Submittal PackageViega MegaPress G FittingsProjectDateEngineerContractorSubmitted byApproved bySM-MP 0321 MegaPressG FittingsDateApproved byDate1 of 23

Table of ContentsTable of ContentsHeating Fuel OilNatural GasCompressed AirLubricants/OilsIndustrial GasesVacuum12345System Data Sheet 3MegaPressG Fittings 3Product Instructions 4MegaPressG ½" to 2" Fittings 4MegaPressG 2½" to 4" Fittings 5Engineering Specifications 6MegaPressG Natural Fuel Gas Systems 6Dimensional Documents 10MegaPress ½" to 4" Fittings 10Limited Warranty 22Viega MegaPressG 22Viega Metal Systems for Industrial Applications 23This document is subject to updates. For the most current Viegatechnical literature please visit www.viega.us.Viega products must be installed by trained installers.MegaPress credential training is provided at no cost by Viegaand is recommended every two years. Please contact Viega toarrange credential training onsite or at our training facility. Installation bynon-professionals may void Viega LLC’s warranty.SM-MP 0321 MegaPressG Fittings2 of 23

System Data Sheet1 System Data SheetMegaPressG FittingsViega MegaPressG is a carbonsteel, cold press fitting systemdesigned for use in fuel gassystems and applications witha high oil content. MegaPressGfittings in sizes from ½" to 4" areoffered in numerous configurations.Components Alloy: carbon steel with corrosion-resistant zinc/nickel coatingHNBR sealing element420 stainless steel grip ring304 stainless steel separator ring for ½" to 2" fittingsGraphite separator ring for 2½" to 4" fittingsOperating Parameters Operating Pressure: 125 psi max for fuel gas applications200 psi max for other approved applications Test Pressure: 600 psi max Operating Temperatures: -40 to 180 FApproved Piping Fuel gas applications: ASTM A53 Schedule 10 toSchedule 40 carbon steel pipe Non-fuel gas applications: ASTM A53, A106, A135, andA795 Schedule 5 to Schedule 40 carbon steel pipe.Schedule 80 pipe may be used but operating pressuresare limited to Viega Approved Applications guide.Adopted code versions, standards compliance,and local approvals should be considered forselecting pipe schedule and type.Listings and Certifications ASTM F3226 CSA: ANSI LC 4a/CSA 6.32a ASME B31.1, B31.3, B31.9 IAPMO: ANSI LC 4a/CSA 6.32a CRN 23019.5 A/B/C ICC-ES: ANSI LC 4a/CSA 6.32aSM-MP 0321 MegaPressG FittingsCompliant With CAN/CSA-B149.1IAPMO National Standard Plumbing Code (NSPC)IAPMO Uniform Mechanical Code (UMC)IAPMO Uniform Plumbing Code (UPC)ICC International Fuel Gas Code (IFGC)ICC International Residential Code (IRC)NFPA 54/Z223: National Fuel Gas CodeNFPA 58: Liquefied Petroleum Gas CodeApproved Applications Natural gasPropane gasLubricants/oilsCompressed airIndustrial gasesVacuumFor more specific information on applications for MegaPressG,contact Viega Technical Services at 1-800-976-9819.Viega MegaPressG systems are approved for underground useand must be protected against corrosion in accordance with NFPA54 section 404.8, NACE Standard RP0169-2002 section 5, 2009UPC Chapter 6 section 609.3.1, 2009 UMC Chapter 13 section1312.1.3, and in accordance with local and national codes.Recommended Tools Standard size press tool (minimum hydraulic ramoutput of 7200 lbs.) #56013 MegaPress jaw/ring kit ( ½" to 2") #26200 MegaPress XL PressBooster with 2½" press ring #26201 MegaPress XL 3" and 4" press ring kit #57081 Z3 Actuator with 2½ ring (must be used withpress gun with minimum 80mm press stroke)Smart Connect TechnologyViega MegaPressG fittings are manufactured with Viega’sunique Smart Connect technology. A design of the fitting,Viega Smart Connect technology allows identification of anunpressed fitting during pressure testing.3 of 23

Product Instructions2 Product InstructionsMegaPressG ½" to 2" Fittings12345668b8c9a9bmin. 4"8a7d109c5 Illustration demonstrates proper fit of gripring, separation ring and sealing element.6 Mark proper insertion depth. Improperinsertion depth may result in an improperseal. The depth marking shall be visible onthe completed assembly.Caution!The fittings are for use with fuelgases and are intended for theoperating pressure 0-125 psi.Caution!The fuel gas system shall not beused as a grounding electrode foran electrical system.1 Cut piping at right angles using displacementtype cutter.2 Keep end of piping a minimum of 4” awayfrom the contact area of the vise to preventpossible damage to the piping in the pressarea. See the MegaPress Installation Manualfor minimum clearance required for preptools.3 Remove burr from inside and outsideof piping and prep to proper insertiondepth using a preparation tool or fine gritsandpaper.4 Check seal and grip ring for correct fit. Donot use oils or lubricants.SM-MP 0321 MegaPressG FittingsPipe Size (in)½¾11¼1½2Insertion Depth (in)11/161 3/161⅜113/161⅞28a Viega MegaPress ½” - 1” fitting connections8b8c9a9b7 Refer to chart for minimum distancebetween fittings. To ensure a correct press,a minimum distance between press fittingsmust be maintained. Failure to provide thisdistance may result in an improper seal.Pipe Diameter (in)½¾11¼1½2d (in)¼¼¼½½½d (mm)666131313Warning!Keep extremities and foreignobjects away from press tool duringpressing operation to prevent injury orincomplete press.9c10must be performed with MegaPress jaws.See the pressing tool’s Operator’s Manualfor proper tool instructions.Open the MegaPress jaw and place at rightangles on the fitting. Visually check insertiondepth using mark on piping.Start pressing process and hold the triggeruntil the jaw has engaged the fitting.Viega MegaPress 1¼” - 2” fittingconnections must be performed withMegaPress rings and V2 actuator. See thepressing tool’s Operator’s Manual for propertool instructions.Open MegaPress ring and place at rightangles on the fitting. MegaPress ring mustbe engaged on the fitting bead. Checkinsertion depth.Place V2 actuator onto MegaPress ring andstart pressing process. Hold the trigger untilthe actuator has engaged the MegaPress ring.Remove MegaPress jaw from fitting orrelease V2 actuator from the MegaPress ringand then remove the MegaPress ring fromthe fitting on completion of press. Removecontrol label to indicate press has beencompleted.The installation, inspection, testingand purging of the fuel gas systemshall be in accordance with localcodes or, in the absence of local codes, inaccordance with the International Fuel GasCode, NFPA 54/National Fuel Gas Codez223.1, the Uniform Plumbing Code, NFPA58 or CSA B 149.1 as applicable.4 of 23

Product InstructionsProduct InstructionsMegaPressG 2½" to 4" Fittings123456691011min. 4"78x2-3Caution!The fittings are for use with fuelgases and are intended for theoperating pressure 0-125 psi.5 Mark proper insertion depth. ImproperCaution!The fuel gas system shall not beused as a grounding electrode foran electrical system.Insertion Depth (in)2½341 Cut piping at right angles using displacementtype cutter.2 Keep end of piping a minimum of 4" awayfrom the contact area of the vise to preventpossible damage to the piping in the pressarea. See MegaPress Installation Manual forminimum clearance required for prep tools.3 Remove burr from inside and outsideof piping and prep to proper insertiondepth using a preparation tool or fine gritsandpaper.4 Illustration demonstrates proper fit of gripring, separation ring and sealing element.Caution!Due to the brittle nature of thegraphite separator ring, extra caremust be taken when sliding the fitting ontothe pipe so as not to damage the separatorring.SM-MP 0321 MegaPressG Fittingsinsertion depth may result in an improperseal. The depth marking shall be visible onthe completed assembly.d (in)113/162 5/163⅛d (mm)4659806 While turning slightly, slide fitting onto tubingto the marked depth. End of tubing mustcontact stop.Warning!Keep extremities and foreignobjects away from press toolduring pressing operation to prevent injury orincomplete press.9 Remove the retaining bolt of the pressmachine. Slide the PressBooster in via thepress jaw fixture.10 Place PressBooster/Z3 actuator ontoMegaPress XL rings and start pressingprocess. Hold the trigger until the actuatorhas engaged the MegaPress ring.11 The PressBooster requires two presses ofthe trigger to execute a complete press.A third press may be needed to initiate arelease cycle to reset the rollers back to theoriginal position.Info: The installation, inspection,testing and purging of the fuel gassystem shall be in accordance withlocal codes or, in the absence of local codes,in accordance with the International FuelGas Code, NFPA 54/National Fuel Gas Codez223.1, the Uniform Plumbing Code, NFPA58 or CSA B 149.1 as applicable.7 Viega MegaPressG 2½" to 4" fittingconnections must be made usingMegaPress XL rings and a PressBooster/Z3actuator. See Operator’s Manual for propertool instructions.8 Open MegaPress ring and place at rightangles on the fitting. MegaPress ring mustbe engaged on the fitting bead. Checkinsertion depth.5 of 23

Engineering Specifications3 Engineering SpecificationsMegaPressG Natural Fuel Gas SystemsPart 1: General1.1 SummaryMegaPressG is a cold press mechanical joint fitting system made for use with ASTM A53 carbon steel pipe innatural gas applications.1.2 DefinitionsASME: American Society of Mechanical EngineersASTM: American Society for Testing and MaterialsCSA: Canadian Standards AssociationHNBR: Hydrogenated Nitrile Butadiene RubberFM: Factory MutualIACS: International Association of Classification SocietiesIAPMO: International Association of Plumbing & Mechanical OfficialsICC: International Code CouncilMSS: Manufacturers Standardization SocietyNACE International: National Association of Corrosion EngineersNFPA: National Fire Protection AssociationUL: Underwriters Laboratory1.3 ReferencesANSI LC-4/CSA 6.32 Press-connect Metallic Fittings for use in Fuel Gas Distribution SystemsASME A13.1 Scheme for the Identification of Piping SystemsASME B1.20.1 Pipe Threads, General Purpose (inch)ASME B16.3 Malleable Iron Threaded FittingsASME B16.9 Factory Made Wrought Steel Butt-welding FittingsASME B31.1 Power PipingASME B31.3 Process PipingASME B31.9 Building Piping SystemsASME B36.10 Welded and Seamless Wrought Steel PipeASTM A135 Specification for Electric-Resistance-Welded Steel PipeASTM A420 Piping Fittings of Wrought Carbon Steel and Alloy Steel for Low Temperature ServiceASTM A53 Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless PipeASTM D2000 Classification System for Rubber Products in Automotive ApplicationsASTM F1476 Performance of Gasketed Mechanical Couplings for Use in Piping ApplicationsASTM F3226 Standard Specification for Metallic Press-Connect Fittings for Piping and Tubing SystemsIAPMO Uniform Mechanical CodeIAPMO Uniform Plumbing CodeICC International Plumbing CodeNACE RP 0169 control of External Corrosion on Underground or Submerged Metallic Piping SystemsNFPA 54 National Fuel Gas CodeMSS-SP58 Pipe Hangers and Supports Materials, Design and Manufacturer1.4 Quality AssuranceA. Installer shall be qualified, licensed within the jurisdiction, and familiar with the installation of cold pressmechanical joint systems.B. MegaPressG press fittings shall be installed using the proper tool, actuator, jaws and rings as instructed by thepress fitting manufacturer.SM-MP 0321 MegaPressG Fittings6 of 23

Engineering SpecificationsC. The installation of carbon steel pipe in natural gas systems shall conform to the requirements of the IAPMOUniform Plumbing Code or National Fuel Gas Code.D. Compliance to ASME B31.9 for building services piping valves.1.5 Delivery, Storage and HandlingA. Carbon steel pipe shall be shipped to the jobsite in such a manner to protect the pipe. The pipe and fittings shallnot be roughly handled during shipment. Pipe and fittings shall be unloaded with reasonable care.B. Protect the stored product from moisture and dirt. Elevate above grade. When stored inside, do not exceed thestructural capacity of the floor.C. Protect fittings and piping specialties from moisture and dirt.1.6 Project ConditionsVerify length of pipe required by field measurements.1.7 WarrantyA. Viega LLC (Viega) warrants to end users, installers and distribution houses that its Viega metal press products(MegaPressG) when properly installed shall be free from failure caused by manufacturing defects. Refer to Viegawarranties for specific information.B. Viega LLC (Viega) manufacturer of the fittings shall not be responsible for the improper use, handling orinstallation of the product.Part 2: Products2.1 ManufacturerViega LLC585 Interlocken Blvd.Broomfield CO, 80021Phone: (800) 976-9819www.viega.us2.2 Pipe and FittingsA. Pipe: Carbon steel pipe shall conform to ASTM A53. Pipe schedule (pipe wall thickness) shall conform to thestandard referenced dimensions for Schedule 10 or Schedule 40. Adopted code versions, standards compliance,and local approvals should be considered.B. Fittings: Cold Press Mechanical Joint Fitting shall conform to material requirements of ASTM A420 or ASMEB16.3 and performance criteria ANSI LC-4/CSA 6.32. Sealing elements for press fittings shall be HNBR. Sealingelements shall be factory installed or an alternative supplied by fitting manufacturer. Press ends shall have SC(Smart Connect ) technology design (leakage path). MegaPress fittings with Smart Connect technology assureleakage of liquids and/or gases from inside the system past the sealing element of an un-pressed connection.The function of this feature is to provide the installer quick and easy identification of connections which have notbeen pressed prior to putting the system into operation.C. Note: Verify pipe and fittings with applicable codes.D. Piping and fittings shall comply with ANSI LC-4/CSA 6.32 and the latest edition of NFPA-54.E. Fittings shall comply to the requirements of ASTM F3226.2.3 ValvesA. Valves shall conform to the performance criteria ANSI LC-4/CSA 6.32.B. Metallic Valves, shall comply with ASME B16.33.2.4 Gas Safety Shut-Off ValvesGas safety shut-off valves shall be FM & UL listed, with a visual indicator to note the position of the valve whether“OPEN” or “SHUT”SM-MP 0321 MegaPressG Fittings7 of 23

Engineering Specifications2.5 Pressure RegulatorsA. Pressure regulators shall be FM & UL listed for gas service and the gas system pressure rating.B. Service Pressure Regulators shall comply with ANSI Z21.80.C. Pressure regulators shall be equipped with an approved elevation compensator.2.6 Cathodic ProtectionProvide a complete electrically isolated, cathodic protection system for entire length of underground gas line,including all components, suitable for temperatures and pressures involved.Part 3: Execution3.1 ExaminationA. Examine roughing-in for natural-gas piping system to verify actual locations of piping connections beforeequipment installation.B. Proceed with installation only after unsatisfactory conditions have been corrected.3.2 PreparationA. Close equipment shutoff valves before turning off natural gas to premises or piping section.B. Inspect natural-gas piping according to NFPA 54 Fuel Gas Code to determine that natural-gas utilization devicesare turned off in piping section affected.C. Comply with NFPA 54 Fuel Gas Code requirements for prevention of accidental ignition.3.3 InstallationA. Install piping free from traps and with drain pocket consisting of nipple and cap at low points for inside buildingand drip pot for underground piping.B. Install shut-off valves at connection to each piece of equipment. Provide union of equipment side of individualshut-off valve.C. Install gas meter in a well ventilated and accessible location. Gas meter room (3 hr. rated enclosure) withexplosion-proof fixtures.3.4 Outdoor Piping InstallationA. Comply with NFPA 54 Fuel Gas Code for installation and purging of natural-gas piping.B. Install underground, natural-gas piping to comply with NFPA-54 and local codes.C. Install fittings for changes in direction and branch connections.3.5 Piping InstallationA. Comply with NFPA 54 Fuel Gas Code for installation and purging of natural-gas piping.B. Locate valves for easy access.C. Install piping free of sags and bends.D. Install fittings for changes in direction and branch connections.3.6 Fire-Barrier Penetrations:Maintain indicated fire rating of walls, partitions, ceilings, and floors at pipe penetrations. Seal pipe penetrations withapproved fire-stop materials.3.7 Drips and Sediment Traps:A. Install drips at points where condensate may collect, including service-meter outlets. Locate where accessible topermit cleaning and emptying. Do not install where condensate is subject to freezing.B. Construct drips and sediment traps using tee fitting with bottom outlet plugged or capped.C. Do not use natural-gas piping as grounding electrode.D. Install strainer on inlet of each line-pressure regulator and automatic or electrically operated valve.SM-MP 0321 MegaPressG Fittings8 of 23

Engineering Specifications3.8 Service-Meter Assembly InstallationA. Install service-meter assemblies above ground.B. Install metal shutoff valves upstream from service regulators.C. Install strainer on inlet of service-pressure regulator and meter set.D. Install service regulators mounted outside with vent outlet horizontal or facing down. Install screen in vent outletif not integral with service regulator.E. Install metal shutoff valves upstream from service meters. Install dielectric fittings downstream from servicemeters.F. Install service meters downstream from pressure regulators.3.9 Valve InstallationA. Install manual gas shutoff valve for each gas appliance as required by local codes.B. Install underground valves with valve boxes.C. Install regulators and overpressure protection devices with maintenance access space adequate for servicingand testing.D. Install earthquake valves above ground outside buildings according to local codes.3.10 Piping Joint ConstructionA. Ream ends of pipes and tubes and remove burrs.B. Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before assembly.3.11 Hanger and Support InstallationA. Hangers and hanger spacing shall conform to MSS-SP58: Pipe Hangers and Supports Materials, Design andManufacturerB. Install seismic restraints on piping as required by local codes.3.12 ConnectionsA. Connect to utility’s gas main according to utility’s procedures and requirements.B. Install natural-gas piping electrically continuous, and bonded to gas appliance equipment grounding conductorof the circuit powering the appliance according to NFPA 70.C. Install piping adjacent to appliances to allow service and maintenance of appliances.D. Connect piping to appliances using manual gas shutoff valves and unions. Install union between valve andappliances or equipment as required by local codes.E. Sediment Traps: Install tee fitting with capped nipple in bottom to form drip, as close as practical to inlet of eachappliance.3.13 Labeling and IdentifyingA. Comply with requirements of NFPA-54 and ASME A13.1 for piping and valve identification.B. Underground piping shall have detectable warning tape directly above gas piping, including under pavementsand slabs and protected from corrosion in accordance with NACE RP 0169.3.14 PaintingA. Comply with requirements for painting interior and exterior natural-gas piping.B. Paint exposed, exterior metal piping, valves, service regulators, service meters and meter bars, earthquakevalves, and piping specialties, except components, with factory-applied paint or protective coating.3.15 Field Quality ControlTests and Inspections:A. Test, inspect, and purge natural gas according to NFPA 54 and authorities having jurisdiction.B. Purge all piping after pressure test and all appliances after piping has been purged.C. Prepare test and inspection reports.SM-MP 0321 MegaPressG Fittings9 of 23

Dimensional Documents4 Dimensional DocumentsMegaPress ½" to 4" FittingsMegaPress 90 Elbow, Carbon Steel, P x P - Models 4816 / 5916 / 6616-" "-EPDM252002520525210252152522025225Part 25211252162522125226Size (in)1½¾11¼1½2A (in)L 78 Viega MegaPress 90 Elbow P x P - Models 4816XL / 6616XLPart No.FKM265002650526510HNBR286002860528610Size (in)12½34A (in)L (in)4.154.766.005.947.099.17MegaPress 90 Elbow, Carbon Steel, P x FTG - Models 4816.1 / 5916.1 / 6616.1" - EPDM260502605526060260652607026075Part 26061260662607126076Size (in)1 2½x½¾x¾1x11¼ x 1¼1½ x 1½2x2A (in)L (in)L1 782.562.873.394.044.215.08 SM-MP 0321 MegaPressG Fittings10 of 23

Dimensional DocumentsViega MegaPress 90 Street Elbow P x FTG - Models 4816.1XL / 6616.1XLPart No.FKMHNBR265152861526520286202652528625Size (in)1 22½ x 2½3x34x4A (in)L (in)L1 (in)4.154.766.005.947.099.176.066.818.78Size (in)1½¾11¼1½2A (in)L 31MegaPress 45 Elbow, Carbon Steel, P x P - Models 4826 / 5926 / 6626"-" EPDM252302523525240252452525025255Part 25241252462525125256Viega MegaPress 45 Elbow P x P - Models 4826XL / 6626XLFKM265302653526540Part No.HNBR286302863528640Size (in)12½34A (in)L (in)2.102.262.743.904.565.92MegaPress 45 Elbow, Carbon Steel, P x FTG - Models 4826.1 / 5926.1 / 6626.1-" - SM-MP 0321 MegaPressG FittingsEPDM261002610526110261152612026125Part 26111261162612126126Size (in)1 2½x½¾x¾1x11¼ x 1¼1½ x 1½2x2A (in)L (in)L1 311.972.132.522.993.073.5811 of 23

Dimensional DocumentsViega MegaPress 45 Street Elbow P x FTG - Models 4826.1XL /6626.1XLPart No.FKMHNBR265452864526550286502655528655Size (in)1 22½ x 2½3x34x4A (in)L (in)L1 (in)2.102.262.743.904.565.923.954.345.62MegaPress Tee, Carbon Steel, P x P x P - Models 4818 / 5918 / 6618 - " ""-EPDM253002530525310253152532025325Part 25311253162532125326Size (in)1½¾11¼1½2A (in)A1 (in)L (in)L1 A (in)A1 (in)L (in)L1 4.064.134.204.294.314.824.774.864.885.436.26-Viega MegaPress Tee P x P x P - Models 4818XL / 6618XL- " " "- SM-MP 0321 MegaPressG FittingsPart 8670Size (in)1 2 32½ x 2½ x 12½ x 2½ x 1¼2½ x 2½ x 1½2½ x 2½ x 22½ x 2½ x 2½3 x 3 x 1¼3 x 3 x 1½3x3x23 x 3 x 2½3x3x34 x 4 x 1½4x4x24 x 4 x 2½4x4x34x4x412 of 23

Dimensional DocumentsMegaPress Reducing Tee, Carbon Steel, P x P x P - Models 4818 / 5918 / 6618 - " 0253752538025385253902539525400Part 5844408444584450844558446084465SM-MP 0321 MegaPressG 536625371253762538125386253912539625401Size (in)1 2 3¾x¾x½1x1x½1x1x¾1¼ x 1¼ x ½1¼ x 1¼ x ¾1¼ x 1¼ x 11½ x 1½ x ½1½ x 1½ x ¾1½ x 1½ x 11½ x 1½ x 1¼2x2x½2x2x¾2x2x12 x 2 x 1¼2 x 2 x 1½A (in)A1 (in)L (in)L1 2.552.732.512.642.833.322.812.953.103.603.7113 of 23

Dimensional DocumentsMegaPress Reducing Tee, Carbon Steel, P x P x FPT - Models 4817.2 / 5917.2 / 6617.2 - " 025445254502545525460254652547025475Part 4662547125476Size (in)1 2 3¾x¾x½¾x¾x¾1x1x½1x1x¾1¼ x 1¼ x ½1¼ x 1¼ x ¾1¼ x 1¼ x 11½ x 1½ x ½1½ x 1½ x ¾1½ x 1½ x 11½ x 1½ x 1¼2x2x½2x2x¾2x2x12 x 2 x 1¼2 x 2 x 1½A (in)A1 (in)L (in)L1 552.452.41Viega MegaPress Tee P x P x FPT - Models 4817.2XL / 6617.2XLPart No.FKMHNBR266252872526630287302663528735SM-MP 0321 MegaPressG FittingsSize (in)1 2 32½ x 2½ x ¾3x3x¾4x4x¾A (in)A1 (in)L (in)L1 3114 of 23

Dimensional DocumentsMegaPress Adapter, Carbon Steel, P x MPT - Models 4811 / 5911 / 6611 -"EPDM251002510525110251152512025125Part 25111251162512125126Size (in)1 2½x½¾x¾1x11¼ x 1¼1½ x 1½2x2A (in)L 92Viega MegaPress Adapter P x MPT - Models 4811XL / 6611XLFKM266402664526650Part No.Size (in)1 22½ x 2½3x34x4HNBR287402874528750A (in)L (in)2.752.893.034.555.206.21MegaPress Adapter, Carbon Steel, P x FPT - Models 4812 / 5912 / 6612 -"EPDM251302513525140251452515025155Part 25141251462515125156Size (in)1 2½x½¾x¾1x11¼ x 1¼1½ x 1½2x2A (in)L 44Viega MegaPress Adapter P x FPT - Models 4812XL /6612XLFKM266552666026665SM-MP 0321 MegaPressG FittingsPart No.HNBR287552876028765Size (in)1 22½ x 2½3x34x4A (in)L (in)1.131.171.153.864.495.4215 of 23

Dimensional DocumentsMegaPress Reducing Adapter, Carbon Steel, P x FPT - Models 4812 / 5912 / 6612 5256202562525630256352564025645Part 5646Size (in)1 2¾x½1x½1x¾1¼ x ½1¼ x ¾1¼ x 11½ x ½1½ x ¾1½ x 11½ x 1¼2x½2x¾2x12 x 1¼2 x 1½A (in)L 3.414.064.084.003.933.70A (in)L 75MegaPress Coupling with Stop, Carbon Steel, P x P - Models 4815 / 5915 / 6615 "-EPDM250002200525010250152502025025Part 25011250162502125026Size (in)1½¾11¼1½2Viega MegaPress Coupling with Stop P x P - Models 4815XL / 6615XLFKM266702667526680Part No.HNBR287702877528780Size (in)12½34A (in)L (in)1.321.381.574.925.987.87Size (in)1½¾11¼1½2L (in)MegaPress Coupling No Stop, Carbon Steel, P x P - Models 4815.5 / 5915.5 / 6615.5 -SM-MP 0321 MegaPressG FittingsEPDM250302503525040250452505025055Part 250412504625051250562.712.943.294.344.634.7416 of 23

Dimensional DocumentsViega MegaPress Coupling No Stop P x P - Models 4815.5XL / 6615.5XLFKM266852669026695Part No.HNBR287852879028795Size (in)12½34L (in)4.925.987.91MegaPress Extended No Stop Coupling, Carbon Steel, P x P - Models 4815.3 / 6615.3 -EPDM250702507525080250852509025095Part No.HNBR250712507625081250862509125096Size (in)1½¾11¼1½2L (in)3.824.004.385.335.445.63MegaPress Reducer, Carbon Steel, FTG x P - Models 4815.1 / 5915.1 / 6615.1 "-SM-MP 0321 MegaPressG 60352604026045Part 26260362604126046Size (in)1 2¾x½1x½1x¾1¼ x ¾1¼ x 11½ x ¾1½ x 11½ x 1¼2x12 x 1¼2 x 1½A (in)L 853.213.243.973.984.134.164.524.494.834.8317 of 23

Dimensional DocumentsViega MegaPress Reducer FTG x P - Models 4815.1XL / 6615.1XL 7452675026755 "-Part No.Size (in)1 22½ x 12½ x 1¼2½ x 1½2½ x 23 x 1¼3 x 1½3x23 x 2½4 x 1½4x24 x 2½4x3A (in)L HNBR2593125936259412594625951259562596125966Size (in)1 2¾x½1x½1x¾1¼ x ¾1¼ x 11½ x 1¼2 x 1¼2 x 1½A (in)L 0Size (in)1½¾11¼1½2A (in)L 0288452885028855MegaPress Reducer, Carbon Steel, P x P - Models 4815.2 / 52ALPart No.MegaPress Union, Carbon Steel, P x P - Model 4860 / 5960 "-EPDM257002570525710257152572025725Part No.MegaPress Union, Carbon Steel, P x P - Model 666011ALSM-MP 0321 MegaPressG FittingsPart No.HNBR257012570625711257162572125726Size (in)1½¾11¼1½2A (in)L 3518 of 23

Dimensional DocumentsMegaPress Union, Carbon Steel, P x FPT - Model 4862 "" -Part No.EPDM256502565525660256652567025675Size (in)1 2½x½¾x¾1x11¼ x 1¼1½ x 1½2x2A (in)A1 (in)L 702.853.203.384.034.105.00Size (in)1 2½x½¾x¾1x11¼ x 1¼1½ x 1½2x2A (in)A1 (in)L 702.983.353.634.354.354.77MegaPress Union, Carbon Steel, P x FPT - Model 6662 "-" Part No.HNBR256512565625661256662

1.3 References ANSI LC-4/CSA 6.32 Press-connect Metallic Fittings for use in Fuel Gas Distribution Systems ASME A13.1 Scheme for the Identification of Piping Systems ASME B1.20.1 Pipe Threads, General Purpose (inch) ASME B16.3 Malleable Iron Threaded Fittings ASME B16.9 Factory Made Wrought Steel Butt-welding Fittings ASME B31.1 Power Piping

Related Documents:

Pipe Viega ProPress Stainless steel pipe is offered in either 304 stainless or 316 stainless to compliment the Viega fittings and offer a complete system solution. Viega ProPress Stainless steel pipe meets the requirement of ASTM A312 or ASTM A554 for schedule 5 304 and 316 stainless steel pipe. Smart Connect (SC feature) dimensions the Smart .

In the United States, Canada, Mexico, and Latin America, Viega specializes in plumbing, heating, and pipe joining technologies. The values of Viega's founder, Franz-Anselm Viegener, are just as present today as they were when he started the company in 1899. Courage, passion, and innovative spirit are still the basics of Viega's foundation.

Automotive Hose and Fittings CONTENT 6 6.1 6.2 6.3 Hose and Fittings 634 G-Line Hose and Fittings 634 Quick Release Couplings 645 600 - 700 Series Hose and Fittings 648 200 Series Hose and Fittings 673 Push Fit Hose and Fittings 679 Adaptors 683 Air Conditioning Hose and 695 Fittings . 634 www.pirtek.com 6. 1 Series Page Hose 910 910 636 Hose 811 811 636 Hose 910 FC 910 FC 636 (Fuel Cell) G .

cobra compression fittings plastic fittings galvanised fittings couplings & clamps capillary fittings . 36 pvc fittings . 37 pvc fittings . 38 pvc fittings . 39 . 40 . plumbing supplies . 52 valves . 53 valves . 54 latco valves valves . 55 brassware other . 56 tekflo brassware uni-flo geyser valves . 57 geyser valves . 58

Pipe Fittings. pages 32-37. Unpolished Fittings. pages 74-80. Polished Fittings. pages 64-73. European Fittings. pages 81-85. Filters / Strainers. pages 111-117. Custom Fabrications. pages 109. Swivels. pages 140-141. Instrumentation. pages 118-133. Air Fittings. pages 162-170. High Press. Quick Disc. pages 171-179. Check Valves. pages 214-222 .

ASME B16.51, B31.1, B31.3, B31.9 . Smart Connect technology. A design of the fitting, Viega Smart Connect technology allows identification of an unpressed fitting during pressure testing. . MSS-SP-58 Pipe Hangers and Supports Materials, Design and Manufacturer

Super-rapid fittings in 316L stainless steel Series X6000 6 2 Push-on Fittings Rapid push-on fittings in 316L stainless steel Series X1000 11 3 Stainless steel accessories and plugs Pipe fittings in 316L stainless steel Series X2000 14 4 Flow Regulators, Function Fittings and Silencers Flow regulators in 316L stainless steel Series XSCU, XSCO .

THE GUIDE SPRING BREAK CAMPS 2O2O MARCH 16–27 AGES 5–13. 2 2020 Spring Break Camp Guide WELCOME Build Your COCA Camp Day 2 March 16–20 Camps 3–4 March 23–27 Camps 5–6 Camp Basics 7 Registration Form 8–9 Registration Guidelines/Policies 10 Summer’s coming early this year! Join us over Spring Break for unique and fun arts learning experiences. You’ll find favorites from .