Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: Wet Lab 2 ELECTRICAL Electrical Comments: 120V Duplex outlets every 4' @ countertop. No more than 3 dupl ex outl ets per circuit. (3) 50A 208V 3 phase receptacl es- 1 on each side wall and one mounted in center of lab in ceiling. 120V duplex outlets every 6' wall space where cabinets not install ed. 2 conduit in ceiling with pull wire for future 480V, 3 phase, 30 amp service. 1?DY PPW§[ fur each hood LIGHTING Lighting Level: Li ghting Comments: fc 50 avg., 70 task Light Type: Fluorescent Lighting will provide general illumination. Supplemental lighting will provide additional illumination in task areas, and task lighting will have separate controls. Lighting circuits will be controlled by a schedule base programmable building-wide lighting control system to achi eve automatic shutoff in compliance with IECC-2009 lighting controls mandatory requirements. Local switches will be provided to control overhead lights and task lighting. COMMUNICATION Data/ Phone Outlets: 1 data drop, with 3 RJ45 jacks with cat . 6 cable each, on 3 walls, 3 drops total. No Communication Comments: phon e. 1 wireless access point. PIPING/ PLUMBING Fixtures: type Work Sink {res in} Erner. Sh/ Eye Wash quantity 1 notes 1 Floor Drain Only at the emergency shower/eyewash Misc: Cold water connection a Ion side of the i ed as connections in hoods onl . GASES Gases Comm ents: 3 Piped Gases- Compressed Air (125 psi}, Nitrogen, Argon . Piped to all hoods, ce nter island, and two wall locations. OTHER Fire Protection Comments: Acoustical Comments: No special requirements Structural Comm ents: Security Comments : August 19, 2016 Design Narrative – Part 2: Room Data Sheets Page 24

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: Wet Lab 3 GENERAL Room Name: Function: Number of Occupants: Hours pe r Day: Wet Lab 3 Traditional Wet Chemistry Days per Week: Quantity of this Room: Minimum Floor Area: Function Comm ent: 1 Primary Adjacencies: Secondary Adjacenci es: Types: nusf none 4 11 (in and out) 5 (in and out) lab support WetLabs1&2 CONSTRUCTION AND FINISHES Wall Mat erial: GWB metal stud Minimum Ceiling Height: Wall Finishes: Paint Floor Finishes: Epoxy paint on concrete Vinyl Wall Base : Windows: Observation Finish Comments: Construction Comments: Ceiling Material: Door Material: Doors: Window Treatments: ft . 11' min . clear exposed structure wd/half glass, h.m. frame pair 3' x 7' Blinds Lab walls extend to structure above. FURNITURE Quantity Description Supplied by 2 chairs DBF Furniture Comments: EQUIPMENT Quantity 10 LF Description Supplied by base cabinet with one 36' wide sink DBF 10 LF 10 LF wall ca bin et mobile (wheeled) base cabinet DBF DBF 2 1 10' x 4' walk-in hood acid storage cabinet, lockabl e DBF DBF 1 2 flammabl e material storage cabinet, lockable mobile work benches, 30' x 60" (center island) DBF DBF 1 vented flamm abl e gas cylinder cabinet (3 cylinders) DBF Equipment Comments: HVAC Relative Humidity: Directional Airflow: HVAC Comments: 30% to 65% Humidity HVAC Reliability: no 100% outage Bldg. Standard Heat Generating Equipment: Equipment List Merv 8 filtration Ventilation alarm system & HVAC to maintain 72F-78F 3 stub outs for exhaust snorkels in ceiling, one at each end and center. once-through air circulation N 1 exhaust capacity HAZARD Haza rd Comments: August 19, 2016 Chem ica l inventory being developed. Design Narrative – Part 2: Room Data Sheets Page 25

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: Wet Lab 3 ELECTRICAL Electrical Comments: 120V Duplex outlets every 4' @ countertop. No more than 3 duplex outlets per circuit. (3) 50A 208V 3 phase receptacl es - 1 on each wall and one mounted in center of lab in ceiling. 120V duplex outlets every 6' wall space where cabinets not installed. 2 conduit in ceiling with pull wire for future 480V, 3 phase, 30 amp service. 2 overhead drops at center island. 120V power at each hood. Lighting Level: Lighting Comments: fc 50 avg., 70 task Light Type: Fluorescent Lighting will provide general illumination. Supplemental lighting will provide additional illumination in task areas, and task lighting will have separate controls. Lighting circuits will be controlled by a schedule base programmable building-wide lighting control system to achieve automatic shutoff in compliance with IECC-2009 lighting controls mandatory requirements. Local switches will be provided to control overhead LIGHTING lights and task lighting COMMUNICATION Data/ Phone Outlets: Communication Comments: Fixtures: 1 data drop, with 3 RJ45 jacks with cat. 6 cable each, on 3 walls, 3 drops total. No phone. 1 wireless access oint. PIPING/ PLUMBING type Work Sink {resin} quantity 1 notes Floor Drain Erner. Sh/ Eye Wash 1 Only at the emergency shower/eyewash Misc: Cold water connection along side of the piped gas connections in hoods only. GASES Gases Comm ents: 3 Piped Gases - Compressed Air (125 psi}, Nitrogen, Argon . Piped to all hoods, center island, and two wall locations. Fire Protection Comments: Acoustical Comments: Structural Comments: No special requirements. Sprinkler system OTHER Security Comments : August 19, 2016 Design Narrative – Part 2: Room Data Sheets Page 26

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: Robotics Lab (Low-High Bay) GENERAL Room Name: Robotics Lab ([bw-High Bay) Number of Occupants: Function: High Bay Lab Hours per Day: 10 Days per Week: Quantity of this Room: 1 Primary Adjacencies: Minimum Floor Area: nusf Secondary Adjacencies: Function Comm ent: none Metal Add. Ma nuf. Lab Types: CONSTRUCTION AND FINISHES Wall Mat erial: GWB met al stud Minimum Ceiling Height: ft . Wall Finishes: Paint Ceiling Material: exposed structure Floor Finishes: Sea led concrete Door Mat eri al: solid core wood Wall Base: Doors: pr. 3' Window Treatments: 12'W x 16'H overhead door Non e none Windows: observation windows Finish Comments: Construction Comments: 25 ft . clear X 7' Provide work pl atform over th e Met al Additive Manufacturing Lab. "Roboti cs Control Station', with concrete floor and removabl e railing. Provide bollard protection both sides of overhead door. Designed as control a rea . Req uires 1-hour construction separating it from th e rest of the building. FURNITURE Quantity Description Supplied by 12 chair DBF Furniture Comments: EQUIPMENT Quantity Description Supplied by 20 LF 20 LF base cabinet with 36' sink DBF wall cabinet DBF desk DBF work bench DBF 6 6 Equipment Comments: HVAC Relative Humidity: 40%-60% Directional Airflow: Building Standard HVAC Comments: Temp. between 72F-78F. HVAC Reliability: Heat Gene rating Equipment: 2 stubouts for exhaust snorkels HAZARDS Hazard Comments: August 19, 2016 Oil and grease, solder, flux, cleaners, degreas ing compounds Design Narrative – Part 2: Room Data Sheets Page 27

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: Robotics Lab (Low-High Bay) ELECTRICAL Electrical Comments: 120V duplex outlet every 8' of wall. 120V duplex outlet every 4' of countertop. (4) outl ets 208V, 3 phase, 60 amps, (4) 480V, 3 phase, 60 amps. Max 6 duolex outlets oer 20 amo circuit LIGHTING Lighting Level: Lighting Comments: fc 50 avg., 70 task Light Type: Fluorescent Lighting will provide general illumination. Supplemental lighting wi ll provide additional illumination in task areas, and task lighting will have separate controls. Lighting circuits will be controlled by a schedule base programmable building-wide lighting control system to achi eve automatic shutoff in compliance with IECC-2009 lighting controls mandatory requirements. Local switches will be provided to control overhead Hghts and task Hghtjpg COMMUNICATION Data/ Phone Outlets: Communication Comments: 1 data drop, with 3 RJ45 jacks with cat. 6 cable each, on 3 walls, 3 drops total. Phone outlet at on e location. 2 wireless access points (1) dedicated LAN Iine. PIPING/ PLUMBING Fixtures: Floor Drain Misc: type quantity 1 notes Work Sink {res in} Erner. Sh/ Eye Wash as required by code ANSI/ISEA Z358 .1 Only at the emergency shower/eyewash Cold water connection along side of the piped gas connections. GASES Gases Comm ents: 3 Piped Gases - Compressed Air (125 psi}, Nitrogen, Argon. 1 manifold each on 3 walls lus additional com ressed air outlet at 20' o.c. on 3 walls. OTHER Fire Protection Comments: Acoustical Comments: Structural Comm ents: Security Comments : August 19, 2016 Design Narrative – Part 2: Room Data Sheets Page 28

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: Metal Additive Manuf. Lab (Low-High Bay) GENERAL Room Name: Metal Additive Manuf. Lab (Ibw-High Bay) Function: Metal Printing Quantity of this Room: 1 Minimum Floor Area: Function Comment: nusf none Number of Occupants: Hours per Day: 4 various Days per Week: various Robotics Lab Primary Adjacencies: Secondary Adjacencies: Types: CONSTRUCTION AND FINISHES Wall Material: GWB metal stud Wall Finishes: Paint Minimum Ceiling Height: Ceilin g Material: ft . 11' min. clea r ACT in lab, open to structure over work platform Floor Finishes: Antistatic epoxy coating on concrete Wall Base: Door Materi al: Doors: Vinyl Windows: solid core wood pr. 3' x 8', removable/no center post 3' x 7' egress door Non e Window Treatm ents: Interior observation windows. Ext erior windows not required Finish Comments: Interior finishing should be easy to clean to insure no metal powder can accumulate sepa rated from robotics area by partition. Robotics Control Station platform above. Construction Comments: Lab proportions should be rectangular, not square. FURNITURE Quantity Description Supplied by 2 chairs DBF Furniture Comments: EQUIPMENT Quantity Description Supplied by 2 2 Arcam A2x Metal Printer Arcam PRS GFE GFE 3 1 Russe l Finex Sifter flammabl e storage cabinents, lockable, for liquid solvents, 4 ' H GFE DBF 2 6 flammabl e storage cabinents, for metals, 6 ' H standard storage cabinets, 6'H x 3'W DBF DBF 5 1 counter height storage cabinets desk DBF DBF Equipment Comments: August 19, 2016 Provide 4' clear around Aram A2X metal printer. Design Narrative – Part 2: Room Data Sheets Page 29

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: Metal Additive Manuf. Lab (Low-High Bay) HVAC Relative Humidity: Directional Airflow: HVAC Comments: 50%-60% HVAC Reliability: Building Standard Heat Generating Equipment: Arcam Printers Appropriate HVAC system to maintain lab betwee n 68F-78F@ relative humidity between 50%-60%. Possible need for oxygen monitor due to the use of helium gas (2 gas bottles), notification inside lab (GFE). HAZARDS Hazard Comments: Metal ' powders" are used in the printing process. At small enough sizes, they can be pyrophoric and possibly explosive. Materials are classed according to the IBC as Pyrophoric material. With appropriate storage, allowed 8 cubic feet of solid material. Limit activities to the maximum allowed in a control area. Electrical Comments: 120V duplex outlet every 6' of wall at 48' above finished floor. (2) 440V outlets (for printers) (4) 208V outlets ELECTRICAL Transformers must be at least 30 feet from the printers. Transformers must be at least 30 f eet from interior room walls. All equipment in the room must be well grounded. Grounding lugs must be ava ilable to tie equipment to grounding lugs, perimeter ground bus around room. Provide 24" copper ground bar at 48 ' above finish ed floor - 1 each short wall 2 each long wall 6 total LIGHTING Lighting Level: Lighting Comments: fc 50 avg., 70 task Light Type : Fluorescent Lighting will provide general illumination. Additional lighting will provid e further illumination in task areas, and task lighting will have sepa rate controls. Lighting circuits will be controlled by a schedule base programmable building-wide lighting control system to achi eve automatic shutoff in com pliance with IECC-2009 lighting controls mandatory requirements. Local switches will be provided to control overhead li ghts and task lighting. Data/ Phone Outlets: 1-2 data drops, with 3 RJ45 jacks with cat. 6 cable each, on each side wall , 3 drops total. No phone. COMMUNICATION Communication Comments: Fixtures: Floor Drain Misc: August 19, 2016 type quantity PIPING/ PLUMBING notes 1 work sink (future) Erner. Sh/ Eye Wash 1 Only at the emergency shower/eyewash stub out plumbing for future sink outside room by door Design Narrative – Part 2: Room Data Sheets Page 30

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: Metal Additive Manuf. Lab (Low-High Bay) GASES Gases Comments: Piped Gases, Nitrogen, Argon, valved, stubbed and capped. Compressed Air (125 psi), 2 drops in ceiling and 2 drops on one short wall. 200 gallon buffer tank for compressed air. Needs 42 CFM compressed air for 5-10 minutes at at time. 1x1 helium manifold with automatic changeover. OTHER Fire Protection Comments: Acoustical Comments: Structural Comments: Security Comments : August 19, 2016 Design Narrative – Part 2: Room Data Sheets Page 31

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: Lab Support GENERAL Room Name: Function: Lab Support Support Number of Occupants: Hours per Day: 0 Days per Week: 0 0 Primary Adjacencies: wet and dry labs Quantity of this Room: 2 Minimum Floor Area: Function Comment: Secondary Adjacencies: one each floor nusf May function as required control area for chemical storage. 240 SF lab su art er 1200 SF lab excludes low-hi h ba labs. CONSTRUCTION AND FINISHES Wall Material: GWB metal stud Wall Finishes: Paint Floor Finishes: Vinyl Tile Wall Base: Vinyl Windows: None Finish Comments: Construction Comments: Minimum Ceiling Height: Ceiling Material: Door Material: Doors: ft. Window Treatments: None exposed structure solid core wood pair 3' x 7' Walls extend to structu re above. FURNITURE Quantity Description Supplied by Furniture Comments: EQUIPMENT Quantity 15 LF 3 Description Supplied by mobile open shelf unit, wire shelving, 5 high DBF mobile storage cabinet, (3' x 6') Equipment Comments: August 19, 2016 DBF Design Narrative – Part 2: Room Data Sheets Page 32

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: Lab Support HVAC Relative Humidity: HVAC Reliability: Directional Airflow: Heat Generating Equipment: HVAC Comments: Building Standard HAZARDS Hazard Comments: ELECTRICAL Electrical Comments: 120V duplex outlet every 12'-0 " of wall Lighting Level: Lighting Comments: fc 10-30fc Light Type: Fluorescent Single Switch Control lighting will be provid ed. Occupancy sensors will be installed that LIGHTING will turn lighting off within 30 minutes of an occupant leaving a space. Lighting circuits will be controlled by a schedule base programmable building-wide lighting control system to achieve automatic shutoff in compliance with IECC-2009 lighting controls maodatorv reauiremeots COMMUNICATION Data/ Phone Outlets: 1 data drop, with 3 RJ45 jacks with cat. 6 cable each, on each short wall, 2 drops total. 1 phone outlet. Communication Comm ents: (1) dedicated LAN lin e. PIPING/ PLUMBING Fixtures: quantity type notes None Floor Drain Misc: GASES Gases Comments: None OTHER Fire Protection Comments: Acoustical Comments: Structural Comments: Security Comments : August 19, 2016 Design Narrative – Part 2: Room Data Sheets Page 33

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: VTC Room GENERAL Room Name: Function: VTC Room Video Teleconference Meeting and Training Number of Occupants: Hours pe r Day: 20 9 Days per Week: 5 Quantity of this Room: Minimum Floor Area: 1 Primary Adjacenci es: first floor nusf Secondary Adjacencies: Function Comm ent: shared space Types: CONSTRUCTION AND FINISHES Wall Mat erial: GWB metal stud Minimum Ceiling Height: Wall Finishes: Paint tackable surface Ceiling Material: Floor Finishes: Sea led concrete & raised floor system with carpet tile Wall Base: Vinyl Windows: Per Building Design Finish Comments: Construction Comments: Door Material: ft . 10 Acoustical Ceiling Tile solid core wood Doors: 3' X 7' Window Treatments: Vertical Blinds. Blackout shades Provide tackable surface at monitor wall. Provide acoustical sound transmission treatment around perimeter of room - STC 45 Provide 3' high raised computer floor system. Provide addition al wa ll blocking - TV's. Provide 8 LF millwork, ve nted A/V equipment cabinet with countertop & 30" wide knee soace Quantity FURNITURE Description Conference table, 'V" shaped , adjustable Supplied by DBF 20 Conference chairs DBF 1 task chair DBF 1 Furniture Comments: EQUIPMENT Quantity 1 Description 70" monitor on wall opposite door Supplied by 1 6 1 video camera mounted und er monitor DBF DBF ceiling mounted microphones computer to drive A/V equ ipm ent DBF DBF 1 1 white board space for portable video conference equ ipment cart GFE DBF Equipment Comments: HVAC Relative Humidity: Directional Airflow: HVAC Comments: HVAC Reliability: Heat Generating Equipment: HAZARDS Hazard Comments: August 19, 2016 Design Narrative – Part 2: Room Data Sheets Page 34

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: VTC Room ELECTRICAL Electrical Comments: Provisions for conduit from wa ll/1V to conference table. (2) 120V duplex outlets built into to A/V cabinet (1) 120V duplex outlet at 10' o.c. along walls. (1) power drop in ce iling at center of room for future use. Provide power to conference tabl e via raised floor system. Prnvide 1?OY dtJnlex outlet hieh mounted for wall LIGHTING Li ghting Level: Li ghting Comments: moll ted monitor 35 avg., 50 task Light Type : Dimmable fc Dimmable lighting will provide general illumination. Separate lighting for three level task. Dimm able light located over th e table, no lights over smart board without a separate dimmer switch. Lighting circuits will be controlled by a schedule base programm able building-wide lighting control system to achieve automatic shutoff in compliance with IECC-2009 lightin g controls mandatory requirements. Occupancy sensors will be installed that will turn lighting off within 30 minutes of an occupant leaving a space. COMMUNICATION Data/ Phone Outlets: 1 Phone connection Communication Comments: Provide data conduit to conference table via raised floor system. Provide data to monitor, and AjV equipment cabinet. (1) data drop in ceiling at center of room for future use. (1) dedicated LAN Iin e. PIPING/ PLUMBING Fixtures: type quantity notes None Misc: GASES Gases Comm ents: None OTHER Fire Protection Comments: Acoustical Comments: Structural Comm ents: Security Comments : Audiovisual Comments: August 19, 2016 Provide microphones in ceiling. Design Narrative – Part 2: Room Data Sheets Page 35

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: Offices GENERAL Room Name: Offices Number of Occupants: 1 Function: Open office works space Hours per Day: 8 Days per Week: 5 Primary Adjacenci es: Secondary Adjacenci es: 1 each floor, 9000 SF total Quantity of this Room: Minimum Floor Area: 2 nusf Function Comm ent: open office workstations Types: CONSTRUCTION AND FINISHES Wall Mat erial: GWB metal stud Minimum Ceiling Height: Wall Finishes: Paint Ceiling Material: Floor Finishes: Carpet Wall Base: Vinyl Door Material: Doors: Windows: Finish Comments: Window Treatments: ft . 9 Acoustical Ceiling Tile solid core wood 3' X 7' Blinds Construction Comments: FURNITURE Description Supplied by DBF 100 task chair workstation, 6' x 7' 6 lounge chair DBF DBF 2 3 trellis ottoman DBF DBF Quantity* 100 Furniture Comments: *Includes furniture inside quiet rooms within open office. * Furniture listed is total for both levels. EQUIPMENT Quantity Supplied by Description Equipment Comments: HVAC Relative Humidity: HVAC Reliability: Directional Airflow: HVAC Comments: Heat Generating Equipment: HAZARDS Hazard Comments: None Electrical Comments: 120V outlet at 10' o.c. around perimeter of room . (3) 120V duplex outlets per workstation ELECTRICAL Dedicated 20 amp circu it for each copier. LIGHTING Lighting Level: fc Li hti n Comments: Task Ii htin with local controls. COMMUNICATION Data/ Phone Outlets: No phone outlets. (2) RJ45 Cat 6 telecomm. outl ets at each workstation Communication Comments: covered by wireless network, 2 wireless access points each floor August 19, 2016 35 avg., 50 task Light Type: Fluorescent Design Narrative – Part 2: Room Data Sheets Page 36

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: Offices PIPING/ PLUMBING Fixtures: Floor Drain Misc: type quantity notes None None GASES Gases Comments: None Fire Protection Comments: Acoustical Comments: Structural Comments: Security Comments : None None None None OTHER August 19, 2016 Design Narrative – Part 2: Room Data Sheets Page 37

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: Private Office GENERAL Room Name: Private Office Function: Director / Private Office Quantity of this Room: Minimum Floor Area: 12 nusf Function Comment: none 1 Number of Occupants: Hours per Day: 8 Days per Week: 5 Primary Adjacencies: Secondary Adjacencies: Types: office area, 1/ 2 each floor CONSTRUCTION AND FINISHES GWB metal stud Minimum Ceiling Height: ft. Wall Finishes: Paint Floor Finishes: Carpet Ceiling Material: Door Material: Acoustical Ceiling Tile solid core wood Wall Base: Windows: Doors: Window Treatments: 3' X 7' Blinds at exterior windows Wall Material: Vinyl Per Building Design Acoustical Finish Comments: Construction Comments: 9 Insulation in walls between offices & above ceilings. Provisions for additional wall blocking for wall hung furniture. FURNITURE Quantity 1 1 2 Description L shaped desk Supplied by "Executive" chair DBF DBF Guest chair DBF Furniture Comments: EQUIPMENT Quantity Description Equipment Comments: Supplied by Door stops. Coat hooks HVAC Relative Humidity: Directional Airflow: HVAC Comments: Building Standard HVAC Reliability: Heat Generating Equipment: Thermostat control @ each office HAZARDS Hazard Comments: ELECTRICAL Electrical Comments: Lighting Level: Lighting Comments: 1 120V du lex outlet on each wall. LIGHTING fc 35 avg., 50 task Light Type: Fluorescent Overhead lighting with local switch will be provided. Occupancy sensors will be install ed that will turn lighting off within 30 minutes of an occupant leaving a space. Lighting circuits will be controlled by a schedule base programmable building-wide lighting control system to achieve automatic shutoff in compliance with IECC-2009 lighting controls mandatory requirements. August 19, 2016 Design Narrative – Part 2: Room Data Sheets Page 38

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: Private Office COMMUNICATION Data/ Phone Outlets: (1) telcomm. outlet with (3) RJ45 jacks, cat . 6, at desk. Communication Comments: wireless access in ceiling PIPING/ PLUMBING Fixtures: Floor Drain Misc: type quantity notes None None GASES Gases Comments: None Fire Protection Comments: Acoustical Comments: Structural Comm ents: Security Comments : None None None None OTHER August 19, 2016 Design Narrative – Part 2: Room Data Sheets Page 39

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: Conference Room GENERAL Room Name: Function: Conference Room meeting space Quantity of this Room: Minimum Floor Area: 1 nusf Function Comm ent: 16 Number of Occupants: Hours pe r Day: 8 Days per Week: 5 Primary Adjacenci es: Secondary Adjacencies: 2nd floor office area Types: CONSTRUCTION AND FINISHES Wall Mat erial: GWB metal stud Minimum Ceiling Height: Paint tackable surface Floor Finishes: Carpet Wall Base: Vinyl Ceiling Material: 9 Acoustical Ceiling Tile Door Material: Doors: solid core wood 3' X 7' Windows: Finish Comments: Window Treatments: Blinds Wall Finishes: Construction Comments: ft . Provide blocking in wa ll for future wall-mounted TV monitor. Provide tackable surface at north wall. FURNITURE Quantity Description Supplied by 16 1 conference room chair table, oblong/oval DBF DBF Furniture Comments: EQUIPMENT Quantity Description 1 white board Supplied by DBF Equipment Comments: HVAC Relative Humidity: HVAC Reliability: Directional Airflow: HVAC Comments: Heat Generating Equipment: HAZARDS Hazard Comments: ELECTRICAL Electri cal Comments: provide convenience outlet on each wall Li ghting Level: fc Lighting Comments: Dimmabl e lighting for general illumination. Task lighting with local controls. Occupancy sensors will be installed that will turn lighting off within 30 minutes of an occupant LIGHTING 35 avg., 50 task Light Type: Fluorescent leaving a space. Lighting circuits will be controlled by a sched ule base programmable building-wide lighting control system to achieve automatic shutoff in compliance with IECC-2009 Ii htin co ntrols mandate COMMUNICATION Data/ Phone Outlets: Communication Comments: re uirements. (1) phone outlet. covered by wi reless network (1) dedicated LAN lin e. August 19, 2016 Design Narrative – Part 2: Room Data Sheets Page 40

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: Conference Room PIPING/ PLUMBING Fixtures: Floor Drain Misc: type quantity notes None None GASES Gases Comments: None Fire Protection Comments: Acoustical Comments: Structural Comments: Security Comments : None None None None OTHER August 19, 2016 Design Narrative – Part 2: Room Data Sheets Page 41

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: Small Meeting Room GENERAL Room Name: Function: Small Meeting Room meeting space Quantity of this Room: Minimum Floor Area: 4 nusf Function Comm ent: 4 Number of Occupants: Hours pe r Day: 8 Days per Week: 5 Primary Adjacenci es: Secondary Adjacencies: offices and workstations Types: CONSTRUCTION AND FINISHES Wall Mat erial: GWB metal stud Minimum Ceiling Height: Wall Finishes: Paint tackable surface Floor Finishes: Carpet Wall Base: Vinyl Windows: Finish Comments: Ceiling Material: 9 Acoustical Ceiling Tile Door Material: Doors: solid core wood 3' X 7' Window Treatments: Provide tackable surface at one (back) wall. ft . Blinds Construction Comments: FURNITURE Quantity 4 Description Supplied by chair DBF 1 table, round Furniture Comments: DBF EQUIPMENT Quantity 1 Description Supplied by white board DBF Equipment Comments: HVAC Relative Humidity: HVAC Reliability: Heat Generating Equipment: Directional Airflow: HVAC Comments: HAZARDS Hazard Comments: ELECTRICAL Electrical Comments: outlets as required by code Lighting Level: Lighting Comments: fc 35 avg., 50 task Light Type: Fluorescent Lighting for general illumination. Task lighting with local controls. Occupancy sensors LIGHTING will be installed that will turn lighting off within 30 minutes of an occupant leaving a space . Lighting circuits will be controlled by a schedule base programmable buildingwide lighting control system to achieve automatic shutoff in compliance with IECC-2009 lighting controls mandatory requirements. COMMUNICATION Data/ Phone Outlets: Communication Comments: August 19, 2016 1 phone outlet. covered by wireless network Design Narrative – Part 2: Room Data Sheets Page 42

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: Small Meeting Room PIPING/ PLUMBING Fixtures: Floor Drain Misc: type quantity notes None None GASES Gases Comments: None Fire Protection Comments: Acoustical Comments: Structural Comments: Security Comments : None None None None OTHER August 19, 2016 Design Narrative – Part 2: Room Data Sheets Page 43

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: Quiet Room GENERAL Room Name: Function : Quiet Room meeting space Quantity of this Room: Minimum Floor Area: 4 nusf 4 Number of Occupants: Hours pe r Day: 8 Days per Week: 5 Primary Adjacenci es: Secondary Adjacencies: open office area, Types: Function Comm ent: CONSTRUCTION AND FINISHES Wall Mat erial: GWB metal stud Minimum Ceiling Height: Paint Floor Finishes: Carpet Wall Base: Vinyl Ceiling Material: 9 Acoustical Ceiling Tile Door Material: Doors: 3' X 7' Windows: Finish Comments: Window Treatments: none Wall Finishes: ft . glass Construction Comments: FURNITURE Quantity Description Supplied by 1 1 1 sofa DBF ottoman lounge chair (only occurs in one Quiet Room} DBF DBF Furniture Comments: EQUIPMENT Quantity Description Supplied by Equipment Comments: HVAC Relative Humidity: HVAC Reliability: Directional Airflow: Heat Generating Equipment: HVAC Comments: HAZARDS Hazard Comments: ELECTRICAL Electrical Comments: convenience outlet on each wall Lighting Level: 35 avg., 50 task Light Type: Fluorescent fc Lighting for general illumination. Occupancy sensors will be installed that will turn li ghting off within 30 minutes of an occupant leaving a space. Lighting circuits will be controlled by a schedule base programmable building-wide lighting control system to achieve automatic shutoff in compliance with IECC-2009 li ghting controls mandatory LIGHTING Lighting Comments: requirements. COMMUNICATION Data/ Phone Outlets: Communication Comments: August 19, 2016 covered by wireless net wo rk Design Narrative – Part 2: Room Data Sheets Page 44

Advanced Manufacturing Collaborative GMP Proposal HEERY Comm. No. 16006-00 Room Name: Quiet Room PIPING/ PLUMBING Fixtures: Floor Drain Misc: type quantity notes None None GASES Gases Comments: None Fire Protection Comments: Acoustical Comments: Structural Comments: Security Comments : None None None None OTHER August 19, 2016 Design Narrative – Part 2: Room Data Sheet

Sh/ Eye Wash as required by code ANSI/ISEA Z358.1 Floor Drain Misc: Only at the emergency shower/eyewash Cold water connection along side of the piped gas connections. Gases Comments: Fire Protection Comments: Acoustical Comments: Structural Comments: Security Comments : GASES 3 Piped Gases -Compressed Air (125 psi}, Nitrogen, Argon.

Related Documents:

Jul 26, 2017 · meeting minutes livingston county july 12, 2017 – 7:30 a.m. administration building - board chambers 304 e. grand river avenue, howell, mi 48843 finance committee reen comm.kate lawrence comm.doug helzerman comm.carol griffith ill comm.b g-finance chair ave comm.don parker comm.dennis dolan comm.d domas comm.bob bezotte comm.g

EU GMP Guide-Annex 15 Qualification & Validation draft released In February 2014, a draft of the revised Annex 15 was released by the European Commission (EC) for public comment. The draft version is based on an EMA Concept Paper, published in November 2012 which outlined various reasons for the revision of Annex 15.File Size: 553KBPage Count: 17Explore furtherEU GMP Annex 15: Qualification and Validation - ECA Acad www.gmp-compliance.orgEU GMP Annex 15 Revisions: Improving Qualification and .www.cleanroomtechnology.c GUIDELINES ON VALIDATION APPENDIX 6 VALIDATION O www.who.intGuideline on Process Validationwww.ema.europa.euEudraLex - Volume 4 - Good Manufacturing Practice (GMP .ec.europa.euRecommended to you b

Therapeutic Goods Administration GMP clearance guidance V18.3 July 2019 Page 9 of 84 GMP clearance basics What GMP clearance is GMP Clearance is a non-statutory mechanism used to verify that overseas manufacturing sites

AIR CAPS COMPACT MINI SPRAY GUNS Part Number Description COMM-HS1-10 HVLP 1.0 mm Fluid Nozzle COMM-HS1-12 HVLP 1.2 mm Fluid Nozzle COMM-TS1-10 Trans-Tech 1.0 mm Fluid Nozzle COMM-TS1-12 Trans-Tech 1.2 mm Fluid Nozzle COMM-RS1-08 Round Spray Trans-Tech 0.8 mm Fluid Nozzle Part Number Description COMM-200-08 0.032" (0.8 mm)

winner was Bryan Heery of Everclear Enterprises. Before adjourning the meeting, Bryan Heery thanked everyone for their attendance and encouraged everyone to attend the upcoming March . Euclid Chemical, Evonik, TCC Mate-CIRCLE #91 ON RESPONSE FORM–PAGE 60. CHAPTER. NEWS.

3. Good Manufacturing Practices (GMP) guidelines GMP is a production and testing practice that helps to ensure a quality product. Many countries have legislated that pharmaceutical and medical device companies must follow GMP procedures, and have created their own GM P

GMP GMP is the part of QA that ensures products are consistently manufactured to a standard appropriate to their intended use. It is concerned with both manufacturing and Quality Control procedures. QC Quality Control is the part of GMP which is concerned with sampling, specification and testing and also organization, documentation and release. 17

LITERARY(THEORY(An(introduction((!! ClassReader! Spring2014!! Prof.DavidMiralles,PH.D.! University!of!Oregon!! Universidad!Autónoma!de!Querétaro!