Arc Fault Ground Fault - Canena

1y ago
20 Views
2 Downloads
4.87 MB
50 Pages
Last View : Today
Last Download : 3m ago
Upload by : Nadine Tse
Transcription

Ground Fault Breakers and Arc Fault Circuit Interrupters (AFCI) Kevin J. Lippert Manager, Codes & Standards Eaton Corporation 2008 Eaton Corporation. All rights reserved.

Agenda History of Circuit Protection Thermal Magnetic Breakers Ground Fault Breakers Arc Fault Circuit Interrupters Resources 2 2

Agenda History of Circuit Protection Thermal Magnetic Breakers Ground Fault Breakers Arc Fault Circuit Interrupters Resources 3 3

We Have Come A Long Way In Electrical Safety 1930 Circuit Protection 1950 2-Conductor BX Replacing Knob & Tube No Ground Required Residential Fuses Primary Protection Of Circuit With Ground Only Required In laundry room 1970 Aluminum Bonding Strip Required On BX Knob & Tube Primary Wiring Receptacles & Ground Fault Wiring 1900 Expanded Basements, Garages, Outdoors Innovative Circuit Breaker Products And Fuses Used For Circuit Protection Expanded Rest Of Home 1990 2000 Aluminum Armored BX Cable & NM-B Primary Wiring Ground Fault Protection Begins In the 70’s On Swimming Pools (Electrocutions 1100/ year) ‘70s: Bathroom, Garage, And near pools ’80s: Whirlpools, Tubs, Kitchen Sinks ‘90s: Basements, Crawl Spaces, Wet Bars, Kitchens ’00s: Outside and Other Locations (Electrocutions 400/year) Arc Fault & Standard Thermal Mag Circuit Breakers Used For Circuit Protection Thermal Magnetic Circuit Breakers Protect Residential Circuits Residential Homes Are Safer Because Of Codes and Standards Yet We Still Have Needless Deaths And Injuries 4 4

Overcurrent Protective Device Milestones 1918 Need Arises 1927 Westinghouse introduces a circuit breaker can interrupt a fault current of 5,000A at 120V 1973 Introduction of electronic trip units 5 5

Evolution Of Circuit Protection Knife Switch Residential Fuses Thermal Mag Breaker Thermal Mag GFCI Branch Feeder AFCI Combination AFCI The Electrical industry is continuing to make steps to improve electrical safety Electrical Safety Requires Industry Advancements In Product & Installation Practices 6 6

Agenda History of Circuit Protection Thermal Magnetic Breakers Ground Fault Breakers Arc Fault Circuit Interrupters Resources 7 7

What Is A Circuit Breaker? Definition: A device designed to open and close a circuit by non-automatic means and to open the circuit automatically on a predetermined overcurrent, without damage to itself when properly applied within its rating. Ref: NFPA 70-2008 8 8

Introducing Thermal Magnetic Circuit Breakers In the 1930’s Westinghouse introduced the “No-Fuze Load Center” featuring circuit breakers. The basic design and concept of the thermal magnetic breaker has not changed since its initial release Thermal magnetic breakers protect the homes wiring from damage due to overcurrents (overloads & short circuits) 9 9

Thermal Magnetic Circuit Breaker Designed to protect conductors and their insulation from damage 10 10

Overload Protection Overload protection is provided by bi-metal The bi-metal is made of two different metals which expand at different rates when heated. Bi-metal An overload event causes heating in the bimetal which bends and allows the trip mechanism to release 11 11

Short Circuit Protection Short Circuit protection is provided by a magnetic mechanism Per Ampere’s law, the strength of a magnetic field formed around an electrical current is proportional to the amount of current When a short circuit event occurs, a large amount of current flows creating a strong magnetic field. The armature is pulled down by the magnetic field, releasing the tripping mechanism Magnetic Armature 12 12

Time Current Curves Type BR 10-70 Amperes, 1 Pole 1000 Thermal Response 100 10 Magnetic Response 1 0.1 0.01 1,000,000 100,000 10,000 1,000 100 0.001 10 Shows both the thermal (overload) and magnetic (short circuit) responses 10000 TIME IN SECOND Time current curves detail the response of a breaker to overcurrent events CURRENT IN PERCENT OF BREAKER AMPERE RATING 13 13

UL 489 Molded Case Circuit Breakers Calibration 100% - No Tripping 135% - Trip within 1 hr for ratings less than 50A 200% 2 min – 0-30A 4 min – 31-50A Endurance (below 100A) 6,000 operations w/ current 4,000 operations w/o current Overload Must break 600 percent of its rated current 14 14

Agenda History of Circuit Protection Thermal Magnetic Breakers Ground Fault Breakers Arc Fault Circuit Interrupters Resources 15 15

UL 943 Ground Fault Circuit Interrupters, GFCI UL 943 Provides “people protection” from electric shock Leakage 6 mA Trip time 15 mS 16 16

Ground Fault Circuit Interrupters, GFCI GFCI monitors the difference in the current leaving the breaker, versus the current returning to the breaker § 5.000A §4.993A OK X 5.000A 17 17

UL 1053 Ground-Fault Sensing and Relaying Equipment UL 1053 Provides “equipment protection” from low level faults to ground Leakage within 10% of level defined by manufacturer 18 18

National Electrical Code, NEC NFPA 70, contains “installation” rules 2008 Edition has 882 Pages Created by 19 NEC Code-Making Panels (CMP) Balanced Representation (Manufacturers, Electricians, Inspectors, UL, etc.) Represent Groups/Associations (Directed Votes) K. Lippert – Alternate NEMA Rep. On CMP 10 3-year revision cycle Mentions “Listed” products References “product” Standards (Annex A) 19 19

NEC Ground Fault Origins 1968 GFCI required for swimming pool underwater lights 1971 GFCI expanded to Construction sites, Swimming pool receptacles, outdoors of dwellings 1971 GF protection of equipment required where Services 150V to ground and Service Disconnect 1200A 20 20

NEC Ground Fault Expands 1975 1978 GFCI for dwelling bathrooms GFCI for dwelling garages, Recreational vehicle parks; 2nd Level of equipment GF for health care facilities 1981 1987 1990 GFCI for Kitchens (near sink) Every new Code edition seems to continue to expand Ground Fault requirements. 21 21

Agenda History of Circuit Protection Thermal Magnetic Breakers Ground Fault Breakers Arc Fault Circuit Interrupters Resources 22 22

Need for Further Enhanced Fire Prevention Annual Fire Statistics 70,000 Residential Electrical Fires 500 Deaths 2000 Burn Injuries 1 Billion Direct Property Damage 23 23

AFCI – History and Technology 1980, 1984 and 1985 -- CPSC sponsored studies to investigate the causes of electrical distribution fires. The electrical arc was determined to be a major source of electrical fires ( 80%). The electrical industry was challenged to provide an engineered solution. Advances in electronics made possible the development of arc fault detection technology 24 24

Arcing Faults Unintentional Arcing Condition Temperatures In Excess Of 10,000 degrees Fahrenheit Not persistent enough to heat the bimetal in Thermal Magnetic Breakers 25 25

Classifying An Arc Fault Operational Arcs - occur in a properly functioning electrical system Switching loads on/off Contact closure/opening Non-Operational Arcs - potential fire hazards Damaged insulation in fixed wiring and appliance cords Loose connections 26 26

Operational Arcs Some examples of operational arcs: 27 27

Hazardous Arcs Some examples of non-operational arcs: 28 28

Types Of Arcing Faults Series Arcing L1 Load Parallel Arcing (Line-Neutral) N Gnd Parallel Arcing (Line-Gnd) Equipment Grounding Conductor High Current Level Arc “Parallel Arc” An Arc Fault That Occurs at 75Amps and higher An Arc Fault That Occurs Line-Line or Line-Neutral Low Current Level Arc “Series Arc” An arc fault at low levels down to 5 Amps An arc fault at a break or gap in a single conductor in series with a connected load 29 29

Introducing AFCI Push To Trip Test Button Arc Fault Sensing Circuitry Operating Handle Load Terminal Latch Piece Panel Neutral Wire Mechanism Spring Moving Contact Member Load Neutral Terminal Electromagnet Instantaneous Trip Element ( Armature ) Stationary Contact Member Long Delay Trip Element ( Bimetal ) 30 30

UL 1699 – AFCI Standard UL 1699 details the required testing Extensive “detection” testing required 31 31

Circuit Breaker - Levels of Protection Device Thermal Magnetic Breaker Branch Feeder Arc Fault Circuit Interrupter Combination Arc Fault Circuit Interrupter Protection Method Example Thermal Overload Current flow heats a bi-metal device within the breaker which bends and trips breaker Overloaded Circuit Over Current Condition Flowing current creates a magnetic field which trips breaker Short Circuit Thermal Overload Over Current Protection High Current Arcing Low Current Arcing in Installed Wiring Same the thermal magnetic plus electronic circuitry monitors parallel arcing current signature Any line to neutral or line to ground arc such as a drywall screw or nail which penetrates electrical wiring Thermal Overload Over Current Protection High Current Arcing Low Current Arcing Same as the thermal magnetic breaker and the branch feeder plus electronic circuitry monitors series arcing current signature 32 A broken wire or poor connection in connected appliance cords or permanent house wiring 32

Eaton’s AFCI Protection NM-B wire Connected Cords Typical Household Load Standard Receptacle Branch AFCI Arcing Fault Protection Earth Leakage Protection 5 Amps 75 Amps 30 mA Combo AFCI Arcing Fault Protection Earth Leakage Protection 5 Amps 30 mA 33 33

National Electrical Code (NEC) Introduction of Branch Feeder AFCI to the National Electrical Code. Protection of branch circuits supplying bedroom receptacle outlets as of January 1, 2002. Listed Branch Feeder AFCI protection of branch circuits supplying bedroom outlets. Branch circuits supplying outlets installed in dwelling unit bedrooms shall be protected by a listed arc-fault circuit interrupter, Combination type, installed to provide protection of the branch circuit Branch feeder AFCI’s permitted to be used until January 1, 2008. Location of the of AFCI is permitted to be within 6’ of the origin of the branch circuit via a metal raceway or a cable with a metallic sheath. Combination-Type AFCI required on Bedroom, Family Rooms, Living Rooms, Parlors, Libraries, Dens, Sun Rooms, Recreation Rooms, or Similar Rooms. It shall be permitted to install a combination AFCI at the first outlet. RMC, IMC or EMT or steel armored cable, Type AC, meeting the requirements of 250.118, using metal outlet or junction boxes must be installed between the origin of the Branch Feeder and the first outlet. 34 34

NEC Article 210.12 The National Electrical Code requires AFCIs 2008 NEC expands AFCI requirements from Bedroom circuits only, to many other circuits of a home Combination-Type AFCI is the new technology required by the 2008 NEC 35 35

2005 NEC Branch Feeder Coverage Bedroom 1 Family Room Bathroom Bedroom 2 Green Highlighted Rooms Are Those Required To Be Protected By AFCI Red Highlighted Rooms Are Those Not Required To Be Protected By AFCI Outside Receptacles Also Do Not Require AFCI Protection Kitchen Living Room Hallway Unfinished Basement Den 36 36

2008 NEC – Article 210.12 “(B) Dwelling Units. All 120-volt, single-phase, 15- and 20ampere branch circuits supplying outlets installed in dwelling unit family rooms, parlors, bedrooms, closets, dining rooms, libraries, sun rooms, hallways, living rooms, dens, recreation rooms, or similar rooms or areas shall be protected by a listed arc fault circuit interrupter, combination-type, installed to provide protection of the branch circuit” 37 37

2008 NEC Combination AFCI Coverage Bedroom 1 Family Room Bathroom Bedroom 2 Green Highlighted Rooms Are Those Required To Be Protected By AFCI Red Highlighted Rooms Are Those Not Required To Be Protected By AFCI Outside Receptacles Also Do Not Require AFCI Protection Kitchen Living Room Hallway Unfinished Basement Den 38 38

AFCI Supporters 39 39

Agenda History of Circuit Protection Thermal Magnetic Breakers Ground Fault Breakers Arc Fault Circuit Interrupters Resources 40 40

Eaton’s Resources Available 9 Combination AFCI Brochure Publication # BR00402001E 9 CH Plug-on Neutral Brochure Publication # BR00301005E 9 UL Classified Replacement Circuit Breakers Publication# SA00304001E 9 Residential Warranty Folder Publication # SA00305001E 9 Application Documents FAQs “How an AFCI Works” Preventative Maintenance Troubleshooting Guides 41 41

Additional Eaton Resources 9 FAQs 9 “How an AFCI Works” 9 Preventative Maintenance 9 Homeowner Troubleshooting Guide 42 42

Eaton’s Residential Applications Team Phone: 1.800.326.9513 Option 1: Technical Support Option 1: Arc Fault Circuit Interrupter Option 2: Ground Fault Circuit Interrupter Email: resiapps@eaton.com 24/7/365 Support Eaton’s application technicians are available around the clock to support any issue. US Based Support Staff Eaton’s support staff is located in the United States and is trained in US and Canadian electrical codes and standard wiring practices. Real World Experience Eaton’s support staff is comprised of degreed engineers with industry experience as well as accredited electricians, each familiar with real world field issues and solutions. 43 43

Questions And Comments Thank You 2008 Eaton Corporation. All rights reserved.

“EXTRA” Material The following slides are “extra” to be used only if physical demonstration samples are not available Additional “Case Study” slides can be used time permitting 45 45

Arc Detection / Fire Prevention AFCI versus Thermal Magnetic Demo’s High Energy Arcing High Energy Arcing Thermal Magnetic AFCI Low Energy Arcing Low Energy Arcing Thermal Magnetic AFCI 46 46

Case Study Location: Fort Mill, SC Age of Home: Home Built in 2005 Background: An arc fault breaker began tripping intermittently on a bedroom lighting circuit when turning on fan or lights. 47 47

Case Study Electrician initially replaced AFCI but new breaker tripped as well Inspection of the homerun showed wires were pulled through a truss connector plate 48 48

Case Study Wire was siliconed and taped to prevent grounding Breaker continued to trip intermittently Homeowner requested the homerun be replaced 49 49

Case Study When removing the homerun, evidence of an arcing condition was found on the wire which was in the wall. Note the carbonization on the neutral indicating arcing 50 50

High Current Level Arc "Parallel Arc" An Arc Fault That Occurs at 75Amps and higher An Arc Fault That Occurs Line-Line or Line-Neutral Types Of Arcing Faults Low Current Level Arc "Series Arc" An arc fault at low levels down to 5 Amps An arc fault at a break or gap in a single conductor in series with a connected load

Related Documents:

energized the arc-faults in the time period required by the arc-fault circuit interrupt testing standard, UL 1699B. . the prototype first opens the PV DC disconnect to stop the series arc-fault and then, if there still is arc-fault noise on the system, it shorts the PV strings to mitigate the parallel arc-fault. This is a robust solution that .

For Reference Only ARC 8D ARC 10D ARC 12D ARC 15D Dimensions And Specs 1 Recommended Enclosures ARC 8D 2 ARC 10D 2 ARC 12D 3 ARC 15D 3 . .65 cu.ft. .75 cu.ft. .85 cu.ft. Minimum SPL SQ ARC 10D2 ARC 10D4. 3 TOP NOTE: These woo

In this paper, the calculation of double line to ground fault on 66/33 kV transmission line is emphasized. Figure 3. Double-Line-to-Ground Fault 2.4 Three-Phase Fault In this case, falling tower, failure of equipment or . ground fault, fault current on phase a is I a 0. Fault voltages at phase b and c are: V b .

NEC 240.67 is a requirement that relates to arc-fault currents, which is not explicitly defined in NEC. IEEE 1584-2018 defines arc current as "A fault current flowing through an electrical arc plasma." Due to the added impedance of the electrical arc plasma, the value of an arcing fault current will always be less than the bolted fault potential.

The SE-601 is a microprocessor-based ground-fault relay for ungrounded dc systems. It provides sensitive ground-fault protection without the problems associated with nuisance tripping. Ground-fault current is sensed using an SE-GRM Series Ground-Reference Module—a resistor network that limits ground-fault current to 25 mA. The SE-601 is used

Arc Flash Facts Arc Flash Fact Sheet Brady Arc Flash Training Aids Promote awareness of the dangers associated with arc flash accidents and make sure your workers know how to protect themselves! Poster Highlights the common causes of arc flash and provides safe work practices and personal protection equipment requirements

HMP presents a wide range of AR -200 or MMA-200 of 200 AMP single phase inverter welding machine. These ARC Welding machines are available in various model ranges. HMP have a wide range of 200A ARC inverter welding machine with all standard accessories. HMP have 200A models of Welding as ARC-200N, ARC-200G, ARC-200MOS, ARC-200L, ARC-

Alex’s parents had been killed shortly after he was born and he had been brought up by his father’s brother, Ian Rider. Earlier this year, Ian Rider had died too, supposedly in a car accident. It had been the shock of Alex’s life to discover that his uncle was actually a spy and had been killed on a mission in Cornwall. That was when MI6 had