Chapter News - Hawaii

1y ago
23 Views
2 Downloads
1.69 MB
11 Pages
Last View : 1d ago
Last Download : 3m ago
Upload by : Lilly Andre
Transcription

Chapter NewsNorthern California/Hawaii NEBB ChapterFebruary 2015Disclaimer: The views, opinions and conclusions expressed in this publication are those of the authors and do not necessarily reflectthe official policy or position of the NEBB Chapter.this issueUnderstanding Chilled BeamSystems Part 2 P. 1ASHRAE Hawaii ChapterMeeting P. 7Featured Member P. 8NEBB Chapter Annual Meetingin Hawaii P.10Calendar of Events P.112015 N. Cal/Hawaii ChapterBoard of DirectorsSteve Smith, PresidentPacific Test & Balance, Inc.understandingChilled Beam SystemsPart 2 by TraneVic Congi, President ElectCarter Air BalanceArt DeLeon, Technical ChairAlthough chilled beam systems have been used in Europe and Australia for many years, theyare a new concept to many in the U.S. Those interested in learning more about these systems, as with any new concept, are faced with the task of discerning its true strengths andweaknesses. The goal of this article is to investigate the common claims about chilled beamsystems. This is part two.Table 1 demonstrates the impact of these three functions for an example office space. Using the default occupant density from ASHRAE 62.1-2007, theminimum outdoor airflow required for an office space is 0.085 cfm per squarefoot of floor area.Based on typical occupant latent loads in an office space, if primary airflow isonly 0.085 cfm/ft2, it must be dehumidified to 47 F dew point to offset thespace latent load and maintain the indoor dew point at 55 F (75ºF dry bulband 50 percent RH). However, if primary airflow is increased, the primary airwould not need to be dehumidified as much (Table 1).Final Air Balance, Inc.Amber Ryman, Education ChairACCODaniel Wong, Marketing ChairWestern Allied MechanicalCurtis Worley, Past PresidentPacific Test & Balance, Inc.Audrey KearnsNEBB Chapter Coordinator

Finally, based on typical sensible cooling loads in an office space, catalog performance data from several manufacturers of active chilled beams indicates that between 0.35 and 0.40 cfm/ft2 of primary air is required to provide therequired sensible cooling capacity.For this same example office space, the design airflow delivered by a conventional VAV system would be 0.90 cfm/ft2. At design cooling conditions, primary airflow required for the ACBs serving this space is 60 percent less thanfor the conventional VAV system. However, this does not translate to a 60 percent reduction in fan energy use, aswill be discussed later in this EN under the claimed advantage 3 section.As you can see from this example (Table 1), the primary airflow required for space sensible cooling in the ACB systemis four times larger than the minimum outdoor airflow requirement of 0.085 cfm/ft2. Even if this project was beingdesigned to achieve the "Increased Ventilation" credit ofLEED 2009 (which requires 30 percent more outdoor airthan required by ASHRAE 62.1-2007), the required outdoorairflow would still be much lower than the primary airflow required for space sensible cooling.A survey of performance data from various chilled beammanufacturers indicates that the typical primary airflow ratefor active chilled beams ranges from 0.30 to 0.70 cfm/ft2.This is typically higher than the minimum outdoor airflow required by ASHRAE 62.1-2007 for many applications.Figure 3. Primary airflow (PA) in an active chilledbeam.

In this case, the primary AHU for an active chilled beam system must be designed to either a) bring in more than theminimum required amount of out -door air—which will increase energy use in most climates—or b) mix the minimumrequired outdoor airflow with recirculated air to achieve the necessary primary airflow.Claimed advantage 2: An ACB system can typically achieve relatively low sound levels. Chilled beams do nothave fans or compressors located in (or near) the occupied space, so they have the opportunity to achieve lowsound levels. Of course, most VAV systems can also be very quiet when designed and installed properly. Fanpowered VAV terminals do have fans located near the space, so they can be more challenging.Claimed advantage 3: An ACB system uses significantly less energy than a VAV system, due to 1) significantfan energy savings—because of the reduced primary airflow—2) higher chiller efficiency—because of the warmerwater temperature delivered to the chilled beams—and 3) avoiding reheat—because of the zone-level cooling coils.Is there significant supply-fan energy savings? In some applications, a zone served by active chilled beams mayrequire 60 to 70 percent less primary airflow, at design cooling conditions, than the same zone served by a conventional VAV system (0.36 cfm/ft2 versus 0.90 cfm/ft2 in the previous office space example). However, the differencein annual fan energy use is likely much less because the VAV system benefits from reduced zone airflow at partload, system load diversity, and unloading of the supply fan.1) VAV systems benefit from reduced zone airflow at part load. An active chilled beam relies on primary airflowto induce room air through the coils inside the beam, so the quantity of primary air delivered to the chilled beams istypically constant (not variable). This means that, for this example, primary airflow is 0.36 cfm/ft2 at all load conditions (Figure 4).

In a VAV system, however, primary airflowdelivered to the zone is reduced at partload. Assuming a 30 percent minimum airflow setting for the VAV terminal, primaryairflow to this example office space variesbetween 0.90 cfm/ft2 at design cooling conditions and 0.27 cfm/ft2 at minimum airflow(Figure 4).If a cold-air VAV system (48 F primary air,rather than the conventional 55 F) is used,however, design airflow for this exampleoffice space is reduced to 0.67 cfm/ft2,which shrinks the difference even further(Figure 4).2) VAV systems benefit from load diversity. Because of load diversity, the centralsupply fan in a multiplezone VAV systemdoes not deliver 0.90 cfm/ft2 on a buildingwide basis. Assuming 80 percent systemload diversity for this example, the supply fan only delivers 0.72 cfm/ft2 (the "block" airflow), at design cooling conditions.For an ACB system, primary airflow delivered to each zone is typically constant (capacity is adjusted by modulating, or cycling, water flow). Therefore,the fan in the centralized, primary AHUmust deliver the sum of the zone primary airflows—the "sum-of-peaks" airflow,rather than the "block" airflow—which is0.36 cfm/ft2 for this example.VAV systems benefit from unloading ofthe supply fan at part load. But reducedairflow (cfm) at part load is only part ofthe story. Fan energy depends on bothairflow and pressure. In a VAV system,as the supply fan delivers less airflow,the pressure loss through the components of the air distribution system(ductwork, diffusers and grilles, airhandling unit, etc.) decreases. The result is that the fan power decreases exponentially (not linearly) as airflow is reduced. Figure 5 depicts the part-loadperformance of the supply fan in a typicalVAV system, according to ASHRAEStandard 90.1.[2]

Using this performance curve, Table 2 and Figure 6 demonstrate how fan power decreases as the supply fan unloads for this office space example. Again, because of load diversity, the supply fan in the VAV system only delivers 0.72 cfm/ft2 at design cooling conditions. For the ACB system, primary airflow (0.36 cfm/ft2), and therefore fanpower, remains constant at all load conditions.

Notice that as soon as the VAV supply fan unloads below 68 percent of design fan airflow,the conventional VAV system is actually usingless fan energy than the constant-volume primary AHU fan in the ACB system (Figure 6).For a cold-air VAV system, this threshold increases to 80 percent of design fan airflow(Figure 7).Considering that the central supply fan in aVAV system typically operates at less than design airflow for much of the year, the actualdifference in fan energy use between the twosystems may be small. And in climates withseveral months of cold weather, the VAV system might actually use less fan energy thanthe ACB system over the year.When operation of the system is consideredover the entire year, the difference in fan energy use is much less than the difference in zoneprimary airflow (at design cooling conditions)might suggest. The actual difference dependson climate, building usage, and design of theair distribution system, so it requires a wholebuilding energy simulation.A business of Ingersoll-RandTrane believes the facts and suggestions presented here to be accurate. However, final design and application decisions are your responsibility. Trane disclaims any responsibility for actions takenon the material presented.CONGRATULATIONS!NEW NEBB TECHNICIANRobert CortezACCO

NEBB ROUNDTABLE TOPIC AT HAWAII ASHRAE CHAPTER MEETINGASHRAE Hawaii Chapter’s November meeting was held at the Plaza Club Honolulu. The meeting topic wasTesting, Adjusting, Balancing Roundtable, and the 3 speakers did a great job reinforcing the values of NEBB andsharing interesting points about our profession. Steve Smith, President of the Northern California/Hawaii NEBBChapter was one of the speakers. Ryan Chang, a NEBB Certified Professional with TAB Engineers, LLC was themoderator for the event.Ryan Chang, TAB Engineers, LLCSteve Smith, Pacific Test & Balance, Inc.

FEATURED ASSOCIATEThermaTherma Corporation, founded in 1967 by Joe and Nicki Parisi, is a full-servicedesign/build mechanical contractor located in San Jose, California. Therma Corporation performed the mechanical installation of many of the founding semiconductor, pharmaceutical, biotechnology, and medical facilities in the San Francisco Bay Area and many are still Therma’s valued customers today. Therma hasalso performed HVAC installation in local office and public buildings that totalmillions of square feet. Therma has a solution-based approach that is tailored toeach client, resulting in efficient and economical designs. Whether it’s a “one off”custom part or a full-service design/build mechanical system, Therma Corporation is an expert at finding the perfect configuration for each client. If it can beimagined - Therma can build it.Therma1601 Las Plumas Ave.San Jose, CA 95133408/347-3400408/347-3535 Faxwww.therma.comTherma is always striving to improve and develop new construction methods thatutilize the most current technology to facilitate today’s needs as well as lookingahead to future demands. Therma’s 280,000-square-foot headquarters includesa 60,000-square-foot ASME-certified fabrication shop that incorporates automated systems, lasers and the newest welding technology. The duct fabrication andpipe prefab facilities are the most state-of-the-art in Northern California. ThermaCorporation embraces change and innovation to continually reinvent itself.In 1998, then-President Bill Clinton held a roundtable at Therma Corporation tolearn more about its “work smart” culture and history of success. And in 2013,Joe and Nicki Parisi, were awarded honorary Doctorates of Humane Letters fromSan Jose State University for their impact on the innovative growth of the BayArea’s mechanical industry.Troy StenstromTherma Corporation employs the most highly trained and experienced designers,installers, and service technicians. Therma’s talented engineering and projectmanagement team can take the most complicated design build project fromschematic design all the way to the completed as-built and commissioning phaseof construction. Therma’s detailers utilize the most current CAD software whichincludes Building Information Modeling (BIM) providing 3D imaging for designcoordination with other trades. Therma Corporation employs more pipe fitter,plumber and sheet metal union trained craftsmen than any other Bay Area mechanical contractor.Therma Corporation has been a NEBB certified firm since 1979. Being NEBB certified complements Therma as a company by delivering to its clients a turn-keyproduct from conceptual design to project completion by providing final Test,Adjust and Balance of the installed systems. The NEBB logo assures the clientthat the system is performing at the highest efficiency and has been adjusted tooperate as designed. Therma is proud to be a part of NEBB because “NEBB is theLong Nguyen

premier internationally recognized certification association forfirms that deliver high performance building systems”. The NEBBstamp of approval on each complete project report instills industry recognized confidence.Therma currently employs two NEBB Certified Professionals. TroyStenstrom graduated with a HVAC Engineering Technology degree from Cal-Poly San Luis Obispo and is a NEBB Certified Professional in the Testing, Adjusting and Balancing (TAB), CleanroomPerformance Testing (CPT), and Sound and Vibration (S&V) disciplines. Long Nguyen graduatedwith an Electrical Engineering degree from San Jose State UniversityTherma Cleanroom Pre-Fabricationand is a NEBB Certified Professionalin the CPT and S&V disciplines. Therma Corporation is also recognized by SheetMetal Workers’ International Association ANSI Accredited International Certification Board (ICB/TABB) as a TAB, Sound and Vibration Testing and HVAC Fire LifeSafety Level 1 and 2 Certified Firm. Therma’s TAB department offers the followingservices: Testing, Adjusting and Balancing (NEBB and ICB/TABB certified professional) HVAC Retro-Commissioning (RCx) Duct Leakage Testing per SMACNA or as specified Cleanroom Performance Testing (CPT) (NEBB certified professional) Biological Safety Cabinet (BSC) (NSF accredited field certifier) Laboratory Fume Hood Testing and Certification (ICB/TABB certified professional)Fabrication Fiber Tube Laser Sound and Vibration Testing (NEBB and ICB/TABB certified professional) As-built mechanical drawing services HVAC system installation, operational analysis, and troubleshooting Fire/Smoke Control System Testing (ICB/TABB certifiedprofessional) Calibration services (Directly traceable to the National Institutes of Standards and Technology (NIST))Therma’s TAB department performs in-house design build services as well as independent planand specification projects.Process Gas Piping InstallationTherma Corporation has completed some of the most technically advanced projects in Silicon Valley and the San Francisco Bay Area for nearly 50 years. They continue to illustrate their ability to meet demanding schedules and budgets while providing the highest levels of quality makingthem a leader in the industry. Over the years, Therma has completed projects for customers such as Intel, IBM, Applied Materials, Apple, Google, Facebook, Stanford University, Santa Clara University, Digital Realty Trust and many more.Sheet Metal Specialty Fabrication

COMMITTEES:Upcoming EventsNEBB CLEANROOM PERFORMANCE TESTING CERTIFIED TECHNICIANSEMINAR AND NEBB FUME HOOD TESTING SEMINAR FOR CERTIFIEDPROFESSIONALSApril 13-15, 2015Honolulu, HawaiiContact the NEBB Office to sign up or to receive more information at www.nebb.orgNEBB ANNUAL CONFERENCEApril 16-18, 2015Hyatt Regency Waikiki Beach Resort & SpaHawaiiContact the NEBB Office to sign up or to receive more information at www.nebb.orgNEBB CHAPTER ANNUAL MEETINGTECHNICAL:Art DeLeon, Final Air Balance , ChairAmber Ryman, ACCOSteve Smith, Pacific Test &Balance, Inc. - NapaGreg Bluhm, CSI, Inc.Vic Congi, Carter Air BalanceDaniel Wong, Western AlliedMechanicalCurtis Worley, Pacific Test &Balance, Inc. - NapaBrent Hahn, Pacific Test & Balance,Inc. - HawaiiCarey Tomasa, - Air Balance HawaiiEDUCATION:Amber Ryman, ACCO, ChairSteve Smith, Pacific Test & Balance,Inc. - NapaSargon Ishaya, PragmaticProfessional Engineers,Vic Congi, Carter Air BalanceJason Huffman, Pacific Test &Balance, Inc. - HawaiiMartin Burke, TSS, Inc.MARKETING:Daniel Wong, Western AlliedMechanical, ChairSteve Smith, Pacific Test &Balance, Inc. - NapaJason Huffman, Pacific Test &Balance, Inc. - HawaiiApril 17, 2015Hyatt Regency Waikiki Beach Resort & SpaHawaiiContact the NEBB Chapter to sign up or to receive more informationTAB CERTIFIED PROFESSIONAL REVIEW SEMINARMay 25-27, 2015Arlington, VAContact the NEBB Chapter to sign up or to receive more informationNEBB WEBINARS AND EDUCATIONAL SEMINARSFor More Training Information visit www.nebb.org.Follow us on Facebook atNorthern California/Hawaii NEBBNorthern California/Hawaii NEBB7100 Stevenson Blvd.Fremont, CA 94538Phone: 510-386-1270E-mail: akearns@nocalhawaiinebb.orgwww.nocalhawaiinebb.org

Understanding hilled eam Systems Part 2 P. 1. ASHRAE Hawaii hapter. Meeting P. 7. Featured Member P. 8. NE hapter Annual Meeting in Hawaii P.10 alendar of Events P.11. . Chilled Beam Systems Part 2 by Trane. Finally, based on typical sensible cooling loads in an office space, catalog performance data from several manufac- .

Related Documents:

Part One: Heir of Ash Chapter 1 Chapter 2 Chapter 3 Chapter 4 Chapter 5 Chapter 6 Chapter 7 Chapter 8 Chapter 9 Chapter 10 Chapter 11 Chapter 12 Chapter 13 Chapter 14 Chapter 15 Chapter 16 Chapter 17 Chapter 18 Chapter 19 Chapter 20 Chapter 21 Chapter 22 Chapter 23 Chapter 24 Chapter 25 Chapter 26 Chapter 27 Chapter 28 Chapter 29 Chapter 30 .

Hindi News NDTV India 317 Hindi News TV9 Bharatvarsh 320 Hindi News News Nation 321 Hindi News INDIA NEWS NEW 322 Hindi News R Bharat 323. Hindi News News World India 324 Hindi News News 24 325 Hindi News Surya Samachar 328 Hindi News Sahara Samay 330 Hindi News Sahara Samay Rajasthan 332 . Nor

TO KILL A MOCKINGBIRD. Contents Dedication Epigraph Part One Chapter 1 Chapter 2 Chapter 3 Chapter 4 Chapter 5 Chapter 6 Chapter 7 Chapter 8 Chapter 9 Chapter 10 Chapter 11 Part Two Chapter 12 Chapter 13 Chapter 14 Chapter 15 Chapter 16 Chapter 17 Chapter 18. Chapter 19 Chapter 20 Chapter 21 Chapter 22 Chapter 23 Chapter 24 Chapter 25 Chapter 26

Hawaii Hawaii Affordable Properties, Inc. 48 (808)322-3422; hawaiiaffordable.com F Waikoloa Gardens; 68-1820 Pua Melia Street Waikoloa; Hawaii Bob Tanaka, Inc. 24 (808)949-4111; F(FPH) Ke Kumu Ekolu 68-3385 Ke Kumu Place; Waikoloa Hawaii; Hawaii Public Housing Authority 20 (808)832-5960 hpha@hawaii.gov;

81 news nation news hindi 82 news 24 news hindi 83 ndtv india news hindi 84 khabar fast news hindi 85 khabrein abhi tak news hindi . 101 news x news english 102 cnn news english 103 bbc world news news english . 257 north east live news assamese 258 prag

DEDICATION PART ONE Chapter 1 Chapter 2 Chapter 3 Chapter 4 Chapter 5 Chapter 6 Chapter 7 Chapter 8 Chapter 9 Chapter 10 Chapter 11 PART TWO Chapter 12 Chapter 13 Chapter 14 Chapter 15 Chapter 16 Chapter 17 Chapter 18 Chapter 19 Chapter 20 Chapter 21 Chapter 22 Chapter 23 .

About the husband’s secret. Dedication Epigraph Pandora Monday Chapter One Chapter Two Chapter Three Chapter Four Chapter Five Tuesday Chapter Six Chapter Seven. Chapter Eight Chapter Nine Chapter Ten Chapter Eleven Chapter Twelve Chapter Thirteen Chapter Fourteen Chapter Fifteen Chapter Sixteen Chapter Seventeen Chapter Eighteen

18.4 35 18.5 35 I Solutions to Applying the Concepts Questions II Answers to End-of-chapter Conceptual Questions Chapter 1 37 Chapter 2 38 Chapter 3 39 Chapter 4 40 Chapter 5 43 Chapter 6 45 Chapter 7 46 Chapter 8 47 Chapter 9 50 Chapter 10 52 Chapter 11 55 Chapter 12 56 Chapter 13 57 Chapter 14 61 Chapter 15 62 Chapter 16 63 Chapter 17 65 .