loop test7 D/A trim4-5-2Hart output1 Poll addr2 Num req preams3 Num resp preams1 Default Unit2 Modbus function Code3 Register address4 Register Date Type5 Scaling Factor6 Uper Register Address7 Lower Register AddressDevice variable 24-3-64-6-121 Default Unit2 Modbus function Code3 Register address4 Register Date Type5 Scaling Factor6 Uper Register Address7 Lower Register AddressDevice variable 14-3-52 HART output4-6Device Status1 Device Status register address2 Device Status Bit parttren3 Register Data TypeSignal Condition4-41 Address2 Baud Rate3 Data Bits4 Parity5 Stop Bits6 CRC OrderDevice 0Device 1Device 2Device 3Device 4Device 5Max dev varsModbus1234567891 Classe2 UnitRevision #’s1 Universal rev2 Fld dev rev3 Software rev1 Default Unit2 Modbus function Code3 Register address4 Register Date Type5 Scaling Factor6 Uper Register Address7 Lower Register AddressDevice variable 34-3-71 Default Unit2 Modbus function Code3 Register address4 Register Date Type5 Scaling Factor6 Uper Register Address7 Lower Register AddressDevice variable 44-3-81 Default Unit2 Modbus function Code3 Register address4 Register Date Type5 Scaling Factor6 Uper Register Address7 Lower Register AddressDevice variable 54-3-9Figure 2.5 Function Menu Tree141 Default Unit2 Modbus function Code3 Register address4 Register Date Type5 Scaling Factor6 Uper Register Address7 Lower Register Address

http://www.microcyber.cn2.2To Configure Modbus IntefaceTo unify communication parameter is the keypoint that HART module is able tocorrectly communicate with user board, the communication between them isModbus-RTU protocol. To use 'ModBus to Hart Setting \ Detailed Setup \Modbus Variables‟ of configuration software, the user can configure Modbusinterface according to interface features of Modbus device (user board), asshown in Figure 2.6:Figure 2.6 Modbus Communication ParametersParameter Meaning:Table 2.1 Modbus Communication ParametersFunction NameAddressBaud RateData BitsParityStop BitsCRC OrderFaultUsageParametersModbus slave device addressThebaudrateusedwhen1HARTmodulecommunicate with user boardLength of data bits when HART module communicatewith user boardBytes use parity mode: odd parity, even parity, noparityNumber of stop bits9600bps8EVEN1The last two-byte CRC sending order of Modbusprotocol data packetLow-High OrderOnly when all communication parameters in Table 2.1 are fully tallied withModbus device interface features, normal communication can be ensured.After setting parameters, click „Apply‟ button to save configuration data intoHART module. To communicate with the communication parametersdescribed in Table 2.1 when HART module exchanges data with user board.15

http://www.microcyber.cn2.3To Configure Device VariablesTo configure device variable, that means to configure Modbus device data(such as instantaneous flow, cumulative flow, velocity, medium indensity,medium temperature, etc. of flow meter) information into the device variable ofHART module. HART module can support 6 device variables‟ configuration.Using „ModBus to Hart Setting \ Detailed Setup \ Device Variable‟ to configure,detailed configured information is shown in Figure 2.7:Figure 2.7 Device Variable ConfigurationUnder quick configuration, meaning of each item is shown in Table 2.2.Table 2.2 Device Variable ConfigurationDevice Variable n (n 0 5)Function NameUsageData type of user Modbus device, according to theClassdifferent type, select the corresponding item (such asvolume flow rate, temperature, pressure, density, etc.) inthe 'Type' drop-down list.UnitUSLLSLDevice data current used and displayed unit (unit of PV)Maximum limit of device variable n acquired by user‟sModbus deviceMinimum limit of device variable n acquired by user‟s16

http://www.microcyber.cnModbus deviceMin SpanRange span, usually set as sensor range upper limitdivied by 100URVBetween upper and lower limit of sensor rangeLRVBetween upper and lower limit of sensor rangeDefault UnitVariable value unit read from Modbus deviceModbus Function CodeFunction code sent out when reading device variable nRegister AddressRegister Data TypeData register address in Modbus device of devicevariable nByte order in Modbus data register of device variable nAmong them, range upper and lower limit can be modified only when currentdevice variable mapping is primary variable; Here, range upper/lower limit ofdevice variable are the same parameters with that of HART device.According the number and important degree, device data of Modbus device isassigned to 6 device variables respectively. After configuration, click on 'Apply'button to save the data into HART

MODBUS input device (measure instruments, like flow, level etc.), and then MODBUS application layer protocol is run by TTL level signal. HART module as MODBUS master and HART slave, converts data registers (such as input register, holding register) of MODBUS device into all the dynamic variables of HART commands.

Related Documents:

3. System description 5 3.1 Modbus 5 3.2 CIM 200 Modbus RTU 5 3.3 CIM 260 3G/4G cellular Modbus 5 3.4 CIM 500 Modbus TCP 5 4. Specifications 6 4.1 CIM module 6 4.2 CIM 200 Modbus RTU 6 4.3 CIM 260 3G/4G cellular 7 4.4 CIM 500 Modbus TCP 7 5. CIM 200 Modbus RTU setup 8 5.1 Setting the Modbus transmission speed 8 5.2 Setting the stop bits and the .

Modbus/TCP Modbus Master/Slave A Modbus master/slave network provides a protocol for data transfer and programming with a single RTU master and up to 247 slave . The Modbus/TCP KEPServer driver supports Modbus and Mailbox device models. Modbus Device Model. Publication 2711P-UM002B-EN-P - March 2007 Modbus Applications PanelView Plus

system functions as a Modbus Slave to the external control system that is the Modbus Master. The Modbus/CAN bus I/O Module communicates with the . Elemec3. system using a CAN bus and with the third party control system using the Modbus protocol over RS-485 serial data lines. The CAN bus and Modbus cabling connects to the I/O module with RJ45 jacks.

User Guide: FAAST XT Fire Alarm Aspiration Sensing Technology Modbus Protocol Schema 10 5 Rev A Modbus Resources 1. Modbus Application Protocol Specification, Version 1.1b3, Modbus Organization, Hopkinton, MA, 2012 2. Modbus over Serial Line Specification and Implementation Guide, Version 1.02, Modbus Organization, Hopkinton, MA, 2006

2.2 Modbus RTU connection to the SIMOCODE pro device SIMOCODE pro Modbus RTU 12 Configuration Manual, 04/2015, A5E33498234002A/RS-AA/001 2.2 Modbus RTU connection to the SIMOCODE pro device Connecting Modbus RTU to the SIMOCODE pro V Modbus basic unit Modbus RTU can be connected to the SIMOCODE pro V basic unit both viathe connectingFile Size: 1MB

NP ModBus TCP N System Configuration Example 8 Add a ModBus Master Port and Node Expand the "MB NP Modbus TCP" branch on the I/O Configuration Form by clicking on the . Expand the Modbus TCP by clicking on the . Expand the "ModBus Port NP ModBus TCP Master Port" branch on the I/O Configuration Form by clicking on the . Expand the Nodes branch on the I/O Configuration Toolbox by .

Modbus(2) AirTF . Modbus(3) RH . Modbus(4) WS_mph . Modbus(5) WindDir . Modbus(6) SlrW . Modbus(7) Rain_in . NextScan . EndProg . Near the end of the program are several lines that copy values from measurements to values within an array. For example, this line copies the air temperature measurement into the second value of an array called .

Titulli I diplomuar në administrim publik Numri në arkiv i akreditimit [180] 03-619/9 Numri në arkiv i akreditimit [240] 03-1619/19 (10.11.2017) Vendimi për fillim me punë 03-1619/19 (10.11.2017) Data akreditimit 21.03.2017 Përshkrimi i programit Programi i administrimit publik ka një qasje multidisiplinare të elementeve kryesore të studimit në fushën e Administratës publike dhe .