NEC 240.67 ARC ENERGY REDUCTION TECHNICAL PAPER

NEC 240.67 ARC ENERGY REDUCTION The NFPA 70 National Electric Code (NEC) has been updated for 2020. The NEC update adds a new requirement for Arc Energy Reduction regarding the use of fuses. The new requirement is effective January 1, 2020. (C) Performance Testing. The arc energy reduction protection system shall be performance tested by primary current injection testing or another approved method when first installed on site. This testing shall be conducted by a qualified person(s) in accordance with the manufacturer’s instructions A written record of this testing shall be made and shall be available to the authority having jurisdiction. Previous Requirement There were no previous requirements for fuses regarding Arc Energy Reduction. The requirements for Arc Energy Reduction were previously only applicable to circuit breakers rated 1200 A or higher (NEC 240.87). New Requirement 240.67 Arc Energy Reduction Where fuses rated 1200 A or higher are installed, 240.67(A), (B), and (C) shall apply. This requirement shall become effective January 1, 2020. (A) Documentation. Documentation shall be available to those authorized to design, install, operate, or inspect the installation as to the location of the fuses. Purpose Documentation shall also be provided to demonstrate that the method chosen to reduce clearing time is set to operate at a value below the available arcing current. Arc energy reduction is critical for electrical safety in the workplace. NEC 2011 introduced an Arc Energy Reduction requirement for circuit breakers (NEC 240.87) rated 1200 A and higher. The added circuit breaker requirement has reduced arc-flash injuries since being introduced by lowering fault clearing times. The value of 0.07 s for the new fuse clearing time requirement was chosen to align with circuit breakers using zone selective interlocking. (B) Method to Reduce Clearing Time. A fuse shall have a clearing time of 0.07 seconds or less at the available arcing current, or one of the following means shall be provided and shall be set to operate at less than the available arcing current: (1) Differential relaying However, it should be reinforced that additional arc energy reduction methods ONLY need to be implemented if the specified fuse is greater than 1200 A AND cannot clear the minimum arcing current in less than 0.07 s. (2) Energy-reducing maintenance switching with local status indicator (3) Energy-reducing active arc-flash mitigation system (4) Current-limiting, electronically actuated fuses Effectivity Date (5) An approved equivalent means The code change goes into effect on January 1, 2020. 2020 Littelfuse, Inc. 2 Littelfuse.com

NEC 240.67 ARC ENERGY REDUCTION Supporting Information Using the standard parameters shown below, minimum available arcing currents for various bolted fault current levels can be calculated using the IEEE 1584-2018 equations. A gap distance of 25 mm is used in this calculation as it is common for electrical equipment that typically uses low voltage industrial fuses such as fused disconnects, MCCs, and panelboards. NEC 240.67 is a requirement that relates to arc-fault currents, which is not explicitly defined in NEC. IEEE 15842018 defines arc current as “A fault current flowing through an electrical arc plasma.” Due to the added impedance of the electrical arc plasma, the value of an arcing fault current will always be less than the bolted fault potential. Typically, an estimated bolted fault current potential for a given system is known. However, arc currents may not always be provided for the same system. Using the estimated bolted fault potential and other system parameters, a minimum available arcing current can be calculated using equations in IEEE 1584-2018, IEEE Guide for Performing Arc Flash Hazard Calculations. This document replaces IEEE 1584-2002, which is referenced in “Informational Note No. 3” of NEC 240.67. Unfortunately, the upper bound of IEEE 1584-2018 is 106 kA. When an electrical system can deliver more than 106 kA to the fuse installation point, there is not an industry accepted method of calculating arcing currents based on bolted fault currents. Call 1-800-TEC-FUSE or email techline@littelfuse.com for technical support when a system’s bolted fault current exceeds 106 kA. Electrical System: 50–60Hz, 3-phase Voltage: 208, 480, 600 V ac Equipment Configuration Class: VCB Conductor Gap Distance: 25 mm Bolted Fault Current Levels: 10–106 kA Figure 1 shows the relationship between calculated minimum arcing currents and estimated bolted fault currents from 10–106 kA. The figure assumes the parameters above applied at three voltages: 208, 480, and 600 V ac. FIGURE 1. Relationship between calculated minimum arcing currents and estimated bolted fault currents. 2020 Littelfuse, Inc. 3 Littelfuse.com

NEC 240.67 ARC ENERGY REDUCTION Compliance Table 1 shows which Littelfuse Class L series would be a suitable solution and provide compliance with NEC 240.67 by ensuring a fault clearing time of less than .070 s at calculated minimum arcing currents up to 100 kA. Most Class L fuse ratings greater than 1200 A are shown. A key point of the NEC 240.67 requirement is that a system shall include a method to reduce arc energy only when the clearing time of the fuse is greater than 0.07 s at the available arcing current. If it can be shown the installed fuse has a clearing time of less than 0.07 s using the fuse’s time current curve (TCC), no further consideration is required for compliance. The following three points can give guidance on being compliant with the NEC 240.67 requirement and general electrical safety. 1. Not all fuses are created equal 1.1. Fuse Current Rating Lower fuse ratings will clear a fault faster than higher ratings within the same product series providing arc energy reduction. Some systems may utilize fuses that are oversized for the application. If the specified Class L fuse rating will not clear the arc current in less than 0.07 s, it may be worth recalculating the maximum load current for the system. Noting that Class L fuses can be loaded at 100 % of their rated current, there may be a chance a lower current rating could be utilized leading to compliance. Fortunately, Class L fuses are uniquely designed so that downsizing can occur without equipment changes or adapters. 2. 1.2. Fuse Series Not all Class L fuses series have the same electrical performance. For example, Littelfuse offers three different Class L fuses: KLLU, KLPC, and LDC. Each series offers unique characteristics and fault clearing times. Some series are designed with optimal short circuit and time delay performance (KLPC). Others are designed specifically for exceptional short circuit performance (LDC). The unique designs will therefore lead to varying levels of arcing currents they can clear in less than 0.07 s. Install an Arc-flash Detection System For unique scenarios, a single fuse solution cannot guarantee compliance (see Table 1). In these situations, an energy-reducing active arc-flash mitigation system may need to be installed. Littelfuse offers a full line of arc-flash protection relays that meet the requirement in 240.67(B) (3) and 240.87(B)(4) for an energy-reducing active arc-flash mitigation system. These relays use light sensors installed inside the cabinets and switchgear to detect the formation of an arc flash, and provide a high-speed shunt trip (or undervoltage release) signal in less than 5 ms to a circuit breaker or other interrupting device. This high-speed trip signal can significantly reduce the arc energy by ensuring the system is de-energized as quickly as possible. To fit all types of equipment applications, both single-point sensors and innovative fiber-optic light sensors (8 m or 18 m in length) are available. Sensors include active self-check and use copper wiring to connect back to the relay, ensuring installation flexibility and confidence in system operation. Arc-flash relays are available with as few as 2 sensor inputs, and are scalable to any size of system that is needed. Table 1 helps identify when an active arc-flash relay should be designed into the system when a fuse alone cannot guarantee full NEC 240.67 compliance. See Littelfuse.com/ArcFlash or contact relays@littelfuse.com for brochures, manuals, and detailed application guides. 2020 Littelfuse, Inc. 4 Littelfuse.com

NEC 240.67 ARC ENERGY REDUCTION 3. Safety First This cannot be stressed enough. Personnel safety should always be a priority, and the best way to ensure this is to always put energized conductors into an electrically safe work condition by putting switches into the OFF position. Authorized personnel should always apply lockout/ tagout procedures and approach any conductor as if it were energized. The safest way to work near conductors is when they are de-energized. Even in cases where a maintenance mode is an option, turning the switch OFF provides a safer environment than an activated maintenance mode with the switch ON. When fully de-energizing all conductors is not an option, design features and proper equipment should be implemented to minimize arc-flash energy resulting in maximum personnel safety. 2020 Littelfuse, Inc. 5 Littelfuse.com

NEC 240.67 ARC ENERGY REDUCTION TABLE 1. Littelfuse Arc-Flash Energy Reduction Solutions FUSE RATING MINIMUM ARCING CURRENT 10 KA 15 KA 20 KA 25 KA 30 KA 35 KA 40 KA 45 KA 1200 A RELAY LDC LDC KLPC LDC KLPC KLLU LDC KLPC KLLU LDC KLPC KLLU LDC KLPC KLLU LDC KLPC KLLU 1300 A RELAY LDC LDC LDC KLPC LDC KLPC LDC KLPC LDC KLPC LDC KLPC 1350 A RELAY RELAY LDC LDC KLPC KLLU LDC KLPC KLLU LDC KLPC KLLU LDC KLPC KLLU LDC KLPC KLLU 1400 A RELAY RELAY LDC LDC KLPC KLLU LDC KLPC KLLU LDC KLPC KLLU LDC KLPC KLLU LDC KLPC KLLU 1500 A RELAY RELAY LDC LDC LDC KLPC LDC KLPC LDC KLPC LDC KLPC 1600 A RELAY RELAY LDC LDC LDC KLPC KLLU LDC KLPC KLLU LDC KLPC KLLU LDC KLPC KLLU 1800 A RELAY RELAY RELAY LDC LDC KLLU LDC KLPC KLLU LDC KLPC KLLU LDC KLPC KLLU 1900 A RELAY RELAY RELAY LDC LDC KLPC LDC KLPC LDC KLPC 2000 A RELAY RELAY RELAY RELAY LDC LDC KLLU LDC KLPC KLLU LDC KLPC KLLU 2100 A RELAY RELAY RELAY RELAY RELAY RELAY KLPC KLPC 2200 A RELAY RELAY RELAY RELAY RELAY RELAY KLPC KLPC 2300 A RELAY RELAY RELAY RELAY RELAY RELAY KLPC KLPC 2400 A RELAY RELAY RELAY RELAY RELAY RELAY RELAY KLPC 2500 A RELAY RELAY RELAY RELAY RELAY RELAY KLLU KLPC KLLU 3000 A RELAY RELAY RELAY RELAY RELAY RELAY RELAY RELAY 2020 Littelfuse, Inc. 6 Littelfuse.com

NEC 240.67 ARC ENERGY REDUCTION Notes 2020 Littelfuse, Inc. 7 Littelfuse.com

For more information, visit Littelfuse.com/ArcFlash 2020 Littelfuse, Inc. FORM NO. PF759 Rev: 060820

NEC 240.67 is a requirement that relates to arc-fault currents, which is not explicitly defined in NEC. IEEE 1584-2018 defines arc current as "A fault current flowing through an electrical arc plasma." Due to the added impedance of the electrical arc plasma, the value of an arcing fault current will always be less than the bolted fault potential.

Related Documents:

For Reference Only ARC 8D ARC 10D ARC 12D ARC 15D Dimensions And Specs 1 Recommended Enclosures ARC 8D 2 ARC 10D 2 ARC 12D 3 ARC 15D 3 . .65 cu.ft. .75 cu.ft. .85 cu.ft. Minimum SPL SQ ARC 10D2 ARC 10D4. 3 TOP NOTE: These woo

NEC 3 Professional Services Contract (PSC). NEC 3 Short Contract (ECSC) and Short Subcontract (ECSS). NEC 3 Adjudicator’s Contract (AC). NEC 3 Term Services Contract (TSC). NEC 3 Term Service Short Contract (TSSC). NEC 3 Framework Contract (Framework Contract). NEC 3 Supply Contract (SC).

Dec 02, 2017 · Based on 2017 National Electrical Code (NFPA 70) The Philippine Electrical Code Part 1 2009 Edition was based on NEC 2005 Regularly revised (every three years) to reflect the evolution of products, materials, and installation techniques. NEC 2008, NEC 2011, NEC 2014 & NEC 2017 NEXT NEC REVISION: NEC 2020, 2023, 2026, 2029

High Current Level Arc "Parallel Arc" An Arc Fault That Occurs at 75Amps and higher An Arc Fault That Occurs Line-Line or Line-Neutral Types Of Arcing Faults Low Current Level Arc "Series Arc" An arc fault at low levels down to 5 Amps An arc fault at a break or gap in a single conductor in series with a connected load

5 Location NEC 2008 NEC 2011 NEC 2014 NEC 2017 NEC 2020 Family Rooms AFCI AFCI AFCI AFCI AFCI Dining Rooms AFCI AFCI AFCI AFCI AFCI Kitchens - 125V Receptacles GFCI GFCI AF/GF AF/GF AF/GF Kitchens - 250V Receptacles TM TM TM TM GFCI1 Bedrooms AFCI AFCI AFCI AFCI AF/GF1 Living Rooms AFCI AFCI AFCI AFCI AFCI Garage - 125V Receptacles GFCI GFCI GFCI GFCI GFCI Garage - 250V Receptacles TM TM .

Arc Flash Facts Arc Flash Fact Sheet Brady Arc Flash Training Aids Promote awareness of the dangers associated with arc flash accidents and make sure your workers know how to protect themselves! Poster Highlights the common causes of arc flash and provides safe work practices and personal protection equipment requirements

HMP presents a wide range of AR -200 or MMA-200 of 200 AMP single phase inverter welding machine. These ARC Welding machines are available in various model ranges. HMP have a wide range of 200A ARC inverter welding machine with all standard accessories. HMP have 200A models of Welding as ARC-200N, ARC-200G, ARC-200MOS, ARC-200L, ARC-

ComponentSpace SAML for ASP.NET Okta Integration Guide 1 Introduction This document describes integration with Okta as the identity provider. For information on configuring Okta for SAML SSO, refer to the following articles.