Trane Application Guide Retrofit Guidelines - Replacing .

2y ago
101 Views
4 Downloads
314.78 KB
16 Pages
Last View : 1m ago
Last Download : 3m ago
Upload by : Melina Bettis
Transcription

Application GuideRetrofit GuidelinesAPP-APG011-ENReplacing systems that use HCFC-22Reusing existing refrigerant linesConverting HCFC-22 systems to HFC410AConverting HFC410A indoor units to HCFC-22 forreplacement systems

The purpose of this bulletin is to convey procedures when replacing an existing system that utilizedHCFC-22 refrigerant with an HFC410A refrigerant bearing system.For convenience, section V includes information for applying a new HFC410A indoor product withan existing HCFC-22 outdoor unit.This bulletin discusses:I.Basic practices for HVAC systemsII.Refrigeration LinesIII.Existing indoor equipmentIV.Reusing existing lines and indoor equipmentV.Reusing existing HCFC-22 outdoor unitsPOSITION STATEMENT:Trane has always recommended installing approved, matched indoor and outdoor systems. Thebenefits of installing approved matched sytems are maximum efficiency, optimum performance,and best overall system reliabilityWarnings and Cautions appear at appropriate sections throughout this manual. Read these carefully.WARNING – Indicates a potentially hazardous situation which, if notavoided, could result in death or serious injury.CAUTION – Indicates a potentially hazardous situation which, if notavoided, may result in minor or moderate injury. It may also be used to alert againstunsafe practices.CAUTION – Indicates a situation that may result in equipment or propertydamage-only accidents.ISSUED BY:Product Application Engineering DepartmentTraneTyler, TexasAPP-APG011-ENPage 202/08/2010

I. Basic practices for HVAC systemsThe following guidelines should be observed when installing any refrigerant bearing system in order to assurereliable and efficient operation.These practices apply regardless of refrigerant type.1. Use only compatible indoor and outdoor coil combinations.a) Retrofitted systems in most cases, will not be rated in the AHRI directory.1) There is no plan to supply ratings to AHRI for retrofitted systems.b) Sources for rated system combinatons:1. www.ahrinet.org2. www.comfortsite.com3. Electronic Performance Data4. Local distributor or sales office2. Refrigerant line sets must be sized properly.a) Refer to the current refrigerant piping publications:1) SS-APG006-EN for 1.5 through 5.0 ton split systems.2) SS-APG008-EN for 6 through 20 ton split systems.b) Table 1 and Table 2 in this document indicate compatible line diameters for single speed systems.3. Sealed refrigerant systems must be kept clean!a) De-burr all ends of copper tubing to assure free flow of refrigerant.b) Use emery cloth or scuff pad to clean the ends of the copper tube to assuregood braze joints. Special care should be taken to eliminate any shavings fromentering the tubing.c) Always allow dry nitrogen to flow through the refrigerant lines to prohibit oxidationwhile brazing.d) Refer to Service Procedures Publication 34-1005 ( latest Version ) for properbrazing techniques.4. Moisture compromises performance and operation of all HCFC / HFC refrigerant systems.a) Keep all oil bearing containers sealed tight until ready to use.b) Do not open system service valves until ready to start up.1) Leak check system as soon as possible after brazing joints.Explosion Hazard!NEVER leak test with air and R410A. At pressures above 1 atmosphere, just likeR-22, mixtureof R-410A and air can be combustible! Failure to follow this warningcould result in property damage, personal injury or death.2) Begin evacuation process immediately after leak check process is completed.a) Do not leave service valves open longer than four hours. Moisture absorbed into the system isremovable only by driers.a) Evacuate to 300 microns, then close all service gauge valves. After one minute, if thereading on the micron gauge rises above 500 microns, leak check and evacuate the systemagain. (Please note that a micron gauge must be used, dial gauges cannot read microns.)5. Proper refrigerant handling is a must.a) Service personnel must be properly certified in order to handle refrigerant!b) Refrigerant in existing system must be recovered in accordance with all applicable federal, state andlocal standards.1) New or recycled refrigerant must be used when charging a system2) Recovered refrigerant must be recycled at an approved recycling facility or disposed of in accordance with national, state, and local standards.3) Recovered refrigerant, that is free from non-condensables and acid, may be used for chargingpurposes only in the system in which it was recovered from.APP-APG011-ENPage 302/08/2010

Section II - Refrigerant LinesA. Compatible line diameters and lengths:When replacing any HVAC system, the existing refrigerant lines must be evaluated todetermine if they are properly sized for the new system. Refer to Table 1 for compatiblevapor line and maximum lengths and Table 2 for approved liquid line sizes, length andvertical change.B. Preparation for re-use:After verifying the line diameters and length are compatible, the existing line set must becleared of as much existing mineral oil and contaminants as possible. The lines should becleared prior to installing new outdoor and / or indoor units.Section III - Existing indoor equipment:In January 2001, the Department of Energy published a rule under NAECA (National ApplianceEnergy Conservation Act of 1987) to advance the minimum SEER to 13 effective January 23rd,2006 for single phase HVAC systems. (three phase systems with capacity ratings under 65,000BTUH followed at a later date). In 1992, the minimum SEER was increased to 10.0. Prior to 1992,SEER ratings were as low as 7.0. In addition, in 2006, HSPF was required to be 7.7. Before 2006HSPF’s were as low as 6.8.Some of the ways in which the HVAC industry achieved the higher efficiencies include:A. Increased air to coil surface contact.1) Normally, increasing the air to coil surface contact meant the refrigeration coils increasedin both physical size as well as refrigerant volume size.B. Compressor motor, blower motor, and fan motor efficiencies increased.C. Improved heat transfer technologiesD. Combination of the above.Regardless of the method, HVAC systems manufacturers typically offer their brand of furnace coilsand fan coil units that are specifically designed and tested to operate with compatible outdoor airconditioning units and heat pump units. For the reasons listed, when replacing an outdoor unit, it isin the customer’s best interest to replace the indoor furnace coil or fan coil unit. In the case of a heatpump system, the above cannot be overstated since refrigerant flows in both directions, thusrequiring the indoor coil and outdoor coil be volumetrically balanced. In order to locate a list ofrated HVAC system combinations, the AHRI Directory of Certified Systems should be utilized, orthe manufacturer’s data be obtained.Other reasons complete system change-out is preferred over replacing only the indoor or only theoutoor unit include:A. There is a possibility the aged component may fail prior to the replaced component. Inaddition, if a refrigerant leak occurs and moisture is introduced into the system, the systemoil will be contaminated. It must be understood that Trane systems which use R410A as arefrigerant utilize Polyolester Oil ( POE ) This oil is hygroscopic, meaning it absorbsmoisture quickly. Leaks in the refrigeration system (which is intended to be sealed fromatmosphere) can actually allow atmospheric moisture to enter the otherwise sealed system.When this occurs, POE oil breaks down acid forms. Acid is harmful to the compressormotor windings as well as the refrigerant flow control devices, reversing valves, etc. Onceany damage occurs, it is very difficult and costly to clean the system to a point in which therefrigeration system will be reliable.B. Be familiar with the local energy, mechanical, and building codes.APP-APG011-ENPage 402/08/2010

Section III - continued:However, if, on a retrofit, the building owner determines it is not feasible to replace the indoor section (airhandler and coil), some of the previously installed indoor sections may be modified to be compatible withR410A. Refer to Tables 3 and 4 for compatible air handlers and coils, and Table 5 for TXV kits. Pleaseunderstand, a retrofitted system may not be listed in the AHRI directory. In addition, the manufacturer willnot be able to provide any type of performance data. If the component has surpassed the OEM or extendedwarranty period, it is recommended to replace the indoor and outdoor unit with an AHRI listed system. If thecustomer requests an outdoor unit with a nominal rating above 13 SEER, the indoor and outdoor unit shall bereplaced. System matches may be located in the Certified HVACR Equipment directories @ www.ahrinet.orgSection IV - Reusing existing lines and indoor equipment:Wear required personal protective equipment to minimize the risk of oil and debris comingin contact with eyes and skin.A - Reusing existing refrigeration line and indoor coils.1. Drain as much oil as possible from line set and / or indoor coil.2. Purging the line set and coil with dry nitrogen may be required to recover oil from the horizontalrefrigerant piping and coil circuitry. The indoor coil may require removal in order to purge allexisting oil from the coil.3. All oil must be captured and recycled or disposed of in accordance with national, state, and localstandards.Such a standard is the EPA Clean Air Act. Reference www.epa.gov4. Conduct an acid test using the appropriate test kit for R-22 / Mineral oil systems.a)If the acid test shows negative, then proceed with installing the new OD unit.b)If the acid test indicates acid, then treat this system as a burnout.1. If at all possible, replace the refrigerant lines.c)If acid test returns positive and the lines are inaccessible or if there is a concern of debris inthe lines, a flush agent may be used.d)If the previous system failed as a result of compressor burnout, it is recommended to replacethe indoor coil.e)It is not necessary to measure the amount of residual mineral oil left in the system.Clearing the indoor coil and or refrigeration lines as detailed in this document isadequate. However, suction line riser traps may pose an issue with mineral oil anddebris removal. If the exising vapor line includes suction riser traps, line replacementis recommended if the traps are unable to be eliminated.d)The new refrigerant flow control device should be installed after clearing theexisting mineral oil from the system. Please reference Tables 5 and 6 for the appropriateTXV / OD unit match.CAUTIONThere are multiple HVAC flush agents available to our industry. Prior to using any flush agent, please readand understand all directions printed by the manufacturer as there may be differences from one manufacturer to another. Flush agents should be used for line cleaning only. Do not flush an indoor or outdoor coilfor re-use with Trane HVAC split systems. The coil may trap residue and promote premature compressorand flow control failure. If using a flush product in lines where POE oil will be the system lubricant, such asin R410A systems, it is recommended to use an HFC flush product. In all cases, the system must be evacuated below 300 microns in order to remove residual flush fluid that may contain unstable chlorinatedhydrocarbon solvent. At compressor discharge temperatures this solvent will breakdown and form strongacids.APP-APG011-ENPage 502/08/2010

Table 1 - Allowable Suction Line Length (equivalent feet) Versus Nominal Capacity for single speed R410A split systems onlyCapacity in TonsOutsideDiameter1.5 ton2.0 ton2.5 ton3.0 ton3.5 ton4.0 ton5.0 ton1/2"90Not "Not Approved1501501501501501501501501 1/8"Not ApprovedNot ApprovedTable 2 - Vertical Change (feet) Versus Equivalent Length (feet) For Single Speed Heat Pumps and Condensing Units (R410A)RefrigerantLine ODNominalOrientationCapacity (above or belowin TonsIndoor unit)102030405060708090100110120130140150HP or CU Below10203040506060575043352820146CU Above102030405060606090100110120130140150HP or CU Below10203040268Not approvedCU Above102030405060Not approvedHP or CU Below102030405060606060606060606060CU Above102030405060708090100110120130140150HP or CU Below102030405060606060606060606060CU t Length (feet)1.5 ton1/4"2.0 ton1.5 ton2.0 ton5/16"HP or CU Below102030405060606060606058534844CU Above102030405060708090100110120130140150HP or CU Below102030405060606055494235282215CU Above102030405060708090100110120130140150HP or CU Below10203040506053443526179Not ApprovedCU Above102030405060708090100110120Not ApprovedHP or CU Below102030405060606060606060606060CU Above102030405060708090100110120130140150HP or CU Below1020304050606060606060606060602.5 ton3.0 ton3.5 ton1.5 ton2.0 tonCU Above102030405060708090100110120130140150HP or CU Below102030405060606060606060606060CU Above102030405060708090100110120130140150HP or CU Below102030405060606060606060606060CU Above102030405060708090100110120130140150HP or CU Below1020304050606060606060606060602.5 ton3/8"3.0 ton3.5 tonCU Above102030405060708090100110120130140150HP or CU Below102030405060606060606060606056CU Above102030405060708090100110120130140150HP or CU Below102030405060606060565044383226CU Above1020304050607080901001101201301401504.0 ton5.0 tonTable 1 and Table 2 are intended to be used as a quick check to determine if existing refrigerant lines are the correct sizefor a replacement R410A system. For new installations, high rise applications as well as complete details regardingrefrigeration line sizing, please consult SS-APG006-EN or Publication 32-3312-03 version 3.3.3 or later version.APP-APG011-ENPage 602/08/2010

Table 3 - Fan Coil Compatibility MatrixApplies to 4TTA3, 4TTB3, 4TTR3, 4TWA3, 4TWB3, and 4TWR3 condensing units and heat pump units onlyIndoor UnitModelCLGIndoor UnitModelCLGHPIndoor B3F30A1X024, 3F42A/BXX2TGB3F42A1X036, 042TWE048CX2TEC3F48A/BXX2TGB3F48A1X042, E031EX018, 024, 0302TEE3F31A/BX018, 025, 0302TFE3F25B1XTWE037EX030, 0362TEE3F37A/BX030, 036TWG018AXTWE040EX0422TEE3F39A/BX024, 036, 2TEE3F48A/BX042, X2TEE3F65A/BXTWG048AXTWG060AXHP048, 060HPX018, 024, 030,Notes:1. X in the block indicates compatibility size per size2. Numbers indicate size of units that are compatible with the particular indoor unit.(Example - TWE031E has 024 in the block, this indicates that a 2TWB3024 and the2TWR3024 are compatible with the TWE031E.3. Please reference Table 5 for the appropriate expansion device.4. Unless the system is listed in the AHRI directory, system efficiency ratings are unavailable forretrofitted systems.APP-APG011-ENPage 702/08/2010

Table 4 - Furnace Coil Compatibility MatrixApplies to 4TTA3, 4TTB3, 4TTR3, 4TWA3, 4TWB3, and 4TWR3 condensing units and heat pump units onlyIndoor UnitModelCLGIndoor UnitModelCLGHPX2TXCA018ACX2TXFH018ASX018, 024TX*024C4/D4HPCX2TXCA024ACX2TXFH033ASX024, 030, 036TX*025C4/D4HPCX2TXCB025ACX018, 0242TXFH041ASX036, 31C4/D4HPCX2TXCB036ACX030, 036TX*035C4HPCX2TXCC037ACX030, 036TX*036C4HPCX0302TXCB042ACX036, 49ACX042, 048TX*043C4HPCX2TXCD050ACX048, 060TX*048C4HPCX036, 042, 0482TXCC060ACX048. 060TX*049C4HPCX036, 042, 0482TXCD061ACX048, 060TX*050C4HPCX042, 0482TXCA018BCX018TX*060C5HPCX048, 0602TXCA024BCX024TX*061C5HPCX048, 0602TXCB025BCX024TXC031E5/S3HPX018, 024, 0302TXCB031BCX018, 024, 030TXC036E5/S3HPX036, 0422TXCB036BCX036TXC037E5/S3HPX036, 0422TXCC037BCX036TXC054E5/S3HPX042, 0482TXCB042BCX036, 042TXC065E5/S3X048, 0602TXCC043BCX036, 042TXH025A4HPX2TXCB048BCX048TXH033A4HPX018, 54A4HPX036, 042, 0482TXCC060BCX048TXH063HPX0602TXCD061BCX048Indoor Unit ModelCLGTX*018C4/D4HPCHP024HPNotes:1. Asteriks indicates A or C2. X in the block indicates compatibility size per size3. Numbers indicate size of units that are compatible with the particular indoor unit.(Example - TX*024C4/D4HPC has 024 in the block, this indicates that a 2TWB3024 and the2TWR3024 are compatible with the TX*024C4/D4HPC coil.4. Please reference Table 6 for the appropriate expansion device.5. Unless the system is listed in the AHRI directory, system efficiency ratings are unavailable forretrofitted systems.APP-APG011-ENPage 802/08/2010

Table 5 - TXV / Fan Coil Unit 381D3HVXTYA4A1381D3HVXTYA402/08/2010Page FB3F302TEC3Fand2TEH3F048TWE-Cand 39VariableSpeedModelsTTA, 4TTB, 4TTR, 4TWA, 4TWB, 4TWRFanCoilUnitFan CoilPrefixTable 5 references the appropriate TXV device for each capacity range Reference Table 3 for compatible combinations of existing fan coil units and replacement 13 SEER outdoor units.Unless the system is listed in the AHRI directory, system efficiency ratings are unavailable forretrofitted systems.

Table 6 - TXV / Furnace Coil Unit 010Page A0381A3HVXTYA40183024A0381A3HVXTYA40244TTA, 4TTB, 4TTR, 4TWA, 4TWB, 4TWRCoilUnitFurnaceCoil Prefix050054060063ASTable 6 provides the appropriate TXV device for each capacity range. Reference Table 4 for compatible combinations of furnace coil units and replacement 13 SEER outdoor units. Unless the system islisted in the AHRI directory, system efficiency ratings are unavailable for retrofitted systems.

Table 7 - Fan Coil HFC-410A TXV to Part seyValve OnlyOutletconnectionValve XVH3J3737AAccessory / Kit Accessory / KitInletOutletConnectionConnectionTXV Valve OnlyPart Numbers s s s s s s s o o o oe n n n ne ye ye ye ye ye ye yy91780LAV4AYTXVH3J3131A02/08/2010Page 43 a a a a1 / / / /T n n n e FirstKit NumberAccessory NumberValve OnlyOutletConnectionValve OnlyInletConnectionAccessory / Kit Accessory / dTXV Valve OnlyPart NumberService FirstKit NumberAccessory Number4AYTXVH3J6565ATable 8 - Furnace Coil HFC-410A TXV to Part Matrix4AYTXVH3D3343A

V. Reusing existing HCFC-22 outdoor units:Please reference the following tables to determine if an existing HCFC-22 outdoor unit may beused with a new HFC-410A indoor product. Tables 12, 14 and 16 includes TXV informationTable 9 - Single Speed Cooling Units with R410A Indoor Fan Coil and Furnace Coil UnitsIndoorPrefix184TEC3F4TEH3F4TGB3F4TFB3FTTA, TTB, TTP, TTR, TTX, TTY, 2TTA, 2TTB, 2TTR, 2TTXUnit012018X, TEC / 4TXFHCopper060Page 12XX02/08/2010

Table 10- HCFC22 heat pump units with HFC410A fan coil units4TEE3F-A/B, 4TEE3D-A/B4TEC3F-A/B, TEH3F-A/B4TGB3F-A4TFB3F-A, 4TFE3F-AOutdoor /DXXXPage 1302/08/2010

Table 11 - HCFC22 heat pump units with HFC410A tan coil units4TEE3F-A/B, 4TEE3D-A/B4TEC3F-A/B, TEH3F-A/B4TGB3F-A4TFB3F-A, 4TFE3F-AOutdoor X036AX048AXX060AXTable 12 - HCFC-22 Two Stage / Two Compressor Compatibility Matrix with TXVFan Coil / Indoor D1830A4TEE3C / 4TEE3F31VAL04471VAL044714TEE3C / XVH3D4260A4TEE3C / XVH3D4260A4TEE3C / XVH3D4260A4TEE3C / 4TEE3F65VAL04416VAL044164TEE3C001 - 010Not approved for two stage HCFC-22 condensing units or heat pumps4TXA / 4TXCB0252AYTXVH3C2425AA4TXA / 4TXCB0312AYTXVH3C3031AA2AYTXVH3C3031AA4TXA / 4TXCB0362AYTXVH3C3337AA2AYTXVH3C3337AA4TXA / 4TXCB0482AYTXVH3C4850AA2AYTXVH3C4850AA4TXA / 4TXCC0372AYTXVH3C3337AA2AYTXVH3C3337AA4TXA / 0AA2AYTXVH3C4850AA4TXA / YTXVH3C5463AA2AYTXVH3C5463AA 2AYTXVH3C5463AA2AYTXVH3C5463AA2AYTXVH3C5463AA4TXA / 4TXCC0604TXA / 4TXCD0504TXA / 3AA 2AYTXVH3C5463AA2AYTXVH3C5463AA2AYTXVH3C5463AA4TXA / 3AA 2AYTXVH3C5463AA2AYTXVH3C5463AA2AYTXVH3C5463AA4TXA / YTXVH3C5463AA TXVH3C5463AATable 12 indicates the fan coil / furnace coil and outdoor unit is compatible if TXV is listed in thecell. Only variable speed indoor units shall be used with the 2TTZ9 / 2TWZ9 series outdoor units.APP-APG011-ENPage 1402/08/2010

Table 13 - HCFC-22 TXV To Part K02/08/2010Page 15APP-APG011-ENValve OnlyOutletConnectionAccessory / Kit Accessory / KitInletOutletConnectionConnectionValve TypeezarBInternallyCheckedValve OnlyInletConnectionezarBTXV Valve OnlyPart NumberezarBService FirstKit NumberAccessory VH3D4260A2AYTXVH3D4260AN/A2AYTXVH3D4260AN/A

Table 14 - Single Speed HCFC-22 OD unit TXV MatrixMechanical Coil Connection / brazed liquid lineBraze TXVMechanical ConnectionsOD UnitHeat PumpNon BleedCooling OnlyBleed PortCooling OnlyNon BleedHeat PumpCompatibleCoilFan Coil Unit1.0 ton single XVH3C1818A2AYTXVH3D1830A1.5 ton single XVH3C1818A2AYTXVH3D1830A2.0 ton single XVH3C2425A2AYTXVH3D1830A2.5 ton single XVH3C3031A2AYTXVH3D1830A3.0 ton single XVH3C3337A2AYTXVH3D3636A3.5 ton single XVH3C4243A2AYTXVH3D4260A4.0 ton single XVH3C4850A2AYTXVH3D4260A5.0 ton single XVH3C5463A2AYTXVH3D4260ATable 15 - Variable Speed Fan Coil TXV MatrixFan Coil UnitBrazedInlet and Ou

refrigerant piping and coil circuitry. The indoor coil may require removal in order to purge all existing oil from the coil. 3. All oil must be captured and recycled or disposed of in accordance with national, state, and local standards.Such a st

Related Documents:

Trane Xv95 Installation Manual instructions guide, service manual guide and maintenance manual guide on your products. Before by using this manual, service or . Trane Xv95 Xl16I Heat Pump - Honeywell Visionpro. . Manual Trane RTAA-200 Manuals Download 254 Trane Chiller P

Trane Technicians will capture and track all refrigerant activity performed by Trane for each piece of Covered Equipment Refrigerant Usage Reports can be generated annually 0 Trane Laboratory Analysis The Trane Chemical Laboratory performs routine analysis and trending of oil, absorption

Tracer UC210 Trane VAV Controller Tracer UC400 Trane- and field-applied terminal equipment (VAV, WSHP, fan coil, blower coil, generic) BCI-I (IPAK) Trane IntelliPak Rooftop equipment BCI-R (Reliatel) Trane Voyager and Precedent Rooftops Tracer UC600

66 21 2 359 135 BMW Advanced Car Eye retrofit kit (front and rear camera) 66 21 2 359 136 BMW Advanced Car Eye retrofit kit (front camera) 66 21 2 364 600 BMW Advanced Car Eye retrofit kit (front and rear camera) 66 21 2 364 601 BMW Advanced Car Eye retrofit kit (front camera) 66 21 2 288 543 BMW Advanced Car Eye retrofit kit (front and rear .

If you have any questions concerning the Retrofit Kit and / or the Retrofit process, contact Cutler-Hammer at 1-800-937-5487. Work Sequence Figure 1 illustrates the general work sequence for all DS Breaker Retrofit Kits. The available Retrofit Kits are listed across the top of the figure. Under each kit, the components

4 FI9 retrofit kit installation 2. FI9 RETROFIT KIT INSTALLATION 2.1 Retrofit kit contents Figure 1. FI9 DC fan retrofit kit contents Table 2. FI9 DC fan retrofit assembly kit (SPR-MEC23728) part list # Item number Item description Pcs 1 70CPA00556 DC main fan assembly 1 2 70CMC05006 External DC fan supply assembly 1 3 70CPA03288 Asic cover and .

THE NV SERIES NAMING GUIDE Trane Mitsubishi Re-Name Ductless Products To enhance our Mitsubishi Electric Trane HVAC branding efforts, we will be re-naming the co-branded ductless products to Nv-Series. Trane together with Mitsubishi Electric for ductless will give your customers

Trane customers demanded a product that provided exceptional reliability, was easy to install, and was competitively priced. Trane listened and is proud to introduce the new Trane Foundation Light Commercial rooftop unit. With Foundation, Trane continues to provide the highest standards in quality and reliability,