Overview Of IEC/TS 60076-20 Ed. 1.0: Power Transformers .

2y ago
187 Views
25 Downloads
794.95 KB
21 Pages
Last View : 1m ago
Last Download : 3m ago
Upload by : Azalea Piercy
Transcription

2017/EWG/EGEEC/WKSP2/003Overview of IEC/TS 60076-20 Ed. 1.0: PowerTransformers - Part 20: Energy EfficiencySubmitted by: Bergamo UniversityWorkshop on Reducing Losses in PowerDistribution Through Improved Efficiency ofDistribution TransformersJeju, Korea28 March 2017

Reducing Losses in Power Distribution through ImprovedEfficiency of Distribution Transformers (EWG 05 2015A)Overview of IEC/TS 60076-20 Ed. 1.0Power transformers - Part 20: Energy efficiency28 March 2017 Jeju, Republic of KoreaAngelo BagginiBergamo University - Engineering DepartmentORGANISERS:

Introduction“* The objective of the technical specification is to promote a higher average level of energyperformance for transformers.It provides a basic model for national standards and alternatively a supplement to national standardswhich do not cover the whole range of transformers. * It also gives minimum efficiency andmaximum losses which lead to a generally acceptable balance between losses and use of otherresources.”It is “based on existing regional practices: the Peak Efficiency Index (PEI) incorporating a Total Cost of Ownership(TCO) approach the no-load and load losses at rated power for rationalization of transformer cores and coils fortransformers generally produced in large volumes the efficiency at a defined power factor and particular load factor (typically at 50%)A transformer that does not comply with the requirements of this technical specification can stillcomply with the requirements of other standards in the IEC 60076 series.Energy efficiency is not the sole basis for choosing a transformer. The total capital and estimatedlifetime operating and maintenance costs (TCO Total Cost of Ownership) are also significantconsiderations in determining the most suitable transformer for the intended application and may offermore economical solutions over the lifetime of the transformers.”

Contents1.2.3.4.5.6.7.ScopeNormative referencesDefinitionsEfficiency and Efficiency Index calculationSpecification of energy performanceEnergy performance levelsToleranceAnnex A (informative)Annex B (informative)Annex C (informative)Annex D (informative)Calculation of transformer efficiencyCapitalisation of lossesEfficiency based on a survey of world practiceJapanese practice

1. ScopeThis part of IEC 60076 is applicable to transformers in the scope of IEC 60076-1.The energy performance levels given in section 6 are not applicable to the followingtransformers: Transformers for high current rectifiers following IEC61378 series and IEC 60146 series.Transformers for furnace applicationsTransformers for offshore applicationsTransformers for emergency or temporary mobile installationsTraction transformers for 16.7 HzEarthing transformers following IEC60076-6Transformers which cannot fulfil the energy performance requirements due tounavoidable size and weight limitationsIn this standard ‘transformers’ includes both separate winding transformers andautotransformers.

3. Definitions3.1Efficiency3.2Electrical losses3.3Efficiency Index (EIA) method A3.4Efficiency Index (EIB) method B3.5Peak Efficiency Index (PEI)3.6Input power (Pinput)3.7Output power (Poutput)3.8Transformer load factor (k)3.9Load factor of Peak Efficiency Index (kPEI)3.10 Transmitted apparent power (kSr)

DefinitionsEnergy efficiencyPINPOUT(W)(W)POUT PIN(IEV 151-15-25 modified)

DefinitionsElectrical lossesElectrical Lossesthe electrical power consumed by the transformer atparticular value of transmitted apparent powerexcluding the power consumed by the cooling system

DefinitionsEnergy Efficiency Index Method AS (VA)LossesCoolingS ( Losses Cooling ) Sthe ratio of the transmitted apparent power of a transformer minus electrical lossesincluding the power consumed by the cooling to the transmitted apparent power ofthe transformer for a given load factor

DefinitionsEnergy efficiency index Method BS (VA)LossesS S Lossesthe ratio of the transmitted apparent power of a transformer to the transmittedapparent power of the transformer plus electrical losses for a given load factorNote to entry: This method is only applicable for naturally cooled transformers

DefinitionsPeak efficiency index020406080* Usually 40–50%Energy efficiency index (%)100100 Load (%)10

4. Efficiency and Efficiency Index calculation4.1General4.2Methods of evaluatingenergy performance4.34.3.14.3.2Method A Efficiency Index general formula Peak Efficiency Index4.44.4.14.4.2Method BEfficiency Index general formulaEfficiency Index at 50% loading("EIB50" ) 3 methods of evaluating the energyperformance: the Peak Efficiency Index (PEI) the no-load and load losses at ratedpower or at a particular reference power the efficiency at a defined power factorand particular load factor (typically at50%)2 methods of calculating efficiency index(method A and B)the voltage and load current systems aresymmetrical and sinusoidalthe line voltage is equal to the rated voltagethe power factor is assumed to be unity andefficiency can be defined in terms of anefficiency index at a specific power.

DefinitionsEfficiency Index method A and B12

Efficiency Index Method AP0NLL measured at rated voltage, rated frequency and on rated tapPc0electrical power required by the cooling system for NL operation derived from the type test measurement of thepower taken by the fan and pump motors.Pkmeasured LL at rated current and rated frequency on the rated tap corrected to reference temperature accordingto IEC 60076-1.Pck(k)is the additional electrical power required (in addition of Pc0) by the cooling system for operation at load factor k,derived from the type test measurement of the power taken by the fan and pumps motorsSr is the rated power of the transformer or autotransformer as defined in IEC60076-1 on which Pk is basedkis the load factorThis approach respects the philosophy of IEC60076 which refers the rated power to the rated voltage and current of one of thetransformer windings.For the calculation, the following shall be considered:a) For liquid immersed transformers with rated average winding temperature rise less than or equal to 65 K for OF or ON, or 70 Kfor OD, the reference temperature is 75 C.b) For transformers with other rated average winding temperature rise, the reference temperature is equal to the rated averagewinding temperature rise 20 C, or rated winding temperature rise yearly external cooling medium average temperature,whichever is higher.If a purchaser needs to compare transformer with different insulation systems and different average winding temperature rises,the reference temperature should be according to b) above.The reference temperature at rated power chosen for the losses shall be in accordance with IEC60076-1

Peak Efficiency Index P0Pc0PkSr***measured at rated voltage and rated frequency, on the rated tap20 C Average winding rise (i.e. 90 C for OD cooled transformers, 85 C for ON or OF cooled transformers) no load losses* electrical power required by the cooling system for no load operation load losses* corrected to reference temperature** rated power of the transformer on which Pk is basedThe Peak Efficiency Index includes the losses associated with only that part of the coolingsystem that is in service at kPEI.At kPEI loading sufficient cooling shall be in service to ensure the transformer temperature risedoes not exceed the requirements of IEC60076-2 or the customer specification.14

Peak Efficiency IndexEfficiency (%)10001520406080100 Load(%)

Efficiency Index Method BkSuEIB kSu P0 k²Tf Pk(pu)P0is the no-load loss measured at rated voltage, rated frequency and on rated tapPkis the measured load loss at rated current and rated frequency on the rated tap corrected toreference temperature according to IEC 60076-1.Suis the rated power of the transformer or autotransformer as defined in IEEE C57.12.80 on which Pkis based. Su is used to distinguish from Sr.kis the load factorTfIs the temperature correction factor used to correct the losses from the standard referencetemperature to the reference temperature used for calculation of EIrThis is different from usual practice of IEC.This formula is only applicable to transformers with natural cooling AN,ONAN,KNAN,GNAN and LNAN. Forforced cooled transformers method A shall apply16

Efficiency Index at 50% loading0,5 SuEIB50 0,5 Su P0 0,25 Tf Pk(pu)Tf shall be taken as 1Su is the rated power of the transformer or autotransformer as defined in IEEE57.12.80The exact correction factor Tf depends at least on the type of conductor (copper or aluminum) and thereference temperature at full load and ratio of eddy to I2R lossesIn some countries, for transformers with an assumed average winding temperature at 50% load factor of 55 Cfor liquid immersed transformers and 75 C for dry type transformers, Tf is approximated as 0,91.Other values of Tf are based on the temperature correction of losses given in IEC60076-1 and 60076-2If Tf is not equal to 1, the value of Tf must be given when EIB50 is stated.There is no provision for cooling losses in the formula and different ratings for different cooling modes are notaccounted for.17

5. Specification of energy performanceThe energy performance of a transformer maybe specified in one of the following ways:1. Minimum Peak Efficiency Index with load and noload loss capitalisation values2. Maximum load losses and maximum no load losses3. Minimum efficiency index at a load factor of 50%EIB50

6. Energy performance levels6.1 General Level 1 is for basic energy performanceLevel 2 is for high energy performance6.2 Liquid immersed transformersThe level chosen should be economically6.2.1Minimum Peak Efficiency Indexvalidated for the intended applicationmethod A6.2.2Maximum load loss and maximum no load loss fortransformers with rated frequency equal to 50Hz.6.2.3Efficiency Index Method B6.3 Dry type transformers6.3.1Minimum Peak Efficiency Index value Method A6.3.2Maximum load loss and maximum no load loss for transformers withrated frequency equal to 50Hz.6.3.3Efficiency Index Method B at 50% load factor

Thank youFor more information please contactAngelo BagginiUniversità di BergamoDipartimento di IngegneriaViale Marconi 5,24044 Dalmine (BG) Italyemail: angelo.baggini@unibg.itECD Engineering Consulting and DesignVia Maffi 21 27100 PAVIA Italy

This part of IEC 60076 is applicable to transformers in the scope of IEC 60076-1. The energy performance levels given in section 6 are not applicable to the following transformers: Transformers for high current recti

Related Documents:

iec 60076-10-1 ed. 2.0 ccdv mt 60076-10 2015-12 5 iec 60076-11 ed. 2.0 (new) mt 60076-11 - 6 iec 60076-15 ed. 2.0 dec mt 60076-15 2015-07 7 iec 60076-16 ed. 2.0 amw mt 60076-16 2017-05 8 iec 60076-21 ed. 2.0 amw mt 60076-21 2018-02 9 iec 60214-2 ed. 2.0 amw mt 60214 2016-09 1

con tensión inducida IEC 60076-3 Medida de las descargas parciales IEC 60076-11 prUeBas especiales Prueba impulso tipo rayo IEC 60076-3 Prueba de calentamiento IEC 60076-2 Medida del nivel de ruido IEC 60076-10 Prueba de resistencia al cortocircuito IEC 60076-11

con tensione indotta IEC 60076-3 Misura delle scariche parziali IEC 60076-11 PROVE DI TIPO Prova ad impulso atmosferico IEC 60076-3 Prova di riscaldamento IEC 60076-2 PROVE SPECIALI Misura del livello di rumore IEC 60076-10 Prova di tenuta al cortocircuito IEC 60076-11

IEC 60076-10 2001 Power transformers -- Part 10: Determination of sound levels EN 60076-10 2001 IEC 60076-11 2004 Power transformers -- Part 11: Dry-type transformers EN 60076-11 2004 IEC 60076-12 2008 Power transformers -- Part 12: Loading guide for dry-type power transformers - - IEC 60076

IEC 61215 IEC 61730 PV Modules Manufacturer IEC 62941 IEC 62093 IEC 62109 Solar TrackerIEC 62817 PV Modules PV inverters IEC 62548 or IEC/TS 62738 Applicable Standard IEC 62446-1 IEC 61724-1 IEC 61724-2 IEC 62548 or IEC/TS 62738 IEC 62548 or IEC/TS 62738 IEC 62548 or IEC/TS 62738 IEC 62548 or IEC/

IEC has formed IECRE for Renewable Energy System verification - Component quality (IEC 61215, IEC 61730, IEC 62891, IEC 62109, IEC 62093, IEC 61439, IEC 60947, IEC 60269, new?) - System: - Design (IEC TS 62548, IEC 60364-7-712, IEC 61634-9-1, IEC 62738) - Installation (IEC 62548, IEC 60364-7-712)

IEC 60076-11 – Power transformers – Part. 11: Dry – type. IEC 60076-1 – Power transformers – Part. 1: General. IEC 60076-2 – Power transformers – Part. 2: Temperature rise. IEC 60076-3 – Power transformers – Part. 3: Insulation levels, dielectric test and external clearances in air.

IEC 60076-1 Power transformers – Part 1: General IEC 60076-2 Power transformers – Part 2: Temperature rise IEC 60076-3 Power transformers – Part 3: Insulation levels, dielectric tests and external clearances in air IEC 60076-5 Power transformers – Part 5: Ability to withstand short circuit